Ejercicio parcial
j∗5 MVA
G 1=0.15 =0.15 j=G 2 =G 3
5 MVA
Para la línea se tiene
0.15 Ω
X L= =0.01722 j
8.712Ω
Para el transformador
0.06∗5 MVA
XT = =0.3 j
1 MVA
Para el motor
S 100 kVA
S= √3 V M I M I L = = =139.121 A
√3 V M √ 3 0.415 kV
VM 0.415 kV X 2.98302 Ω
X M= = =2.98302 Ω X M = real = =0.3424
I M 0.139121 kA X base 8,7120 Ω
0.3424∗5 MVA
X M= =17.12 j
0.1 MVA
Corrientes máximas
1
X equi− gen= =0.05 j
1 1 1
+ +
0.15 j 0.15 j 0.15 j
Nodo A
1 1 1
I F ( pu)= = = =−20.0573 j
0.05 j∨¿(0.01722 j+0.3 j+17,12 j) 0.05 j∨¿ 17.4372 j 0.049857 j
j∗5 MVA
I F =−20.0573 =−8772.81 j [ A ] =−8.77281 j[kA]
√ 3∗6.6 kV
Nodo B
1 1 1
I F ( pu)= = = =−14.9339 j
(0.05 j+ 0.01722 j)∨¿(0.3 j+17,12 j) 0.06722 j∨¿17.42 j 0.067 j
j∗5 MVA
I F =−14.9339 =−6531.9 j [ A ] =−6.5319 j[kA]
√ 3∗6.6 kV
Nodo C
1 1 1
I F ( pu)= = = =−2.78157 j
( 0.05 j+0.01722 j+0.3 j ) ∨¿(17,12 j) 0.36722 j∨¿ 17.12 j 0.3595 j
j∗5 MVA
I F =−2.78157 =−19348.7 j [ A ]=−19.3487 j[kA ]
√ 3∗0.415 kV
Corrientes Mínimas
X equi− gen=0.15 j
Nodo A
1 1 1
I F ( pu)= = = =−6.72402 j
0.15 j∨¿(0.01722 j+0.3 j+17,12 j) 0.15 j∨¿ 17.4372 j 0.1487 j
j∗5 MVA
I F =−6.72402 =−2940.99 j [ A ] =−2.94099 j[kA]
√ 3∗6.6 kV
Nodo B
1 1 1
I F ( pu)= = = =−6.03827 j
(0.15 j+ 0.01722 j)∨¿(0.3 j+17,12 j) 0.1672 j∨¿17.42 j 0.16561 j
j∗5 MVA
I F =−6.03827 =−2641.06 j [ A ] =−2.64106 j[kA ]
√ 3∗6.6 kV
Nodo C
1 1 1
I F ( pu)= = = =−2.19873 j
( 0.15 j+0.01722 j+0.3 j ) ∨¿(17,12 j) 0.46722 j∨¿ 17.12 j 0.4548 j
j∗5 MVA
I F =−2.19873 =−15294.4 j [ A ] =−15.2944 j[kA ]
√ 3∗0.415 kV
Corrientes de carga
100 kVA
I cargaC = =139,121[ A]
√ 3∗0.415 kV
[ A ]∗0.415 kV
I cargaB=139,121 =8.74773 [ A ] =I cargaA
6.6 kV
Corrientes Nominales
100 kVA
I nominalC = =139,121[ A ]
√3∗0.415 kV
1000 k VA 5 00 0 kVA
I nominal B= =87.4773 [ A ] I nominalGenerador = =437.387 [ A ]
√ 3∗6.6 kV √ 3∗6.6 kV
I nominalA =437.387∗3=1312.16 [ A ]
Tabla resumen
Analizando el sistema desde el lugar más alejado de la fuente, es decir, para el relé en C.
El relé ubicado en C debe proteger la barra 3 de la que sabemos maneja una carga de 140
amperios por fase. Entonces se ajusta la corriente de disparo con un margen del 5%
0.02
I
t=
TMS∗0.14
TMS=
t∗
IP
−1 ( )
I 0.02 0.14
( )
IP
−1