CARGA MUERTA DE LA LOSA

P loseta = 1m*1m*0.05m*2400 kg/m³ = 120 Kg/m²


P nervios = 0.1m*0.2m*3.6m*2400Kg/m³ = 172.8 Kg/m²
P bloque = 8bloq*8Kg= 64 Kg/m²
P alisado+Cr = 0.05m*1m*1m*1900 Kg/m³ = 95 Kg/m²
P acabado = 0.015m*1m*1m*1800 Kg/m³ = 27 Kg/m²
CMT = 478.80 Kg/m²

CÁLCULO DEL PESO DE LAS PAREDES

PARED TIPO 1
P1= 0.15m*1m*2.75m*1600 Kg/m³ = 660 Kg/m³
Long. P1 = 58.05 m
𝐾𝑔
660 ∗ 58.05 𝑚 𝐾𝑔
𝐶𝑀𝑃1 = 𝑚³ = 385.13
99.48 𝑚²
PARED TIPO 2
P2= 1m*0.7m*0.15m*1600 Kg/m³= 168 Kg/m³
Long. P2 = 7.6 m
𝐾𝑔
168 ∗ 7.6 𝑚 𝐾𝑔
𝐶𝑀𝑃2 = 𝑚³ = 12.83
99.48 𝑚²

PARED TIPO 3
P2= 1m*1m*0.15m*1600 Kg/m³= 261.84 Kg/m³
Long. P2 = 43.55 m
𝐾𝑔
261.84 ∗ 8.10 𝑚 𝐾𝑔
𝐶𝑀𝑃2 = 𝑚³ = 21.32
99.48 𝑚²

CARGA VIVA (NEC-SE-CG)

4.2 SOBRE CARGAS MÍNIMAS


CV entrepiso= 200 Kg/m²
CÁLCULO DEL CORTANTE BASAL Y ESPECTRO DE DISEÑO NEC-SE-DS.

ESPECTRO DE ACELERACIONES ELÁSTICO Y REDUCIDO


NEC-SE-DS-2015

Ingrese datos en las celdas en verdes

VIVIENDS
PROYECTO UNIFAMILIAR
PROVINCIA CANTON
SITIO
TUNGURAHUA AMBATO
SUELO C
H.A. SIN MUROS
VIGAS
S. ESTRUCTURAL DESCOLGADAS

PARÁMETRO VALOR NEC-SE-DS


DATOS
ELÁSTICO
Z(%g) 0.40 3.1.1
η 2.48 3.3.1
Fa 1.20 3.2.2
Fd 1.10 3.2.2
Fs 1.10 3.2.2
r 1.00 3.3.1
DATOS
REDUCIDO
R 8.00 6.3.4
I 1.00 4.1
φp 1.00 5.2.3
φe 1.00 5.2.3
hn(m) 8.50
Ct 0.055 6.3.3
α 0.90 6.3.3
CÁLCULOS
Ta(s) 0.377
To(s) 0.101
Tc(s) 0.555
Sa(%g) 1.1904
C(%g) 0.1488
K 1.00
cortante Basal 40.06

ESPECTRO PARA ANÁLISIS SÍSMICO DINÁMICO


T(s) Sa(%g) C(%g)
0.00 0.480 0.060
0.05 0.832 0.104
0.10 1.185 0.148
0.15 1.190 0.149
0.20 1.190 0.149
0.25 1.190 0.149
0.30 1.190 0.149
0.35 1.190 0.149
0.40 1.190 0.149
0.45 1.190 0.149
0.50 1.190 0.149
0.55 1.190 0.149
0.60 1.100 0.138
0.65 1.016 0.127
0.70 0.943 0.118
0.75 0.880 0.110
0.80 0.825 0.103
0.85 0.777 0.097
0.90 0.734 0.092
0.95 0.695 0.087
1.00 0.660 0.083
1.05 0.629 0.079
1.10 0.600 0.075
1.15 0.574 0.072
1.20 0.550 0.069
1.25 0.528 0.066
1.30 0.508 0.063
1.35 0.489 0.061
1.40 0.472 0.059
1.45 0.455 0.057
1.50 0.440 0.055
1.55 0.426 0.053
1.60 0.413 0.052
1.65 0.400 0.050
1.70 0.388 0.049
1.75 0.377 0.047
1.80 0.367 0.046
1.85 0.357 0.045
1.90 0.347 0.043
1.95 0.339 0.042
2.00 0.330 0.041
2.05 0.322 0.040
2.10 0.314 0.039
2.15 0.307 0.038
2.20 0.300 0.038
2.25 0.293 0.037
2.30 0.287 0.036
2.35 0.281 0.035
2.40 0.275 0.034
2.45 0.269 0.034
2.50 0.264 0.033
2.55 0.259 0.032
2.60 0.254 0.032
2.65 0.249 0.031
2.70 0.245 0.031
2.75 0.240 0.030
2.80 0.236 0.029
2.85 0.232 0.029
2.90 0.228 0.028
2.95 0.224 0.028
3.00 0.220 0.028
3.05 0.216 0.027
3.10 0.213 0.027
3.15 0.210 0.026
3.20 0.206 0.026
3.25 0.203 0.025
3.30 0.200 0.025
3.35 0.197 0.025
3.40 0.194 0.024
3.45 0.191 0.024
3.50 0.189 0.024
3.55 0.186 0.023
3.60 0.183 0.023
3.65 0.181 0.023
3.70 0.178 0.022
3.75 0.176 0.022
3.80 0.174 0.022
3.85 0.171 0.021
3.90 0.169 0.021
3.95 0.167 0.021
4.00 0.165 0.021
4.05 0.163 0.020
4.10 0.161 0.020
4.15 0.159 0.020
4.20 0.157 0.020
4.25 0.155 0.019
4.30 0.154 0.019
4.35 0.152 0.019
4.40 0.150 0.019
4.45 0.148 0.019
4.50 0.147 0.018
4.55 0.145 0.018
4.60 0.144 0.018
4.65 0.142 0.018
4.70 0.140 0.018
4.75 0.139 0.017
4.80 0.138 0.017
4.85 0.136 0.017
4.90 0.135 0.017
4.95 0.133 0.017
5.00 0.132 0.017
ESPECTRO ELÁSTICO Y REDUCIDO NEC
2015 Tr = 475años
1.400
1.200
1.000
Período T(s)

0.800
0.600
0.400
0.200
0.000
0.00 1.00 2.00 3.00 4.00 5.00 6.00
Aceleraciones (%g)

ELÁSTICO REDUCIDO

CARGA SÍSMICA REACTIVA POR PISO

PISO I
Área= (17.3m*5.75m) = 99.48 m²
Wlosa= 478.80 Kg/m² * 99.48 m² = 47628.63Kg
Wpared= 397.96 Kg/m² * 99.48m² = 39589.06 Kg
Wcol = (0.25m* 0.25m)* 2.875m*21cols * 2400Kg/m³ = 9056.25 Kg
Wviga = 0.25m*0.05m*2400Kg/m³*69.15m= 2074.5 Kg
WCv = 25% * 200 Kg/m²*99.48m²= 4974 Kg
W1= 103322.44 Kg
W1= 103.31 Tn

PISO II
Área= (17.3m*5.75m) = 99.48 m²
Wlosa= 478.80 Kg/m² * 99.48 m² = 47628.63Kg
Wpared= 397.96 Kg/m² * 99.48m² = 39589.06 Kg
Wcol = (0.25m* 0.25m)* 2.75m*21cols * 2400Kg/m³ = 8662.5 Kg
Wviga = 0.25m*0.05m*2400Kg/m*99.48 m²= 2984.4 Kg
WCv = 25% * 200 Kg/m²*99.48m²= 4974 Kg
W2= 103838.59 Kg
W2= 103.84Tn

PISO III
Área= (17.3m*5.75m) = 99.48 m²
Wlosa= 478.80 Kg/m² * 99.48 m² = 47628.63Kg
Wpared= 21.32 Kg/m² * 99.48m² = 2120.91 Kg
Wcol = (0.25m* 0.25m)* 1.375*21cols * 2400Kg/m³ = 4331.25 Kg
Wviga = 0.25m*0.05m*2400Kg/m*99.48 m²= 2984.4 Kg
WCv = 25% * 200 Kg/m²*99.48m²= 4974 Kg
W3= 62039.19 Kg
W3= 62.039Tn

WT = W1+W2+W3
WT = 103.31 Tn + 103.84Tn+62.039Tn
WT = 269.189 Tn
CÁLCULO DE FUERZA REDUCIDA “V”
CORTANTE BASAL
V = C*W
V = 0.1488* 69.189 Kg
V = 14960.69 Kg
V = 10.30 Tn
DISTRIBUCIÓN DE FUERZAS LATERALES A LOS PISOS

PISO hx hi wi (Tn) Wi*hi^k Fx (Tn) Vx


3 2.75 8.5 62.04 527.33 14.73 14.73
2 2.75 5.75 103.84 597.08 16.67 31.40
1 3 3 103.31 309.93 8.66 40.06
1434.34 40.06

FACTORES DE DISTRIBUCIÓN
 Cálculo pórtico 2
Portico 1=2=3=4=5=6=7
Piso K F piso (Tn) F. Portico (Tn)
3 0.143 14.73 2.11
2 0.143 16.67 2.38
1 0.143 8.66 1.24