PERIODOS Y MODOS

Period
Case Mode UX UY UZ
sec
Modal 1 0.225 0.7411 0 0
Modal 2 0.219 0 0.7434 0
Modal 3 0.216 0.0308 0 0
Modal 4 0.066 0.1511 0 0
Modal 5 0.058 0 0.1769 0
Modal 6 0.054 0.0035 0 0
Modal 7 0.034 0.0457 0 0
Modal 8 0.029 0 0.0545 0
Modal 9 0.025 0.0002 0 0
Modal 10 0.023 0.0203 0 0
Modal 11 0.019 0 0.0203 0
Modal 12 0.018 0.0063 0 0
Modal 13 0.016 0.0007 0 0
Modal 14 0.015 0 0.0049 0
Modal 15 0.013 0.0003 0 0

ESPECTRO DE RESPUESTA

DATOS T
0.01
Z 0.45 0.4
U 1 0.45
S 1 0.5
Tp 0.4 0.55
Tl 2.5 0.6
R 3 0.65
g 9.81 0.7
0.75
0.8
0.85
0.9
0.95
1

DISTORSIONES EJE XX
Load
Story Direction Drift
Case/Combo
Drift*0.75*R cumple?
Story5 sismoXX Max X 0.000466
0.0010485 si
Story4 sismoXX Max X 0.000579
0.00130275 si
Story3 sismoXX Max X 0.000641
0.00144225 si
Story2 sismoXX Max X 0.000606
0.0013635 si
Story1 sismoXX Max X 0.000362
0.0008145 si

DISTORSIONES EJE YY

Story Load Direction Drift


Case/Combo
Drift*0.75*R cumple?
Story5 sismoYY Max Y 0.000532
0.001197 si
Story4 sismoYY Max Y 0.00059
0.0013275 si
Story3 sismoYY Max Y 0.000599
0.00134775 si
Story2 sismoYY Max Y 0.000513
0.00115425 si
Story1 sismoYY Max Y 0.000278
0.0006255 si

FUERZA CORTANTE MINIMA EN LA BASE

FUERZA CORTANTE ESTATICA

V=ZUSCP/R

DATOS

Z 0.45
U 1
S 1
Tp 0.4 Vx=Vy= 186387.513138 Kg
Tl 2.5
R 3
C= 2.5
Peso= 497033.3684

Diaphrag Mass X
Story
m kgf-s²/m
Story1 LOSA1 10691.58
Story2 LOSA2 10746.65
Story3 LOSA3 10746.65
Story4 LOSA4 10746.65
Story5 LOSA5 7751.51
50683.04
Peso Total
497033.368368 Kg

Verificacion
Peso1 104849.117586
Area1 122.4

Peso/Area 856.610437794 Kg/m2

Fuerza cortante minima

Eje Ve en Kg 80% Ve Vd Cumple?


x 186387.513 149110 146410.18 no
y 186387.513 149110 142981.85 no

Load P VX
Story Case/Comb Location
o kgf kgf
sismoXX
Story1 Bottom 0 146410.18
Max
sismoYY
Story1 Bottom 0 144.33
Max

Cortante minimo Escalado:

Load P VX
Story Case/Comb Location
o kgf kgf
sismoXX
Story1 Bottom 0 149338.64
Max

Story1 sismoYY Bottom 0 150.54


Max
Sum UX Sum UY Sum UZ RX RY RZ Sum RX

0.7411 0 0 0 0.2917 0.0315 0


0.7411 0.7434 0 0.3376 0 0 0.3376
0.7719 0.7434 0 0 0.0143 0.6957 0.3376
0.923 0.7434 0 0 0.4921 0.0024 0.3376
0.923 0.9203 0 0.4504 0 0 0.788
0.9265 0.9203 0 0 0.0073 0.1823 0.788
0.9722 0.9203 0 0 0.1066 0.0009 0.788
0.9722 0.9748 0 0.1333 0 0 0.9213
0.9724 0.9748 0 0 0.0004 0.0587 0.9213
0.9927 0.9748 0 0 0.0663 0 0.9213
0.9927 0.9951 0 0.0638 0 0 0.9851
0.9991 0.9951 0 0 0.0186 0.0004 0.9851
0.9997 0.9951 0 0 0.0019 0.0222 0.9851
0.9997 1 0 0.0149 0 0 1
1 1 0 0 0.0008 0.006 1

C Sa Sa sin G
2.5 3.67875 0.375
2.5 3.67875 0.375
2.22222222222 3.27 0.33333333333333
2 2.943 0.3
1.81818181818 2.67545454545455 0.27272727272727
1.66666666667 2.4525 0.25
1.53846153846 2.26384615384615 0.23076923076923
1.42857142857 2.10214285714286 0.21428571428572
1.33333333333 1.962 0.2
1.25 1.839375 0.1875
1.17647058824 1.73117647058823 0.17647058823529
1.11111111111 1.635 0.16666666666667
1.05263157895 1.54894736842105 0.15789473684211
1 1.4715 0.15
Nro Escalar
1.01844018299 1.02 149338.3836
1.04285970919 1.043 149130.06955

VY T MX MY

kgf kgf-m kgf-m kgf-m

144.33 648736.21 1136.61 1299195.78


147.2166
142981.85 1187510.3 1279569.73 1137.26

VY T MX MY

kgf kgf-m kgf-m kgf-m


147.22 661712.05 1159.34 1325181.92

149131 1238580.97 1334599.56 1186.17


Sum RY Sum RZ

0.2917 0.0315
0.2917 0.0315
0.306 0.7272
0.7981 0.7296
0.7981 0.7296
0.8054 0.9119
0.912 0.9128
0.912 0.9128
0.9124 0.9715
0.9787 0.9715
0.9787 0.9715
0.9973 0.9719
0.9992 0.994
0.9992 0.994
1 1
PREDIMENCIONAMIENTO

LOSAS MACIZAS

Luz libre menor a 4m

Espesor de losa= 0.12m

ESPESOR DE MUROS

t= h/20
t= 12.6 m
t= 13 m
PERIODOS Y MODOS

Period
Case Mode UX UY
sec
Modal 1 0.473 0.0011 0.0039
Modal 2 0.462 0.0001 0.7368
Modal 3 0.309 0.6987 3.15E-05
Modal 4 0.117 1.03E-06 0.1517
Modal 5 0.113 0.0006 8.53E-06
Modal 6 0.078 0 0.0232
Modal 7 0.07 0.1966 2.53E-06
Modal 8 0.052 0.0017 2.08E-06
Modal 9 0.049 6.42E-07 0.0506
Modal 10 0.039 0.0256 0
Modal 11 0.032 0.0011 0
Modal 12 0.03 1.01E-06 0.0238
Modal 13 0.028 0.0478 0
Modal 14 0.025 1.70E-05 0
Modal 15 0.022 0 0.0086

ESPECTRO DE RESPUESTA

DATOS

Z 0.45
U 1
S 1
Tp 0.4
Tl 2.5
R 3
g 9.81

DISTORSIONES EJE XX

Story Load Case/Combo Direction Drift


Drift*0.75*R

Story7 SDIN_COMBINACIÓN Max X 0.000589 0.00132525

Story6 SDIN_COMBINACIÓN Max X 0.000611 0.00137475

Story5 SDIN_COMBINACIÓN Max X 0.000771 0.00173475


Story4 SDIN_COMBINACIÓN Max X 0.000823 0.00185175

Story3 SDIN_COMBINACIÓN Max X 0.000778 0.0017505

Story2 SDIN_COMBINACIÓN Max X 0.000626 0.0014085

Story1 SDIN_COMBINACIÓN Max X 0.0003 0.000675

DISTORSION
ES EJE YY

Story Load Case/Combo Direction Drift


Drift*0.75*R

Story5 SDIN_COMBINACIÓN Max Y 0.000164 0.000369

Story4 SDIN_COMBINACIÓN Max Y 0.000223 0.00050175

Story3 SDIN_COMBINACIÓN Max Y 0.000234 0.0005265

Story2 SDIN_COMBINACIÓN Max Y 0.000204 0.000459

Story1 SDIN_COMBINACIÓN Max Y 0.000104 0.000234

DETERMINACION DE LA FUERZA CORTANTE MINIMA EN LA BASE

DATOS

Z 0.45
U 1
S 1 VE=
C 2.5
R 3 VEx=VEy=
P 924749.842992 Kg

Mass X Mass Y
Story Diaphragm
Story Diaphragm
tonf-s²/m tonf-s²/m
Story1 D1 19.63139 19.63139
Story2 D2 19.63139 19.63139
Story3 D3 19.63139 19.63139
Story4 D4 19.63139 19.63139
Story5 D5 15.7722 15.7722
94.29776
PESO TOTAL 924.749842992

Fuerza cortante minima

Eje Ve en Kg 80% Ve Vd Cumple?


x 346781.191122 277424.952898 158228.4 no
y 346781.191122 277424.952898 1939.5 no

P VX
Story Load Case/Combo Location
tonf tonf
Story1 SDIN_COMBINACIÓN Max Bottom 0 158.2284
Story1 SDIN_COMBINACIÓN Max Bottom 0 158.2284

Cortante minimo Escalado:

P VX
Story Load Case/Combo Location
kgf kgf
Story1 sismoXX Max Bottom 0 277374.385
Story1 sismoYY Max Bottom 0 277374.385
UZ Sum UX Sum UY Sum UZ RX RY RZ Sum RX

0 0.0011 0.0039 0 0.0017 0.0021 0.7427 0.0017


0 0.0011 0.7407 0 0.3382 4.49E-05 0.0037 0.3399
0 0.6999 0.7407 0 1.63E-05 0.3821 0.0013 0.3399
0 0.6999 0.8924 0 0.4173 1.47E-06 5.14E-06 0.7572
0 0.7004 0.8924 0 1.78E-05 0.0007 0.1658 0.7572
0 0.7004 0.9156 0 0.0326 0 1.10E-06 0.7898
0 0.897 0.9156 0 0 0.3607 0.0009 0.7898
0 0.8987 0.9156 0 6.20E-06 0.0031 0.0548 0.7898
0 0.8987 0.9662 0 0.1122 2.98E-06 3.53E-06 0.9021
0 0.9242 0.9662 0 0 0.0513 0.0018 0.9021
0 0.9253 0.9662 0 0 0.0023 0.0218 0.9021
0 0.9253 0.9899 0 0.0705 1.84E-06 0 0.9726
0 0.9731 0.9899 0 0 0.1195 0.0001 0.9726
0 0.9731 0.9899 0 6.85E-07 4.62E-05 0.0069 0.9726
0 0.9731 0.9985 0 0.0228 0 0 0.9954

cumple?

si

si

si
si

si

si

si

cumple?

si

si

si

si

si

ZUSCP/R

346781.191 Kg
Nro Escalar
1.75331959 1.753 277374.385
143.039419 143.039 277424.141

VY T MX MY
tonf tonf-m tonf-m tonf-m
1.9395 1431.4179 18.1913 1411.5121
1.9395 1431.4179 18.1913 1411.5121

VY T MX MY
kgf kgf-m kgf-m kgf-m
3399.9435 2509275.579 31889.3489 2474380.71
3399.9435 2509275.579 31889.3489 2474380.71
Sum RY Sum RZ

0.0021 0.7427
0.0021 0.7464
0.3842 0.7477
0.3842 0.7477
0.3849 0.9134
0.3849 0.9134
0.7456 0.9144
0.7487 0.9691
0.7487 0.9691
0.7999 0.971
0.8023 0.9928
0.8023 0.9928
0.9218 0.9929
0.9218 0.9998
0.9218 0.9998
PARA SISMO SEVERO R=3

Load P V2 V3
Story Pier Case/Comb Location
o kgf kgf kgf
sismoYY
Story1 M1Y Bottom 1047.57 5410.53 0.94
Max
sismoYY
Story1 M2Y Max Bottom 5403.29 9187.74 3.69

sismoYY
Story1 M3Y Bottom 7302.19 8687.16 12.87
Max

Story1 M4Y sismoYY Bottom 26712.1 12216.34 0.66


Max
sismoYY
Story1 M5Y Bottom 7321.8 8713.28 13.26
Max
sismoYY
Story1 M6Y Bottom 5426.62 9315.66 3.29
Max
sismoYY
Story1 M7Y Bottom 1077.15 5574.36 0.62
Max
sismoYY
Story1 P8Y Bottom 4841.57 26730.62 3.78
Max
sismoYY
Story1 M9Y Bottom 1962.92 7889.31 1.52
Max
sismoYY
Story1 M10Y Bottom 20012.1 9940.94 7.57
Max
sismoYY
Story1 M11Y Bottom 20016.89 9969.8 7.49
Max
sismoYY
Story1 M12Y Bottom 1926.87 8005.85 1.84
Max
sismoYY
Story1 P13Y Bottom 4970.87 26306.27 4.33
Max

PARA UN SISMO MODERADO R=6


Load V2 M3
Story Pier Case/Comb Location
o kgf kgf-m

Story1 M1Y sismoYY Bottom 2705.265 7862.725


Max
sismoYY
Story1 M2Y Bottom 4593.87 11340.845
Max
sismoYY
Story1 M3Y Bottom 4343.58 11482.83
Max

Story1 M4Y sismoYY Bottom 6108.17 19184.555


Max
sismoYY
Story1 M5Y Bottom 4356.64 11508.005
Max
sismoYY
Story1 M6Y Bottom 4657.83 11440.18
Max
sismoYY
Story1 M7Y Max Bottom 2787.18 7984.855

sismoYY
Story1 P8Y Bottom 13365.31 47684.075
Max
sismoYY
Story1 M9Y Bottom 3944.655 11536.39
Max
sismoYY
Story1 M10Y Max Bottom 4970.47 11386.995

sismoYY
Story1 M11Y Bottom 4984.9 11411.73
Max

Story1 M12Y sismoYY Bottom 4002.925 11637.4


Max
sismoYY
Story1 P13Y Bottom 13153.135 47267.74
Max

RESISTENCIA AL CORTE DE LOS MUROS


v'm L α α
Story Pier
Kg/cm2 m corregido
Story1 M1Y 8.1 2.6 0.89456124 0.89456124
Story1 M2Y 8.1 3.1 1.25572627 1
Story1 M3Y 8.1 3.1 1.17262887 1
Story1 M4Y 8.1 4 1.2735599 1
Story1 M5Y 8.1 3.1 1.17358169 1
Story1 M6Y 8.1 3.1 1.26215435 1
Story1 M7Y 8.1 2.6 0.90755161 0.90755161
Story1 P8Y 2.6
Story1 M9Y 8.1 3.1 1.05998761 1
Story1 M10Y 8.1 3.1 1.35316271 1
Story1 M11Y 8.1 3.1 1.35414963 1
Story1 M12Y 8.1 3.1 1.06630927 1
Story1 P13Y 2.6

Pg

Load P V2
Story Pier Case/Comb Location
o kgf kgf
Story1 M1Y Pg Bottom -16650.93 238.3
Story1 M2Y Pg Bottom -21113.7 267.19
Story1 M3Y Pg Bottom -19919.41 42.55
Story1 M4Y Pg Bottom -24318.94 -246.3
Story1 M5Y Pg Bottom -19946.39 44.88
Story1 M6Y Pg Bottom -21126.13 268.22
Story1 M7Y Pg Bottom -16727.46 238.03
Story1 P8Y Pg Bottom -38215.52 239.94
Story1 M9Y Pg Bottom -17068.24 -501.92
Story1 M10Y Pg Bottom -16302.07 -138.17
Story1 M11Y Pg Bottom -16436.61 -125.72
Story1 M12Y Pg Bottom -17042.11 -502.08
Story1 P13Y Pg Bottom -38289.09 239.25
T M2 M3

kgf-m kgf-m kgf-m

0.62 0.87 15725.45

1.28 3.12 22681.69

13.01 10.47 22965.66

0.53 0.7 38369.11

12.76 10.97 23016.01

1.58 2.62 22880.36

0.42 0.46 15969.71

3.8 2.68 95368.15

1.07 1.16 23072.78

6.52 6.27 22773.99

6.74 6.08 22823.46


1.37 1.62 23274.8

5.58 3.18 94535.48


t Pg Vm Vc
cm Kg Kg Kg
13 16650.93 16075.3627
13 21113.7 21177.651
13 19919.41 20902.9643
13 24318.94 26653.3562
13 19946.39 20909.1697
13 21126.13 21180.5099
13 16727.46 16270.7898
13 23697.9945
13 17068.24 20247.1952
13 16302.07 20070.9761
13 16436.61 20101.9203
13 17042.11 20241.1853
13 23697.9945

V3 T M2 M3

kgf kgf-m kgf-m kgf-m


0.31 0.18 0.24 280.98
1 0.22 0.8 314.75
-6.73 3.62 -5.53 370.76
0.01 -0.05 -0.01 1165.26
6.53 -3.53 5.34 368.69
-1.02 -0.23 -0.85 307.76
-0.31 -0.18 -0.27 274.86
6.88 -7.87 5.57 1431.96
2.63 -2.34 2.14 524.42
-0.39 -0.3 -0.34 396.12
0.43 0.34 0.34 390.84
-2.63 2.34 -2.17 517.83
-6.22 8.14 -4.47 1389.44
DISEÑO

1 la verificación de la necesidad de refuerzo horizontal en el muro;

V2 Vm Vc
Story Pier
kgf Kg Kg cumple Vu≥ Vm ?
Story1 M1Y 5410.53 16075.3627 no
Story1 M2Y 9187.74 21177.651 no
Story1 M3Y 8687.16 20902.9643 no
Story1 M4Y 12216.34 26653.3562 no
Story1 M5Y 8713.28 20909.1697 no
Story1 M6Y 9315.66 21180.5099 no
Story1 M7Y 5574.36 16270.7898 no
Story1 P8Y 26730.62 23697.9945 si
Story1 M9Y 7889.31 20247.1952 no
Story1 M10Y 9940.94 20070.9761 no
Story1 M11Y 9969.8 20101.9203 no
Story1 M12Y 8005.85 20241.1853 no
Story1 P13Y 26306.27 23697.9945 si

PRIMER
PISO
Pm L t
Story Pier
Kg m cm sm en Kg/cm2
Story1 M1Y 19206.35 2.6 13 5.68235207100592
Story1 M2Y 24635.84 3.1 13 6.11311166253102
Story1 M3Y 22991.62 3.1 13 5.70511662531017
Story1 M4Y 27797.43 4 13 5.34565961538462
Story1 M5Y 23023.48 3.1 13 5.7130223325062
Story1 M6Y 24650.52 3.1 13 6.11675434243176
Story1 M7Y 19296.83 2.6 13 5.70912130177515
Story1 P8Y 44068.42 2.6 13
Story1 M9Y 20124.82 3.1 13 4.99375186104218
Story1 M10Y 18857.47 3.1 13 4.6792729528536
Story1 M11Y 19016.45 3.1 13 4.71872208436725
Story1 M12Y 20093.95 3.1 13 4.98609181141439
Story1 P13Y 44155.28 2.6 13

Pm
Load P
Story Pier Case/Comb Location
o kgf
Story1 M1Y Pm Bottom -19206.35
Story1 M2Y Pm Bottom -24635.84
Story1 M3Y Pm Bottom -22991.62
Story1 M4Y Pm Bottom -27797.43
Story1 M5Y Pm Bottom -23023.48
Story1 M6Y Pm Bottom -24650.52
Story1 M7Y Pm Bottom -19296.83
Story1 P8Y Pm Bottom -44068.42
Story1 M9Y Pm Bottom -20124.82
Story1 M10Y Pm Bottom -18857.47
Story1 M11Y Pm Bottom -19016.45
Story1 M12Y Pm Bottom -20093.95
Story1 P13Y Pm Bottom -44155.28

SEGUNDO
PISO
Pm L t
Story Pier
Kg m cm sm en Kg/cm2
Story2 M1Y 15433.28 2.6 13 4.56605917159763
Story2 M2Y 19525.37 3.1 13 4.84500496277916
Story2 M3Y 18243.53 3.1 13 4.52693052109181
Story2 M4Y 22157.15 4 13 4.26099038461538
Story2 M5Y 18279.85 3.1 13 4.5359429280397
Story2 M6Y 19537.99 3.1 13 4.8481364764268
Story2 M7Y 15522.57 2.6 13 4.59247633136095
Story2 P8Y 37145.76 2.6 13
Story2 M9Y 14693.06 3.1 13 3.6459205955335
Story2 M10Y 14526.27 3.1 13 3.60453349875931
Story2 M11Y 14748.1 3.1 13 3.65957816377171
Story2 M12Y 14660.13 3.1 13 3.63774937965261
Story2 P13Y 37228.88 2.6 13

pm
Load P
Story Pier Case/Comb Location
o kgf
Story2 M1Y Pm Bottom -15433.28
Story2 M2Y Pm Bottom -19525.37
Story2 M3Y Pm Bottom -18243.53
Story2 M4Y Pm Bottom -22157.15
Story2 M5Y Pm Bottom -18279.85
Story2 M6Y Pm Bottom -19537.99
Story2 M7Y Pm Bottom -15522.57
Story2 P8Y Pm Bottom -37145.76
Story2 M9Y Pm Bottom -14693.06
Story2 M10Y Pm Bottom -14526.27
Story2 M11Y Pm Bottom -14748.1
Story2 M12Y Pm Bottom -14660.13
Story2 P13Y Pm Bottom -37228.88
TERCER
PISO
Pm L t
Story Pier
Kg m cm sm en Kg/cm2
Story3 M1Y 11521.9 2.6 13 3.40884615384615
Story3 M2Y 14455.71 3.1 13 3.58702481389578
Story3 M3Y 13474.78 3.1 13 3.34361786600496
Story3 M4Y 16415.09 4 13 3.15674807692308
Story3 M5Y 13521.38 3.1 13 3.35518114143921
Story3 M6Y 14464.98 3.1 13 3.58932506203474
Story3 M7Y 11605.5 2.6 13 3.4335798816568
Story3 P8Y 28296.53 2.6 13
Story3 M9Y 10454.63 3.1 13 2.59420099255583
Story3 M10Y 10396.58 3.1 13 2.57979652605459
Story3 M11Y 10781.27 3.1 13 2.67525310173697
Story3 M12Y 10419.82 3.1 13 2.58556327543424
Story3 P13Y 28370.86 2.6 13

Pm
Load P
Story Pier Case/Comb Location
o kgf
Story3 M1Y Pm Bottom -11521.9
Story3 M2Y Pm Bottom -14455.71
Story3 M3Y Pm Bottom -13474.78
Story3 M4Y Pm Bottom -16415.09
Story3 M5Y Pm Bottom -13521.38
Story3 M6Y Pm Bottom -14464.98
Story3 M7Y Pm Bottom -11605.5
Story3 P8Y Pm Bottom -28296.53
Story3 M9Y Pm Bottom -10454.63
Story3 M10Y Pm Bottom -10396.58
Story3 M11Y Pm Bottom -10781.27
Story3 M12Y Pm Bottom -10419.82
Story3 P13Y Pm Bottom -28370.86

CUARTO
PISO
Pm L t
Story Pier
Kg m cm sm en Kg/cm2
Story3 M1Y 7518.5 2.6 13 2.22440828402367
Story3 M2Y 9426.06 3.1 13 2.33897270471464
Story3 M3Y 8737.56 3.1 13 2.16812903225806
Story3 M4Y 10683.44 4 13 2.05450769230769
Story3 M5Y 8805.86 3.1 13 2.18507692307692
Story3 M6Y 9431.53 3.1 13 2.3403300248139
Story3 M7Y 7584.22 2.6 13 2.24385207100592
Story3 P8Y 18288.36 2.6 13
Story3 M9Y 6956.41 3.1 13 1.72615632754342
Story3 M10Y 6250.26 3.1 13 1.55093300248139
Story3 M11Y 6987.96 3.1 13 1.73398511166253
Story3 M12Y 6926.37 3.1 13 1.71870223325062
Story3 P13Y 18342.3 2.6 13

Pm
Load P
Story Pier Case/Comb Location
o kgf
Story4 M1Y Pm Bottom -7518.5
Story4 M2Y Pm Bottom -9426.06
Story4 M3Y Pm Bottom -8737.56
Story4 M4Y Pm Bottom -10683.44
Story4 M5Y Pm Bottom -8805.86
Story4 M6Y Pm Bottom -9431.53
Story4 M7Y Pm Bottom -7584.22
Story4 P8Y Pm Bottom -18288.36
Story4 M9Y Pm Bottom -6956.41
Story4 M10Y Pm Bottom -6250.26
Story4 M11Y Pm Bottom -6987.96
Story4 M12Y Pm Bottom -6926.37
Story4 P13Y Pm Bottom -18342.3

2 . la verificación del agrietamiento diagonal en los entrepisos superiores; y,

PRIMER PISO

V2 Vm Vc
Story Pier
kgf Kg Kg 0.55Vm
Story1 M1Y 2705.265 16075.3627 884144.946821333
Story1 M2Y 4593.87 21177.651 1164770.805
Story1 M3Y 4343.58 20902.9643 1149663.0365
Story1 M4Y 6108.17 26653.3562 1465934.591
Story1 M5Y 4356.64 20909.1697 1150004.3335
Story1 M6Y 4657.83 21180.5099 1164928.0445
Story1 M7Y 2787.18 16270.7898 894893.437386339
Story1 P8Y 13365.31 23697.9945 0
Story1 M9Y 3944.655 20247.1952 1113595.736
Story1 M10Y 4970.47 20070.9761 1103903.6855
Story1 M11Y 4984.9 20101.9203 1105605.6165
Story1 M12Y 4002.925 20241.1853 1113265.1915
Story1 P13Y 13153.135 23697.9945 0
223831.08 47395.989

verificacion de la resistencia al corte del edificio


∑Vm1= 271227.069 Kg relacion 1.81871689606152
VE= 149131 Kg

3 el diseño de los confinamientos para la combinación de fuerzas de corte, compresión o tracción y corte fricc

MURO 1Y
rectangular Ele
1) Pg= 16.65093 16.65093
2) Vu= 5.41053 5.41053
3) Mu= 15.72545 15.72545
4) L= 2.6 2.6
5) Lm= 2.6 2.6
6) Nc= 2 2
7) F= 6.04825 6.04825
8) Pc= 8.325465 8.325465
9) Pt= 0 5.144308

Load P
Story Pier Case/Comb Location
o kgf
Story1 M1X Pg Bottom -19785.8
Pg 19.7858
L 3
Lt= 0.75
o Lt= 0.78
Pt= 5.144308

10) T= -2.277215 -7.421523


11) C= 14.373715 14.373715
12) As= -0.60243783 -1.96336587
13) As= 2.84 5.68

4 de 3/8" 8 de 3/8"

2.84 5.68 cm2


14) Factor conf. 0.8 1
15) An= 75.1583073 -16.6535894
16) Dimensiones de columnas
25cm

25cm 25cm

13cm 13cm

17) Ac= 325 481


18) An= 189 297
19) Asmin= 1.35416667 2.00416667 cm2
4 de 3/8" 8 de 3/8"
estibos será [] 6mm, 1 @ 5, 4@ 10, r @ 25 cm.

Diseño de la Viga solera

20) Ts= 2.705265


21) As= 0.715678571428571
22) As a utilizar

30cm Asmin= 1.625 cm2

13cm

4 de 3/8"
estibos será [] 6mm, 1 @ 5, 4@ 10, r @ 25 cm.
ENTONCES

NO LLEVA REFUERZO HORIZONTAL CONTINUO


NO LLEVA REFUERZO HORIZONTAL CONTINUO
NO LLEVA REFUERZO HORIZONTAL CONTINUO
NO LLEVA REFUERZO HORIZONTAL CONTINUO
NO LLEVA REFUERZO HORIZONTAL CONTINUO
NO LLEVA REFUERZO HORIZONTAL CONTINUO
NO LLEVA REFUERZO HORIZONTAL CONTINUO

NO LLEVA REFUERZO HORIZONTAL CONTINUO


NO LLEVA REFUERZO HORIZONTAL CONTINUO
NO LLEVA REFUERZO HORIZONTAL CONTINUO
NO LLEVA REFUERZO HORIZONTAL CONTINUO

ENTONCES
0.05f`m cumple sm≥ 0.05f`m ?
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO

3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO


3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
ENTONCES
0.05f`m cumple sm≥ 0.05f`m ?
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO

3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO


3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
ENTONCES
0.05f`m cumple sm≥ 0.05f`m ?
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 no NO LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 si LLEVA REFUERZO HORIZONTAL CONTINUO

3.25 NO NO LLEVA REFUERZO HORIZONTAL CONTINUO


3.25 NO NO LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 NO NO LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 NO NO LLEVA REFUERZO HORIZONTAL CONTINUO

ENTONCES
0.05f`m cumple sm≥ 0.05f`m ?
3.25 NO NO LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 NO NO LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 NO NO LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 NO NO LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 NO NO LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 NO NO LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 NO NO LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 NO NO LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 NO NO LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 NO NO LLEVA REFUERZO HORIZONTAL CONTINUO
3.25 NO NO LLEVA REFUERZO HORIZONTAL CONTINUO

Cumple? Entonces
Ve≤ 0.55Vm
si no hay agrietamiento por corte
si no hay agrietamiento por corte
si no hay agrietamiento por corte
si no hay agrietamiento por corte
si no hay agrietamiento por corte
si no hay agrietamiento por corte
si no hay agrietamiento por corte
si no hay agrietamiento por corte
si no hay agrietamiento por corte
si no hay agrietamiento por corte
si no hay agrietamiento por corte
si no hay agrietamiento por corte
si no hay agrietamiento por corte
se comporta inelasticamente

sión o tracción y corte fricción.


ton
m
m
m
ton