PARAMETROS DE CONFIGURACION DEL CONTROLADOR UDC-3000 VERS-PRO

Cliente: INDULAC (PARMALAT)


Fecha: 11-ENE-2018
Equipo: Controlador UDC 3000 VERSA-PRO:

SETUP TUNING:
 PROPBD 20.0
 RATE MIN 0.75
 RSET RPM 3.00
 SECURITY 0
 LOCKOUT CALIB
SETUP SP RAMP
 SP RAMP DISABL
 SP RATE DISABL
 SP PROG DISABL
SETUP INPUT 1
 DECIMAL XXX.X
 UNITS Deg C
 IN1 TYPE 100 PT
 IN1 HI 648.8
 IN1 LO -184.4
 BIAS IN1 0.0
 FILTER 1 10
 BURNOUT NONE
 PWR FREQ 60 HZ
 LANGUARE ENGLIS
SETUP CONTROL
 PID SETS 1 ONLY
 SP SOURC 1 LOCAL
 SP TRACK NONE
 POWER UP A LSP
 SP HiLIM 100.0
 SP LoLIM 0.0
 ACTION REVRSE
 OUT RATE DISABL
 OUTHiLIM 100.0
 OUTLoLIM 0.0
 DROPOFF 0.0
 FAILSAFE 0.0
 MAN OUT 0.1
 AUTO OUT 0.0
 PBorGAIN PB PCT
 MINorRPM RPM
SET ALARMS
 A 1S 1 VAL 88.0
 A 1S 2 VAL 30.0
 A 2S 1 VAL 10.0
 A 2S 2 VAL 10.0
 A 1S 1TYPE PV
 A 1S 2TYPE PV
 A 2S 1TYPE PV
 A 2S 2TYPE PV
 A 1S 1 HL HI
 A 1S 2 HL LO
 A 2S 1HL LO
 A 2S 2HL LO
 ALM HYST 0.2
REAR STATUS
 VERSION 31 13
 FAILSAFE NO
 RAM TEST PASS
 CONFTEST PASS
 CAL TEST PASS
 FACT CRC PASS
HONEYWELL York PA USA
UDC 3000 VERSA-PRO
DC300K-E-000-20-0000-0