DATOS:
F'c Concreto (kg/cm^2)
Peso especifico del concreto (kg/m^3)
210
2400
Superficie del camino
Fy acero de refuerzo (kg/cm^2) 4200
Peso especifico del suelo (t/m^3) 1800
Capacidad portante del suelo (kg/cm^2) 1.5
Angulo de friccion interna del suelo (°) 19
Profundidad del nivel freático (m) 2 r= 0.50 m
DIMENSIONES DE LA SECCION
2.00 m
NF
########################## ########################
D E F
D
1929.14 kg.m 2448.84 kg.m E 2448.84 kg.m F 1929.14 kg.m
6799.11 kg/m^2 6799.11 kg/m^2
3116.70 kg.m 3809.30 kg.m 3116.70 kg.m
-10017.15 kg/m^2
DISTRIBUCION DE MOMENTOS
Rigideces = 4EI/L
Tramos horizontales 2.025316456
Tramos verticales 1.904761905
Suma 3.93007836
Factores de distribucion
AB=CB=DE=FE 0.515
BA=BC=ED=EF 0.340
AD=DA=CF=FC 0.485
AD BA CB FC E D
AD AB BA BE BC CB CF FC FE EF EB ED DE DA
F. DIST 0.485 0.515 0.340 0.340 0.340 0.515 0.485 0.485 0.515 0.340 0.340 0.340 0.515 0.485
M. EMP. 1644.37 -2049.89 2505.42 -2505.42 2049.89 -1644.37 1929.14 -3116.70 3809.30 -3809.30 3116.70 -1929.14
1.- M. DIST. 196.54 208.98 -208.98 -196.54 575.57 612.00 -612.00 -575.57
TRANS. -287.78 104.49 -104.49 287.78 -98.27 306.00 -306.00 98.27
2.- M. DIST. 139.48 148.31 -148.31 -139.48 47.63 50.64 -50.64 -47.63
TRANS. -23.81 74.15 -74.15 23.81 -69.74 25.32 -25.32 69.74
3.- M. DIST. 11.54 12.27 -12.27 -11.54 33.80 35.94 -35.94 -33.80
TRANS. -16.90 6.14 -6.14 16.90 -5.77 17.97 -17.97 5.77
4.- M. DIST. 8.19 8.71 -8.71 -8.19 2.80 2.97 -2.97 -2.80
TRANS. -1.40 4.35 -4.35 1.40 -4.10 1.49 -1.49 4.10
5.- M. DIST. 0.68 0.72 -0.72 -0.68 1.98 2.11 -2.11 -1.98
M. FINAL 1670.90 -1670.90 2694.55 -2694.55 1670.90 -1670.90 2413.04 -2413.04 4160.08 -4160.08 2413.04 -2413.04
MOMENTOS FINALES
MAB=MCB 1670.90
MBA=BBC 2694.55
MDE=MFE 2413.04
MEF=MED 4160.08
EN PAREDES LATERALES
CORTANTES ISOSTATICOS
Puntos superiores A y C (kg) 4562.59
Puntos inferiores D y F (kg) 5647.42
CORTANTE HIPERESTATICA
V -353.3988851
CORTANTES FINALES
Puntos superiores A y C (kg) 4209.19
Puntos inferiores D y F (kg) 6000.82
Calculando el cortante igual a cero para determinar el momento CARGA (kg/m^2) 10017.15
MOMENTOS EN CENTROS DE CLARO máximo CAPACIDAD DEL SUELO (kg/m^2) 15000
FACTOR DE SEGURIDAD ">1.5" 1.50
Losa superior 1029.63 X (cortante igual a cero) 0.84
Losa inferior 1597.59 f(x)=RA- (P1(2L-X)+P2X/2L)X 610.15
En paredes laterales 53.53 f(x)^2 372279.49
B C 4209.19 kg
A
1670.90 kg.m A B C 1670.90 kg.m ########################
1029.63 kg.m 1029.6 kg.m
######################## 4879.53 kg
7418.95 kg ########################
########################## ########################
D E F
##########################
D 2005.21 kg.m 2005.21 kg.m F 1929.14 kg.m
E
6799.11 kg/m^2 6799.11 kg/m^2
2552.09 kg.m 2005.21 kg.m 2552.09 kg.m
-8202.47 kg/m^2
DISTRIBUCION DE MOMENTOS
Rigideces = 4EI/L
Tramos horizontales 2.025316456
Tramos verticales 1.904761905
Suma 3.93007836
Factores de distribucion
AB=CB=DE=FE 0.515
BA=BC=ED=EF 0.340
AD=DA=CF=FC 0.485
AD BA CB FC E D
AD AB BA BE BC CB CF FC FE EF EB ED DE DA
F. DIST 0.485 0.515 0.340 0.340 0.340 0.515 0.485 0.485 0.515 0.340 0.340 0.340 0.515 0.485
M. EMP. 1644.37 -2049.89 2505.42 -2505.42 2049.89 -1644.37 1929.14 -2552.09 2005.21 -2005.21 2552.09 -1929.14
1.- M. DIST. 196.54 208.98 -208.98 -196.54 301.92 321.03 -321.03 -301.92
TRANS. -150.96 104.49 -104.49 150.96 -98.27 160.51 -160.51 98.27
2.- M. DIST. 73.16 77.80 -77.80 -73.16 47.63 50.64 -50.64 -47.63
TRANS. -23.81 38.90 -38.90 23.81 -36.58 25.32 -25.32 36.58
3.- M. DIST. 11.54 12.27 -12.27 -11.54 17.73 18.85 -18.85 -17.73
TRANS. -8.87 6.14 -6.14 8.87 -5.77 9.43 -9.43 5.77
4.- M. DIST. 4.30 4.57 -4.57 -4.30 2.80 2.97 -2.97 -2.80
TRANS. -1.40 2.28 -2.28 1.40 -2.15 1.49 -1.49 2.15
5.- M. DIST. 0.68 0.72 -0.72 -0.68 1.04 1.11 -1.11 -1.04
M. FINAL 1745.55 -1745.55 2657.23 -2657.23 1745.55 -1745.55 2157.48 -2157.48 2201.96 -2201.96 2157.48 -2157.48
MOMENTOS FINALES
MAB=MCB 1745.55
MBA=BBC 2657.23
MDE=MFE 2157.48
MEF=MED 2201.96
PAREDES LATERALES
CORTANTES ISOSTATICOS
Puntos superiores A y C (kg) 4562.59
CAPACIDAD DEL SUELO
Puntos inferiores D y F (kg) 5647.42
CARGA (kg/m^2) 8202.47
CORTANTE HIPERESTATICO CAPACIDAD DEL SUELO (kg/m^2) 15000
V -196.16 FACTOR DE SEGURIDAD ">1.5" 1.83 SI CUMPLE
Puntos superiores A y C (kg) 4366.43
Puntos inferiores D y F (kg) 5843.58
MOMENTOS EN CENTROS DE CLARO
8132.55 kg 4879.53 kg
6074.95 kg ########################
CALCULO DE ACERO
LECHOS EXTERIORES LECHO INFERIOR
ARMADO DE LA ALCANTARILLA
NOTAS:
# 4 @ 19 cm # 3 @ 19 cm
# 4 @ 19 cm # 3 @ 19 cm
# 4 @ 19 cm # 4 @ 19 cm
# 4 @ 19 cm # 4 @ 19 cm
# 4 @ 19 cm # 4 @ 19 cm
# 3 @ 19 cm
# 3 @ 19 cm # 3 @ 19 cm
# 4 @ 19 cm # 3 @ 19 cm
# 4 @ 19 cm # 3 @ 19 cm
RESUMEN DE REFUERZOS
ELEMENTO LECHO AREA DE ACERO (cm^2) No. DE BARRA PROPUESTA SEPARACION (cm)
Losa superior Exterior 6.67 4 19
Losa superior Exterior por temperatura 3.6 3 19
Losa superior Interior 6.67 4 19
Losa superior Interior por temperatura 3.6 3 19
Losa inferior Interior 6.67 4 19
Losa inferior Interior por temperatura 3.6 3 19
Losa inferior Exterior 6.67 4 19
Losa inferior Exterior por temperatura 3.6 3 19
Paredes laterales Exterior 6.67 4 19
Paredes laterales Exterior por temperatura 3.6 3 19
Paredes laterales Interior 6.67 4 19
Paredes laterales Interior por temperatura 3.6 3 19
Pared central Verticales 6.67 4 19
Pared central Horizontales ( por temperatura) 3.6 3 19
VOLUMEN DE MATERIALES
Volumen de concreto
Losa superior (m^3) 2.5875
Losa Inferior (m^3) 2.5875
Pared interior (m^3) 1.2
Paredes laterales (m^3) 3.15
Total de concreto (m^3) 9.525
Volumen de acero
Acero principal
Largo de barras (m) 2.16
Numero de barras 11.05
total de ml 24
Varilla a utilizar # 4
Total de varilla (kg) 23.78