PRÁCTICA NÚMERO 5
NOMBRE DE LA PRÁCTICA:
MÉTODO DIRECTO
PROFESORES:
CALIFICACIÓN: ________
Contenido:
OBJETIVOS:.....................................................................................3
DIAGRAMA ELÉCTRICOS.............................................................4
DIAGRAMA FÍSICO........................................................................4
RELACION DE INSTRUMENTOS Y EQUIPOS............................5
MODO DE OPERAR.........................................................................5
CALCULOS INICIALES..................................................................7
CALCULOS POSTERIORES.........................................................10
RESULTADOS................................................................................20
TABLA NÚMERO 1....................................................................20
TABLA NÚMERO 2....................................................................20
TABLA NÚMERO 3 ...................................................................21
TABLA NÚMERO 4....................................................................22
TABLA NÚMERO 5....................................................................22
TABLA NÚMERO 6....................................................................23
TABLA NÚMERO 7....................................................................23
TABLA NÚMERO 8....................................................................24
TABLA NÚMERO 9....................................................................24
TABLA NÚMERO 10..................................................................25
DIAGRAMA FASORIALES...........................................................25
TRIÁNGULOS DE POTENCIAS...................................................25
CONCLUSIONES...........................................................................28
OBJETIVOS:
Presentar la adaptación del teorema de Blondel a la medición de la potencia reactiva
de un circuito trifásico de tres hilos, conexión delta, haciendo notar que se debe
observar que la fuente debe ser simétrica.
Enseñar el uso del fasómetro para determinar las relaciones angulares entre las
tensiones y las corrientes, con el fin de definir las ambigüedades que se tienen en la
determinación de los ángulos, en las mediciones de las magnitudes desbalanceadas.
Determinar las magnitudes de las cargas tomando en cuenta las indicaciones de los
aparatos de medición y sus características.
DIAGRAMA FÍSICO
RELACION DE INSTRUMENTOS Y EQUIPOS
Fuente de corriente alterna trifásica variable, de 60 Hz.
Tres Vóltmetros analógicos de corriente alterna, alcance de 150 V.
Tres Ampérmetros analógicos de corriente alterna, alcance 5 A.
Dos wáttmetros electrodinámicos, alcance de tensión 120 V, alcance de corriente 5 A.
Un indicador de secuencia de fases.
Fasómetro
Banco de cargas trifásico, con elementos resistivos.
Banco de cargas trifásico, con elementos inductivos.
Banco de cargas trifásico, con elementos capacitivos.
Desconectador de pruebas de tres elementos.
MODO DE OPERAR
En esta práctica primero se hizo la selección de los aparatos de medición se
debe tener en cuenta las magnitudes que se van a medir. Para la selección de
los alcances de dichos aparatos, se debe tener en cuenta tanto la tensión de
alimentación como el campo de las corrientes que van a tomar las cargas.
Se tiene que Considerar que se van a realizar mediciones en las que se
requiere que se elimine el efecto de carga de los aparatos de medición, conecte
estos de acuerdo con el diagrama eléctrico de la figura número 9.
Repita el modo anterior para las cargas C.3 y C.4, pero además para
determinar los ángulos de las corrientes de línea siga el procedimiento
siguiente:
Posteriormente conecte el circuito de tensión del fasómetro a la tensión V AB en
el desconectador de pruebas DES.P como se muestra en la figura número
10.A, tenga cuidado de que su marca de polaridad quede conectada a la fase
A; para medir el ángulo de la intensidad de corriente I A , intercale el circuito
de corriente del fasómetro en la fase A como se muestra en la figura número
10A, tenga cuidado de que su marca de polaridad quede del lado de la fuente,
abra el desconectador de pruebas DES.P correspondiente a la fase A, y tome la
indicación del fasómetro, anótela en la tabla número 4. Cierre la fase A del
desconectador de pruebas y retire el circuito de corriente del fasómetro.
Una vez determinados los ángulos de las tres intensidades de corriente, retire
del desconectador de pruebas DES.P el circuito de tensión del fasómetro.
CALCULOS INICIALES
C.1. CARGA RESISTIVA-INDUCTIVA BALANCEADA.
PAB 133.3∨0 °
IAB* = VAB = 127 ∨0 °
= 1.0498¿0 ° A
PBC 133.3∨0 °
IBC* = VBC = 127 ∨ ° =1.0498¿−120 ° A
−120
PCA 133.3∨0 °
ICA* = VCA = 127 ∨ ° = 1.0498¿120 ° A
120
3
IAB = IABR + IABL = 1.0498¿0 ° A + √3 ∨90 ° A = 2.0253¿58.7798 ° A
3
IBC = IBCR + IBCL =1.0498¿−12 0 ° A+ √ 3 ∨−30 ° A = 2.0253¿61.2201 ° A
3
ICA = ICAR + ICAL =1.0498¿0 ° A + √3 ∨−150 ° A = 2.0253¿178.7798 ° A
3
QAB = VAB ( IAB)=127( √3 )=219.97
3
QBC= VBC (IBC)= 127( √3 )=219.97
3
QCA=VCA(ICA)= 127( √3 )=219.97
Pt = P1 + P2 + P3
Pt = 400w
QT=659.91 VAR’S IND
IA = IAB – ICA
IA = 2.33¿63.5 ° A−¿2.33¿10.9 ° A = 4.03¿33.5 º A
IB = IBC – IAB
IB = 2.33¿−56.4 ° A−¿2.33¿63.5 ° A =4.03¿−86.45 º A
IC = ICA – IBC
IC = =2.33¿−176.45 ° A−2.33 ∨10.9 ° A=4.03 ∨153.55 º A
Pt = P1 + P2 + P3
Pt = 400w
QT=800 VAR’S IND
Pt = P1 + P2 + P3
Pt = 332w
QT=600 VAR’S IND
Pt = P1 + P2 + P3
Pt = 332w
QT=600 VAR
ST= √ P + Q2=√(332)2+(600)2=685.7 VA
2
P 332w
FP = S = 685.7 VA = 0.49
ϴ = cos−1 (FP) = cos−1 (0.48)= 61.31 °
CALCULOS POSTERIORES
TABLA NÚMERO 5. RESULTADOS DE LAS MAGNITUDES SIN CORREGIR. CARGAS
BALANCEADAS
Q= ( √ 3 ) ( 5 ( 9+ 63 ) )=623.58
θ=cos−1 0.49=60.65
I A + I B+ I C
I L=
3
I A=I A 1−I BR 2−I V 1+ I V 30=( 4.72∟−90 )−( 0.0304 ∟−30.01 )− ( 0.0304 ∟−1.4037 ) + ( 0.0304 ∟118.5903 )=4.7
I B=I B 1−I R + I V 1−I V 2=( 4.72∟−210 ) −( 1.7560∟−150 )−( 0.0304 ∟−121.4037 ) −( 0.0304 ∟−1.4037 )=4.16
I C =I C 1+ I BR 1 + I V 1−I V 3=( 4.72∟−330 ) + ( 0.0304 ∟−90.01 )−( 0.0304 ∟118.5963 )−( 0.0304 ∟−121.4037 )=4
4.73+ 4.16+4.76
I L= =4.55
3
4.55
IF= =2.62
√3
2
121.662 3 ( 121.66 )
P=360− − =345.2
4000 4000
S= ( √3 ) ( 121.66 )(4.55)=958.78
Q= √ 958.78 2−345.22=894.48
345.2
F . P .= =0.36
958.78
θ=cos−1 0.36=68.89
TABLA NÚMERO 7. RESULTADOS DE LOS CÁLCULOS DE LOS ERRORES
RELATIVOS SISTEMÁTICOS, DEBIDOS AL EFECTO DE CARGA DE LOS APARATOS
DE MEDICIÓN. CARGAS BALANCEADAS
e V L %= |121.66−121.66
121.66 | X 100=0.0 %
e I L %= |4.72−4.55
4.55 |
X 100=3.73 %
2.72−2.62
e I %=|
2.62 |
F X 100=3.81 %
360−345.2
eP %=|
345.2 |
X 100=4.28 %
623.58−894.48
eQ %=| | X 100=30.28 %
894.48
720.03−958.78
eS %=| |X 100=24.9 %
958.78
0.49−0.36
eF . P . %=|
0.36 |
X 100=36.11%
60.65−68.89
eθ %=| | X 100=11.96 %
68.89
Q= ( √ 3 ) ( 5 ( 42+ 61 ) )=892
θ=cos−1 0.49=60 ᵒ
V L1=V L =126
I A + I B+ I C
I L=
3
I A=I A 1−I BR 2−I V 1+ I V 30=( 3.89 ∟90 )−( 0.0304 ∟−30.01 )−( 0.0304 ∟−1.4037 ) + ( 0.0304 ∟118.5903 )=3.93 ∟
I B=I B 1−I R + I V 1−I V 2=( 3.89 ∟210 ) −( 1.7560∟−150 ) −( 0.0304 ∟−121.4037 )− ( 0.0304 ∟−1.4037 )=2.107 ∟
I C =I C 1+ I BR 1 + I V 1−I V 3=( 3.89 ∟330 ) + ( 0.0304 ∟−90.01 )−( 0.0304 ∟118.5963 )−( 0.0304 ∟−121.4037 )=3.8
3.93+ 2.107+3.87
I L= =3.302
3
3.302
IF= =1.906
√3
2
126 2 3 ( 126 )
P=515− − =499.124
4000 4000
S= ( √3 ) ( 126 )(3.302)=720.62
Q= √ 720.622−499.1242=519.77
499.124
F . P .= =0.69
720.62
θ=cos−1 0.69=46.36
TABLA NÚMERO 7. RESULTADOS DE LOS CÁLCULOS DE LOS ERRORES
RELATIVOS SISTEMÁTICOS, DEBIDOS AL EFECTO DE CARGA DE LOS APARATOS
DE MEDICIÓN. CARGAS BALANCEADAS
e I L %= |3.89−3.302
3.302 |
X 100=17.8 %
2.24−1.906
e I %=|
1.906 |
F X 100=17.52%
515−499.124
eP %=|
499.124 |
X 100=3.18 %
892−519.77
eQ %=|
519.124 |
X 100=71.6 %
1029.99−720.62
eS %=| | X 100=42.93 %
720.62
0.50−0.69
eF . P . %=|
0.69 |
X 100=27.5 %
60−46.36
eθ %=|
46.36 |
X 100=29.42%
IBP1 = 27.5X10*-3|_0º A
IBP2 = 27.5X10*-3|_-300º A
IBR1 = 31.8X10*-3|_-90ºA
IBR2 = 31.8X10*-3|_-30ºA
IR = 31.8X10*-3|_-150ºA
IV1 = 22X10*-3|_-0.6ºA
IV2 = 22X10*-3|_-120.6ºA
IV3 = 22X10*-3|_-240.6ºA
IA = 2.78|_-82.20ºA
IB = 3.65|_147.38º A
IC = 2.80|_16.26º A
P = 295.38 w
2.83+3.7+2.85
IL = = 3.12 A
3
S = 220x3.12 = 686.4 VA
%e ϴA = ((80.54-82.20)/82.20)x100 = 2.01%
CÁLCULOS POSTERIORES
CARGA 4. RESISTIVA - CAPACITIVA DESBALANCEADA.
VM1= 124 V AM1= 4.2 A WM1= 41
VM2=125 V AM2= 2.6 A divisiones
VM3=125 V AM3= 3.5 A WM2= 46
divisiones
374
VL=Vf= = 124.66 V
3
10.3
Ilínea= =3.433 A
3
P= (5) (41+46) = 435 w
S P 2 Q 2 = S=√ 4352 +753.44 2 = 869.99 VA
3.433
Ifase= =1.982 A
√3
Q 3 VARM1+ VARM2
Q= √ 3 ( 5 ( 41+46 ) )=753.44 vars
donde I A1 , I B1 e I C1 son las intensidades de corriente por fase sin corregir, las cuales
considerando a V AB como referencia, serán iguales a,
I A1 I L1 / 30, 0 θ1
I B1 I L1 / 150, 0 θ1
I C1 I L1 / 270, 0 θ1
Carga 4 Corregida
I BP1 e I BP 2 son las intensidades de corriente tomadas por los circuitos de potencial de
los wáttmetros, I BR1 e I BR 2 son las intensidades de corriente tomadas por los circuitos
de potencial de los vármetros, I R es la intensidad de corriente tomada por la
resistencia adicional e I V 1 , I V 2 e I V 3 son las intensidades de corriente que toman los
vóltmetros, estas corrientes se pueden determinar a partir de los datos de las
impedancias de los circuitos de tensión de los wáttmetros ZBP, de los vármetros ZBR y
de los vóltmetros ZV, además del valor de la resistencia adicional R.
V AB VL
I BP1 / θ BP
Z BP Z BP
124.6∨0 °
I BP 1= ∨ ¿ 0.03115 ∨60 ° A
( 4000∨0 ° ) (−theta)
V CB VL
I BP 2 / 300, 0 θ BP
Z BP Z BP
124.6∨0 °
I BP 2= ∨ ¿
( 4000∨0 ° ) (−300−theta)
¿ 0.03115 ∨−300 −(−60)=0.03115 ∨−240 ° A
I BR 1=¿
124.6∨0 °
I BR 1= =0.01789|_-30° A
( 4000∨0 ° )¿ ¿
V AO VL
I BR 2 / 30, 0 θ BR
Z BR 3 Z BR
I BR 2=¿ =0.01789|_30° A
V BO VL
IR / 150, 0
R 3R
I R =¿= 0.01789|_-150°A
V AB VL
IV1 / θV
Z V ZV
V BC VL
IV 2 / 120,0 θV
Z V ZV
V CA VL
IV 3 / 240,0 θV
Z V ZV
124.6∨0 °
I v 1= ∨−theta ° =¿0.0249 |_60° A
5000
124.6∨0 °
I v 2= ∨−120 °−theta=0.024 ∨−120 −(−60)° A=0.0249 ∨−60 ° A
5000
124.6∨0 °
I v 3= ∨−240 °−theta=¿ 0.024|_-240-(-60°)A = 0.0249|_-180° A
5000
I A I A1 I BR 2 I V 1 I V 3
I A=[4.2 ∨−90 ° ]−[0.01789∨30 ° ]−[0 .0249∨60 ° ]+[0.0249 ∨−180 ° ]
I A=4.3153 ∨−92.55 ° A
I B I B1 I BP1 I BP 2 I R I V 2 I V 1
I B=¿ ¿] + [0.03115 ∨60 ¿] + [0.03115 ∨−240 ¿ ] - [0.01789|_-150° ] – [0.0249 ∨−60 °]
+ [0.0249 |_60° ]
I B=[2.6415 ∨147 ° ] A
I C I C1 I BP 2 I BR1 I V 3 I V 2
I C =[3.5 ∨−330 °]−¿ +[0.0249 ∨−60 ° ]
I C =3.531 ∨28.63 ° A
4.315+2.6415+3.531
I corregida promedio= =3.495833 A
3
3.4958
Ifase-corregida = =2.0183 A
√3
Potencia corregida =
2
V
2
3 L 2
2VL 3 3VL 2VL2 VL2 3VL2
P P1 P1
RBP RBR RV RBP RBR RV
2 V 2L V 2L 3V 2L
P=P1 − − −
R BP R BR RV
RESULTADOS
TABLA NÚMERO 1. RESULTADOS DE LOS CÁLCULOS PARA OBTENER
LAS MAGNITUDES DE LAS CARGAS BALANCEADAS BAJO PRUEBA.
CARGAS
MAGNITUDES
C.1 C.2
TENSIÓN DE LÍNEA VL V 127 127
CORRIENTE DE LÍNEA IL A 3.51 4.07
CORRIENTE DE FASE IF A 2.03 2.35
POTENCIA ACTIVA TOTAL P W 400 400
POTENCIA APARENTE TOTAL S VA 772 894
POTENCIA REACTIVA TOTAL Q var 660 IND 800 CAP
0.518 0.447
FACTOR DE POTENCIA FP
AT AD
0
ÁNGULO DEL FACTOR DE POTENCIA θ -58.8 63.4
IA 2.85 3.73
CORRIENTE DE LÍNEA IB A 3.73 2.85
IC 2.87 2.87
θA 30.9
ÁNGULOS DE LAS -80.3
0
θB 149.2 -99.5
CORRIENTES DE LÍNEA 18.3
θC 161.7
600 600
POTENCIA REACTIVA TOTAL Q var
IND CAP
POTENCIA APARENTE
S VA 68.6 68.6
TOTAL
TABLA NÚMERO 3 . LECTURAS.
CARGAS
MAGNITUDES
C.1 C.2
TENSIÓN DE LÍNEA VL1 V 121.66 126
CORRIENTE DE LÍNEA IL1 A 4.72 3.89
CORRIENTE DE FASE IF1 A 2.72 2.24
POTENCIA REACTIVA TOTAL Q1 var 623.58 892
POTENCIA APARENTE TOTAL S1 VA 720.03 1029
POTENCIA ACTIVA TOTAL P1 W 360 515
FACTOR DE POTENCIA FP1 0.49 0.69
ÁNGULO DEL FACTOR DE POTENCIA θ1 o -60.65 46.36
CARGAS
MAGNITUDES
C.1 C.2
TENSIÓN DE LÍNEA VL V 121.66 126
CORRIENTE DE LÍNEA IL A 4.55 3.302
CORRIENTE DE FASE IF A 2.62 1.906
POTENCIA REACTIVA TOTAL Q var 894.48 519.77
POTENCIA APARENTE TOTAL S VA 958.78 720.62
POTENCIA ACTIVA TOTAL P W 345.20 499.12
FACTOR DE POTENCIA FP 0.36 0.69
ÁNGULO DEL FACTOR DE POTENCIA θ o -68.89 46.36
TABLA NÚMERO 7. RESULTADOS DE LOS CÁLCULOS DE LOS ERRORES
RELATIVOS SISTEMÁTICOS, DEBIDOS AL EFECTO DE CARGA DE LOS
APARATOS DE MEDICIÓN. CARGAS BALANCEADAS.
CARGAS
MAGNITUDES
C.3 C.4
TENSIÓN DE LÍNEA VL1 V 127 124.66
2.83
IA1 4.2
3.7
CORRIENTES DE LÍNEA IB1 A 2.6
2.85
IC1 3.5
θA1 80.54 270
ÁNGULOS DE LAS
θB1 o 148.99 150
CORRIENTES DE LÍNEA
θC1 17.99 30
POTENCIA REACTIVA TOTAL Q1 var 596.48 753.44
POTENCIA ACTIVA TOTAL P1 W 332 435
POTENCIA APARENTE TOTAL S1 VA 755.49 869.99
TABLA NÚMERO 9. RESULTADOS DE LAS MAGNITUDES CORREGIDAS.
CARGAS DESBALANCEADAS.
CARGAS
MAGNITUDES
C.3 C.4
TENSIÓN DE LÍNEA VL V 127 124.66
IA 2.78 4.31
CORRIENTES DE LÍNEA IB A 3.65 2.64
IC 2.80 3.53
θA 82.20 267.45
ÁNGULOS DE LAS
θB o 147.38 147
CORRIENTES DE LÍNEA
θC 16.26 28.63
POTENCIA REACTIVA TOTAL Q var 619.59 766.44
POTENCIA ACTIVA TOTAL P W 295.38 414.02
POTENCIA APARENTE TOTAL S VA 686.4 871.12
El tipo de conexión utilizada fue la delta se utilizaron las tres cargas y que en total dieran
una suma de 332 w, se usaron dos de estas que fueron balanceadas y el otro resto
desbalanceadas como se sabe las cargas inductiva, capacitiva y resistiva se usan de forma
ya conocida.
Una vez que se conectan los dos varmetros, tres volmetros, tres ampermetros como lo
indica el diagrama de la práctica se sigue hacia las cargas y se hacen las mediciones
correspondientes de igual forma con el fasometro que indica la magnitud del angulo solo se
desatornilla el desconectador un poco para aquí medirlo.
Una vez que se obtienen todas las medidas de las cargas se comparan con los cálculos
previos que se tuvieron con anterioridad y se llego a la conclusión de que estos fueron
correctos.