Documentos de Académico
Documentos de Profesional
Documentos de Cultura
Sistemas Electricos Parcial
Sistemas Electricos Parcial
70hp
cos θ = 0.87
n=80,1
70 hp∗746 w
Pent = 1 = 65193,50w
0,801
Pent 65193
I= = = 98,32A
√ 3∗V ∗θ √ 3∗440∗0,8 7
S = √ 3 * V * I = √ 3 *440 * 96,11A = 74929,90 W -> 74,92 KW
Bomba #1 y2 Dosificadora
5.5 hp
cos θ = 0.87
n=80,1
5.5 hp∗746 w
Pent = 1 = 5122.34w
0,801
Pent 5122
I= = = 7,72A
√ 3∗V ∗θ √ 3∗440∗0,8 7
S = √ 3 * V * I = √ 3 *440 * 7,72A = 5883,43 W -> 58,83 KW
20 hp
cos θ = 0.89
n=80,1
20 hp∗746 w
Pent = 1 = 18626,71W
0,801
Pent 18626
I= = = 27,46A
√ 3∗V ∗θ √3∗440∗0,8 9
S = √ 3 * V * I = √ 3 *440 * 27,46A = 20927,33 -> 20,92 KW
2 hp
cos θ = 0.89
n=80,1
2 hp∗746 w
Pent = 1 = 1855,72W
0,801
Pent 1855
I= = = 2,73
√ 3∗V ∗θ √3∗440∗0,8 9
S = √ 3 * V * I = √ 3 *440 * 2,73A = 2080.53 W-> 20,80 KW
2. Cableado
Bomba # 1
Succion pulpa
2∗R∗L 2∗0.656∗234 m
= = 9,13
A 33,60 mm 2
Dosificadora
2∗R∗L 2∗0.656∗234 m
= = 3,61
A 85.00 mm 2
Se le recomienda al eléctrico usar cable 3/0 AWG (THHN- para protecciones de áreas con
aceites), por tubería de aluminio de 2” donde puede pasar máximo 5 conductores y de estos
uno debe ser sin carga como máximo.
Bomba # 2
Succion pulpa
2∗R∗L 2∗0.656∗24 5 m
= = 154.53
A 2,0800
Dosificadora
2∗R∗L 2∗0.656∗2 45 m
= = 4,76
A 67,40
Se le recomienda al eléctrico usar cable 2/0 AWG (THHN- para protecciones de áreas con
aceites ) , por tubería de aluminio de 1.5” donde puede pasar máximo 4 conductores y de estos
uno debe ser sin carga como máximo
Bomba # 3
Succion pulpa
2∗R∗L 2∗0.656∗2 64 m
= = 104.64
A 3,3100
Dosificadora
2∗R∗L 2∗0.656∗264 m
= = 5,13
A 67,40
Se le recomienda al eléctrico usar cable 2/0 AWG (THHN- para protecciones de áreas con
aceites ) , por tubería de aluminio de 1.5” donde puede pasar máximo 4 conductores y de estos
uno debe ser sin carga como máximo.
Pt = 65193+5122+65193+5122+70315+18626+1855 = 161111 W
Q t = 36732}2893+36732+2893+9539+940 = 89729 W
st = 74929+5883+74929+5883+20927+2080= 184631 W