LINEAS DE TRANSMISION
PUERTO 60KV
Ingeniera Bsica para lneas de transmisin y
subestaciones
Rev.
A
B
Fecha
22-05-2015
11-06-2015
Por
L.Q.O
L.Q.O
Revisado
D.B.P
D.B.P
Aprobado
D.B.P
D.B.P
Descripcin
Revisin Interna
Revisin del Cliente
No es permitido la copia de este documento sin permiso de Fosfatos del Pacifico o Delcrosa
SECCION
DESCRIPCION
0506.00-EL-CAL-0001
Description
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
Originat
or
Reviewer
Delcrosa
Approval
Date
MA.CH.V
G.Palacios
01-Jun15
MA.CH.V
G.Palacios
11-Jun15
Client
Approval
Date
INDICE
1
OBJETIVO............................................................................................................................................................................4
ALCANCES...........................................................................................................................................................................4
4.2
4.3
4.4
Requerimiento mecnico............................................................................................................................................7
4.5
Cadena de aisladores..................................................................................................................................................7
Cada de Tensin...............................................................................................................................................................12
Estimacin de Prdidas....................................................................................................................................................13
8.1
Prdidas Joule...........................................................................................................................................................13
9.2
Puestas a tierra..........................................................................................................................................................15
10
11
Distribucin de estructuras......................................................................................................................................22
11.1
Tensiones mecnicas...........................................................................................................................................22
11.2
11.3
Coordinacin de flechas......................................................................................................................................23
11.4
Localizacin de estructuras................................................................................................................................24
12
12.1
Vanos caractersticos...........................................................................................................................................24
12.2
Clculo de prestaciones......................................................................................................................................25
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
1 OBJETIVO
El objetivo del presente documento es presentar los clculos justificativos del diseo
electromecnico de la ingeniera definitiva de la lnea de transmisin en 60 kV del proyecto
FOSPAC (Fosfatos del Pacfico).
2 ALCANCES
Diseo del aislamiento.
Clculos elctricos del conductor.
Clculo de los parmetros de la lnea.
Diseo de las puestas a tierra.
Diseo mecnico de estructuras (geometra y prestaciones).
Distribucin de estructuras.
en condiciones normales
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
kVmax
3
Lf min
* RUSCD[A]
Considerando una cadena de 06 aisladores, se verifica que el valor de USCD es mayor que el
RUSCD corregido:
Selected Insulator
Glass antifog U120BLP x 06
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
Creepage
distance mm
2670
USCD
63,8
Check
USCD>RUSCD[A]
OK
Ka = 1 / m = 1
La tensin de contorneo a una altura de 0 m.s.n.m es:
CFO [PF-A] = 69,9 kV.
La distancia de aislamiento requerida para este valor de tensin de flameo es 0,24 m. La distancia
adoptada en el diseo ser:
Valor para diseo: GAP diseo = 0,40 m
Se verifica que los aisladores seleccionados cumplen con los niveles de aislamiento requeridos a
frecuencia industrial:
Aislador / cadena
Disrupcin
Disrupcin
estndar kV
corregido kV
Check
(frec.ind./
(frec.ind./
>CFO[PF-S]
lluvia)
240
lluvia)
240
OK
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
Aislador / cadena
Tensin disruptiva
Tensin disruptiva
665
665
Check
>
CFO[LI-S]
OK
TR
5990 kg
TM
60% (TR)
Factor de seguridad
FS
3.0
TMA
105.8 kN
TRA
120 kN
Valor
06
2670 mm
240 kV
665 kVp
1,20 m
0,80 m
0,40 m
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
Cadena en suspensin
Cadena en anclaje
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
60 kV 5%
35 C
45 C
12,5 MVA
S
3 *V
I = 120.28 A
El anlisis se hace en condiciones extremas desfavorables (temperatura ambiental elevada,
conductor envejecido, mes del ao con mayor radiacin solar), a fin de prever que la temperatura
de diseo del conductor no ser superada en ninguna poca del ao.
De los clculos y grfica de ampacidad se observa que la temperatura del conductor analizado
ser menor a 60 C por lo que no se presentarn problemas de ampacidad en el conductor
seleccionado.
***********************************************************************************
J738.exe
v2.0
- 23/01/2013
CALCULO DE LA TEMPERATURA - CORRIENTE EN EL CONDUCTOR EN ESTADO ESTABLE
Basado en el IEEE Std 738-2006 "...Current-Temperature of Bare Overhead Conductors"
C:\J738\PROYECTOS\2012\Fosfatos ACAR 500MCM.amp
***********************************************************************************
DATOS DEL CONDUCTOR: C:\J738\CABLES\PhelpsDodge\ACAR 500 MCM (18+19).dat
----------------------------------------------------------------------------------ACAR 500MCM (18+19h)
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
10
===================================================================================
BALANCE DE ENERGIA EN ESTADO ESTABLE:
===================================================================================
Prdida de calor por conveccin
= 17.52 W/m
Prdida de calor por radiacin
= 4.57 W/m
Ganancia de calor solar
= 16.13 W/m
Corriente I [T = 60 C]
= 205.237 A
Menor ampacidad = 205.2 A para el mes : 3
Mayor ampacidad = 213.4 A para el mes : 6
Menor ampacidad = 205.2 A para el mes : 10
===================================================================================
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
11
CONDUCTOR
Denominacin :
Dimetro
:
Resistencia :
DISPOSICION
Configuracin:
Simple Terna
Fases :
Simplex
Frecuencia
:
60.0
Hz
Tensin
:
60.0
kV
CALCULOS
D.M.G. :
4069.5
Radio conductor
RMG (1 cond.):
Radio equiv. :
CONSTANTES FISICAS
Resistencia Rk
C.Autoinduc. Lk
Capacidad
Ck
mm
:
10.33 mm
7.933 mm
7.933 mm
DE LA LINEA
:
0.1369 Ohm/km
:
0.00125
H/km
:
9.324 nF/km
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
12
7 CADA DE TENSIN
Debido a que la topografa para esta lnea de transmisin en gran parte de su extensin es
relativamente plana, para el clculo de cada de tensin se considera una longitud de conductor
3,5% mayor a la longitud horizontal topogrfica.
Longitud = 34,1 x 1,035 = 35,3 km
El anlisis se hace en condiciones de operacin normal
Se muestra que la cada de tensin ser menor al 5%.
Gen-0
Fosf atos
Puerto
Puerto 10 MVA
LT 60 kV ACAR 500MCM
Nombre
N Tipo Voltaje % grados Estado Pgen MW Qgen MVAR Pcarga Qcarga
Puerto
1 Carga
97.223 -2.35 Normal
0.000
0.000
9.500
3.122
Fosfatos
2 Slack 100.000 0.00 Normal
9.640
3.169
0.000
0.000
Totales =
9.640
3.169
9.500
3.122
|
A>B
|
B>A
|
| Prdidas
|
Barra A
Barra B
| P MW
Q MVAR | P MW
Q MVAR | Inom Amp | Carga | MW | MVAR |
| |
||||
|
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
13
8 ESTIMACIN DE PRDIDAS
Se calculan las prdidas en los conductores de las lneas de transmisin propuestos en cada
caso.
Prdidas de potencia producidas por efecto Joule
TE
M
DENOMINAC CORRESPOND
IN
ENCIA
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
NMER
O DE
ESTRAT
1
(.m)
2
(.m)
h (m)
14
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
ZR-01
ZR-02
ZR-03
ZR-04
ZR-05
ZR-06
ZR-07
ZR-08
ZR-09
ZR-10
ZR-11
ZR-12
ZR-13
ZR-14
ZR-15
ZR-16
ZR-17
ZR-18
ZR-19
ZR-20*
ZR-21*
ZR-22
ZR-23
LT
LT
LT
LT
LT
LT
LT
LT
LT
LT
LT
LT
LT
LT
LT
LT
LT
LT
LT
LT
LT
LT
LT
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
kV
kV
kV
kV
kV
kV
kV
kV
kV
kV
kV
kV
kV
kV
kV
kV
kV
kV
kV
kV
kV
kV
kV
OS
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
1151
7.3
1
2772.9
6401.4
1436.2
1970.8
351.6
368
2361.9
2322.6
66.63
67.6
58
107
38.7
32.8
35.1
14.7
209.5
42.8
48.9
241.6
111.5
49.3
2858.7
150.7
662.1
142.8
134.2
69.5
96
914
998.7
94.5
1193
3200.8
578.4
139.4
121
1202.2
155.2
7456.4
3091.2
159.4
4618.5
5.394
78.163
0.422
34.261
1.807
10.753
80.13
1.985
1.363
1.389
1.422
5.043
6.303
4.287
10.108
0.881
0.697
3.045
0.309
7.251
1.535
0.34
9.031
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
15
Configuraciones bsicas
Las puestas a tierra estn conformadas por un arreglo de electrodos, que consisten en:
TIPO D2B: Dos conductores horizontales que se conectan a travs de los conectores de bronce de
vas paralelas provenientes de los postes de madera (Biposte) y que se encontrarn enterrados a
0,6 m de profundidad, tal como se muestra en la figura T1.
TIPO D2T: Dos conductores horizontales que se conectan a travs de los conectores de bronce de
vas paralelas provenientes de los postes de madera (Triposte) y que se encontrarn enterrados
0,6 m de profundidad, tal como se muestra en la figura T2.
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
16
TIPO D4B: Cuatro conductores horizontales que se conectan a travs de los conectores de bronce
de vas paralelas provenientes de los postes de madera (Biposte) y que se encontrarn enterrados
0,6 m de profundidad, tal como se muestra en la figura T3.
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
17
TIPO D4T: Cuatro conductores horizontales que se conectan a travs de los conectores de bronce
de vas paralelas provenientes de los postes de madera (Triposte) y que se encontrarn enterrados
0,6 m de profundidad, tal como se muestra en la figura T4.
9.2.2
Materiales a utilizar
Se utilizar el conductor tipo Copper_clad steel wire 30%, para los contrapesos, por su buena
resistencia a los suelos corrosivos y tambin con la finalidad de evitar sustracciones (robos).
Para el clculo de la seccin del conductor de las puestas a tierra se usar la siguiente frmula
propuesta por Sverak incluida en la norma IEEE Std 80-2000:
A mm =
2
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
K +T
TCAP104
ln o m
t c rr
K o+ T a
)(
)
18
Dnde:
Tm
Ta
: Temperatura ambiente, C.
Tr
r
: Coeficiente trmico de resistividad a la temperatura de referencia Tr, 1/C.
r
: Resistividad
del
conductor
de
tierra
la
temperatura
de
referencia
1
Tr
r
K0
Tc
, C.
: Duracin de la corriente, s.
Datos
Valor
Unidades
TCAP
3.85
J/cm3.C
0.00378
1/C
5.86
.cm
K0
245
Tm
1084
Tr
20
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
19
Valor
Unidades
kA
tc
0.5
Ta
35
Remplazando los datos en la frmula de Sverak se tiene que la seccin mnima del conductor debe
ser mayor o igual a:
A = 34,3827 mm2
Seleccionamos el conductor Copperweld calibre 7#10 (36.83 mm 2) el cual puede soportar para las
condiciones antes calculadas las siguientes corrientes de cortocircuito:
Corriente de cortocircuito mxima en los conductores seleccionados
Seccin
Icc (kA)
8.5694
Para el clculo del valor de resistencia de puesta a tierra se utilizara el software FdcGrd V-2.00, el
cual permite analizar el comportamiento de electrodos a tierra en un suelo de dos capas, usando
una metodologa de elementos finitos, bajo criterios y parmetros de la norma IEEE Std 80-2000.
Con el software mencionado modelaremos dicha configuracin, variando la longitud del
contrapeso, a fin de encontrar una resistencia de puesta a tierra menor o igual a 25.
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
20
Valor
9.2.4
Puntos medidos
0,6
7,77
Una vez obtenidos los valores de resistividad equivalente del terreno para cada caso de
configuracin de electrodos, se elegir una adecuada longitud de contrapeso de las siguientes
tablas desarrolladas para cada una de las configuraciones.
Tabla de utilizacin Tipo D2
Tipo
eq (.m)
Lc (m)
C. Total (m)
RPATmax ()
D2-5
D2-10
D2-15
D2-20
D2-25
D2-30
D2-35
0 - 160
160 - 280
280 - 390
390 - 500
500 - 610
610 - 710
710 - 800
5
10
15
20
25
30
35
10
20
30
40
50
60
70
25
25
25
25
25
25
25
D2-40
800 - 900
40
80
25
D2-45
900 - 1000
45
90
25
D2-50
900 - 1090
1090 -
50
100
25
55
110
25
60
120
25
D2-55
D2-60
1250
> 1250
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
21
Tipo
D4-45
D4-50
D4-55
D4-60
eq (.m)
1350 1470
1470 1610
1610 1740
> 1740
LC (m)
LC Total
(m)
RPAT max ()
45
180
25
50
200
25
55
220
25
60
240
25
Dnde:
eq (Ohm-m) : Resistividad equivalente del terreno visto por el arreglo de electrodos
Lc (m)
Lc Total (m)
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
22
Velocidad del
Presin del
Hielo
Temperatura
viento (m/s)
viento (Pa)
(cm)
EDS
26 (*)
VMAX
26
414,4
11
TMAX
60 (**)
TMIN
11
Hiptesis
(*) En el estado final se considera la estimacin del efecto CREEP incrementado, de 10 aos
(estndar) a 20 aos (requerimiento de El Cliente).
(**) Para el caso del cable OPGW la temperatura mxima a considerar ser 50C
11 DISTRIBUCIN DE ESTRUCTURAS
11.1 TENSIONES MECNICAS
Para la ubicacin (distribucin) de estructuras se adopta las siguientes tensiones mecnicas:
Conductor
Condicin
EDS final
nominal)
750 daN
OPGW
EDS final
nominal)
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
23
f c. g .
f ACAR( EDSf )
0,85
As tenemos:
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
24
Estructura
(m)
(m)
400
900
400
500
30
450
650
-100
450
1000
-300
90
400
600
-200
0 (90)
300
600
-100
Angulo
0
AS1
AS2
AR1
AT1
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
25
Estructura AS1
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
26
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
27
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
28
Estructura AS2
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
29
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
30
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
31
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
32
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
33
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
34
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
35
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
36
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
37
ANEXOS
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
38
ANEXO A
Resultados de la simulacin de las puestas a tierra
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
39
Capa
Ohm-m
H(m)
============================
1
1151.00
5.394
2
111.50
Ohmios
Amperios
Voltios
No. IdMalla
Parcial
Total
Inyectados
Disipados
Tension
=========================================================================
1 PAT-FOSPAC
22.3581
22.3581
8.6
8.6
191.6
IdMalla: PAT-FOSPAC
No.:
Seg.
Longitud
Radio <------------------ Coordenadas en
metros ------------------>
No.
Amperios
metros
mm
X1
Y1
Z1
X2
Y2
Z2
=========================================================================
=========================
1
0.2890
3.00
3.885
0.00
0.00
0.60
0.00
3.00
0.60
2
3.9957
37.00
3.885
0.00
3.00
0.60
-37.00
3.00
0.60
3
0.2890
3.00
3.885
0.00
0.00
0.60
0.00
-3.00
0.60
4
3.9957
37.00
3.885
0.00
-3.00
0.60
37.00
-3.00
0.60
TSEG:
0.828
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
40
Capa
Ohm-m
H(m)
============================
1
7.30
78.163
2
49.30
Ohmios
Amperios
Voltios
No. IdMalla
Parcial
Total
Inyectados
Disipados
Tension
=========================================================================
1 PAT-FOSPAC
1.1602
1.1602
8.6
8.6
9.9
IdMalla: PAT-FOSPAC
No.:
Seg.
Longitud
Radio <------------------ Coordenadas en
metros ------------------>
No.
Amperios
metros
mm
X1
Y1
Z1
X2
Y2
Z2
=========================================================================
=========================
1
2.4339
3.00
3.885
0.00
0.00
0.60
0.00
3.00
0.60
2
1.8508
2.00
3.885
0.00
3.00
0.60
-2.00
3.00
0.60
3
2.4339
3.00
3.885
0.00
0.00
0.60
0.00
-3.00
0.60
4
1.8508
2.00
3.885
0.00
-3.00
0.60
2.00
-3.00
0.60
TSEG:
0.812
Capa
Ohm-m
H(m)
============================
1
1.00
0.422
2
2858.70
Ohmios
Amperios
Voltios
No. IdMalla
Parcial
Total
Inyectados
Disipados
Tension
=========================================================================
1 PAT-FOSPAC
23.9749
23.9749
8.6
8.6
205.5
IdMalla: PAT-FOSPAC
No.:
Seg.
Longitud
metros ------------------>
No.
Amperios
metros
X2
Y2
Z2
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
1
Radio <------------------ Coordenadas en
mm
X1
Y1
Z1
41
=========================================================================
=========================
1
0.2792
3.00
3.885
0.00
0.00
0.60
0.00
3.00
0.60
2
4.0055
42.00
3.885
0.00
3.00
0.60
-42.00
3.00
0.60
3
0.2792
3.00
3.885
0.00
0.00
0.60
0.00
-3.00
0.60
4
4.0055
42.00
3.885
0.00
-3.00
0.60
42.00
-3.00
0.60
TSEG:
0.828
Capa
Ohm-m
H(m)
============================
1
1436.20
10.753
2
142.80
Ohmios
Amperios
Voltios
No. IdMalla
Parcial
Total
Inyectados
Disipados
Tension
=========================================================================
1 PAT-FOSPAC
22.9532
22.9532
8.6
8.6
196.7
IdMalla: PAT-FOSPAC
No.:
Seg.
Longitud
Radio <------------------ Coordenadas en
metros ------------------>
No.
Amperios
metros
mm
X1
Y1
Z1
X2
Y2
Z2
=========================================================================
=========================
1
0.2032
3.00
3.885
0.00
0.00
0.60
0.00
3.00
0.60
2
4.0815
52.00
3.885
0.00
3.00
0.60
-52.00
3.00
0.60
3
0.2032
3.00
3.885
0.00
0.00
0.60
0.00
-3.00
0.60
4
4.0815
52.00
3.885
0.00
-3.00
0.60
52.00
-3.00
0.60
TSEG:
0.828
Capa
Ohm-m
H(m)
============================
1
1970.80
80.130
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
42
134.20
Ohmios
Amperios
Voltios
No. IdMalla
Parcial
Total
Inyectados
Disipados
Tension
=========================================================================
1 PAT-FOSPAC
23.9855
23.9855
8.6
8.6
205.5
IdMalla: PAT-FOSPAC
No.:
Seg.
Longitud
Radio <------------------ Coordenadas en
metros ------------------>
No.
Amperios
metros
mm
X1
Y1
Z1
X2
Y2
Z2
=========================================================================
=========================
1
2.1127
58.50
3.885
0.00
-3.00
0.60
-58.50
-3.00
0.60
2
2.1127
58.50
3.885
0.00
-3.00
0.60
58.50
-3.00
0.60
3
0.0592
3.00
3.885
0.00
0.00
0.60
0.00
3.00
0.60
4
2.1127
58.50
3.885
0.00
3.00
0.60
-58.50
3.00
0.60
5
2.1127
58.50
3.885
0.00
3.00
0.60
58.50
3.00
0.60
6
0.0592
3.00
3.885
0.00
0.00
0.60
0.00
-3.00
0.60
TSEG:
0.828
Capa
Ohm-m
H(m)
============================
1
351.60
1.985
2
69.50
Ohmios
Amperios
Voltios
No. IdMalla
Parcial
Total
Inyectados
Disipados
Tension
=========================================================================
1 PAT-FOSPAC
22.8480
22.8480
8.6
8.6
195.8
IdMalla: PAT-FOSPAC
No.:
Seg.
Longitud
Radio <------------------ Coordenadas en
metros ------------------>
No.
Amperios
metros
mm
X1
Y1
Z1
X2
Y2
Z2
=========================================================================
=========================
1
1.2154
3.00
3.885
0.00
0.00
0.60
0.00
3.00
0.60
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
43
2
-7.00
3
0.00
4
7.00
3.0693
3.00
1.2154
-3.00
3.0693
-3.00
TSEG:
7.00
0.60
3.00
0.60
7.00
0.60
3.885
0.00
3.00
0.60
3.885
0.00
0.00
0.60
3.885
0.00
-3.00
0.60
0.828
Capa
Ohm-m
H(m)
============================
1
368.00
1.363
2
96.00
Ohmios
Amperios
Voltios
No. IdMalla
Parcial
Total
Inyectados
Disipados
Tension
=========================================================================
1 PAT-FOSPAC
22.9873
22.9873
8.6
8.6
197.0
IdMalla: PAT-FOSPAC
No.:
Seg.
Longitud
Radio <------------------ Coordenadas en
metros ------------------>
No.
Amperios
metros
mm
X1
Y1
Z1
X2
Y2
Z2
=========================================================================
=========================
1
1.2223
3.00
3.885
0.00
0.00
0.60
0.00
3.00
0.60
2
3.0624
7.00
3.885
0.00
3.00
0.60
-7.00
3.00
0.60
3
1.2223
3.00
3.885
0.00
0.00
0.60
0.00
-3.00
0.60
4
3.0624
7.00
3.885
0.00
-3.00
0.60
7.00
-3.00
0.60
TSEG:
0.828
Capa
Ohm-m
H(m)
============================
1
2361.90
1.389
2
914.00
No.
IdMalla
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
Ohmios
Total
Parcial
Amperios
Inyectados
Disipados
Voltios
Tension
44
=========================================================================
1 PAT-FOSPAC
24.2592
24.2592
8.6
8.6
207.9
IdMalla: PAT-FOSPAC
No.:
Seg.
Longitud
Radio <------------------ Coordenadas en
metros ------------------>
No.
Amperios
metros
mm
X1
Y1
Z1
X2
Y2
Z2
=========================================================================
=========================
1
2.0896
43.50
3.885
0.00
-3.00
0.60
-43.50
-3.00
0.60
2
2.0896
43.50
3.885
0.00
-3.00
0.60
43.50
-3.00
0.60
3
0.1055
3.00
3.885
0.00
0.00
0.60
0.00
3.00
0.60
4
2.0896
43.50
3.885
0.00
3.00
0.60
-43.50
3.00
0.60
5
2.0896
43.50
3.885
0.00
3.00
0.60
43.50
3.00
0.60
6
0.1055
3.00
3.885
0.00
0.00
0.60
0.00
-3.00
0.60
TSEG:
0.844
Capa
Ohm-m
H(m)
============================
1
2322.60
1.422
2
998.70
Ohmios
Amperios
Voltios
No. IdMalla
Parcial
Total
Inyectados
Disipados
Tension
=========================================================================
1 PAT-FOSPAC
22.8513
22.8513
8.6
8.6
195.8
IdMalla: PAT-FOSPAC
No.:
Seg.
Longitud
Radio <------------------ Coordenadas en
metros ------------------>
No.
Amperios
metros
mm
X1
Y1
Z1
X2
Y2
Z2
=========================================================================
=========================
1
2.0961
48.50
3.885
0.00
-3.00
0.60
-48.50
-3.00
0.60
2
2.0961
48.50
3.885
0.00
-3.00
0.60
48.50
-3.00
0.60
3
0.0925
3.00
3.885
0.00
0.00
0.60
0.00
3.00
0.60
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
45
4
-48.50
5
48.50
6
0.00
TSEG:
2.0961
3.00
2.0961
3.00
0.0925
-3.00
0.84
48.50
0.60
48.50
0.60
3.00
0.60
3.885
0.00
3.00
0.60
3.885
0.00
3.00
0.60
3.885
0.00
0.00
0.60
Capa
Ohm-m
H(m)
============================
1
66.63
5.043
2
94.50
Ohmios
Amperios
Voltios
No. IdMalla
Parcial
Total
Inyectados
Disipados
Tension
=========================================================================
1 PAT-FOSPAC
10.7896
10.7896
8.6
8.6
92.5
IdMalla: PAT-FOSPAC
No.:
Seg.
Longitud
Radio <------------------ Coordenadas en
metros ------------------>
No.
Amperios
metros
mm
X1
Y1
Z1
X2
Y2
Z2
=========================================================================
=========================
1
2.4321
3.00
3.885
0.00
0.00
0.60
0.00
3.00
0.60
2
1.8526
2.00
3.885
0.00
3.00
0.60
-2.00
3.00
0.60
3
2.4321
3.00
3.885
0.00
0.00
0.60
0.00
-3.00
0.60
4
1.8526
2.00
3.885
0.00
-3.00
0.60
2.00
-3.00
0.60
TSEG:
0.829
Capa
Ohm-m
H(m)
============================
1
67.60
6.303
2
1193.00
Ohmios
Amperios
Voltios
No. IdMalla
Parcial
Total
Inyectados
Disipados
Tension
=========================================================================
1 PAT-FOSPAC
14.3060
14.3060
8.6
8.6
122.6
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
46
IdMalla: PAT-FOSPAC
No.:
Seg.
Longitud
Radio <------------------ Coordenadas en
metros ------------------>
No.
Amperios
metros
mm
X1
Y1
Z1
X2
Y2
Z2
=========================================================================
=========================
1
2.4281
3.00
3.885
0.00
0.00
0.60
0.00
3.00
0.60
2
1.8566
2.00
3.885
0.00
3.00
0.60
-2.00
3.00
0.60
3
2.4281
3.00
3.885
0.00
0.00
0.60
0.00
-3.00
0.60
4
1.8566
2.00
3.885
0.00
-3.00
0.60
2.00
-3.00
0.60
TSEG:
0.829
Capa
Ohm-m
H(m)
============================
1
58.00
4.287
2
3200.80
Ohmios
Amperios
Voltios
No. IdMalla
Parcial
Total
Inyectados
Disipados
Tension
=========================================================================
1 PAT-FOSPAC
11.9927
11.9927
8.6
8.6
102.8
IdMalla: PAT-FOSPAC
No.:
Seg.
Longitud
Radio <------------------ Coordenadas en
metros ------------------>
No.
Amperios
metros
mm
X1
Y1
Z1
X2
Y2
Z2
=========================================================================
=========================
1
1.1089
3.00
3.885
0.00
0.00
0.60
0.00
3.00
0.60
2
3.1758
7.00
3.885
0.00
3.00
0.60
-7.00
3.00
0.60
3
1.1089
3.00
3.885
0.00
0.00
0.60
0.00
-3.00
0.60
4
3.1758
7.00
3.885
0.00
-3.00
0.60
7.00
-3.00
0.60
TSEG:
0.828
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
47
Capa
Ohm-m
H(m)
============================
1
107.00
10.108
2
578.40
Ohmios
Amperios
Voltios
No. IdMalla
Parcial
Total
Inyectados
Disipados
Tension
=========================================================================
1 PAT-FOSPAC
11.5702
11.5702
8.6
8.6
99.1
IdMalla: PAT-FOSPAC
No.:
Seg.
Longitud
Radio <------------------ Coordenadas en
metros ------------------>
No.
Amperios
metros
mm
X1
Y1
Z1
X2
Y2
Z2
=========================================================================
=========================
1
1.1544
3.00
3.885
0.00
0.00
0.60
0.00
3.00
0.60
2
3.1303
7.00
3.885
0.00
3.00
0.60
-7.00
3.00
0.60
3
1.1544
3.00
3.885
0.00
0.00
0.60
0.00
-3.00
0.60
4
3.1303
7.00
3.885
0.00
-3.00
0.60
7.00
-3.00
0.60
TSEG:
0.828
Capa
Ohm-m
H(m)
============================
1
38.70
0.881
2
139.40
Ohmios
Amperios
Voltios
No. IdMalla
Parcial
Total
Inyectados
Disipados
Tension
=========================================================================
1 PAT-FOSPAC
10.1821
10.1821
8.6
8.6
87.3
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
48
IdMalla: PAT-FOSPAC
No.:
Seg.
Longitud
Radio <------------------ Coordenadas en
metros ------------------>
No.
Amperios
metros
mm
X1
Y1
Z1
X2
Y2
Z2
=========================================================================
=========================
1
2.3294
3.00
3.885
0.00
0.00
0.60
0.00
3.00
0.60
2
1.9553
2.00
3.885
0.00
3.00
0.60
-2.00
3.00
0.60
3
2.3294
3.00
3.885
0.00
0.00
0.60
0.00
-3.00
0.60
4
1.9553
2.00
3.885
0.00
-3.00
0.60
2.00
-3.00
0.60
TSEG:
0.829
Capa
Ohm-m
H(m)
============================
1
32.80
0.697
2
121.00
Ohmios
Amperios
Voltios
No. IdMalla
Parcial
Total
Inyectados
Disipados
Tension
=========================================================================
1 PAT-FOSPAC
9.4668
9.4668
8.6
8.6
81.1
IdMalla: PAT-FOSPAC
No.:
Seg.
Longitud
Radio <------------------ Coordenadas en
metros ------------------>
No.
Amperios
metros
mm
X1
Y1
Z1
X2
Y2
Z2
=========================================================================
=========================
1
2.3235
3.00
3.885
0.00
0.00
0.60
0.00
3.00
0.60
2
1.9612
2.00
3.885
0.00
3.00
0.60
-2.00
3.00
0.60
3
2.3235
3.00
3.885
0.00
0.00
0.60
0.00
-3.00
0.60
4
1.9612
2.00
3.885
0.00
-3.00
0.60
2.00
-3.00
0.60
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
49
TSEG:
0.828
Capa
Ohm-m
H(m)
============================
1
35.10
3.045
2
1202.20
Ohmios
Amperios
Voltios
No. IdMalla
Parcial
Total
Inyectados
Disipados
Tension
=========================================================================
1 PAT-FOSPAC
10.5143
10.5143
8.6
8.6
90.1
IdMalla: PAT-FOSPAC
No.:
Seg.
Longitud
Radio <------------------ Coordenadas en
metros ------------------>
No.
Amperios
metros
mm
X1
Y1
Z1
X2
Y2
Z2
=========================================================================
=========================
1
2.3961
3.00
3.885
0.00
0.00
0.60
0.00
3.00
0.60
2
1.8886
2.00
3.885
0.00
3.00
0.60
-2.00
3.00
0.60
3
2.3961
3.00
3.885
0.00
0.00
0.60
0.00
-3.00
0.60
4
1.8886
2.00
3.885
0.00
-3.00
0.60
2.00
-3.00
0.60
TSEG:
0.828
Capa
Ohm-m
H(m)
============================
1
14.70
0.309
2
155.20
Ohmios
Amperios
Voltios
No. IdMalla
Parcial
Total
Inyectados
Disipados
Tension
=========================================================================
1 PAT-FOSPAC
19.1201
19.1201
8.6
8.6
163.8
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
50
IdMalla: PAT-FOSPAC
No.:
Seg.
Longitud
Radio <------------------ Coordenadas en
metros ------------------>
No.
Amperios
metros
mm
X1
Y1
Z1
X2
Y2
Z2
=========================================================================
=========================
1
2.4845
3.00
3.885
0.00
0.00
0.60
0.00
3.00
0.60
2
1.8002
2.00
3.885
0.00
3.00
0.60
-2.00
3.00
0.60
3
2.4845
3.00
3.885
0.00
0.00
0.60
0.00
-3.00
0.60
4
1.8002
2.00
3.885
0.00
-3.00
0.60
2.00
-3.00
0.60
TSEG:
0.828
Capa
Ohm-m
H(m)
============================
1
209.50
7.251
2
7456.40
Ohmios
Amperios
Voltios
No. IdMalla
Parcial
Total
Inyectados
Disipados
Tension
=========================================================================
1 PAT-FOSPAC
22.7070
22.7070
8.6
8.6
194.6
IdMalla: PAT-FOSPAC
No.:
Seg.
Longitud
Radio <------------------ Coordenadas en
metros ------------------>
No.
Amperios
metros
mm
X1
Y1
Z1
X2
Y2
Z2
=========================================================================
=========================
1
0.5137
3.00
3.885
0.00
0.00
0.60
0.00
3.00
0.60
2
3.7710
17.00
3.885
0.00
3.00
0.60
-17.00
3.00
0.60
3
0.5137
3.00
3.885
0.00
0.00
0.60
0.00
-3.00
0.60
4
3.7710
17.00
3.885
0.00
-3.00
0.60
17.00
-3.00
0.60
TSEG:
0.828
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
51
Capa
Ohm-m
H(m)
============================
1
42.80
1.535
2
30910.20
Ohmios
Amperios
Voltios
No. IdMalla
Parcial
Total
Inyectados
Disipados
Tension
=========================================================================
1 PAT-FOSPAC
22.6761
22.6761
8.6
8.6
194.3
IdMalla: PAT-FOSPAC
No.:
Seg.
Longitud
Radio <------------------ Coordenadas en
metros ------------------>
No.
Amperios
metros
mm
X1
Y1
Z1
X2
Y2
Z2
=========================================================================
=========================
1
0.2725
3.00
3.885
0.00
0.00
0.60
0.00
3.00
0.60
2
4.0122
17.00
3.885
0.00
3.00
0.60
-17.00
3.00
0.60
3
0.2725
3.00
3.885
0.00
0.00
0.60
0.00
-3.00
0.60
4
4.0122
17.00
3.885
0.00
-3.00
0.60
17.00
-3.00
0.60
TSEG:
0.828
Capa
Ohm-m
H(m)
============================
1
48.90
0.340
2
241.60
Ohmios
Amperios
Voltios
No. IdMalla
Parcial
Total
Inyectados
Disipados
Tension
=========================================================================
1 PAT-FOSPAC
18.9223
18.9223
8.6
8.6
162.2
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
52
IdMalla: PAT-FOSPAC
No.:
Seg.
Longitud
Radio <------------------ Coordenadas en
metros ------------------>
No.
Amperios
metros
mm
X1
Y1
Z1
X2
Y2
Z2
=========================================================================
=========================
1
1.1708
3.00
3.885
0.00
0.00
0.60
0.00
3.00
0.60
2
3.1139
7.00
3.885
0.00
3.00
0.60
-7.00
3.00
0.60
3
1.1708
3.00
3.885
0.00
0.00
0.60
0.00
-3.00
0.60
4
3.1139
7.00
3.885
0.00
-3.00
0.60
7.00
-3.00
0.60
TSEG:
0.829
Capa
Ohm-m
H(m)
============================
1
241.60
9.031
2
4618.50
Ohmios
Amperios
Voltios
No. IdMalla
Parcial
Total
Inyectados
Disipados
Tension
=========================================================================
1 PAT-FOSPAC
21.2094
21.2094
8.6
8.6
181.8
IdMalla: PAT-FOSPAC
No.:
Seg.
Longitud
Radio <------------------ Coordenadas en
metros ------------------>
No.
Amperios
metros
mm
X1
Y1
Z1
X2
Y2
Z2
=========================================================================
=========================
1
0.5282
3.00
3.885
0.00
0.00
0.60
0.00
3.00
0.60
2
3.7565
17.00
3.885
0.00
3.00
0.60
-17.00
3.00
0.60
3
0.5282
3.00
3.885
0.00
0.00
0.60
0.00
-3.00
0.60
4
3.7565
17.00
3.885
0.00
-3.00
0.60
17.00
-3.00
0.60
TSEG:
0.828
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
53
209050-00028-0506.00-EL-CAL-0001
Rev.B (11-Jun-15)
54