SOLUCIÓN:
NOTA: Para altitudes bajas, no se considera diseño por diámetro mínimo de Efecto
Corona.
CAPACIDAD DE CORRIENTE:
𝐼 < 725𝐴(𝑃𝐴𝑅𝐴𝐾𝐸𝐸𝑇)
De la tabla: 𝑹𝒄𝒄(𝟐𝟎°𝑪) = 𝟎. 𝟏𝟎𝟑𝟕𝜴/𝒌𝒎
𝐑 𝐭 = 𝐑 𝟐𝟎°𝐂 (𝟏 + 𝛂𝚫𝐭)
𝜶𝑨𝑪𝑺𝑹 = 𝟎. 𝟎𝟎𝟒𝟎𝟑(°𝑪−𝟏 )
𝐨𝐡𝐦
𝐑 𝐜𝐚 = 𝐊𝐑 𝐜𝐜 ( )
𝐤𝐦
𝛍𝐟
𝐗 = 𝟎. 𝟎𝟓𝟎𝟏𝟑𝟖√
𝐑 𝐜𝐜
X K X K
0.1 1.00000 1.0 1.00519
0.2 1.00001 1.5 1.02582
0.3 1.00004 2.0 1.07816
0.4 1.00013 2.5 1.17538
0.5 1.00032 3.0 1.31809
1 ∗ 60
𝑥 = 0.050138 ∗ √ = 1.1378
0.1165
𝐾 = 1.01087
𝜴
𝑹𝒂𝒄 = 𝑲 ∗ 𝑹𝒄𝒄(𝟓𝟎°𝑪) = 𝟎. 𝟏𝟏𝟕𝟖
𝒌𝒎
¿CUÁNTOS SUBCONDUCTORES POR FASE DEBE TENER MI LTA?
Asumir la d=650mm
𝐑𝐚𝐜 𝛀
𝐑= = 𝟎. 𝟎𝟐𝟗𝟒𝟓
𝟒 𝐤𝐦
𝛀
𝐑 𝐭𝐨𝐭 = 𝐑 ∗ 𝐤𝐦 = (𝟎. 𝟎𝟐𝟗𝟒𝟓 ) ∗ 𝟒𝟓𝟎𝐤𝐦 = 𝟏𝟑. 𝟐𝟓𝟐𝟓𝛀
𝐤𝐦
ANÁLISIS GRÁFICO:
𝐧
𝐫 ′ = √𝐫𝐧𝐑𝐧−𝟏
∅
∅ = 𝟐𝟑. 𝟐𝐦𝐦 → 𝐫 = = 𝟏𝟏. 𝟔𝐦𝐦
𝟐
𝐑 = 𝟒𝟓𝟗. 𝟔𝟏𝟗𝟒𝐦𝐦; 𝐧 = 𝟒
𝟒
𝐫 ′ = √𝟏𝟏. 𝟔 ∗ 𝟒 ∗ (𝟒𝟓𝟗. 𝟔𝟏𝟗𝟒)𝟑 = 𝟐𝟓𝟗. 𝟎𝟕𝟔𝟔𝐦𝐦 = 𝟎. 𝟐𝟓𝟗𝟏𝐦
-Para el DMG:
Luego: 52 = L2 + 2.822
L = 4.1289
Entonces:
2.82 𝑦
tan(𝛼) = =
4.1289 1.18
𝑦 = 0.8059
X= 5.00-(2.82+y) =1.3741 m
Este cálculo nos ayudará a hallar el valor de la distancia media geométrica (DMG)
-Cálculo de la DMG:
H μ Dm
Lk ( ) = [ + 4.606 log ′ ] ∗ 10−4
km 2n r
μ = permeabilidadmagnética
n= Nro. de conductores
Dm = distanciamediageométrica
n
r ′ = √rnRn−1
𝟏 𝟏𝟒. 𝟓𝟓𝟕𝟕
𝐋𝐤 = ( + 𝟒. 𝟔𝟎𝟔𝐋𝐨𝐠 ( )) ∗ 𝟏𝟎−𝟒
𝟐∗𝟒 𝟎. 𝟐𝟓𝟗𝟏
𝟏𝟎−𝟒 𝑯 𝜴
𝝌𝑳 = (𝟖. 𝟏𝟖𝟑𝟖 ∗ ) ∗ (𝟐𝝅 ∗ 𝟔𝟎) = 𝟎. 𝟑𝟎𝟖𝟓
𝑲𝒎 𝒌𝒎
𝜴
𝑿𝑳 = (𝟎. 𝟑𝟎𝟖𝟓 ) ∗ (𝟒𝟓𝟎𝒌𝒎) = 𝟏𝟑𝟖. 𝟖𝟐𝟓𝜴
𝒌𝒎
IMPEDANCIA DE LA LTA
F 24.2
Ck ( ) = ∗ 10−9
km Dm
log ′
r
𝟐𝟒. 𝟐
𝑪𝒌 = ( ) ∗ 𝟏𝟎−𝟗 = 𝟏. 𝟑𝟖𝟑𝟐 ∗ 𝟏𝟎−𝟖 𝑭/𝒌𝒎
𝟏𝟒. 𝟓𝟓𝟕𝟕
𝑳𝒐𝒈 ( )
𝟎. 𝟐𝟓𝟗𝟏
𝐒𝐢𝐞𝐦𝐞𝐧𝐬 𝟏
𝐁𝐜 ( )= = 𝐂𝐤 𝐱𝐰 = 𝐂𝐤 ∗ 𝟐𝛑𝐟
𝐤𝐦 𝐗𝐜
𝑺
𝜷𝑪 = (𝟏. 𝟑𝟖𝟑𝟐 ∗ 𝟏𝟎−𝟖 𝑭/𝒌𝒎) ∗ (𝟐𝝅 ∗ 𝟔𝟎) = 𝟓. 𝟐𝟏𝟒𝟓 ∗ 𝟏𝟎−𝟔
𝒌𝒎
𝑺
𝑩𝑪 = (𝟓. 𝟐𝟏𝟒𝟓 ∗ 𝟏𝟎−𝟔 ) ∗ (𝟒𝟓𝟎𝒌𝒎) = 𝟐. 𝟑𝟒𝟔𝟓 ∗ 𝟏𝟎−𝟑 𝑺
𝒌𝒎
ADMITANCIA DE LA LTA
𝒁 𝟏𝟑𝟗. 𝟒𝟓𝟔𝟏
𝒁𝒄 = √ = √ = 𝟐𝟒𝟑. 𝟕𝟖𝟓𝟖𝜴
𝒀 𝟐. 𝟑𝟒𝟔𝟓 ∗ 𝟏𝟎−𝟑
𝑍̅ 𝑌̅ √𝑍̅𝑌̅
𝛾 = √𝑦𝑧= √𝐿𝑜𝑛𝑔 ∗ 𝐿𝑜𝑛𝑔 ⇒ 𝐿𝑜𝑛𝑔2 = 𝛼 + 𝑗𝛽
𝑍̅𝑌̅ 2
= (𝛼 + 𝑗𝛽) = (𝛼 2 − 𝛽 2 ) + 𝑗(2𝛼𝛽)
𝐿𝑜𝑛𝑔2
(𝑅 + 𝑗𝑋)(𝑗𝐵)
= (𝛼 2 − 𝛽 2 ) + 𝑗(2𝛼𝛽)
𝐿𝑜𝑛𝑔2
𝑋𝐵 𝑅𝐵
(− 2 ) + 𝑗( 2 ) = (𝛼 2 − 𝛽 2 ) + 𝑗(2𝛼𝛽)
𝑙 𝑙
ENTONCES:
Parte Imaginaria:
RB
= 2αβ
l2
RB
= 7.6783 ∗ 10−8 = αβ
2l2
7.6783 ∗ 10−8
α= … . (𝟏)
β
Parte Real
XB
(− ) = (α2 − β2 )
l2
−1.6087 ∗ 10−6 = (α2 − β2 ) … . . (𝟐)
Seleccionamos:
𝐊 = 𝐊𝟏 = 𝟏. 𝟔𝟏𝟐𝟒 ∗ 𝟏𝟎−𝟔 = β2
𝛃 = 𝟏. 𝟐𝟔𝟗𝟖 ∗ 𝟏𝟎−𝟑
Reemplazando en (1):
𝟕. 𝟔𝟕𝟖𝟑 ∗ 𝟏𝟎−𝟖
𝛂= = 𝟔. 𝟎𝟒𝟔𝟗 ∗ 𝟏𝟎−𝟓
𝟏. 𝟐𝟔𝟗𝟖 ∗ 𝟏𝟎−𝟑
̅ = cosh (√Z̅Y
A ̅) = D
̅
̅ = Zc ∗ senh (√Z̅̅
B Y)
senh (√Z̅̅
Y)
C̅ =
Zc
𝒆𝟎.𝟎𝟐𝟕𝟐+𝒋𝟎.𝟓𝟕𝟏𝟒 + 𝒆−𝟎.𝟎𝟐𝟕𝟐−𝒋𝟎.𝟓𝟕𝟏𝟒
̅𝒀
𝐜𝐨𝐬𝐡 (√𝒁 ̅ ) = 𝐜𝐨𝐬𝐡(𝟎. 𝟎𝟐𝟕𝟐 + 𝒋𝟎. 𝟓𝟕𝟏𝟒) =
𝟐
̅𝒀
𝐜𝐨𝐬𝐡 (√𝒁 ̅ ) = 𝟎. 𝟖𝟒𝟏𝟒𝟓 + 𝒋𝟎. 𝟎𝟏𝟒𝟕 = 𝟎. 𝟖𝟒𝟏𝟔 < 𝟏. 𝟎𝟎𝟎𝟖𝟒𝟔°
𝐞𝟎.𝟎𝟐𝟕𝟐+𝐣𝟎.𝟓𝟕𝟏𝟒 − 𝐞−𝟎.𝟎𝟐𝟕𝟐−𝐣𝟎.𝟓𝟕𝟏𝟒
𝐬𝐞𝐧𝐡 (√𝐙̅𝐘
̅) = 𝐬𝐞𝐧𝐡(𝟎. 𝟎𝟐𝟕𝟐 + 𝐣𝟎. 𝟓𝟕𝟏𝟒) =
𝟐
̅𝒀
𝐬𝐞𝐧𝐡 (√𝒁 ̅ ) = 𝟎. 𝟎𝟐𝟐𝟖𝟓 + 𝒋𝟎. 𝟓𝟒𝟏 = 𝟎. 𝟓𝟒𝟏𝟓 < 𝟖𝟕. 𝟓𝟖𝟏𝟓°
̅ = 𝐜𝐨𝐬𝐡 (√𝐙̅𝐘
𝐀 ̅) = 𝟎. 𝟖𝟒𝟏𝟓 < 𝟏. 𝟎𝟎𝟎𝟖𝟒𝟔°
̅ = 𝐙𝐜 ∗ 𝐬𝐞𝐧𝐡 (√𝐙̅𝐘
𝐁 ̅) = 𝟏𝟑𝟐. 𝟎𝟏 < 𝟖𝟕. 𝟓𝟖𝟏𝟓°
𝐬𝐞𝐧𝐡 (√𝐙̅𝐘
̅)
𝐂̅ = = 𝟐. 𝟐𝟐𝟏𝟐 ∗ 𝟏𝟎−𝟑 < 𝟖𝟕. 𝟓𝟖𝟏𝟓°
𝐙𝐜
̅ = 𝐜𝐨𝐬𝐡 (√𝐙̅𝐘
𝐃 ̅) = 𝟎. 𝟖𝟒𝟏𝟔 < 𝟏. 𝟎𝟎𝟎𝟖𝟒𝟔°
𝟓𝟎𝟎 ∗ 𝟏𝟎𝟎𝟎
̅𝟐(𝐟𝐚𝐬𝐞) =
𝐕 < 𝟎° = 𝟐𝟖𝟖𝟔𝟕𝟓. 𝟏𝟑𝟒𝟔 < 𝟎° 𝐕
√𝟑
𝐈̅𝟐 = 𝟕𝟏𝟓. 𝟗𝟏𝟒𝟑 < −𝟐𝟏. 𝟓𝟔𝟓𝟐°𝐀
Por lo tanto:
̅𝟏(𝐟𝐚𝐬𝐞) = (𝐀
𝐕 ̅ )(𝐕
̅𝟐(𝐟𝐚𝐬𝐞) ) + (𝐁
̅ )(𝐈̅𝟐 )
̅𝟏(𝐟𝐚𝐬𝐞) = (𝟎. 𝟖𝟒𝟏𝟔 < 𝟏. 𝟎𝟎𝟎𝟖𝟒𝟔°)(𝟐𝟖𝟖𝟔𝟕𝟓 < 𝟎°) + (𝟏𝟑𝟐. 𝟎𝟏 < 𝟖𝟕. 𝟓𝟖𝟏𝟓°)(𝟕𝟏𝟓. 𝟗𝟏𝟒𝟑 < −𝟐𝟏. 𝟓𝟔𝟓𝟐°)
𝐕
̅𝟏(𝐟𝐚𝐬𝐞) = (𝟐𝟒𝟐𝟗𝟐𝟎. 𝟏𝟐𝟓𝟖 < 𝟎. 𝟓𝟎𝟕𝟑°) + (𝟗𝟓𝟕𝟔𝟒. 𝟒𝟗𝟏𝟏 < 𝟔𝟔. 𝟎𝟒𝟖𝟐)
𝐕
𝐈̅𝟏 = (𝐂̅)(𝐕
̅𝟐(𝐟𝐚𝐬𝐞) ) + (𝐃
̅ )(𝐈̅𝟐 )
𝐈̅𝟏 = (𝟐. 𝟐𝟐𝟏𝟐 ∗ 𝟏𝟎−𝟑 < 𝟖𝟕. 𝟓𝟖𝟏𝟓°)(𝟐𝟖𝟖𝟔𝟕𝟓 < 𝟎°) + (𝟎. 𝟖𝟒𝟏𝟔 < 𝟏. 𝟎𝟎𝟎𝟖𝟒𝟔°)(𝟕𝟏𝟓. 𝟗𝟏𝟒𝟑 < −𝟐𝟏. 𝟓𝟔𝟓𝟐°)
𝐈̅𝟏 = (𝟔𝟒𝟗. 𝟕𝟐𝟏𝟏 < 𝟖𝟕. 𝟔𝟏𝟑𝟒°) + (𝟔𝟎𝟐. 𝟒𝟒𝟏𝟗 < −𝟐𝟏. 𝟎𝟓𝟕𝟗)
TABLA DE RESULTADOS:
Debemos calcular:
PORCENTAJES:
Caída de Tensión:
𝐤𝐕𝟏 − 𝐤𝐕𝟐
∆𝐤𝐕(%) = ( ) ∗ 𝟏𝟎𝟎%
𝐤𝐕𝟐
∆𝐤𝐕(%) = 𝟐. 𝟑𝟖%
Pérdidas de Potencia:
𝐊𝐖𝟏 − 𝐊𝐖𝟐
∆𝐤𝐖(%) = ( ) ∗ 𝟏𝟎𝟎%
𝐤𝐖𝟐
∆𝐤𝐖(%) = 𝟔. 𝟕𝟒𝟗𝟖%