Resolucion examen final albañilería Estructural 07-abr-09

PROBLEMA 1
Diseñar el muro del eje A (1° Piso) en albañilería confinada

3.00 1.00
X-2

Y-1 Y-2
Losa Aligerada 5.50
h=0.20 m

X-1
2.50

1.50 2.50

DATOS DE LA EDIFICACION:
Vivienda 3 pisos, ubicación Arequipa
Suelo Intermedio
Muros solidos en soga (t=0.14)
f'm= 800 Ton/m2 v'm= 85 Ton/m2
f'c= 210 kg/cm2 fy= 4200 kg/cm2
h= 2.4 m Em= 400000 Ton/m2
Lx= 4.65 m
S/C = 0.25 Ton/m2 Tipico Ly= 5.15 m
S/C = 0.15 Ton/m2 Azotea

1. Calculo del peso total de la edificacion: Wi  Wcm  %Wcv

Metrado de cargas
AREA= 23.95 m2
PISO TIPICO 1, 2 Y 3 25%S/C 100%S/C
MURO L E H PE Pg Pm LxE
X1 2.50 0.25 2.4 1.9 2.85 2.85 0.6250
X2 3.00 0.25 2.4 1.9 3.42 3.42 0.7500
Y1 5.65 0.15 2.4 1.9 3.86 3.86 0.8475
Y2 5.65 0.15 2.4 1.9 3.86 3.86 0.8475
LOSA 5.15 4.65 0.3 7.18 7.18 3.0700 m2
Pt 5.35 3.85 0.1 2.06 2.06
S/C 5.35 3.85 0.25 1.29 5.15
Peso total 24.53 28.39
Peso por m2 1.02 1.19 ton/m2
PISO 4 (AZOTEA)
MURO L E H PE Pg Pm 9.975
X1 2.50 0.25 1.2 1.9 1.43 1.43
X2 3.00 0.25 1.2 1.9 1.71 1.71
Y1 5.65 0.15 1.2 1.9 1.93 1.93
Y2 5.65 0.15 1.2 1.9 1.93 1.93
LOSA 5.15 4.65 0.3 7.18 7.18
Pt 5.35 3.85 0.1 2.06 2.06
S/C 5.35 3.85 0.15 0.77 3.09
Peso total 17.02 19.33
Peso por m2 0.71 0.81 ton/m2

25%S/C 100%S/C
Piso hi Wg(ton/m2) Pg(ton) Wm(ton/m2) Pm(ton)
1 2.6 1.02 24.53 1.19 28.39
2 2.6 1.02 24.53 1.19 28.39
3 2.6 1.02 24.53 1.19 28.39
4 2.6 0.71 17.02 0.81 19.33
∑= 90.61 104.51

2. Densidad Minima de Muros:


Z 0.4
U 1.0
S 1.2
N 3
ZUSN/56 0.0257

Muros direccion X

MURO t (m) L (m) L*t (m)


X-1 0.24 2.500 0.600
X-2 0.24 3.000 0.720
∑= 1.3200 OK
∑ L.t/Ap= 0.0551 NO PASA

0.0551 > 0.0257 OK

Muros direccion Y

MURO t (m) L(m) L*t (m)


Y-1 0.14 5.650 0.791
Y-2 0.14 5.650 0.791
∑= 1.500
∑ L.t/Ap 0.0626

0.0626 > 0.0257 OK

3. Calculo del Cortante Basal

Z U  C  S
v  Pi
R
Según la Norma Tecnica de Edificacion E. 030

CALCULO DEL FACTOR DE ZONA (Z)

La edificacion se encuentra en Arequipa, por lo tanto se encuentra en una zona tipo 3


Según eso :

Z= 0.4

CALCULO DE LA CATEGORIA DE USO (U)

Por ser una edificación comun (Vivienda Multifamiliar) , es de categoria C


Según eso:

U= 1.0
CALCULO DEL FACTOR DEL SUELO (S)

Por ser un suelo intermedio cuyos componentes principales son la arena y la grava,
es de tipo S2; Según eso:

S= 1.2

CALCULO DEL FACTOR DE AMPLIFICACION SISMICA (C)

T 
C  2.5   P  C  2.5 T 
hn
T  CT
Por ser suelo tipo S2, el periodo del suelo es :

Tp = 0.6

La altura de la edificacion es de :

hn = 10.40 m

Como en la edificación hay predominio de muros de corte y elementos de concreto


armado, entonces:

Ct = 60

Entonces:
T= 0.17
C= 8.65

Como C no debe ser mayor de 2,5, entonces:

C= 2.50

CALCULO DEL COEFICIENTE DE REDUCCION DE FUERZA SISMICA (R)

Consideraremos un sismo moderado, entonces:

R= 6

Por ultimo se verifica que:


C
 0.1
R

C/R = 0.42 OK ! ! !

FUERZA CORTANTE EN LA BASE

V= 18.12 Tn % Peso Total = 20 %

DISTRIBUCION DEL CORTANTE BASAL Pi  hi


Fi  v
 P  h 
i i

Pi  h i Fi Cortante
Piso Pi hi Pi x hi  P i  hi 
por piso Vp
1 24.53 2.6 63.78 0.11 2.07 18.12
2 24.53 5.2 127.56 0.23 4.13 16.06
3 24.53 7.8 191.34 0.34 6.20 11.93
4 17.02 10.4 176.97 0.32 5.73 5.73
 559.64 18.12

5.73
5.73

6.20
11.93

4.13
16.06

2.07
18.12

4. CENTRO DE MASAS

MURO t (m) L (m) h (m) γ(ton/m3) Peso (tn) Y X P*Y P*X


X-1 0.25 2.500 2.4 1.9 2.85 0.075 2.825 0.21 8.05
X-2 0.25 3.000 2.4 1.9 3.42 5.575 1.575 19.07 5.39

Y-1 0.15 5.650 2.4 1.9 3.86 2.825 0.075 10.92 0.29
Y-2 0.15 5.650 2.4 1.9 3.86 2.825 4.075 10.92 15.75
14.00 41.12 29.48

Por lo tanto :

X cm = 2.11 m
Y cm = 2.94 m

5. CALCULO CENTRO DE RIGIDECES.


Εm  t
K 3
h h
1er piso 4   3 
L L

Dirección X
MURO t (m) h (m) L (m) Kx Y Kx*Y
X-1 0.24 2.4 2.500 14955.731 0.075 1121.680
X-2 0.24 2.4 3.000 21582.7338 5.575 120323.741
∑ 36538.4648 121445.421
Ycr = 3.32 m.
Dirección Y
MURO t (m) h (m) L (m) Ky X Ky*X
Y-1 0.14 2.4 5.65 35422.4235 0.075 2656.682
Y-2 0.14 2.4 5.65 35422.4235 4.075 144346.376
∑ 70844.8471 147003.058
Xcr = 2.08 m.

6. CORTANTE TRASLACIONAL.
Ki
VD  V
K i

Piso 1

Muros K Vp Vd Muros K V Vd
X-1 14955.73 18.12 7.42 Y-1 35422.42 18.12 9.06
X-2 21582.73 18.12 10.70 Y-2 35422.42 18.12 9.06
∑ 36538.46 ∑ 70844.85

Piso 2

Muros K V Vd Muros K V Vd
X-1 2526.32 16.06 6.14 Y-1 10318.65 16.06 8.03
X-2 4081.89 16.06 9.92 Y-2 10318.65 16.06 8.03
∑ 6608.21 ∑ 20637.29

Piso 3

Muros K V Vd Muros K V Vd
X-1 790.14 11.93 4.46 Y-1 4066.57 11.93 5.96
X-2 1321.70 11.93 7.46 Y-2 4066.57 11.93 5.96
∑ 2111.84 ∑ 8133.13

Piso 4

Muros K V Vd Muros K V Vd
X-1 338.14 5.73 2.13 Y-1 1934.30 5.73 2.87
X-2 573.42 5.73 3.60 Y-2 1934.30 5.73 2.87
∑ 911.56 ∑ 3868.61

7. EXCENTRICIDADES DE DISEÑO Y MOMENTOS TORSORES

Lx = 4.65 m Accidental Diseño (La mayor)


ex  X cr  X cm
e xacc  0 . 05  L y e  e ex  exacc
Ly = 5.15 m x xacc Ó

e y  Ycr  Ycm e yacc  0.05  L y e y  e yacc


e y  e yacc

Nivel Xcr Ycr Xcm Ycm ex ey exacc eyacc


Piso Tipico(1,2y3) 2.075 3.324 2.106 2.937 -0.031 0.387 0.233 0.258

Exc. De Diseño en X Exc. De Diseño en Y Exc. De


caso 1 caso 2 ex caso 1 caso 2 ey Diseño
0.202 -0.263 0.202 0.644 0.129 0.644 0.644

Momentos Torsores por nivel

MT Vp e
MT Vp e

Piso e Vp Mt (tn.m)
1 0.644 18.122 11.676
2 0.644 16.056 10.345
3 0.644 11.926 7.684
4 0.644 5.730 3.692

6. CORTANTE ROTACIONAL.
Rigidez  d d x  X  X CR d y  Y  YCR
VT  M
 Rigidez  d  2 T

Distribuido por muros


PRIMER PISO MT = 11.68 Tn-m
H= 2.40 m.

Muros K dx K*dx K*dx^2 Vt


X-1 14955.73 2.00 29911.4621 59822.9241 0.50
X-2 21582.73 2.00 43165.4676 86330.9353 0.72
∑ 146153.859

Muros K dy K*dy K*dy^2 Vt


Y-1 35422.42 3.25 115079.28 373866.00 1.92
Y-2 35422.42 2.25 79744.05 179522.28 1.33
∑ 553388.27
∑K.dx^2+∑K.dy^2= 699542.13

SEGUNDO PISO MT = 10.35 Tn-m


h= 5.00

Muros K d Kxd Kd^2 Vt


X-1 2526.32 2.00 5052.63 10105.2632 0.28
X-2 4081.89 2.00 8163.78 16327.5591 0.45
∑ 26432.8222

Muros K d Kxd Kd^2 Vt


Y-1 10318.65 3.25 33522.9029 108908.171 1.85
Y-2 10318.65 2.25 23229.6577 52295.323 1.28
∑ 161203.494
∑K.dx^2+∑K.dy^2= 187636.32

TERCER PISO MT = 7.68 Tn-m


H= 7.60

Muros K d Kxd Kd^2 Vt


X-1 790.14 2.00 1580.2748 3160.5496 0.22
X-2 1321.70 2.00 2643.40902 5286.81804 0.37
∑ 8447.36764

Muros K d Kxd Kd^2 Vt


Y-1 4066.57 3.25 13211.3321 42920.5677 1.84
Y-2 4066.57 2.25 9154.77769 3791.67 1.28
∑ 46712.2377
∑K.dx^2+∑K.dy^2= 55159.61

CUARTO PISO MT = 3.69 Tn-m


H= 10.20

Muros K d Kxd Kd^2 Vt


X-1 338.14 2.00 676.27244 1352.54488 0.09
X-2 573.42 2.00 1146.84379 2293.68758 0.16
∑ 3646.23246

Muros K d Kxd Kd^2 Vt


Y-1 1934.30 3.25 6284.10722 20415.6134 0.88
Y-2 1934.30 2.25 4354.565 3791.67 0.61
∑ 24207.2834
∑K.dx^2+∑K.dy^2= 27853.52

RESUMEN CORTANTES POR TORSION EN MUROS (Tn)

Muros 1º Piso 2º Piso 3º Piso 4° Piso


X-1 0.50 0.28 0.22 0.09
X-2 0.72 0.45 0.37 0.16
Y-1 1.92 1.85 1.84 0.88
Y-2 1.33 1.28 1.28 0.61

RESUMEN CORTANTES POR TRASLACION EN MUROS (Tn)

Muros 1º Piso 2º Piso 3º Piso 4° Piso


X-1 7.42 6.14 4.46 2.13
X-2 10.70 9.92 7.46 3.60
Y-1 8.03 8.03 5.96 2.87
Y-2 8.03 8.03 5.96 2.87

CORTANTES FINALES PARA CADA MURO DE ALBAÑILERIA: V E ( Tn )=Vt+Vd

Muros 1º Piso 2º Piso 3º Piso 4° Piso


X-1 7.92 5.86 4.24 2.03
X-2 9.98 10.37 7.83 3.76
Y-1 9.95 9.88 7.80 3.74
Y-2 6.70 6.75 4.69 2.26

MOMENTOS FINALES PARA CADA MURO DE ALBAÑILERIA: ME ( Tn-m ).

Muros 1º Piso 2º Piso 3º Piso 4º Piso


X-1 51.72 31.14 15.90 4.88
X-2 82.31 56.36 29.40 9.03
Y-1 80.81 54.94 29.27 8.98
Y-2 52.56 35.15 17.61 5.42