Documentos de Académico
Documentos de Profesional
Documentos de Cultura
POST-LABORATORIO #5
NOMBRE DE LA PRÁCTICA:
INTERCAMBIADOR DE CALOR DE PLACAS
3
FI-401 MATERIAL DE INTERCAMBIADORES:
S-101 CARCASA Y TUBOS: ACERO AL CARBÓN,
TK-402 TK-401 COBRE
PLACAS: ACERO
N°
TK-401
FECHA: 19/05/2023
Datos experimentales
TABLA 1.1. DATOS EXPERIMENTALES ICP TAMAÑO LABORATORIO
DATOS EXPERIMENTALES ICP TAMAÑO LABORATORIO
Fh (L/min) Fc (L/min) Tca (°C) Tha (°C) Tcb (°C) Thb (°C)
0.5 1.6 7.6 45.5 15.7 16
1 1.6 12.1 50.7 27.2 28.1
1.5 1.6 15.7 52.9 34.2 35.5
2 1.6 15.6 54 36.7 38.7
2.5 1.6 13.7 54.1 38 40.7
3 1.6 14.5 54.1 40 42.7
Fh (L/min) Fc (L/min) Tca (°C) Tha (°C) Tcb (°C) Thb (°C)
0.5 1 8.6 49.7 22.1 21.4
1 1 11.3 52.8 33.9 33.8
1.5 1 11.8 53 38.3 38.9
2 1 12 52.2 40.3 41.3
2.5 1 12.2 52.5 42.3 43.5
3 1 12.2 52.9 42.9 44.4
Fh (L/min) Fc (L/min) Tca (°C) Tha (°C) Tcb (°C) Thb (°C)
2.5 1 3.3 60.8 46.2 47.9
2 1 3 60.8 44.5 45.4
1.5 1 2.8 60.6 41.1 41.4
1 1 2.5 60 35.7 35.2
0.5 1 2.8 59.4 24.6 22.7
Fh (L/min) Fc (L/min) Tca (°C) Tha (°C) Tcb (°C) Thb (°C)
3.0 1.89 1.9 54.4 31.6 38.2
2.5 1.89 2.6 51.5 28.9 34.9
2.0 1.89 5 51.4 28.2 33.1
1.5 1.89 3.2 51 24 28.6
1.0 1.89 2.4 50.8 20.1 23.5
0.5 1.89 4.2 50.2 13.3 14.4
Fh (L/min) Fc (L/min) Tca (°C) Tha (°C) Tcb (°C) Thb (°C)
0.5 1.85 6.7 56.4 16.3 17.8
1.0 1.85 7.4 57.1 24.6 18.3
1.5 1.85 8.3 56.3 29.2 33.8
2.0 1.85 7.7 54.4 30.8 36.1
2.5 1.85 7.3 52.1 31.5 37
3.0 1.85 6.7 47.9 30.4 35.6
TABLA 1.2. DATOS EXPERIMENTALES ICP TAMAÑO PLANTA PILOTO
CÁLCULOS
INTERCAMBIADOR DE CALOR DE CARCASA DE PLACAS TAMAÑO
PLANTA PILOTO
Calor promedio:
kcal kcal
30783.247 h + 33825.285 h 𝑘𝑐𝑎𝑙
Q prom = = 32304.266
2 ℎ
Efectividad del intercambiador:
Enfriamiento
(90 − 34)°C
𝐸= = 0.823
(90 − 22)°C
Calentamiento
(59 − 22)°C
𝐸= = 0.544
(90 − 22)°C
La diferencia media logarítmica de temperatura para el flujo en contracorriente:
(𝑇ℎ𝑏 − 𝑇𝑐𝑎 ) − (𝑇ℎ𝑎 − 𝑇𝑐𝑏 )
∆𝑇𝑚 =
(𝑇 − 𝑇 )
𝑙𝑛 (𝑇ℎ𝑏 − 𝑇𝑐𝑎 )
ℎ𝑎 𝑐𝑏
𝑘𝑔 𝑘𝑔 𝑘𝑔𝑚 𝑚
(0.0034 𝑚) (982.159 ) (0.0034 𝑚) (26223.55 2𝑓 ) (9.8 )
𝑚3 √ 𝑚 𝑘𝑔𝑓 𝑠 2
𝑁𝑅𝑒 √𝑓 ℎ =
𝑘𝑔 𝑘𝑔
(0.0004577 ) 2 (982.159 3 ) (1.18 𝑚)
𝑚𝑠 𝑚
𝑁𝑅𝑒 √𝑓 ℎ = 4479.02
𝑘𝑔 𝑘𝑔𝑓 𝑘𝑔𝑚 𝑚
(0.0034 𝑚) (992.088
3 ) (0.0034 𝑚) (22690.6316 𝑚2 ) (9.8 𝑘𝑔 𝑠 2 )
𝑚 √ 𝑓
𝑁𝑅𝑒 √𝑓 𝑐 =
𝑘𝑔 𝑘𝑔
(0.0006483 ) 2 (992.088 3 ) (1.18 𝑚)
𝑚𝑠 𝑚
𝑁𝑅𝑒 √𝑓 𝑐 = 2956.539
A partir del factor de Karman, se obtiene el número de Reynolds para el flujo frío y
para el flujo caliente por medio de la siguiente correlación.
0.027(18078.17)−0.2
𝑁𝑆𝑇ℎ = 0.14 = 0.001927
𝑘𝑔
(0.0004577 )
𝑚𝑠
(2.8545)𝟎.𝟔𝟕 ( )
𝑘𝑔
(0.0005398 )
𝑚𝑠
0.027(11272.79)−0.2
𝑁𝑆𝑇𝑐 = 0.14 = 0.001537
𝑘𝑔
(0.0006483 )
𝑚𝑠
(4.2805)𝟎.𝟔𝟕 ( )
𝑘𝑔
(0.0005398 )
𝑚𝑠
Necesitamos la velocidad del fluido:
𝑁𝑅𝑒 𝜇
𝑣=
𝐷𝑒𝜌
𝑘𝑔
(18078.17) (0.0004577) 𝑚
𝑚𝑠
𝑣ℎ = = 2.4781
𝑘𝑔 𝑠
(0.0034 𝑚) (982.159 3 )
𝑚
𝑘𝑔
(11279.79) (0.0006483) 𝑚
𝑚𝑠
𝑣𝑐 = = 2.1667
𝑘𝑔 𝑠
(0.0034 𝑚) (992.088 3 )
𝑚
Área teórica
Q prom
Ateo =
Uo teo ∆Tm
L 1m3 60 min kg kg
ṁ c = 1.38 | || | ∗ 999.446 3 = 82.7541
min 1000L h m h
Calor promedio:
kcal kcal
977.9657 h + 1038.8082 h 𝑘𝑐𝑎𝑙
Q prom = = 1008.387
2 ℎ
TABLA DE RESULTADOS
TABLA 2.1. RESULATDOS ICP TAMAÑO LABORATORIO
Ap (m^2) 0.008
Nt 7
Atp (m^2) 0.04
Fh Fc Tph mh Qced Tpc mc Qgan ∆Tmlog Qprom Uexp
η Ecalen Enfri
(L/min) (L/min) (°C) (kg/h) (kcal/h) (°C) (kg/h) (kcal/h) (°C) (kcal/h) (kcal/hm^2°C)
0.5 1.38 35.65 29.82 1038.808 12 82.754 977.97 94.14 0.251 0.743 21.632 1008.39 1165.364
1 1.38 44.7 59.42 1590.180 18.7 82.672 1834.83 115.39 0.440 0.531 25.932 1712.51 1650.955
1.5 1.38 47.9 89.01 1866.790 21.4 82.627 2245.81 120.30 0.538 0.415 26.379 2056.30 1948.828
2 1.38 48.7 118.64 1990.630 22.05 82.615 2501.17 125.65 0.604 0.335 26.070 2245.90 2153.721
2.5 1.38 49.6 148.24 2072.852 23 82.598 2690.11 129.78 0.653 0.281 25.478 2381.48 2336.764
3 1.38 50.25 177.83 2149.300 23.55 82.587 2846.33 132.43 0.690 0.242 25.053 2497.81 2492.548
0.5 1.6 30.75 29.86 879.587 11.65 95.950 778.46 88.50 0.214 0.778 16.900 829.02 1226.370
1 1.6 39.4 59.55 1343.589 19.65 95.834 1446.45 107.66 0.391 0.585 19.510 1395.02 1787.541
1.5 1.6 44.2 89.15 1548.935 24.95 95.720 1768.73 114.19 0.497 0.468 19.245 1658.83 2154.914
2 1.6 46.35 118.76 1814.524 26.15 95.691 2016.45 111.13 0.549 0.398 20.060 1915.49 2387.146
2.5 1.6 47.4 148.39 1985.696 25.85 95.698 2322.51 116.96 0.601 0.332 21.082 2154.10 2554.379
3 1.6 48.4 177.98 2026.411 27.25 95.662 2436.00 120.21 0.644 0.288 20.342 2231.21 2742.119
0.5 1 35.55 29.82 842.387 15.35 59.941 809.60 96.11 0.328 0.689 19.262 826.00 1072.079
1 1 43.3 59.46 1127.955 22.6 59.859 1351.59 119.83 0.545 0.458 20.648 1239.77 1501.098
1.5 1 45.95 89.09 1254.346 25.05 59.824 1583.44 126.24 0.643 0.342 20.272 1418.89 1749.831
2 1 46.75 118.74 1292.504 26.15 59.807 1690.33 130.78 0.704 0.271 19.311 1491.42 1930.806
2.5 1 48 148.35 1333.370 27.25 59.789 1797.15 134.78 0.747 0.223 18.819 1565.26 2079.404
3 1 48.65 177.96 1510.775 27.55 59.784 1832.78 121.31 0.754 0.209 18.984 1671.78 2201.516
2.5 1 54.35 147.91 1906.413 24.75 59.828 2563.65 134.47 0.746 0.224 26.865 2235.03 2079.904
2 1 53.1 118.40 1821.606 23.75 59.843 2480.87 136.19 0.718 0.266 27.302 2151.24 1969.872
1.5 1 51 88.89 1704.731 21.95 59.868 2291.06 134.39 0.663 0.332 27.972 1997.90 1785.653
1 1 47.6 59.35 1469.895 19.1 59.903 1988.09 135.25 0.577 0.431 28.292 1728.99 1527.785
0.5 1 41.05 29.76 1090.269 13.7 59.955 1308.26 119.99 0.385 0.648 26.660 1199.27 1124.610
3.0 1.89 46.3 178.15 2881.946 16.75 113.263 3364.44 116.74 0.566 0.309 29.029 3123.19 2689.745
2.5 1.89 43.2 148.65 2463.782 15.75 113.281 2980.48 120.97 0.538 0.339 27.162 2722.13 2505.463
2.0 1.89 42.25 118.97 2173.640 16.6 113.266 2628.27 120.92 0.500 0.394 25.572 2400.95 2347.267
1.5 1.89 39.8 89.31 1997.259 13.6 113.316 2359.30 118.13 0.435 0.469 26.192 2178.28 2079.156
1.0 1.89 37.15 59.60 1624.318 11.25 113.346 2009.77 123.73 0.366 0.564 25.601 1817.04 1774.406
0.5 1.89 32.3 29.85 1066.853 8.75 113.370 1034.51 96.97 0.198 0.778 20.765 1050.68 1264.971
0.5 1.85 37.1 29.80 1148.348 11.5 110.944 1066.85 92.90 0.193 0.777 22.578 1107.60 1226.410
1.0 1.85 37.7 59.59 2308.102 16 110.880 1907.76 82.66 0.346 0.781 19.772 2107.93 2665.357
1.5 1.85 45.05 89.12 2002.295 18.75 110.827 2315.65 115.65 0.435 0.469 26.292 2158.98 2052.891
2.0 1.85 45.25 118.82 2171.215 19.25 110.817 2558.92 117.86 0.495 0.392 25.926 2365.07 2280.596
2.5 1.85 44.55 148.57 2240.024 19.4 110.814 2680.62 119.67 0.540 0.337 24.873 2460.32 2472.868
3.0 1.85 41.75 178.49 2191.859 18.55 110.831 2626.09 119.81 0.575 0.299 22.725 2408.97 2650.086
TABLA 2.2. RESULATDOS ICP TAMAÑO PLANTA PILOTO
N Fc Fh mh Qced Tpc Qgan η Ecalen Enfri ∆Tmlog Qprom Uexp
L/min L/min (kg/h) (kcal/h) (°C) (kcal/h) (°C) kcal/h (kcal/hm^2°C)
1.1 14.00 10.25 604.03 33825.28 40.5 30783.25 91.007 0.544 0.824 20.019 32304.27 3470.215
1.2 13.90 7.89 465.20 26048.04 39.5 27269.11 104.688 0.500 0.848 19.264 26658.57 2975.995
1.3 13.95 6.00 353.77 20515.84 37.25 24484.39 119.344 0.437 0.859 20.558 22500.11 2353.653
1.4 14.01 4.04 238.20 13814.00 34 20028.20 144.985 0.353 0.853 22.948 16921.10 1585.729
1.5 13.96 2.83 166.82 9507.83 31 14983.27 157.589 0.265 0.838 25.757 12245.55 1022.406
2.1 13.95 10.05 591.60 30770.58 41 31496.57 102.359 0.559 0.765 22.271 31133.58 3006.273
2.2 12.36 9.91 583.52 28597.44 39.5 25717.50 89.929 0.530 0.742 23.303 27157.47 2506.221
2.3 10.34 9.86 580.25 27280.34 44 27002.14 98.980 0.667 0.712 20.463 27141.24 2852.330
2.4 8.03 10.29 604.01 25392.80 46.5 23330.73 91.879 0.721 0.618 22.317 24361.76 2347.543
2.5 6.40 10.49 614.67 22159.75 49 20472.68 92.387 0.794 0.529 21.774 21316.22 2105.336
2.6 3.61 10.49 611.82 11657.41 51 12393.63 106.315 0.866 0.284 23.298 12025.52 1110.032
3.1 11.59 6.59 388.55 22533.23 42 22028.24 97.759 0.500 0.906 15.532 22280.74 3084.982
3.2 9.80 6.73 396.70 21817.13 45 20931.05 95.939 0.581 0.887 14.480 21374.09 3174.510
3.3 8.71 6.64 390.97 19943.23 47 20654.39 103.566 0.645 0.823 15.870 20298.81 2750.745
3.4 6.54 6.93 407.37 18342.30 50.5 18198.00 99.213 0.758 0.726 15.979 18270.15 2458.871
3.5 5.05 6.97 408.65 15548.56 55 16712.97 107.489 0.889 0.603 14.140 16130.76 2453.275
3.6 4.28 6.88 402.65 12907.75 56.5 14914.45 115.546 0.937 0.508 13.186 13911.10 2268.869
3.7 3.17 6.97 407.67 12254.00 55 10491.11 85.614 0.889 0.476 16.768 11372.56 1458.582
N Tpp Pr Rho Cp Miu Miu w Pha Phb DELTA P NRe √f NRe Nst vel hcorreg
(°C) (kg/m^3) (kcal/kg °C) (kg/ms) (kg/ms) (kgf/m^2) (kgf/m^2) (kgf/m^2) (m/s) (kcal/h m°C)
4.58E-
2.854 5.40E-04
1.1 51.25 982.159 1.0000 04 25000 -1223.559 26223.559 4479 18078 0.00193 2.4781 16880.954
4.65E-
2.900 5.49E-04
1.2 50.25 982.685 0.9999 04 18000 -1359.51 19359.51 3793 14965 0.00198 2.0807 14571.380
4.65E-
2.900 5.59E-04
1.3 49.125 982.685 0.9999 04 8500 -1359.51 9859.51 2707 10197 0.00214 1.4178 10748.210
4.65E-
2.900 5.74E-04
1.4 47.5 982.685 0.9999 04 3700 -1223.559 4923.559 1913 6871 0.00233 0.9553 7866.980
4.61E-
2.877 5.86E-04
1.5 46.25 982.423 0.9999 04 1000 -1223.559 2223.559 1295 4409 0.00257 0.6087 5527.682
4.45E-
2.766 5.29E-04
2.1 52.5 981.088 1.0002 04 25000 -747.7305 25747.7305 4567 18484 0.00196 2.4635 17070.078
4.48E-
2.787 5.38E-04
2.2 51.5 981.358 1.0002 04 25000 -747.7305 25747.7305 4535 18334 0.00196 2.4607 17014.195
4.41E-
2.744 5.15E-04
2.3 54.25 980.817 1.0003 04 25000 -815.706 25815.706 4606 18661 0.00196 2.4699 17118.258
4.14E-
2.566 4.88E-04
2.4 57.75 978.316 1.0010 04 25000 -815.706 25815.706 4904 20043 0.00203 2.4944 17822.013
3.97E-
2.457 4.68E-04
2.5 60.5 976.589 1.0014 04 25000 -815.706 25815.706 5109 20995 0.00207 2.5106 18270.695
3.59E-
2.216 4.37E-04
2.6 65.25 972.075 1.0028 04 25000 -815.706 25815.706 5635 23473 0.00218 2.5505 19476.125
4.65E-
2.900 5.38E-04
3.1 51.5 982.685 0.9999 04 16000 -1631.412 17631.412 3620 14190 0.00200 1.9730 13925.378
4.61E-
2.877 5.23E-04
3.2 53.25 982.423 0.9999 04 16000 -1359.51 17359.51 3618 14182 0.00200 1.9579 13852.310
4.48E-
2.787 5.07E-04
3.3 55.25 981.358 1.0002 04 16000 -815.706 16815.706 3665 14391 0.00204 1.9314 13901.758
4.29E-
2.662 4.82E-04
3.4 58.5 979.719 1.0006 04 16000 -815.706 16815.706 3823 15101 0.00208 1.9443 14262.224
4.03E-
2.493 4.51E-04
3.5 63 977.170 1.0013 04 16000 -815.706 16815.706 4068 16203 0.00214 1.9634 14806.335
3.86E-
2.389 4.37E-04
3.6 65.25 975.413 1.0018 04 16000 -543.804 16543.804 4200 16805 0.00219 1.9578 15077.188
3.81E-
2.356 4.38E-04
3.7 65 974.817 1.0020 04 16000 -543.804 16543.804 4256 17059 0.00221 1.9620 15234.590
N Npr Rho Cp Miu Miu w Pca Pcb DELTA P NRe √f NRe Nst vel hc
(kg/m^3) (kcal/kg °C) (kg/ms) (kg/ms) (kgf/m^2) (kgf/m^2) (kgf/m^2) (m/s) (kcal/h m°C)
1.1 4.28005 992.0877 0.99835 6.48E-04 5.40E-04 22000 -690.63 22690.63 2956.5 11272.8 0.00154 2.1667 11876.091
1.2 4.37601 992.4706 0.99833 6.60E-04 5.49E-04 22000 -690.63 22690.63 2903.4 11042.7 0.00152 2.1609 11718.558
1.3 4.60470 993.3031 0.99830 6.89E-04 5.59E-04 22000 -690.63 22690.63 2784.6 10530.4 0.00148 2.1476 11334.690
1.4 4.96860 994.4325 0.99831 7.34E-04 5.74E-04 22000 -690.63 22690.63 2614.8 9803.5 0.00142 2.1280 10783.864
1.5 5.34296 995.3949 0.99839 7.80E-04 5.86E-04 22000 -690.63 22690.63 2460.1 9146.6 0.00136 2.1093 10275.826
2.1 4.23334 991.8933 0.99836 6.42E-04 5.29E-04 20000 -690.63 20690.63 2848.7 10806.4 0.00156 2.0587 11444.348
2.2 4.37601 992.4706 0.99833 6.60E-04 5.38E-04 15600 -690.63 16290.63 2460.1 9146.6 0.00157 1.7898 10050.715
2.3 3.96977 990.6874 0.99847 6.09E-04 5.15E-04 11500 -690.63 12190.63 2304.7 8492.4 0.00171 1.5359 9377.378
2.4 3.77056 989.6318 0.99860 5.84E-04 4.88E-04 7000 -690.63 7690.63 1909.6 6857.6 0.00185 1.1895 7826.402
2.5 3.58816 988.5320 0.99876 5.60E-04 4.68E-04 4000 -690.63 4690.63 1553.9 5424.7 0.00200 0.9036 6435.170
2.6 3.45331 987.6214 0.99890 5.42E-04 4.37E-04 5000 -690.63 5690.63 1767.3 6279.4 0.00199 1.0134 7148.888
3.1 4.14235 991.4989 0.99840 6.31E-04 5.38E-04 20000 -690.63 20690.63 2899.7 11026.8 0.00158 2.0641 11646.750
3.2 3.88796 990.2706 0.99852 5.99E-04 5.23E-04 12200 -690.63 12890.63 2410.7 8938.1 0.00173 1.5895 9782.107
3.3 3.73278 989.4153 0.99863 5.79E-04 5.07E-04 9000 -690.63 9690.63 2161.5 7895.0 0.00182 1.3583 8803.013
3.4 3.48615 987.8515 0.99886 5.46E-04 4.82E-04 6100 -690.63 6790.63 1915.2 6880.6 0.00196 1.1192 7803.514
3.5 3.20991 985.7214 0.99924 5.09E-04 4.51E-04 5100 -690.63 5790.63 1897.2 6806.8 0.00208 1.0333 7621.821
3.6 3.12676 984.9828 0.99938 4.97E-04 4.37E-04 3000 0.00 3000.00 1397.0 4806.2 0.00227 0.7135 5730.958
3.7 3.20991 985.7214 0.99924 5.09E-04 4.38E-04 1200 0.00 1200.00 863.6 2781.8 0.00248 0.4223 3710.266
N Uteo Ateo
(kcal/h m^2 °C) m^2
1.1 5581.745166 0.28909418
1.2 5272.128979 0.2624818
1.3 4608.767152 0.23747099
1.4 3912.990492 0.18844006
1.5 3185.345166 0.14925184
2.1 5504.313276 0.25396752
2.2 5155.060508 0.22606767
2.3 4980.7976 0.26628933
2.4 4553.789942 0.23971403
2.5 4067.640274 0.24067546
2.6 4406.429614 0.11713907
3.1 5170.992135 0.27741611
3.2 4758.91622 0.31018556
3.3 4519.873976 0.28299387
3.4 4273.924942 0.26752337
3.5 4265.207354 0.26746008
3.6 3616.237073 0.29174642
3.7 2696.312923 0.25154374
GRÁFICAS
Gráfica 1.1. Comparación de flujos variables contra Calor ganado
Tamaño Planta Piloto
35000
30000
25000
Q gan (kcal/h)
20000
Fccte=14 Fh=var
Fhcte=10 Fc=var
Fhcte=7 Fc=var
15000
10000
5000
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
F volum (L/min)
Gráfica 1.2. Comparación de flujos variables contra Calor cedido
Tamaño Planta Piloto
40000
35000
30000
25000
Q ced (kcal/h)
Fccte=14 Fh=var
15000
10000
5000
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
F volum (L/min)
Gráfica 1.3. Comparación de flujos variables contra Coeficiente convectivo hh
Tamaño Planta Piloto
21000
19000
17000
15000
hh (kcal/m2h°C)
13000
Fccte=14 Fh=var
Fhcte=10 Fc=var
Fhcte=7 Fc=var
11000
9000
7000
5000
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
F volum (L/min)
Gráfica 1.4. Comparación de flujos variables contra Coeficiente convectivo hc
Tamaño Planta Piloto
13000
12000
11000
10000
9000
hc (kcal/m2h°C)
8000
5000
4000
3000
2000
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
F volum (L/min)
Gráfico 1.5. Comparación de flujos variables contra la Eficiencia η
Tamaño Planta Piloto
160
155
150
145
140
135
130
125
η (%)
120
Fccte=14 Fh=var
115
Fhcte=10 Fc=var
110 Fhcte=7 Fc=var
105
100
95
90
85
80
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
F volum (L/min)
Gráfico 1.6. Comparación de flujos variables contra U teórica
Tamaño Planta Piloto
6000
5500
5000
4500
Uteórico (kcal/m2h°C)
4000
Fccte=14 Fh=var
Fhcte=10 Fc=var
3500 Fhcte=7 Fc=var
3000
2500
2000
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
F volum (L/min)
Gráfico 1.7. Comparación de flujos variables contra U experimental
Tamaño Planta Piloto
3500
3000
Uexperimental (kcal/m2h°C)
2500
Series1
2000 Series2
Series3
1500
1000
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
F volum (L/min)
Gráfico 1.8. Comparación de flujos variables contra A teórica
Tamaño Planta Piloto
0.5
0.45
0.4
0.35
0.3
Ateo (m2)
Fccte=14 Fh=var
Fhcte=10 Fc=var
0.25
Fhcte=7 Fc=var
Aexp
0.2
0.15
0.1
0.05
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
F volum (L/min)
Gráfica 2.1. Comparación de flujos variables contra Calor ganado
Tamaño Laboratorio
3500
3000
2500
Q ganado (kcal/h)
Fccte=1.38 Fh=var
Fccte=1.6 Fh=var
2000
Fccte=1 Fh=var
Fccte=1.89 Fh=var
Fccte=1.85 Fh=var
Fccte=1 Fh=var 2 corrida
1500
1000
500
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5
F (L/min)
Gráfica 2.2. Comparación de flujos variables contra Calor cedido
Tamaño Laboratorio
3500
3000
2500
Q cedido (kcal/h)
Fccte=1.38 Fh=var
Fccte=1.6 Fh=var
2000
Fccte=1 Fh=var
Fccte=1.89 Fh=var
Fccte=1.85 Fh=var
Fccte=1 Fh=var 2 corrida
1500
1000
500
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5
F (L/min)
Gráfica 2.3. Comparación de flujos variables contra la Eficiencia
Tamaño Laboratorio
160
140
120
100
Fccte=1.38 Fh=var
Fccte=1.6 Fh=var
80
n
Fccte=1 Fh=var
Fccte=1.89 Fh=var
Fccte=1.85 Fh=var
60
Fccte=1 Fh=var 2 corrida
40
20
0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5
F (L/min)
Gráfica 2.4. Comparación de flujos variables contra el coeficiente U exp
Tamaño Laboratorio
3000
2500
2000
U exp (kcal/m2h°C)
Fccte=1.38 Fh=var
Fccte=1.6 Fh=var
1500
Fccte=1 Fh=var
Fccte=1.89 Fh=var
Fccte=1.85 Fh=var
Fccte=1 Fh=var 2 corrida
1000
500
0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5
F (L/min)
CONCLUSIONES
Para comenzar analizando los resultados a escala en el tamaño Planta piloto, se tiene que a
mayor flujo mayor hubo más calor ganado, así como mayor flujo mayor calor cedido,
parcialmente proporcional a la cantidad de las corrientes, en el caso del flujo frio constante de
14 lpm se obtuvo una mayor correlación de datos, más lineal, mientras que al tener un flujo
caliente constante hubo mas variaciones.
Para el coeficiente convectivo hh, con un flujo frio de 14 lpm fue aumentando, mientras que
para un flujo caliente de 10 y 7 lpm junto con la variación del flujo frio se tuvieron valores mas
estables entre 1300 y 1900.Para el coeficiente convectivo de hc para un flujo frio cte de 14 lpm
es para la corrida que se obtuvieron valores más altos de 1200 mientras que para los flujos
calientes constantes de 7 y 10 lpm a un mayor flujo se obtuvieron valores mas altos. Esto se
debe a que los coeficientes convectivos están interrelacionados con la corriente de referencia,
ya sea caliente o fría, y al variar su flujo se tiene una correlación diferente y proporcional a su
flujo.
Para la comparación de la eficiencia, para un flujo frio de 14 lpm se obtuvieron eficiencias
mayores e inestables de hasta 160 al variar el flujo caliente, mientras que para flujos calientes
variando el flujo frio se obtuvieron valores entre 80 y 120.
Al variar el flujo caliente para la comparación del U teorica a mayor flujo fue incrementando los
valores del coeficiente hasta se obtuvieron valores de hasta 5600 kcal/hm^2°C, lo cual es muy
distinto a los obtenidos experimentalmente que se calcularon, podemos concluir que a mayor
flujo las U experimental fueron incrementando hasta obtener valores de hasta 3500
kcal/hm^2°C.
Para la obtención del área teórica, se obtuvieron valores muy lejos a las reales, esto se puede
deber por las pedidas de calor al ambiente, para un flujo frio constante de 14 lpm variando el
caliente va aumentando el área del intercambiador mientras que para un flujo caliente de 7 lpm
variando el caliente se obtuvieron valores más estables y cercanos a los reales.
Los mismos cálculos se realizaron para el tamaño laboratorio, teniendo que a un mayor flujo
existe mayor calor ganado, como calor cedido, en esta caso el fujo mayor, el flujo frio constante
de 1.89 lpm obtuvo mayor valor de calor intercambiado, para la eficiencia en ambos tipo de
variaciones de flujo se tuvieron valores de 80 a 140, valores debido a que se manejaron flujos
pequeños y por lo tanto al ser menos precisos en la toma de temperaturas operando a una
escala mas pequeña existen mayores perdidas y un mayor error. Finalmente como se observó
en las últimas graficas se obtiene un U experimental a un mayor flujo variable, tanto para la
variación del flujo frio y caliente.