Está en la página 1de 13

CUADRO DE CARGAS

INSTALACIONES ELECTRICAS

ELE-MC-0001

Revisión: A

Feb-23
MAXIMA DEMANDA

MAXIMA DEMANDA TABLERO DISTRIBUCION TD


POTENCIA
CARGA UNITARIA FACTOR DE MAXIMA DEMANDA
TABLERO CTO. CARGA CANTIDAD INSTALADA
(Kw) DEMANDA (kW)
(Kw)
1 ALUMBRADO 1° PISO 7.07 1 7.07 0.80 5.66
2 TOMACORRIENTES 1° PISO 10.08 1 10.08 0.80 8.06
3 ILUMINACION EXT. 5.00 1 5.00 1.00 5.00
4 HORNO 8.00 1 8.00 0.80 6.40
TABLERO
DISTRIBU 5 THERMA 6.00 1 6.00 0.80 4.80
CION TD
6 AIRE ACONDICIONADO 12.00 1 12.00 1.00 12.00
7 COSINA ELECTRICA 6.00 1 6.00 1.00 6.00
8 ELECTROBOMBA 1.50 1 1.50 1.00 1.50
9 RESERVA 25% 13.91 1 13.91 1.00 13.91
TOTAL 69.57 63.33

POTENCIA INSTALADA 63.33 kW


FACTOR DE SIMULTANEIDAD 0.80

DEMANDA MÁXIMA 50.67 kW


CUADROS DE CARGAS

###
CUADRO DE CARGAS TABLERO GENERAL (TG)
POTENCIA VOLT COND. In (A) Id (A) LARGO Fn Ft Fu Icc T desp Sección Mínima (mm2) Conductor DUCTO
Nº TIPO DE
TABLERO CTO. CARGA FDP I.T.M. Elegido Reg % CABLE ALIMENTADOR
(kW) (V) FASE x FASE 25% CABLE (m) (kA) (seg) Corr COCI Reg. (mmɸ)
(mm2)
1 ALUMBRADO 1° PISO ###
2 TOMACORRIENTES 1° PISO ###
3 ILUMINACION EXT. ###
4 HORNO ###
TABLERO
GENERAL 5 THERMA ###
(TG)
6 AIRE ACONDICIONADO ###
7 COSINA ELECTRICA ###
8 ELECTROBOMBA ###
9 RESERVA 25% ###
TOTAL 0.00 220 3 1 0.90 0.00 0.00 3x 16 A N2XOH 0 1.00 0.91 1.00 0.32 0.1 4 0.6 0.00 120 0.00 3-1x120mm2 N2XOH+1x4mm2 N2XOH(T) 50

POTENCIA INSTALADA kW ###


DEMANDA MÁXIMA kW ###
NH-80 NH-90

ITM Diametro Diametro


ITM Secciones Area Total
DIFERENCIAL Exterior Exterior

10 2x25A 0 0 0 0
16 2x40A 2.5 3.6 10.18 3.6
20 4x25A 4 4.1 13.20 4.1
25 4x40A 6 4.6 16.62 4.7
32 10 6.0 28.27 6.3
40 16 6.8 36.32 7
50 25 8.4 55.42 8.2
63 35 9.4 69.40 9.2
80 50 11.1 96.77 11.1
100 70 12.7 126.68 12.7
125 95 14.9 174.37 14.4
160 120 16.4 211.24 16.6
200 150 18.2 260.16 18
250 185 20.3 323.65 19.7
400 240 23.1 419.10 22.1
630 300 25.7 518.75 24.9
800 400 28.9 655.97
1000 500
1250
1600
2000 6.1 29.22 97.42
2500
3200

TABLA Factor k : Resist. Ohm mm2/m


Sólido 0.779 Cobre (1)
7 hebras 0.726 Aluminio (2)
19 hebras 0.758 Ra ( ohm/km) = Ro/(Secc)
37 hebras 0.768

ANEXO 1: Extracto Tabla Cable NHX de INDECO


Capacidad Corriente Conductores Aislados
80°C 90°C In 80°C In 90°C
Secc ANSI In In
0.00 4 10 0 0 0 0
4.00 4 10 31 34 31 34
4.10 6 8 32 35
6.00 6 8 39 44 39 44
6.10 10 6 40 45
10.00 10 6 51 62 51 62
10.10 16 4 52 63
16.00 16 4 68 85 68 85
16.10 25 3 69 86
25.00 25 3 88 107 88 107
25.10 35 2 89 108
35.00 35 2 110 135 110 135
35.10 50 1/0 111 136
50.00 50 1/0 138 160 138 160
50.10 70 2/0 139 161
70.00 70 2/0 165 203 165 203
70.10 95 4/0 166 204
95.00 95 4/0 198 242 198 242
95.10 120 250 199 243
120.00 120 250 231 279 231 279
120.10 150 300 232 280
150.00 150 300 264 318 264 318
150.10 185 400 265 319
185.00 185 400 303 361 303 361
185.10 240 500 304 362
240.00 240 500 352 406 352 406
240.10 300 600 353 407
300.00 300 600 391 462 391 462
BAJO 392 463
BAJO BAJO BAJO
N2XOH NYY

Diametro Diametro Secciones de Secciones de


Area Total Area Total Area Total
Exterior Exterior Tierra Tierra (por ITM)

0 0 0 0 0 0.00 4.00
10.18 5.3 22.06 6.5 33.18 4.00 4.00
13.20 5.8 26.42 7.5 44.18 4.00 4.00
17.35 6.3 31.17 8 50.27 4.00 4.00
31.17 7.1 39.59 9.0 63.62 6.00 4.00
38.48 8 50.27 10 78.54 10.00 6.00
52.81 9.7 73.90 12 113.10 16.00 6.00
66.48 10.7 89.92 13 132.73 25.00 6.00
96.77 12.1 114.99 14.5 165.13 25.00 10.00
126.68 14 153.94 16.5 213.82 35.00 10.00
162.86 15.9 198.56 18.5 268.80 50.00 16.00
216.42 17.6 243.28 20 314.16 70.00 16.00
254.47 19.6 301.72 22.5 397.61 95.00 16.00
304.81 22 380.13 24.5 471.44 95.00 25.00
383.60 24.6 475.29 27.5 593.96 120.00 25.00
486.95 27.2 581.07 30.5 730.62 150.00 50.00
0.00 30.6 735.42 34 907.92 240.00 50.00
34.2 918.63 37.5 1104.47 300.00 70.00
95.00
120.00
53.00 5163.02 100 150.00
13 185.00
30 5163.02 250 250 82.6083882657 240.00
10

Resist. Ohm mm2/m


0.0179
0.0295
Ra ( ohm/km) = Ro/(Secc)

ANEXO 2: Extracto Tabla Cable N2XOH de INDE


Capacidad Corriente Conductores Aislados

Ra Xa r2+x2 Secc ANSI


0.004475 0.0001948 2.0063572E-05 0.00 4 10
0.004475 0.0001948 2.0063572E-05 4.00 4 10
0.002983 0.0001878 8.93554662E-06 4.10 6 8
0.002983 0.0001878 8.93554662E-06 6.00 6 8
0.001790 0.0001744 3.23451536E-06 6.10 10 6
0.001790 0.0001744 3.23451536E-06 10.00 10 6
0.001119 0.0001634 1.27830112E-06 10.10 16 4
0.001119 0.0001634 1.27830112E-06 16.00 16 4
0.000716 0.0001506 5.3533636E-07 16.10 25 3
0.000716 0.0001506 5.3533636E-07 25.00 25 3
0.000511 0.0001506 2.84239544E-07 25.10 35 2
0.000511 0.0001506 2.84239544E-07 35.00 35 2
0.000358 0.0001402 1.4782004E-07 35.10 50 1/0
0.000358 0.0001402 1.4782004E-07 50.00 50 1/0
0.000256 0.0001366 8.40493559E-08 50.10 70 2/0
0.000256 0.0001366 8.40493559E-08 70.00 70 2/0
0.000188 0.0001353 5.38085831E-08 70.10 95 4/0
0.000188 0.0001353 5.38085831E-08 95.00 95 4/0
0.000149 0.000134 4.02066944E-08 95.10 120 250
0.000149 0.000134 4.02066944E-08 120.00 120 250
0.000119 0.0001328 3.18762844E-08 120.10 150 300
0.000119 0.0001328 3.18762844E-08 150.00 150 300
0.000097 0.0001317 2.670676E-08 150.10 185 400
0.000097 0.0001317 2.670676E-08 185.00 185 400
0.000075 0.0001312 2.27761136E-08 185.10 240 500
0.000075 0.0001312 2.27761136E-08 240.00 240 500
0.000060 0.0001295 2.03303611E-08 240.10 300 600
0.000060 0.0001295 2.03303611E-08 300.00 300 600
BAJO 0.0001282 #VALUE! BAJO
BAJO BAJO #VALUE! BAJO
Tuberias Area Tipo de Cable

20 314.16 LSOH-80
25 490.87 LSOH-90
32 804.25 N2XOH
40 1256.64 NYY
50 1963.50
65 3318.31
80 5026.55
100 7853.98

Tabla Cable N2XOH de INDECO


e Conductores Aislados

In Ra Xa r2+x2
0.00
4.00
0 0 0.004475 0.0001948 2.0063572E-05 4.10
46 46 0.004475 0.0001948 2.0063572E-05 6.00
47 0.002983 0.0001878 8.93554662E-06 6.10
58 58 0.002983 0.0001878 8.93554662E-06 10.00
59 0.001790 0.0001744 3.23451536E-06 10.10
79 79 0.001790 0.0001744 3.23451536E-06 16.00
80 0.001119 0.0001634 1.27830112E-06 16.10
105 105 0.001119 0.0001634 1.27830112E-06 25.00
106 0.000716 0.0001506 5.3533636E-07 25.10
141 141 0.000716 0.0001506 5.3533636E-07 35.00
142 0.000511 0.0001506 2.84239544E-07 35.10
174 174 0.000511 0.0001506 2.84239544E-07 50.00
175 0.000358 0.0001402 1.4782004E-07 50.10
214 214 0.000358 0.0001402 1.4782004E-07 70.00
215 0.000256 0.0001366 8.40493559E-08 70.10
270 270 0.000256 0.0001366 8.40493559E-08 95.00
271 0.000188 0.0001353 5.38085831E-08 95.10
335 335 0.000188 0.0001353 5.38085831E-08 120.00
336 0.000149 0.000134 4.02066944E-08 120.10
391 391 0.000149 0.000134 4.02066944E-08 150.00
392 0.000119 0.0001328 3.18762844E-08 150.10
452 452 0.000119 0.0001328 3.18762844E-08 185.00
453 0.000097 0.0001317 2.670676E-08 185.10
522 522 0.000097 0.0001317 2.670676E-08 240.00
523 0.000075 0.0001312 2.27761136E-08 240.10
623 623 0.000075 0.0001312 2.27761136E-08 300.00
624 0.000060 0.0001295 2.03303611E-08
717 717 0.000060 0.0001295 2.03303611E-08
718 BAJO 0.0001282 #VALUE!
BAJO BAJO BAJO #VALUE!
ANEXO 3: Extracto Tabla Cable NYY de CEPER
Capacidad Corriente Conductores Aislados

Secc ANSI In Ra Xa r2+x2


4 10 0 0 (ohm/mt) (ohm/mt) (ohm/mt)
4 10 41 41 (ohm/mt) 0.000173 #VALUE!
6 8 42 0.003080 0.000164 9.513296E-06
6 8 52 52 0.003080 0.000164 9.513296E-06
10 6 53 0.001830 0.000152 3.372004E-06
10 6 71 71 0.001830 0.000152 3.372004E-06
16 4 72 0.001150 0.000143 1.342949E-06
16 4 94 94 0.001150 0.000143 1.342949E-06
25 3 95 0.000727 0.000138 5.47573E-07
25 3 126 126 0.000727 0.000138 5.47573E-07
35 2 127 0.000524 0.000132 0.000000292
35 2 156 156 0.000524 0.000132 0.000000292
50 1/0 157 0.387000 0.000128 0.14976901638
50 1/0 192 192 0.387000 0.000128 0.14976901638
70 2/0 193 0.000268 0.000124 0.0000000872
70 2/0 241 241 0.000268 0.000124 0.0000000872
95 4/0 242 0.000193 0.000122 5.2133E-08
95 4/0 300 300 0.000193 0.000122 5.2133E-08
120 250 301 0.000192 0.000119 5.1025E-08
120 250 349 349 0.000192 0.000119 5.1025E-08
150 300 350 0.000124 0.000119 2.9537E-08
150 300 402 402 0.000124 0.000119 2.9537E-08
185 400 403 0.000099 0.000118 2.374481E-08
185 400 464 464 0.000099 0.000118 2.374481E-08
240 500 465 0.000075 0.000117 1.937416E-08
240 500 553 553 0.000075 0.000117 1.937416E-08
300 600 554 0.000060 0.000116 1.706801E-08
300 600 636 636 0.000060 0.000116 1.706801E-08
BAJO 637 BAJO 0.000114 #VALUE!
BAJO BAJO BAJO BAJO #VALUE!
ANEXO 4: Extracto Tabla Cable N2XSY de INDECO
Capacidad Corriente Conductores Aislados

Secc ANSI In Ra Xa r2+x2


0.00 50 1/0 0 0 (ohm/mt) (ohm/mt) (ohm/mt)
50.00 50 1/0 230 230 0.000387 0.0001711 1.7904421E-07
50.01 70 2/0 231 0.000268 0.0001622 9.813284E-08
70.00 70 2/0 280 280 0.000268 0.0001622 9.813284E-08
70.01 95 4/0 281 0.000193 0.0001539 6.093421E-08
95.00 95 4/0 330 330 0.000193 0.0001539 6.093421E-08
95.01 120 250 331 0.000153 0.0001471 4.504741E-08
120.00 120 250 375 375 0.000153 0.0001471 4.504741E-08
120.01 240 500 376 0.000075 0.0001317 2.303005E-08
240.00 240 500 545 545 0.000075 0.0001317 2.303005E-08
240.01 300 600 546 0.000060 0.0001278 1.994485E-08
300.00 300 600 610 610 0.000060 0.0001278 1.994485E-08
BAJO 611 BAJO 0.0001194 #VALUE!
BAJO BAJO BAJO BAJO #VALUE!

También podría gustarte