ESPECIFICACIÓN
CFE V6700-55
JULIO 2005
REVISA Y SUSTITUYE A LA
EDICIÓN DE JUNIO 2002
MÉXICO
SISTEMAS INTEGRADOS DE CONTROL, PROTECCIÓN, MEDICIÓN ESPECIFICACIÓN
Y MANTENIBILIDAD PARA USO EN SUBESTACIONES
DE DISTRIBUCIÓN (SISCOPROMM) CFE V6700-55
C O N T E N I D O
1 OBJETIVO __________________________________________________________________________________ 1
4.3 DEI_________________________________________________________________________________________ 2
4.7 IEC_________________________________________________________________________________________ 2
4.13 MTBF_______________________________________________________________________________________ 2
4.15 MTTR_______________________________________________________________________________________ 2
4.17 MWdmáx____________________________________________________________________________________ 2
4.19 MWr________________________________________________________________________________________ 2
4.24 UCA________________________________________________________________________________________ 2
5 DEFINICIONES _______________________________________________________________________________ 3
5.5 Compatibilidad_______________________________________________________________________________ 3
5.10 Evento______________________________________________________________________________________ 3
5.13 “Hardware”__________________________________________________________________________________ 3
9 GARANTÍAS ________________________________________________________________________________ 26
11 CARACTERÍSTICAS PARTICULARES___________________________________________________________ 27
12 BIBLIOGRAFÍA______________________________________________________________________________ 27
TABLA 1A Periodo mínimo para almacenar la información proveniente de los medidores multifunción _____________ 29
1 de 166
IEC 60068-2-1-1990; Environmental Testing - part 2: Tests. IEC 61000-4-11-2004; Electromagnetic Compatibility (EMC)
Test A: Cold. – Part 4-11: Testing and Measurement Techniques – Voltage
Dips, Short Interruptions and Voltage Variations Immunity
IEC 60068-2-2-1974; Environmental Testing - Part 2: Tests. Tests.
Tests B: Dry Heat.
IEC 61131-3-2004; Programmable Controllers – Part 3:
IEC 60068-2-30-1980; Environmetal Testing - Part 2: Tests. Programming Languages.
Test Db and Guidance: Damp Heat, Cyclic (12+12 hour
cycle). IEC 61850-2003; Communication Networks and Systems in
Substations.
IEC 60255-5-2000; Electrical Relays - Part 5: Insulation
Coordination for Measuring Relays and Protection Equipment CFE G0000-48-1999; Medidores Multifunción para Sistemas
– Requirements and tests. Eléctricos.
IEC 60255-22-1-2005; Electrical Relays - Part 22-1: CFE G0000-62-2002; Esquemas Normalizados de
Electrical Disturbance Tests for Measuring Relays and Protecciones de Transformadores de Potencia.
Protection Equipment - 1 MHz Burst Immunity Tests.
CFE G0000-65-2002; Esquemas Normalizados de
IEC 60255-22-2-1996; Electrical Relays - Part 22: Electrical Protecciones para Líneas de Transmisión, Subtransmisión y
Disturbance Tests for Measuring Relays and Protection Distribución.
Equipment – Seccion 2: Electrostatic Discharge Tests.
CFE G0000-81-2004; Características Técnicas para
IEC 60255-22-3-2000; Electrical Relays Part 22-3: Electrical Relevadores de Protección.
Disturbance Tests for Measuring Relays and Protection
Equipment – Radiated Electromagnetic Field Disturbance CFE G6800-59-1998; Relevador Auxiliar de Disparo con
Tests. Bloqueo y Reposición Manual Tipo Rotativo.
IEC 60255-22-4-2002; Electrical Relays Part 22-4: Electrical CFE V6700-62-2003;Tableros Integrales de Protección,
Disturbance Tests for Measuring Relays and Protection Control, Medición y Supervisión para Subestaciones
Equipment – Electrical Fast Transient/Burst Immunity Test. Eléctricas.
IEC 60870-5-101-2003; Telecontrol Equipment and Systems CFE 54000-56-1999 Tablillas de Prueba Utilizadas en
- Part 5-101: Transmission Protocols - Companion Standard Equipos de Medición.
for Basic Telecontrol Tasks
NOTA: En caso de que los documentos anteriores sean
IEC 60870-5-102-1996; Telecontrol Equipment and Systems revisados o modificados, se debe tomar en cuenta la edición en
- Part 5: Transmission Protocols - Section 102: Companion la fecha de la convocatoria de la licitación, salvo que CFE
indique otra cosa.
Standard for the Transmission of Integrated Totals in Electric
Power Systems.
2 de 166
Tiempo medio entre fallas (Middle time between failure). 4.27 UTRp
3 de 166
Red de área amplia (Wide-area network). Es el conjunto de “hardware” y “software” que contiene,
procesa y administra las bases de datos del SISCOPROMM,
4.29 SWELL controla sus comunicaciones y presenta una interfase
amigable para su operación.
Incremento de tensión entre 1,1 pu y 1,8 pu en la tensión
rcm. 5.7 Dispositivo Electrónico Inteligente
4 de 166
5.17 Lecturas Congeladas por Cambio de Estación Programa de “software” que no ha sido compilado (esto es,
en formato texto en vez de binario ejecutable).
Lecturas de consumo en kWh, consumo de kvarh, demanda
(kW) y fecha y hora de ocurrencia de la misma, que el 5.25 Protocolo
medidor multifunción debe guardar automáticamente en su
memoria con la bandera de “congeladas por cambio de Conjunto de normas y reglas que coordinan el flujo de
estación”, de acuerdo a programación, cada vez que exista información entre diversos elementos que componen un
cambio de estación en la zona donde se encuentra instalado enlace de comunicación teniendo como funciones básicas el
dicho medidor. establecimiento del enlace, transmisión de información,
detección de fallas en la transmisión y corrección de errores.
5.18 Lecturas Congeladas por Cambio de Horario
5.26 Puerto de Comunicación del DEI
Lecturas de consumo en kWh, consumo de kvarh, demanda
(kW) y fecha y hora de ocurrencia de la misma, que el Es el punto de interconexión de comunicaciones a través del
medidor multifunción debe guardar automáticamente en su cual se enlaza un DEI a la red de adquisición de información,
memoria con la bandera de “congeladas por cambio de para su configuración, consulta, ejecución de comandos y
horario”, de acuerdo a programación, cada vez que exista adquisición de datos.
cambio de horario en la zona donde se encuentra instalado
dicho medidor. 5.27 Puerto Transparente
5 de 166
Es el formato de registro de los DEI’s de un evento ocurrido y Es el conjunto de programas de “software” desarrollados por
detectado, con indicación de las magnitudes y parámetros el fabricante de un SISCOPROMM que incluye las rutinas,
que intervienen y pueden ser: Tensión, corriente, frecuencia, algoritmos, funciones especiales, pantallas, reportes,
y con registro también de unidades de protección que operan configuración, explotación, protocolos y todas las funciones
en arranque y/o medición de la falla hasta su disparo, con su que se detallan en esta especificación que residen en el
correspondiente estampado de tiempo, quedando registrados CPS.
en los DEI’s y CPS los oscilogramas y secuencia de eventos
ocurridos durante la falla. 5.40 “Software” de Explotación
6 de 166
- a través de la red de comunicación local (DEI’s) - a través de la red intranet de CFE: Enlace al
con protocolo abierto: Señales digitales servidor SIPASD, acceso a la información
provenientes de los DEI´s hacia el CPS requerida en los apéndices D y E, así como el
(consultas) tales como diagnósticos, alarmas, acceso remoto a los DEI’s a través de la red de
mediciones e indicaciones que hacen la función de puertos transparentes.
supervisión del dispositivo y de los dispositivos
que tiene conectados; así como la ejecución y La transmisión de la información hacia la UCM y las del CPS
operación de comandos, instrucciones o funciones con los DEI’s a través de la red de comunicación local con
que se tenga implementado en un DEI desde el protocolo abierto son prioritarias, por lo que no deben
CPS, perderse en caso de falla en la operación de Ia IHM y/o
DEI`s.
- a través de puertos transparentes para
configuración y ajuste de DEI’s: Configuración y La comunicación con los DEI´s del SISCOPROMM a través
ajustes de los DEI’s tales como protecciones, de la intranet de CFE para configuración, pruebas,
parámetros de comunicación, acumuladores, monitoreo, entre otros, no deben interferir o afectar el
muestreos, integraciones, registros de desempeño normal del equipo ni bloquear las
almacenaje, nivel de las alarmas y toda comunicaciones hacia la UCM, hacia las UTRp, ni las del
configuración de cada uno de los DEI’s que CPS con los DEI’s a través de la red de comunicación local
integran el SISCOPROMM. Adquisición de con protocolo abierto.
información de los DEI´s (consultas) tales como
los parámetros de configuración, mediciones
instantáneas, mediciones acumuladas, mediciones
congeladas, mediciones de cambio de horario,
mediciones de cambio de estación, oscilografías,
eventos, y toda clase de archivos de las funciones
que desempeña el dispositivo interrogado,
7 de 166
6.2 Controlador Principal de la Subestación (CPS) b) Control de las comunicaciones hacia la unidad
central maestra.
El CPS administra el sistema y contiene las bases de datos y
estructuras de la información requerida por el SIPASD, 6.2.1.2 Hacia la red intranet de CFE
contiene los algoritmos de funciones lógicas programales no
efectuados por los DEI’s, la administración de las a) Almacenamiento en bases de datos que cumpla
comunicaciones hacia la UCM, intranet, al nivel local (DEI’s) con la estructura descrita en los apéndices D y E
y al nivel inferior de las UTRp de la red de distribución, de esta especificación.
mantiene sus bases de datos, respaldadas y actualizadas.
b) Control de las comunicaciones hacia la red
Cuenta con una interfaz humano-máquina, mediante la cual intranet (Servidor SIPASD).
se obtienen desplegados de la información procesada,
acceso a los DEI’s que permite en forma local el análisis de c) Acceso remoto a los DEI’s respetando los niveles
la información y efectuar controles al campo. de seguridad correspondientes.
6.2.1 Funciones básicas del CPS 6.2.1.3 Hacia la red local (DEI’s)
8 de 166
a) Funciones lógicas programables locales con base a) IA, IB, IC, IN.
en algoritmos.
b) VA, VB, VC, 3VO.
b) Acepta y distribuye en la red local (DEI’s) y al nivel
inferior (UTRp) la sincronización horaria ya sea vía c) Señales digitales como:
satélite por medio de GPS, por medio de protocolo
y debe tener la capacidad de generar la - arranque de los elementos internos y de las
sincronización cuando no reciba una señal funciones operadas así como su posterior
externa. reposición,
c) Autodiagnóstico a nivel local y a nivel redes de - estado de las entradas y salidas digitales,
comunicación.
- señales del recierre.
d) Acceso remoto a la funcionalidad completa del
d) La señal que originó la captura oscilográfica.
CPS incluyendo configuración y consulta de los
DEI’s, con la sola limitante de los niveles de e) Fecha y hora con una resolución mínima de un
acceso indicados en el punto 6.2.5.5.1. milisegundo.
e) El CPS debe cumplir en su mapeo con la La función o disparo que genera la oscilografía debe ser
estructura de información descrita en los configurable y además, una de las entradas digitales debe
apéndices D y E de esta especificación. permitir generar oscilografía a través de una señal externa.
f) Se debe definir en las reuniones de ingeniería la Cualquier operación de protección debe generar
estructura de la información requerida y las oscilogramas para las señales analógicas asociadas con
variables que no estén contempladas en los protecciones mostradas en la tabla 1.
anexos D y E, pero que estén incluidas en el
alcance de los mismos. Los datos oscilográficos deben ser adquiridos por el CPS en
forma automática cuando sean registrados por el DEI
g) El CPS debe contar con un conmutador correspondiente y permanecer guardados en el CPS sin que
local/remoto implementado por “hardware” o exista duplicidad de registros.
“software” que permita habilitar/deshabilitar todos
los comandos de control de nivel superior, Se deben conocer los ajustes que estaban activos cuando
además, cuando se cambie la función local/remota ocurrió la captura, a través del CPS.
se debe registrar el cambio de estado tanto en la
IHM como en la UCM, cumpliendo con las 6.2.2.2 Secuencia de eventos
siguientes condiciones:
La función de secuencia de eventos de la subestación debe
- en posición remota permite ejecutar comandos de ser realizada por el controlador principal de la subestación
control desde la UCM, (CPS). Esta función está formada por una bitácora que
contiene al menos los últimos 10 000 eventos, ordenados
- en posición local no permite ejecutar los cronológicamente con resolución igual o mejor a 5
comandos de control desde la UCM y se ejecutan milisegundos. Cada evento puede incluir alarmas, operación
solo desde la IHM y controles emergentes. de contactos, disparos, cambios de ajustes y
autodiagnósticos.
9 de 166
El CPS debe registrar y mostrar por cada interruptor el e) Componentes y gabinete tipo industrial.
número de operaciones de a cuerdo a la clasificación
siguiente: - montaje en “rack” de 482 mm,
- por protección, - resistente a vibración e impactos,
- por mando desde la IHM,
- ventilación filtrada,
- por mando desde los controles emergente,
- -10° C a 60 °C,
- por mando desde el control del interruptor,
- capacidad de expansión,
- por mando desde la UCM,
10 de 166
j) Mínimo de 512 kB de memoria “caché”, La Interfase humano máquina (IHM) debe cumplir con lo
siguiente:
k) Controlador de video 32 MB de memoria.
a) Teclado y “software” en español.
l) Discos duros de capacidad suficiente para el
procesamiento y almacenamiento de la b) Interfaz gráfica orientada a objetos (animación
información, tanto del sistema como la opcional), “zoom”, ambiente de ventanas y menú.
correspondiente de tipo operativo de los DEI’s y
carga local. Lo mínimo aceptable es: Dos discos c) Programación en lenguaje de alto nivel.
duros de 80 GB cada uno, la grabación en estos
discos debe realizarse en forma simultánea. d) Debe exportar/importar información de bases de
datos relacionales comerciales y a hojas de
m) Tarjetas multipuertos, con un mínimo disponible cálculo.
para el usuario de 8 puertos, independientemente
de los puertos requeridos por las redes locales del e) Herramientas para edición de diagramas con ligas
sistema. Estos deben estar disponibles para ser dinámicas a la base de datos del sistema.
configurados por el usuario del SISCOPROMM,
quién en Características Particulares deba f) Sin necesidad de “password” se deben realizar:
definir el uso inicial para cada uno de ellos. Reportes tipo texto y gráficas con posibilidad de
impresión y exportación en formato comercial.
n) 4 puertos USB disponibles.
g) Manejo de tendencias, tiempo de muestreo
o) Una Tarjeta “ethernet” 10/100 Mbits para conexión programable, 8 variables por pantalla, ampliación
al “LAN switch” de la subestación para su (“zoom”, opcional) y desplazamiento “panning”.
intercomunicación con la red intranet de CFE. Para cada punto debe permitir definir la escala y el
color.
p) Monitor plano LCD de 17 pulgadas con las
siguientes características mínimas: Resolución h) Actualización sobre el unifilar o cualquier otro
activa 1 280 x 1 024, colores 16,2 millones, tiempo desplegado que se requiera, de los valores
de respuesta 25 milisegundos. instantáneos de los dispositivos de medición y
estados de los interruptores y demás
q) Puerto “Irig-B” para sincronización mediante GPS. señalizaciones digitales (tabla 1).
6.2.3.2 Otros elementos del CPS i) El “software” de aplicación debe permitir abrir
varias ventanas sin que afecte el desempeño del
Debe incluir los equipos de comunicación tales como mismo.
“modems”, radio y los elementos que le permitan enlazarse a
las redes de datos y UCM’s existentes, los cuales se indican 6.2.4.1 Navegación a través de pantallas
en las Características Particulares.
6.2.4.1.1 Pantalla principal
Debe incluir una UPS (unidad ininterrumpible de energía),
alimentada con 127 V c.a. ± 20 %, y con una autonomía Debe mostrar el diagrama unifilar de la subestación al inicio
mínima de 4 horas. de la sesión, sin otros elementos que limiten el espacio para
mostrar sus principales valores analógicos (tensión y
Debe incluir un equipo de sincronización de tiempo GPS con frecuencia de buses, corrientes por fase de los interruptores
antena y accesorios. de A.T. y M.T., respetando el formato y colores establecidos
en las reglas de despacho y operación del Sistema Eléctrico
6.2.4 Interfaz humano-máquina (IHM) Nacional.
11 de 166
d) Unifilar por bahía, en este diagrama deben El CPS debe tener la capacidad de reconocer las alarmas
mostrarse todas las funciones de protección por grupo o en forma individual a través de la IHM
asociadas a la bahía que puede ser de línea, de respetando los “passwords” establecidos.
transformador, alimentador o banco de
capacitores. 6.2.4.1.4 Eventos
Dentro de este diagrama se muestra a detalle la indicación Siempre que se active el botón de función de eventos, se
de alarma de cada función de protección operada deben mostrar los eventos resultado de una acción
parpadeando así como la medición instantánea de tensiones efectuada a través del CPS, ya sea en forma local (desde la
entre fases por bus, amperes por fase, megawatts y IHM) o en forma remota desde la unidad central maestra
megavars trifásicos y frecuencia. (UCM) permitiendo mediante botones de comando ubicados
en la parte inferior de esta ventana, accesar las demás
Los diagramas unifilares de la subestación deben contar con ventanas de eventos:
un icono de alarmas por cada bahía, que al oprimirlo nos
muestre en forma tabular las alarmas asociadas a la bahía, a) Por interruptor.
para el caso de las alarmas generales de la subestación
(servicios propios, clima, intruso, entre otros.), se tendrá un b) Por transformador.
icono adicional de alarmas generales.
c) Por operacdion de protecciones.
La activación de cualquiera de las alarmas del tabular debe
hacer parpadear en rojo el icono de alarma. d) De comunicaciones.
Debe contar con un icono de medición por cada bahía que al e) Diagostico de DEI’s.
oprimirlo nos muestre en forma tabular las mediciones
asociadas a la bahía f) Generales subestación.
12 de 166
Al activar este botón de función se debe mostrar una ventana La activación de este botón debe mostrar una ventana con
con las siguientes opciones de medición por cada bahía: las siguientes opciones:
La activación de este botón de función debe mostrar una a) El “software” debe soportar operaciones de
ventana que presente los siguientes accesos de reporte reconocimiento e inhibición individual o por grupo
indicadas en el punto 6.2.5.2. de alarmas.
13 de 166
Los reportes que como mínimo se deben incluir dentro del d) Para la obtención de un desplegado debe ser
sistema son los siguientes: 3 segundos, medido desde que se oprimió la
última tecla de solicitud hasta que aparece
a) Reporte de operación de interruptores. completo en la pantalla, listo para recibir comando
del operador.
b) Operaciones efectuadas mediante las funciones
lógicas programables en el SISCOPROMM. 6.2.5.4 Autodiagnóstico
c) Reporte de estadísticas de comunicaciones hacia El sistema debe contar con autodiagnóstico continúo en
nivel inferior (DEI's) y nivel superior (UCM's). tiempo real.
d) Resumen de equipos que rebasan los límites Cada uno de los dispositivos del sistema debe contar con
prefijados en estadísticas de comunicaciones. capacidad de autodiagnóstico.
e) Reporte de los equipos de protección El CPS debe contar con el “software” necesario para detectar
monitoreados, que efectuaron operaciones sobre fallas de los diferentes dispositivos conectados a él.
interruptores u otros equipos en forma automática,
por telemandos o manualmente por algún Una vez detectada una falla debe ser mostrada en forma de
operador, agrupándolos por equipos DEI's. alarma y enviada a la UCM.
f) Reporte del comportamiento de la tensión en El autodiagnóstico del CPS debe ser capaz de enviar una
buses. alarma a la UCM cuando la IHM se bloquea.
k) Reporte de calidad de energía. El proveedor debe entregar las licencias necesarias para el
uso de este “software” de aplicación.
l) Reporte de memoria masiva de DEI’s en formato
“Excel” donde aplique. Debido a que cada fabricante puede utilizar diferentes
herramientas de “software” para la integración de este tipo de
Los detalles de los reportes son indicados por la CFE en las sistemas, el proveedor debe indicar el “software” utilizado y
reuniones de ingeniería. desarrollado para cumplir con las características de
operación y funcionales solicitadas, incluyendo los
Los reportes anteriores son enunciativos más no limitativos específicos para cada DEI.
pudiendo el proveedor proponer otros.
Los paquetes comerciales y específicos que sean adquiridos
6.2.5.3 Tiempos máximos de respuesta del sistema o desarrollados por el proveedor como herramientas para el
desarrollo del sistema, deben ser entregados a CFE, por lo
a) Para actualizar un cambio de estado debe ser que el proveedor debe entregarlos con sus licencias,
2 segundos. manuales y elementos de instalación (disquetes o CD-ROM
originales) al entregar el sistema.
b) Para adquisición de todas las mediciones
instantáneas debe ser 30 segundos. 6.2.5.5.1 Claves de acceso (passwords)
c) Para la solicitud de un comando desde el El acceso a la información en forma local y remota vía
momento en que el sistema recibe la solicitud intranet, no debe estar limitado al número de usuarios y debe
hasta la operación del contacto de salida que sujetarse a la utilización de claves de acceso (passwords)
opera directamente sobre el equipo a operar debe como sigue:
ser de 1 segundo.
a) Sin clave de acceso (sin password).
14 de 166
Consulta de información sin acceso a control, c) Que soporte SQL (Software Query Language).
incluyendo estados y mediciones actuales,
información histórica (perfiles kV, kW, kWd, kvar, d) Tener incluidas las funciones de exportar/importar
kWh, kvarh, entre otros.), reportes de falla de los datos con otras bases de datos comerciales.
DEI’s, archivos de secuencia de eventos, base de
datos de mantenimiento, entre otros. e) La base de datos del sistema debe cumplir con lo
descrito en los apéndices D y E de esta
b) Clave de acceso 1 (password 1). especificación.
f) Clave de acceso 5 (password 5). El protocolo DNP3.0 nivel 2 entregado en cada sistema,
debe permitir al usuario, mapear y configurar los objetos,
Acceso a mantenimiento del sistema variación, código de función (fc), tipo de calificador (qualifier),
(interfase humano máquina). asignación de clases, entre otros y siempre debe ser
evaluado en las pruebas de aceptación y en la puesta a
Cada nivel jerárquico debe tener acceso a los niveles punto.
jerárquicos inferiores, considerando que el mayor nivel de
acceso es el nivel 5. 6.2.5.7 Protocolo DNP3.0 nivel 3 para enlace(s) del
CPS con las redes de comunicación local
El sistema debe considerar reportes que indiquen el historial (DEI’s) y nivel inferior (UTRp)
de accesos por nivel y nombre del usuario, indicando fecha y
tiempo de acceso, así como acciones realizadas, ajustes, El protocolo DNP3.0 nivel 3 entregado en cada sistema,
disparos, cierres, entre otros. debe permitir al usuario, mapear y configurar los objetos,
variación, código de función (fc), tipo de calificador (qualifier),
6.2.5.5.2 Configuración del sistema asignación de clases, entre otros y siempre debe ser
evaluado en las pruebas de aceptación y en la puesta a
punto.
La configuración del sistema debe cumplir con el mapeo de
la información descrita en el apéndice D.
6.3 Arquitectura de Comunicaciones
El proveedor debe de entregar documento y manual donde La comunicación en redes entre varios DEI´s implica una
se indiquen los pasos a seguir para configuración del sistema dirección origen y una dirección destino y el medio de
y base de datos. comunicación pueden ser cable UTP nivel 6 y/o fibra óptica.
6.2.5.5.3 Base de datos Cuando se utilice una red tipo estrella, los DEI’s a utilizar con
función de controlador de comunicaciones no deben ser
Sistema básico de información para almacenaje y manejo de propietarios, debiendo ser posible su reemplazo por un
datos, con las siguientes características: equipo similar de otra marca que realice las mismas
funciones con solo realizar las configuraciones necesarias.
a) Portabilidad.
Las comunicaciones que debe utilizar el sistema, en su
b) Herramientas de sistemas de ventanas que arquitectura final están estructuradas con base a la
integren un sistema relacional de administrador de configuración mostrada en la figura 1 y a la descripción del
base de datos. punto 6.1 “Arquitectura del SISCOPROMM”.
15 de 166
a) Redes de comunicación local (DEI’s) con Cuando en el futuro sea necesario un crecimiento de la
protocolo abierto. subestación se conectarán nuevos DEI’s al CPS, esto debe
realizarse en forma transparente para el usuario, quien
b) Redes de puertos transparentes para instalando el “software” de aplicación suministrado con los
configuración y ajuste de DEI’s. nuevos DEI´s en el CPS debe poder configurar y dar de alta
este nuevo equipo en el SISCOPROMM, sin necesidad de
c) Enlace(s) para circuitos de distribución al nivel hacer otras modificaciones al “software” de aplicación del
inferior hacia UTRp. CPS.
d) Enlace(s) a unidades centrales maestras. Para este caso debe contarse adicionalmente, con al menos
una red de comunicación local con protocolo abierto y una
e) Enlace(s) a través de la red intranet de CFE. red de puertos transparentes disponible en el CPS para que
sea configurada por el usuario del SISCOPROMM,
6.3.1 Redes de comunicación local con protocolo cumpliendo con los tiempos de desempeño operativos que
abierto se indican en esta especificación.
El número de redes de comunicación local con protocolo Se permite que un DEI controle la comunicación de otros
abierto, dependerá del diseño y desempeño del fabricante y DEI´s hacia el CPS.
deben considerarse independientes a los 8 puertos que se
indican en la figura 1 (P1 a P8). El proveedor debe demostrar fidedignamente que el
protocolo cumple con lo solicitado, entregando para su
La comunicación entre el CPS y los DEI’s debe hacerse con validación, en las pruebas de aceptación y rutina del
protocolos abiertos y cumpliendo con las siguientes normas: SISCOPROMM, los comandos, objetos, perfiles, mapeo y
configuraciones.
a) IEC-61850.
El proveedor debe demostrar fidedignamente la funcionalidad
b) DNP 3.0 nivel 3 en CPS y nivel 2 en DEI. de los elementos implementados en el CPS para la
comunicación con cada uno de los DEI’s a través del puerto
c) IEC 60870-5-101,102, 103, 104. transparente entregando para su validación, en las pruebas
de aceptación y rutina.
d) TCP/IP.
6.3.3 Enlace(s) para circuitos de distribución al
Se acepta que estas redes locales utilicen puertos RS232, nivel inferior hacia UTRp
RS485, ópticos o “ethernet” con RJ45 para redes “LAN”
10/100 MB. La comunicación entre el CPS y los UTRp debe hacerse con
el protocolo DNP3.0 Nivel 3 en el CPS.
Para cualquiera de los casos anteriores, la documentación
de referencia debe ser del dominio público y el integrador Esta red se utiliza para la comunicación del CPS con
debe proporcionar el “device profile” y mapeo de los dispositivos al nivel inferior UTRp instalados en la red de
protocolos utilizados tanto en los DEI’s como en el CPS y la distribución y el CPS debe incluir la funcionalidad para
información que permita a otros licitantes la conectividad e adquirir información de estos dispositivos y ejecutar controles
intercambio de información con sus sistemas. sobre los mismos desde la interfase humano máquina del
SISCOPROMM o desde la unidad central maestra.
6.3.2 Redes de puertos transparentes para
configuración y ajustes de DEI’s Asimismo, el CPS debe proveer herramientas de
programación para la implantación de funciones lógicas
El número de redes de comunicación local para puertos programables, de acuerdo a la norma IEC 61131-3 o con un
transparentes dependerá del diseño y desempeño del lenguaje de alto nivel del tipo "VBA" (Visual Basic for
fabricante y son independientes a los 8 puertos que se Applications).
indican en la figura 1 (P1 a P8).
6.3.4 Enlace(s) a unidades centrales maestras
La comunicación entre el CPS y los DEI´s se acepta que
utilice puertos RS232, RS485, ópticos o “ethernet” con RJ45, La comunicación entre el CPS y la unidad central maestra
para redes “LAN”, 10/100 Mbps, a través del protocolo debe cumplir con lo siguiente:
propietario para el puerto transparente.
a) Para todos los SISCOPROMM, se debe
La red de puertos transparentes nunca debe bloquear la red considerar el protocolo DNP 3.0 nivel 2, de
de comunicaciones en el control y transferencia de acuerdo a las recomendaciones más recientes del
información. grupo de usuarios de DNP.
16 de 166
b) Los protocolos entregados en cada sistema, e) Un DEI puede realizar funciones de controlador de
deben ser configurables por el usuario a uno o comunicaciones de otros DEI’s, siempre y cuando
varios canales de comunicación dependiendo de utilice los protocolos de comunicaciones
los puertos disponibles en “hardware” y siempre establecidos en esta especificación y transfiera la
deben ser evaluados en las pruebas de estructura, perfil, mapeo de datos, así como los
aceptación y en la puesta a punto. comandos de control hacia los DEI’s conectados a
él.
c) Debe contar con herramientas para configurar los
tiempos de los parámetros de comunicación con la f) Se acepta que las dos funciones anteriores se
finalidad de adaptarse al canal de integren en un solo DEI por sección de tablero. El
comunicaciones. proveedor debe proporcionar en forma impresa y
electrónica, el perfil y mapeo de los datos propios,
Cuando se especifique en Características Particulares el así como de los DEI’s conectados a él.
sistema debe contar con los protocolos adicionales que se
g) Todos los DEI’s que realicen funciones de
indiquen en las mismas.
protección o registro de disturbios deben estar
incluidos en la referencia bibliográfica [8] del
Las características del medio de comunicación se detallan en capítulo 12 de esta especificación.
Características Particulares.
h) Todos los DEI’s que realicen funciones de
6.3.5 Enlace(s) a través de la red intranet de CFE protección deben apegarse a lo establecido en la
especificación CFE-G0000-81.
El CPS del SISCOPROMM debe proporcionar una salida
hacia la red intranet de CFE con protocolo TCP/IP, para i) Todos los DEI’s de entradas-salidas digitales
su incorporación en forma transparente a la red “WAN” deben apegarse a lo establecido en la
mediante puertos “ethernet” 10/100 Mbps con interfase especificación CFE G0000-81 en lo
RJ-45. correspondiente entradas digitales y las
características indicadas para los DEI’s en la
El CPS del SISCOPROMM debe incluir el “software” con presente especificación.
aplicación de servidor de protocolos de transferencia de
archivos (FTP), que pueda ser configurado por el usuario. j) Todos los DEI’s que realicen funciones de
medición deben apegarse a lo establecido en la
Se debe incluir un equipo “LAN Switch” de 10/100 Mbps con especificación CFE G0000-48.
al menos 8 puertos de red “ethernet” administrable
remotamente, que cumpla con la referencia bibliográfica [6] 6.4.1 Funciones de control, protección, medición y
del capítulo 12 de esta especificación. complementarias
17 de 166
18 de 166
Las funciones de protección para transformadores de a) El esquema básico de protección esta compuesto
potencia deben cumplir con lo establecido en la por baja tensión de fases (27), sobre tensión de
especificación CFE G0000-62 considerando como mínimo el fases (59), y sobre tensión de neutro a tierra
esquema para transformadores de 10 MVA. (59N), esta última debe alimentarse con un
transformador de potencial conectado entre el
a) El esquema de transformador debe estar formado neutro flotante del banco y tierra; y un
por tres DEI’s de protección, uno para la temporizador asociado al cierre del interruptor de
diferencial 87T (PPT), uno para la sobrecorriente
potencia con un intervalo ajustable desde 1 minuto
de fases en lado primario 50/51f A.T. (PRP) y otro
a 10 minutos, en pasos de 1 minuto, para dar
para sobrecorriente de fases en lado secundario
tiempo a la descarga del banco de capacitores a
50/51F M.T. (PRS).
través de la resistencia de descarga.
Se deben proporcionar las funciones de falla de
interruptor en alta tensión (50FI) y sobrecorriente 6.4.1.1.6 Alimentadores de media tensión
de neutro de transformador 51NT (PRN) las
cuales se aceptan con el DEI de la protección Las funciones de protección para alimentadores de media
PRP, siempre y cuando disponga de una entrada tensión, deben apegarse con lo establecido en la
independiente de corriente para ser alimentada de especificación CFE G0000-65.
un TC diferente a los de fase.
a) Las funciones de protección requeridas son
El esquema básico incluye las funciones de I²T, sobrecorriente (50/51F, 50/51N), debe contar
registro oscilográfico, registro secuencial de como mínimo con tres grupos de ajustes
eventos y baja frecuencia 81, las cuales pueden seleccionables a través de ““software””, recierre
estar incluidos en cualquiera de los DEI’s de automático (79), baja frecuencia (81), oscilografía,
protección del transformador. I²T.
19 de 166
6.4.2 Funciones de control, supervisión y Para las aplicaciones requeridas según tabla 1, el DEI de
adquisición de datos medición debe cumplir con el registro y medición de lo
siguiente:
Las funciones de control están detalladas en la tabla 1 y las
de supervisión y adquisición de datos en las tablas 2, 3 y 4. a) % THD V ªdistorsión armónica de tensión por fase
hasta la 9 armónica.
Se requiere tener un 10 % adicional disponible como mínimo b) % THD A distorsión armónica de corriente por
de las entradas binarias, salidas digitales y entradas fase hasta la 9ª armónica.
analógicas, del total de señales empleadas en cada sección
del tablero. Estas señales deben quedar alambradas, c) “Sags”.
disponibles en terminales de las tablillas de conexión de
cada sección del tablero y mapeadas en la base de datos d) “Swells”.
del CPS. e) Desbalance de fases.
Se requiere que las entradas digitales se puedan programar Cuando se requiera de funciones de medición para
para proporcionar la siguiente información: aplicaciones de facturación o intercambio de energía, deben
suministrarse DEI’s independientes que cumplan
a) Estado de la entrada digital (abierto/cerrado) estrictamente con la especificación CFE G0000-48 lo cual se
“status”. indica en las Características Particulares.
b) Detección de cambio momentáneo entre Cada uno de los medidores multifunción instalados debe
exploraciones del CPS. estar provisto de una tablilla para pruebas que cumpla con la
especificación CFE 54000-56.
c) Registro de eventos.
La tabla 5 resume lo requerido para los puntos 6.5.2.1 y
d) Memoria masiva de los medidores multifunción. 6.5.3, mostrando con carácter ilustrativo el grado máximo de
integración de funciones permitido con un mínimo número de
Las salidas digitales para comandos del tipo pulsado, deben DEI’s, asociados al esquema de protección y medición de
ser ajustables por programación de 0,1 s a 5 s. cada elemento del sistema.
Los DEI´s empleados para efectuar las funciones de b) Características de sus componentes.
medición deben cumplir con la especificación CFE G0000-48
c) Condiciones de operación.
vigente en el momento de la licitación.
d) Marcado.
Todos los DEI´s de medición deben ser para 3 fases 4 hilos,
3 elementos 120 V, conexión estrella. e) Empaque y embarque.
20 de 166
b) Las nuevas secciones de tablero deben acoplarse - una sección conteniendo los dispositivos
físicamente a la última sección instalada. electrónicos inteligentes correspondientes a cada
banco de transformación,
c) El cableado entre secciones debe ser mínimo y
sólo será aceptado lo siguiente: - una sección con los dispositivos electrónicos
inteligentes correspondientes a los alimentadores
- redes locales de comunicación, de media tensión en esta sección se pueden
colocar los esquemas correspondientes a cuatro
- señales secundarias de circuitos de potenciales y alimentadores como máximo,
sincronización,
- los dispositivos electrónicos inteligentes
- el cableado requerido en caso de coordinación de correspondientes a los bancos de capacitores en
un elemento de protección con otro (por ejemplo, alta tensión pueden ser colocados en secciones
cuando la falla de un interruptor requiera el de líneas de alta tensión si hay espacio disponible,
disparo de otros interruptores o disparo rápido de
bus), - los dispositivos electrónicos inteligentes
correspondientes a los bancos de capacitores en
- el cableado interno en cada sección debe media tensión pueden ser colocados en secciones
considerar los espacios que permitan los accesos de alimentadores de media tensión si hay espacio
para fines de mantenimiento. disponible,
d) La configuración propuesta por CFE para la - para el caso en que las secciones de líneas,
ubicación de los diferentes componentes del bancos y alimentadores, permitan un crecimiento
sistema, se muestra en la figura 2 y corresponde interno, se deben dejar los espacios disponibles
a: para la instalación de los equipos auxiliares y
principales para crecer en la cantidad de
- una sección conteniendo el procesador principal, esquemas que permita la sección
la unidad de interfaz humano-máquina, los puertos correspondiente, la cual debe utilizar la misma
de acceso de comunicación, el equipo de simetría para la disposición de los equipos en
comunicación y la UPS, se acepta que el banco de secciones del mismo tipo.
baterías de la UPS se coloquen en la sala de
baterías de la subestación,
21 de 166
IHM Interfaz-humano-máquina
BP Block de prueba.
22 de 166
L1 L2
152T1 152T2
52T1 52T2
A1 A2 A3 A4 A5 A6
DIAGRAMA UNIFILAR
Los “blocks” de prueba deben cumplir con lo establecido en Adicionalmente a las funciones de control indicadas en la
la especificación CFE V6700-62. tabla 1, se requieren controles emergentes para abrir y cerrar
cada interruptor de potencia y deben estar alambrados
Se debe disponer de un “block” de prueba para cada DEI directamente a los circuitos de cierre y apertura del
utilizado para las funciones de medición, que permita la interruptor y no deben contar con permisivos a excepción del
desconexión de todas las señales de entrada que provengan cierre de los interruptores de líneas de alta tensión y banco
de los transformadores de instrumento; lo anterior con el de transformación cuyos únicos permisivos aceptables son
objeto de poder medir correctamente las entradas o bien los relevadores de disparo y bloqueo sostenido asociados a
permitir la inyección de señales de prueba, dicho “block” de los esquemas de falla de interruptor, protección de
prueba puede estar integrado al DEI de medición o transformador y barra colectora con sus correspondientes
incorporado en forma externa al mismo. No se acepta más indicaciones de estado a través de lámparas de alta
de uno de estos dispositivos por DEI. luminosidad formados por uno o varios “led’s” que permitan
su visibilidad en un ángulo de hasta 120 ° y con luz de día.
Se debe disponer de un “block” de prueba para cada DEI de La localización de estos controles emergentes debe ser
protección, que permita la desconexión de todas las señales distribuida en cada una de las diferentes secciones según
de entrada que provengan de los transformadores de corresponda a los DEI’s asociados con cada interruptor.
instrumento, las señales de salida de disparo, salidas de
control y arranques de reles de falla de interruptor; lo anterior 6.6 Datos Generales de la Subestación
con el objeto de probar el equipo correctamente, permitir la
inyección de señales de prueba y evitar disparos incorrectos Es lo referente a la información específica del lugar en donde
sin necesidad de modificar los alambrados del tablero. No se cada sistema será instalado (subestación), considerando lo
acepta más de uno de estos dispositivos por DEI de siguiente:
protección.
a) Nombre.
b) Diagrama unifilar.
23 de 166
En el caso de los medidores multifunción, deberán ser - las pruebas e inspección final deben ser
aprobados por el LAPEM. efectuadas en presencia del personal de CFE.
Dicha participación no limita la responsabilidad del
En el caso de los DEI’s de protección y registro de disturbio proveedor, total o parcial de la calidad satisfactoria
debe apegarse a lo establecido en la referencia bibliográfica de los equipos,
[7] del capítulo 12 de esta especificación.
- los equipos de medición y pruebas que
El equipo de radiocomunicación debe cumplir con todos los intervengan en el escenario deben de contar con
calibración y trazabilidad vigente,
requisitos técnicos de la especificación de CFE
correspondiente.
- el sistema integrado debe ser probado a plena
capacidad.
24 de 166
- reuniones para interpretación de los resultados de - programación de los tipos de entradas digitales,
las pruebas, así como de las medidas a tomar en
caso de fallas, - deshabilitación / habilitación de salidas de control
para pruebas,
- decisiones sobre nuevas pruebas, derivadas de
los resultados obtenidos en la implementación del - desplegado y procesamiento de alarmas y
programa establecido. eventos,
Las pruebas de aceptación deben efectuarse bajo las - sincronización del sistema,
condiciones especificadas y deben incluir:
- registro de eventos y alarmas.
- inspección visual:
b) Pruebas de los programas de aplicación.
. para detectar defectos de manufactura y
asegurar que el sistema se fabrique de - generación de reportes periódicos automáticos por
acuerdo a lo indicado en las especificaciones tiempo, por evento o por solicitud (Históricos de
SISCOPROMM y normas de referencia y mediciones, demandas, operación de
2
especificaciones propias del fabricante. interruptores, I t, entre otros).
- comunicaciones del CPS a UCM (con simulador) - configuración por la Integración de DEI’s,
con los protocolos especificados en los puertos
respectivos, - edición de diagramas unifilares,
25 de 166
26 de 166
e) Acta de aceptación acompañada de: Bitácora, f) En el caso del “software” de los medidores
resultados de las pruebas aceptación con visto multifunción se deben entregar licencias
bueno del responsable por parte de CFE. Esta institucionales al área usuaria. Adicionalmente a lo
información debe estar debidamente presentada y anterior, se debe entregar copia del certificado de
encarpetada. En el acto de recepción oficial del aprobación del LAPEM.
sistema (400 h después de operar
satisfactoriamente a juicio del usuario, véase
figura 3).
El proveedor ganador debe entregar a la Subgerencia de El proveedor debe garantizar el sistema en todas sus partes
Distribución en un lapso no mayor de 30 días después de por un periodo mínimo de treinta meses contados a partir de
formalizado el contrato, el programa detallado de fabricación la firma del acta de recepción del sistema, 36 meses
de los sistemas, con objeto de que CFE si lo considera después de su entrega en almacén, o como esto sea
necesario, realice las inspecciones conducentes durante indicado en las bases de la licitación. Durante este periodo el
dicha fabricación. proveedor debe proporcionar servicio en sitio por falla
atribuible al sistema, en un tiempo máximo de 36 h, después
Este programa debe ser sujeto al visto bueno de la Gerencia de ser notificado. Esta garantía debe estar respaldada
de Distribución, previo a la entrega antes citada. documentalmente. El servicio en sitio se refiere a dejar el
sistema en condiciones de operación al 100 % de sus
Respecto al programa para la puesta a punto y puesta en funciones y partes.
servicio del sistema, el fabricante conjuntamente con el área
usuaria de CFE, deben establecer el programa respectivo, en El proveedor debe garantizar el suministro de refacciones o
un plazo no mayor de 45 días después de formalizado el partes de repuesto del sistema por un periodo mínimo de 10
contrato. años.
Los licitantes de SISCOPROMM deben entregar con su El proveedor debe proporcionar por escrito a todas las áreas
propuesta a CFE la documentación, donde los diferentes destinatarias de CFE el procedimiento para aplicar tanto la
fabricantes de DEI’s, que integren su sistema, se atención inmediata como la garantía comercial.
comprometen a entregar la información que les sea
requerida por otros integradores, para realizar la conectividad 9.3 Vida Útil
y transportabilidad de la información, sin restricción ni costo
alguno. El proveedor debe presentar una garantía de vida útil del
sistema, contra cualquier falla atribuible al producto por vicio
oculto o diferencias de calidad de algún componente del
9 GARANTÍAS
sistema, por un periodo mínimo de 20 años, contados a partir
de su entrada en operación. Si hubiera una vida útil diferente
9.1 Garantía de Atención Inmediata
para varios elementos, ésta debe indicarse, así como las
condiciones bajo las cuales se garantiza dicha vida útil. Para
Durante las primeras 400 h después de su puesta en
este caso indicar MTBF y el MTTR.
operación, el proveedor debe proporcionar servicio inmediato
en sitio en un tiempo máximo de 24 h después de ser
notificado de la falla del sistema, este periodo se debe
reiniciar cada vez que se atienda una falla o se modifique el
sistema.
27 de 166
- entrega al proveedor, de información detallada [6] IEEE 802.3/IEEE 802.3u; Local Area Network
complementaria de los proyectos, tales como: (LAN) protocols
Diagramas, puntos de la base de datos,
comunicaciones, interfaces IHM y requerimiento [7] LAPEM 05; Procedimiento para la operación y
de protocolos y la estructura de la información mantenimiento del listado de Relevadores de
correspondiente a los apéndices D y E. Protección aprobados por CFE
c) Es necesario que la primera junta se efectúe en un [8] LAPEM 05L; Listado de Relevadores Aprobados
plazo no mayor a 30 días una vez entregado el por CFE.
contrato correspondiente, bajo responsabilidad del
proveedor.
28 de 166
TABLA 1 - Funciones mínimas de control, protección, medición y complementarias, requeridas para el SISCOPROMM
tensión
59N, V residual al cierre, para permitir descarga
A.T. (*)
50FI I desbalance de fases del banco
Sobrecorriente de
desbalance(****)
-Abrir/ cerrar manual y
Abrir/cerrar con funciones
27
En media lógicas programables el equipo
59 V de neutro Alarmas y estado
tensión de desconexión
59N
M.T. (*) -Bloqueo temporizado ajustable
al cierre, para permitir descarga
del banco
MWhd, MWhr, Localización de fallas (LDF)
MVArhd, MVArhr, -Bloqueo 79 desbloqueo 79,
50/51F MWd, MWd max, abrir/ cerrar Interruptor(es) Registrador secuencial de eventos
Alimentadores 50/51N MWd min, MWr, A, kV -Cambio del grupo de
2
M. T. 79 de barras, ErrMsg, ajustes I t (**)
81 Interr, Sags, Swells, -Bloqueo/desbloqueo 81
Desbalance de fases, Oscilografía (***)
frecuencia (Hz).
Disparo de interruptores y
Diferencial de
87B bloqueo de cierre (86B) con Alarmas y estado
Barras (*)
reposición manual
Interruptores
-Abrir y cerrar Interruptores
de amarre Esquema de
-Transferencia automática de Alarmas y estado
o transferencia protección (*)
señales de control y protección
(*)
Cuchillas de
-Abrir y cerrar Indicación de posición
A.T. (*)
29 de 166
TABLA 1A - Periodo mínimo para almacenar la información proveniente de los medidores multifunción
MWhd, MWhr, MVArhd, MVArhr, MWd, MWd max, MWd min, MWr, A, kV, ErrMsg, Interr, Sags, Swells, Desbal
cuartos de
segundos minutos 5 minutos Hora día mes año
hora
60 60 10 080 3 360 840 35 14 10
NOTA: Con la finalidad de optimizar el volumen de información requerido para la operación de la subestación, el sistema debe
tener la facilidad de configurar y agrupar las alarmas comunes de los equipos y dispositivos para ser enviadas
selectivamente a la UCM del nivel superior. Todas las alarmas de la tabla deben registrarse invariablemente en el CPS.
30 de 166
NOTA: Además de las mediciones indicadas en esta tabla, el sistema debe ser capaz de configurar la transmisión a la UCM cualquier
medición disponible en los DEI’s.
31 de 166
Oscilografía
Registro secuencial de eventos.
Banco de capacitores en alta tensión
50/51F Sobrecorriente A.T. instantánea y de tiempo de fase
50/51N Sobrecorriente A.T. instantánea y de tiempo de neutro
59N Sobretensión de neutro
64N(**) Tensión residual
Registro secuencial de eventos.
Alimentadores M.T.
50/51F Sobrecorriente instantánea y de tiempo de fase
50/51N Sobrecorriente instantánea y de tiempo de neutro
79T Recierre con tiempo, con arranque por protección
81 Baja frecuencia
Función de localización de fallas
Oscilografía
Registro secuencial de eventos.
Barras A.T.
87B Diferencial de barras
Registro secuencial de eventos.
Además de la información indicada en esta tabla, el sistema debe ser capaz de configurar la transmisión a la UCM
de cualquier otra disponible en los DEI’s.
32 de 166
IEC 61000-4-4
5 Transitorios rápidos
IEC 60255-22-4
IEC 61000-4-3
6 Campos electromagnéticos radiados de alta frecuencia
IEC 60255-22-3
7 Microinterrupciones IEC 61000-4-11
IEC 61000-4-2
8 Descargas electrostáticas
IEC 60255-22-2
Documentación Aislamiento
11 Pruebas funcionales propias del relevador en estado estable de protección ANSI manifestadas por
el fabricante, se verifican las
funciones y parámetros indicadas en
cada especificación CFE a la que se
12 Pruebas funcionales del relevador en estado dinámico haga referencia de acuerdo a la
tabla 2
En lo que toca a su operación como sistema integrado, se debe cumplir totalmente con la presente especificación.
33 de 166
APÉNDICE A
Este apéndice comprende lo relativo a la descripción corta, la cual es recomendable para tener una referencia de las
Características Particulares.
La siguiente tabla comprende la descripción corta de los sistemas integrados de control, protección y medición, considerados en
esta especificación.
Descripción Corta:
|SISCOPROMM 1T - 4 / 5A - 4 DL3
(a), (b), (c), (d) y (e)
b) Este campo indica el número de transformadores de potencia a emplearse, pudiendo ser el campo desde 0 hasta n.
e) Del número total de alimentadores en alta tensión (c), este campo indica cuantos deben tener esquema de
protección diferencial de línea por enlaces con longitudes menores a 10 km. De donde la diferencia entre (c) y
(e) corresponde al número de alimentadores de A.T. que requieran esquemas de protección de línea de
subtransmisión por enlaces con longitudes mayores a 10 km.
SISTEMAS SISCOPROMM
SISCOPROMM-0T-1/0A SISCOPROMM-0T-4/0A
SISCOPROMM-0T-1/0A-1DL3 SISCOPROMM-0T-4/0A-1DL3
SISCOPROMM-0T-2/0A SISCOPROMM-0T-4/0A-2DL3
SISCOPROMM-0T-2/0A-1DL3 SISCOPROMM-0T-4/0A-3DL3
SISCOPROMM-0T-2/0A-2DL3 SISCOPROMM-0T-4/0A-4DL3
SISCOPROMM-0T-3/0A
SISCOPROMM-0T-3/0A-1DL3
SISCOPROMM-0T-3/0A-2DL3
SISCOPROMM-0T-3/0A-3DL3
SISCOPROMM-1T-0/1A SISCOPROMM-1T-0/4A
SISCOPROMM-1T-0/2A SISCOPROMM-1T-0/5A
SISCOPROMM-1T-0/3A SISCOPROMM-1T-0/6A
SISCOPROMM-1T-1/1A SISCOPROMM-1T-1/4A
SISCOPROMM-1T-1/1A-1DL3 SISCOPROMM-1T-1/4A-1DL3
SISCOPROMM-1T-1/2A SISCOPROMM-1T-1/5A
SISCOPROMM-1T-1/2A-1DL3 SISCOPROMM-1T-1/5A-1DL3
SISCOPROMM-1T-1/3A SISCOPROMM-0T-1/6A
SISCOPROMM-1T-1/3A-1DL3 SISCOPROMM-0T-1/6A-1DL3
SISCOPROMM-1T-2/1A SISCOPROMM-1T-2/4A
SISCOPROMM-1T-2/1A-1DL3 SISCOPROMM-1T-2/4A-1DL3
SISCOPROMM-1T-2/1A-2DL3 SISCOPROMM-1T-2/4A-2DL3
SISCOPROMM-1T-2/2A SISCOPROMM-1T-2/5A
34 de 166
SISCOPROMM-1T-2/2A-1DL3 SISCOPROMM-1T-2/5A-1DL3
SISCOPROMM-1T-2/2A-2DL3 SISCOPROMM-1T-2/5A-2DL3
SISCOPROMM-1T-2/3A SISCOPROMM-1T-2/6A
SISCOPROMM-1T-2/3A-1DL3 SISCOPROMM-1T-2/6A-1DL3
SISCOPROMM-1T-2/3A-2DL3 SISCOPROMM-1T-2/6A-2DL3
SISCOPROMM-1T-3/1A SISCOPROMM-1T-3/4A
SISCOPROMM-1T-3/1A-1DL3 SISCOPROMM-1T-3/4A-1DL3
SISCOPROMM-1T-3/1A-2DL3 SISCOPROMM-1T-3/4A-2DL3
SISCOPROMM-1T-3/1A-3DL3 SISCOPROMM-1T-3/4A-3DL3
SISCOPROMM-1T-3/2A SISCOPROMM-1T-3/5A
SISCOPROMM-1T-3/2A-1DL3 SISCOPROMM-1T-3/5A-1DL3
SISCOPROMM-1T-3/2A-2DL3 SISCOPROMM-1T-3/5A-2DL3
SISCOPROMM-1T-3/2A-3DL3 SISCOPROMM-1T-3/5A-3DL3
SISCOPROMM-1T-3/3A SISCOPROMM-1T-3/6A
SISCOPROMM-1T-3/3A-1DL3 SISCOPROMM-1T-3/6A-1DL3
SISCOPROMM-1T-3/3A-2DL3 SISCOPROMM-1T-3/6A-2DL3
SISCOPROMM-1T-3/3A-3DL3 SISCOPROMM-1T-3/6A-3DL3
SISCOPROMM-1T-4/1A SISCOPROMM-1T-4/4A
SISCOPROMM-1T-4/1A-1DL3 SISCOPROMM-1T-4/4A-1DL3
SISCOPROMM-1T-4/1A-2DL3 SISCOPROMM-1T-4/4A-2DL3
SISCOPROMM-1T-4/1A-3DL3 SISCOPROMM-1T-4/4A-3DL3
SISCOPROMM-1T-4/1A-4DL3 SISCOPROMM-1T-4/4A-4DL3
SISCOPROMM-1T-4/2A SISCOPROMM-1T-4/5A
SISCOPROMM-1T-4/2A-1DL3 SISCOPROMM-1T-4/5A-1DL3
SISCOPROMM-1T-4/2A-2DL3 SISCOPROMM-1T-4/5A-2DL3
SISCOPROMM-1T-4/2A-3DL3 SISCOPROMM-1T-4/5A-3DL3
SISCOPROMM-1T-4/2A-4DL3 SISCOPROMM-1T-4/5A-4DL3
SISCOPROMM-1T-4/3A SISCOPROMM-1T-4/6A
SISCOPROMM-1T-4/3A-1DL3 SISCOPROMM-1T-4/6A-1DL3
SISCOPROMM-1T-4/3A-2DL3 SISCOPROMM-1T-4/6A-2DL3
SISCOPROMM-1T-4/3A-3DL3 SISCOPROMM-1T-4/6A-3DL3
SISCOPROMM-1T-4/3A-4DL3 SISCOPROMM-1T-4/6A-4DL3
SISCOPROMM-2T-0/7A SISCOPROMM-2T-0/10A
SISCOPROMM-2T-0/8A SISCOPROMM-2T-0/11A
SISCOPROMM-2T-0/9A SISCOPROMM-2T-0/12A
SISCOPROMM-2T-1/7A SISCOPROMM-2T-1/10A
SISCOPROMM-2T-1/7A-1DL3 SISCOPROMM-2T-1/10A-1DL3
SISCOPROMM-2T-1/8A SISCOPROMM-2T-1/11A
SISCOPROMM-2T-1/8A-1DL3 SISCOPROMM-2T-1/115A-1DL3
SISCOPROMM-2T-1/9A SISCOPROMM-2T-1/12A
SISCOPROMM-2T-1/9A-1DL3 SISCOPROMM-2T-1/12A-1DL3
SISCOPROMM-2T-2/7A SISCOPROMM-2T-2/10A
SISCOPROMM-2T-2/7A-1DL3 SISCOPROMM-2T-2/10A-1DL3
SISCOPROMM-2T-2/7A-2DL3 SISCOPROMM-2T-2/10A-2DL3
SISCOPROMM-2T-2/8A SISCOPROMM-2T-2/11A
SISCOPROMM-2T-2/8A-1DL3 SISCOPROMM-2T-2/11A-1DL3
SISCOPROMM-2T-2/8A-2DL3 SISCOPROMM-2T-2/11A-2DL3
SISCOPROMM-2T-2/9A SISCOPROMM-2T-2/12A
SISCOPROMM-2T-2/9A-1DL3 SISCOPROMM-2T-2/12A-1DL3
SISCOPROMM-2T-2/9A-2DL3 SISCOPROMM-2T-2/12-2DL3
SISCOPROMM-2T-3/7A SISCOPROMM-2T-3/10A
SISCOPROMM-2T-3/7A-1DL3 SISCOPROMM-2T-3/10A-1DL3
SISCOPROMM-2T-3/7A-2DL3 SISCOPROMM-2T-3/10A-2DL3
SISCOPROMM-2T-3/7A-3DL3 SISCOPROMM-2T-3/10A-3DL3
35 de 166
SISCOPROMM-2T-3/8A SISCOPROMM-2T-3/11A
SISCOPROMM-2T-3/8A-1DL3 SISCOPROMM-2T-3/11A-1DL3
SISCOPROMM-2T-3/8A-2DL3 SISCOPROMM-2T-3/11A-2DL3
SISCOPROMM-2T-3/8A-3DL3 SISCOPROMM-2T-3/11A-3DL3
SISCOPROMM-2T-3/9A SISCOPROMM-2T-3/12A
SISCOPROMM-2T-3/9A-1DL3 SISCOPROMM-2T-3/12A-1DL3
SISCOPROMM-2T-3/9A-2DL3 SISCOPROMM-2T-3/12A-2DL3
SISCOPROMM-2T-3/9A-3DL3 SISCOPROMM-2T-3/12A-3DL3
SISCOPROMM-2T-4/7A SISCOPROMM-2T-4/10A
SISCOPROMM-2T-4/7A-1DL3 SISCOPROMM-2T-4/10A-1DL3
SISCOPROMM-2T-4/7A-2DL3 SISCOPROMM-2T-4/10A-2DL3
SISCOPROMM-2T-4/7A-3DL3 SISCOPROMM-2T-4/10A-3DL3
SISCOPROMM-2T-4/7A-4DL3 SISCOPROMM-2T-4/10A-4DL3
SISCOPROMM-2T-4/8A SISCOPROMM-2T-4/11A
SISCOPROMM-2T-4/8A-1DL3 SISCOPROMM-2T-4/11A-1DL3
SISCOPROMM-2T-4/8A-2DL3 SISCOPROMM-2T-4/11A-2DL3
SISCOPROMM-2T-4/8A-3DL3 SISCOPROMM-2T-4/11A-3DL3
SISCOPROMM-2T-4/8A-4DL3 SISCOPROMM-2T-4/11A-4DL3
SISCOPROMM-2T-4/9A SISCOPROMM-2T-4/12A
SISCOPROMM-2T-4/9A-1DL3 SISCOPROMM-2T-4/12A-1DL3
SISCOPROMM-2T-4/9A-2DL3 SISCOPROMM-2T-4/12A-2DL3
SISCOPROMM-2T-4/9A-3DL3 SISCOPROMM-2T-4/12A-3DL3
SISCOPROMM-2T-4/9A-4DL3 SISCOPROMM-2T-4/12A-4DL3
DISTRIBUCIÓN
LICITACIÓN No.____________________ LICITANTE: ______________________________________________
36 de 166
SUBDIRECCIÓN DIVISIÓN :
De:
DE OBRA:
PROYECTO:
DISTRIBUCIÓN
37 de 166
Procesador
Reloj
Memoria RAM
Disco duro
Memoria video
Memoria cache
Unidad de cinta
CD ROM
Drive 3 ½
Teclado industrial
Monitor
UPS autonomía
Licencias de “software”
Tarjetas multipuerto
“Mouse/track ball”
SUBDIRECCIÓN DIVISIÓN :
De:
DE OBRA:
PROYECTO:
DISTRIBUCIÓN
38 de 166
HARDWARE Referencia de
cumplimiento
Descripción corta Fibra óptica Multiplexor Ruteador “software”
SUBDIRECCIÓN DIVISIÓN :
De:
DE OBRA:
PROYECTO:
DISTRIBUCIÓN
39 de 166
ALCANCE DEL SUMINISTRO DE LOS DEI´S PARA SISCOPROMM Y TABLEROS PCM CONVENCIONALES
Línea corta
Descripción Línea Alimentadores Capacitores Capacitores
Función DEI Datos Cant. Transformadores Cant. Cant. Cant. Cant.
corta Extremo Extremo larga M.T. M.T. A.T.
Cant. Cant.
local colateral
M
DEI Tipo:
1 Mod.:
Func:
Mca:
DEI Tipo:
2 Mod.:
Func:
PROTECCIÓN
Mca:
DEI Tipo:
3 Mod.:
Func:
Mca:
DEI Tipo:
4 Mod.:
Func:
Mca:
DEI Tipo:
5 Mod.:
Func:
Mca:
DEI Tipo:
Medición
n Mod.:
Func:
SUBDIRECCIÓN DIVISIÓN :
De:
DE OBRA:
PROYECTO:
DISTRIBUCIÓN
40 de 166
Mca:
DEI
Tipo:
1
Mod.:
Mca:
DEI
Protección
Tipo:
2
Mod.:
Mca:
DEI
Tipo:
3
Mod.:
Mca:
DEI
Tipo:
4
Mod.:
Funciones de medición Comunicaciones Experiencia Ref. cump.
Mca:
DEI
Tipo:
5
Mod.:
* OPCIONAL SI SE REQUIER EN CARACTERÍSTICAS PARTICULARES
SUBDIRECCIÓN DIVISIÓN :
De:
DE OBRA:
PROYECTO:
DISTRIBUCIÓN
41 de 166
Mca:
DEI
Tipo:
1
Mod.:
Mca:
DEI
Protección
Tipo:
2
Mod.:
Mca:
DEI
Tipo:
3
Mod.:
Mca:
DEI
Tipo:
4
Mod.:
Funciones de medición Comunicaciones Experiencia Ref. cump.
Mca:
DEI
Tipo:
5
Mod.:
SUBDIRECCIÓN DIVISIÓN :
De:
DE OBRA:
PROYECTO:
DISTRIBUCIÓN
42 de 166
Mca:
DEI
Tipo:
1
Mod.:
Mca:
DEI
Protección
Tipo:
2
Mod.:
Mca:
DEI
Tipo:
3
Mod.:
Mca:
DEI
Tipo:
4
Mod.:
Funciones de medición Comunicaciones Experiencia Ref. cump.
Mca:
DEI
Tipo:
5
Mod.:
SUBDIRECCIÓN DIVISIÓN :
De:
DE OBRA:
PROYECTO:
DISTRIBUCIÓN
43 de 166
Mca:
DEI
Tipo:
1
Mod.:
Mca:
DEI
Protección
Tipo:
2
Mod.:
Mca:
DEI
Tipo:
3
Mod.:
Mca:
DEI
Tipo:
4
Mod.:
Funciones de medición Comunicaciones Experiencia Ref. cump.
Mca:
DEI
Tipo:
5
Mod.:
SUBDIRECCIÓN DIVISIÓN :
De:
DE OBRA:
PROYECTO:
DISTRIBUCIÓN
44 de 166
Mca:
DEI
Tipo:
1
Mod.:
Mca:
PROTECCIÓN
DEI
Tipo:
2
Mod.:
Mca:
DEI
Tipo:
3
Mod.:
Mca:
DEI
Tipo:
4
Mod.:
Funciones de medición Comunicaciones Experiencia Ref. cump.
Mca:
DEI
Tipo:
5
Mod.:
Sólo se aplica para bancos de capacitores con conexión de doble estrella, lo que se
(****)
indica en Características Particulares.
SUBDIRECCIÓN DIVISIÓN :
De:
DE OBRA:
PROYECTO:
DISTRIBUCIÓN
45 de 166
Mca:
DEI
Tipo:
1
Mod.:
Mca:
DEI
Protección
Tipo:
2
Mod.:
Mca:
DEI
Tipo:
3
Mod.:
Mca:
DEI
Tipo:
4
Mod.:
Funciones de medición Comunicaciones Experiencia Ref. cump.
Mca:
DEI
Tipo:
5
Mod.:
SUBDIRECCIÓN DIVISIÓN :
De:
DE OBRA:
PROYECTO:
DISTRIBUCIÓN
46 de 166
SUBDIRECCIÓN DIVISIÓN :
De:
DE OBRA:
PROYECTO:
DISTRIBUCIÓN
47 de 166
CARACTERÍSTICAS “MODEMS”
SUBDIRECCIÓN DIVISIÓN :
De:
DE OBRA:
PROYECTO:
DISTRIBUCIÓN
48 de 166
SUBDIRECCIÓN DIVISIÓN :
De:
DE OBRA:
PROYECTO:
DISTRIBUCIÓN
49 de 166
Referencia de cumplimiento
Descripción Protocolo puerto 1 Protocolo puerto 2 Protocolo puerto 3
Carpeta Folios
SUBDIRECCIÓN DIVISIÓN :
De:
DE OBRA:
PROYECTO:
DISTRIBUCIÓN
50 de 166
Referencia de
Radio puerto 1 Radio puerto 2
cumplimiento
Descripción
Marca Modelo Banda Watts Marca Modelo Banda Watts Carpeta Folios
PANTALLAS
DIVISIÓN : HOJA:
SUBDIRECCIÓN DE:
DE SUBESTACIÓN(ES):
DISTRIBUCIÓN
51 de 166
UNIFILAR
SUBDIRECCIÓN DE:
DE SUBESTACIÓN(ES):
DISTRIBUCIÓN
52 de 166
UNIFILARES
Unifilar de
Unifilar
Protecciones
Por Bahía
Configuración
Eventos Medición Reportes Consultas Utilerias Sesión
Unifilares Alarmas Y Ajustes
SUBDIRECCIÓN DE:
DE SUBESTACIÓN(ES):
DISTRIBUCIÓN
53 de 166
RESUMEN DE ALARMAS
Reconocer
Alarmas Alarmas Alarmas de
Alarmas Alarmas de Diagnosticos Alarmas Alarmas de medicion fuera
interruptor Transformador op Protecc. Comuniciones DEI{S Grales S.E.. CPS de banda individual Grupo
s
Configuración
Unifilares Eventos Medición Reportes Consultas Utilerias Sesión
Alarmas Y Ajustes
SUBDIRECCIÓN DE:
DE SUBESTACIÓN(ES):
DISTRIBUCIÓN
54 de 166
Alarmas de
Reconocer
Alarmas Alarmas Alarmas Alarmas de Diagnosticos Alarmas Alarmas de medicion fuera
interruptor Transformado op Protecc. Comuniciones DEI{S Grales S.E.. CPS de banda individual Grupo
s
SUBDIRECCIÓN DE:
DE SUBESTACIÓN(ES):
DISTRIBUCIÓN
55 de 166
EVENTOS
Fecha y hora del evento Descripción del evento Reconocida por: Fecha y hora de reconocimiento
Reconocer
Eventos Eventos Eventos de
Eventos por Eventos por Eventos por Eventos de diagnosticos Generales S.E. Eventos del medicion fuera
Interruptor Transformador Op. Comunicaciones CPS
DEI´s de banda individual Grupo
Configuración
Eventos Medición Reportes Consultas Utilerias Sesión
Unifilares Alarmas Y Ajustes
SUBDIRECCIÓN DE:
DE SUBESTACIÓN(ES):
DISTRIBUCIÓN
56 de 166
MEDICIÓN
Aceptar Cancelar
Configuración
Eventos Medición Reportes Consultas Utilerias Sesión
Unifilares Alarmas Y Ajustes
SUBDIRECCIÓN DE:
DE SUBESTACIÓN(ES):
DISTRIBUCIÓN
57 de 166
UNIFILAR
REPORTES
Equipos fuera
Operación de Operación Estadisticas de Operación de Tensión en
Interruptores
de limites de Buses
Automatismos Comunicaciones Protecciones
Comunicación.
Aceptar Cancelar
Configuración
Eventos Medición Reportes Consultas Utilerias Sesión
Unifilares Alarmas Y Ajustes
SUBDIRECCIÓN DE:
DE SUBESTACIÓN(ES):
DISTRIBUCIÓN
58 de 166
UNIFILAR
CONSULTAS
Localización
Configuración Contador de Estadisticas de
de fallas
de equipos operaciones comunicaciones
Aceptar Cancelar
Configuración
Eventos Medición Reportes Consultas Utilerias Sesión
Unifilares Alarmas Y Ajustes
SUBDIRECCIÓN DE:
DE SUBESTACIÓN(ES):
DISTRIBUCIÓN
59 de 166
UNIFILAR
CONFIGURACIÓN Y AJUSTES
Desbalance de Nivel
Base de DEI´s Interfaz Mapeo de
fases Superior
datos Siscoprom-sipasd base de datos
Red TCP/IP
Nivel Password de Protocolos Red local Time out
inferior usuarios
Medición Consultas
Configuración
Eventos Reportes Utilerias Sesión
Unifilares Alarmas Y Ajustes
SUBDIRECCIÓN DE:
DE SUBESTACIÓN(ES):
DISTRIBUCIÓN
60 de 166
UNIFILAR
UTILERIAS
Aceptar Cancelar
Configuración
Eventos Medición Reportes Consultas Utilerias Sesión
Unifilares Alarmas Y Ajustes
SUBDIRECCIÓN DE:
DE SUBESTACIÓN(ES):
DISTRIBUCIÓN
61 de 166
UNIFILAR
SESIONES
Password de
acceso Terminar
Aceptar Cancelar
Configuración
Eventos Medición Reportes Consultas Utilerias Sesión
Unifilares Alarmas Y Ajustes
SUBDIRECCIÓN DE:
DE SUBESTACIÓN(ES):
DISTRIBUCIÓN
62 de 166
UNIFILAR
PASSWORD DE ACCESO
IDENTIFICACION
CLAVE DE ACCESO
Aceptar Cancelar
Configuración
Eventos Medición Reportes Consultas Utilerias Sesión
Unifilares Alarmas Y Ajustes
63 de 166
APÉNDICE D
ESTRUCTURA DE INFORMACIÓN DE LOS SISCOPROMM
D.1 OBJETIVO
D.2 ALCANCE
Se define un marco que se irá enriqueciendo con la experiencia y participación de especialistas en medición, protección y control.
En esta etapa se requiere actualizar las tablas circulares relacionada con medición indicada en tabla D3 con tiempos de
actualización de 15 minutos.
D.3 PROCEDIMIENTO
El análisis y definición de estructuras y funciones, solo para señales de campo, están basados en las necesidades que se plantean
al analizar una subestación tipo - para distribución representada en la figura D1, así como la información de la especificación
SISCOPROMM en sus tablas:
Se define un arreglo tridimensional donde cada elemento tiene una asignación única.
Cada elemento es un arreglo de tablas circulares con diferentes longitudes y velocidades de actualización.
La subestación de referencia sirve para asignar el nombre o variable única donde se guarda la información específica de un
elemento.
D.4 REQUERIMIENTOS
64 de 166
65 de 166
TABLA D1 - Funciones mínimas de control, protección, medición y complementarias, requeridas para el sistema
50FI, 79 Oscilografía,
115 kV)
50/51N
Banco de
66 de 166
D.4.3 Alarmas
67 de 166
KW
Líneas kWd (demanda)
kV (barras)
Mediciones instantáneas KW
Para Sub-área de control kWd (demanda)
Transformador
kVAr (barras)
kV (bus de M.T)
KWh
Mediciones acumuladas
KVAr
I (amperes)
KW
kWh (acumulados)
kvarh (acumulados)
Transformador
kV en AT
kV en MT
Temperatura devanados
Para Operación Distribución Mediciones instantáneas
Temperatura aceite
I (amperes)
KW
kWh
Alimentadores en MT
kVAr
kVArh
kWd (demanda)
Mediciones instantáneas, MWhd, MWhr, MVArhd, MVArhr,
acumuladas, congeladas, de MWd, MWd max, MWd min,
Líneas, transformadores y
Para medición cambio de horario y de cambio MWr, A, kV, ErrMsg, Interr, Sags,
alimentadores
de estación. Swells, Desbalance de fases.,
frecuencia (Hz).
Tensión en banco de baterías = 125 V c.d.
- líneas,
- transformadores de potencia,
. alta tensión,
. media tensión,
. alimentadores,
. barras,
68 de 166
. interruptores,
. cuchillas.
Para tener registro e historia de los elementos de la subestación para planeación y mantenimiento es necesario contar con tablas
circulares, "buffer's". De estas tablas circulares se procesa el contenido de las tablas y genera un punto o valor para otra tabla
circulante de otro nivel (de mayor tiempo de actualización) de tal modo que se pueda tener análisis de información a diferentes
frecuencias de actualización.
a) Fracción de ciclos.
b) Segundos.
c) Minutos.
d) Horas.
e) Días.
f) Meses.
g) Años.
Toda información tanto analógica como digital, tiene las características de tabla circular que está caracterizada por los siguientes
parámetros:
- frecuencia de actualización,
- algoritmo para que de una tabla se obtenga un punto para la tabla del siguiente nivel.
Condición disparo - - - - - - -
Algoritmo * * * * * * *
69 de 166
En caso de tablas circulares (en fracción de ciclos), 960 puntos por señal, no es necesario actualizarlas en tiempo real, solo se
requiere el espacio de memoria. Este espacio se utiliza para almacenar información de oscilografía para comparar registros de
diferentes DEI's.
Las tablas circulares de "segundos" que constan de 60 puntos se actualizan en forma circular a un punto por segundo, cuando se
han acumulado 60 puntos, se genera un punto que es el valor para actualizar la tabla circular de "minutos". El algoritmo que se
utiliza para que del conjunto de puntos de la tabla de "segundos" se genere el próximo punto de actualización de la tabla circular de
"minutos" depende de la señal en cuestión; así para:
d) MWhd, MWhr, MVArhd, MVArhr, ErrMsg, Interr, Sags, Swells, Desbalance de fases.
.
El siguiente valor de actualización de la tabla "segundos" sustituye al valor más antiguo y así sucesivamente.
Cada 60 s se genera un valor para actualizar la tabla circular de "minutos" cada 60 min se genera un valor con el algoritmo
correspondiente, para actualizar la tabla circular de horas cada 24 h, se calcula el valor que actualizará la tabla de días y así
sucesivamente para tener en tablas circulares la información de la última actualización de cada tabla circular.
Forma automática tenemos los perfiles de las señales requeridas en la tabla D3.
Cada hora se respalda el archivo "Subest***.pmo." (***número único de cada subestación), que contiene la información de las
tablas circulares de las señales requeridas en la tabla D.3, y almacenados en las tablas circulares indicadas en la tabla D4, con
excepción de lo indicado en la columna de "Fracción de Ciclos" de la tabla D4.
Las subestaciones así como sus componentes y señales tienen identificación única; para definirla se toma en cuenta a qué
elemento del sistema de distribución pertenecen (línea, barra, transformador, bancos de capacitores y alimentador), con ayuda de
la figura D1 se definen los siguientes arreglos tridimensionales de tablas circulares para los diferentes elementos del sistema:
Se hace un barrido de la figura D1 por elementos iniciando de líneas y terminando con los alimentadores.
El índice "i" representa los elementos que se van encontrando haciendo un barrido de renglones.
El índice "j" indica el número de líneas, bancos de transformación o alimentadores según sea el arreglo del elemento del sistema;
barre en columnas.
El índice "k" representa las tres fases y neutro del sistema eléctrico su barrido es en profundidad.
70 de 166
LÍNEAS
l i, j, k,
INTERVALOS
i, = 1, 2... 37
j, = 1, 2... 5
k, = 1, 2... 4
BARRA EN ALTA
ba i, j, k,
INTERVALOS
i, = 1, 2... 37
j, = 1, 2... 5
k, = 1, 2... 4
BANCO TRANSFORMACIÓN
ta i, j, k,
INTERVALOS
i, = 1, 2... 37
j, = 1, 2... 5
k, = 1, 2... 4
BARRA TRANSFERENCIA
bt i, j, k,
INTERVALOS
i, = 1, 2... 37
j, = 1, 2... 20
k, = 1, 2... 4
En las tablas de los arreglos tridimensionales para cada elemento del sistema queda insertada la información de requerimientos de
las tablas D1, D2, D3 de la especificación de los SISCOPROMM.
Una vez identificadas las tablas circulares que contienen información analógica y digital se cuenta con un banco de información
para explotarse para varias aplicaciones y niveles.
71 de 166
Líneas
Asignación Descripción
l 1,j,k TC's línea
l 2,j,k TP's línea
Señales primarias
l 9,j,k
l 10,j,k kW
l 11,j,k kVAr
Señales Calculadas
l 12,j,k kWd
l 13,j,k kVArd
l 14,j,k kWh
l 15,j,k kVArh
l 16,j,k Frecuencia (f)
l 17,j,k
l 18,j,k
l 19,j,k
l 20,j,k 87 L
l 21,j,k 67 F
l 22,j,k 50 FI
l 23,j,k 79
Protección
l 24,j,k 25*
l 25,j,k 27*
l 26,j,k 21 F
l 27,j,k
l 28,j,k
l 29,j,k
72 de 166
Barra en alta
Asignación Descripción
Ba 1,j,k
Ba 2,j,k
Señales primarias
Ba 3,j,k
Ba 4,j,k
Ba 5,j,k
Ba 6,j,k
Ba 7,j,k
Ba 8,j,k
Medición
Ba 9,j,k
Ba 10,j,k
Ba 11,j,k
Señales calculadas
Ba 12,j,k
Ba 13,j,k
Ba 14,j,k
Ba 15,j,k
Ba 16,j,k
Ba 17,j,k
Ba 18,j,k
Ba 19,j,k
Ba 20,j,k 87 B
Ba 21,j,k
Ba 22,j,k
Ba 23,j,k
Protección
Ba 24,j,k
Ba 25,j,k
Ba 26,j,k
Ba 27,j,k
Ba 28,j,k
Ba 29,j,k
73 de 166
ta 12,j,k kWd
ta 13,j,k kVArd
ta 14,j,k kWh
ta 15,j,k kVArh
ta 16,j,k
ta 17,j,k
ta 18,j,k A Corriente por fase en capacitores
ta 19,j,k V Tensión residual
ta 20,j,k 87 T
ta 22,j,k 50 FI Banco capacitores
ta 26,j,k 50 / 51
ta 21,j,k
Protección
ta 28,j,k 81 27
ta 23,j,k 50 / 51
ta 24,j,k 59
ta 25,j,k 64 N
ta 29,j,k ta 27,j,k 50 FI
74 de 166
tb 9,j,k
tb 10,j,k kW
tb 11,j,k kVAr
Señales calculadas
tb 12,j,k kWd
tb 13,j,k kVArd
tb 14,j,k kWh
tb 15,j,k kVArh
tb 16,j,k
tb 17,j,k
tb 18,j,k
tb 19,j,k Tensión residual por fase
tb 20,j,k 50 / 51
tb 21,j,k 51 NT
tb 22,j,k 59 N
tb 23,j,k 81
Protección
tb 24,j,k
tb 25,j,k
tb 26,j,k
tb 27,j,k
tb 28,j,k
tb 29,j,k
75 de 166
bb 9,j,k
bb 10,j,k
bb 11,j,k
Señales calculadas
bb 12,j,k
bb 13,j,k
bb 14,j,k
bb 15,j,k
bb 16,j,k
bb 17,j,k
bb 18,j,k
bb 19,j,k
bb 20,j,k
bb 21,j,k
bb 22,j,k
bb 23,j,k
Protección
bb 24,j,k
bb 25,j,k
bb 26,j,k
bb 27,j,k
bb 28,j,k
bb 29,j,k
76 de 166
Barra transferencia
Asignación Descripción
bt 1,j,k TC's Alimentadores
bt 2,j,k ..............
Señales primarias
bt 3,j,k ..............
bt 4,j,k Cuchillas de transferencia
bt 5,j,k
bt 6,j,k
bt 7,j,k
bt 8,j,k
Medición
bt 9,j,k
bt 10,j,k kW
bt 11,j,k kVAr
Señales calculadas
bt 12,j,k kWd
bt 13,j,k kVArd
bt 14,j,k kWh
bt 15,j,k kVArh
bt 16,j,k
bt 17,j,k
bt 18,j,k
bt 19,j,k
bt 20,j,k 50 / 51
bt 21,j,k 79
bt 22,j,k 81
bt 23,j,k
Protección
bt 24,j,k
bt 25,j,k
bt 26,j,k
bt 27,j,k
bt 28,j,k
bt 29,j,k
77 de 166
El registro de señales analógicas, estado de interruptor del elemento del sistema (línea, transformador, alimentador), estados de
protecciones de dicho elemento se guardan en un conjunto de archivos con una extensión que trabaja en forma circular con una
extensión ev1... hasta ev9 en forma consecutiva. Se requiere llevar control del siguiente archivo que se re-escribe, es decir, que se
borra y actualiza. Esto es para no saturar ni administrar el disco duro.
De esta forma debe haber 9 archivos de registros y eventos para cada elemento del sistema con los nombres siguientes:
El formato de la información en las tablas circulares, archivos de banco de información y los archivos de eventos tienen que estar
regidos, mínimo, por los conceptos establecidos en la referencia [5] del capítulo 12 de esta especificación.
La información se puede enviar en forma compactada a nivel superior, siempre y cuando se recobre la información de acuerdo a la
referencia [5] del capítulo 12 de esta especificación, es decir que se requiere control de los archivos de configuración y datos que
contempla esta referencia.
78 de 166
APÉNDICE E
ÍNDICE
ANTECEDENTES
OBJETIVO
ALCANCE
PROCEDIMIENTO
ANEXO
Estructura de Información, Máscaras y
Formatos de Archivos
79 de 166
E.1 ANTECEDENTES
Con base a la estructura de información contemplada en el ANEXO 19 – Estructura de Información de los Sistemas SISCOPROMM
que se ha venido utilizando en las bases de licitación de SISCOPROMM, ahora se amplía el alcance a todas las señales analógicas
y digitales.
Para integrar la información de diferentes versiones de SISCOPROMM al SIPASD se han definido unos archivos de interfaz de los
SISCOPROMM a SIPASD.
Se han separado los archivos para información de señales analógicas de archivos que contienen información de estados y alarmas
digitales.
- líneas,
- transformadores de potencia,
- banco capacitores,
- barras,
- alimentadores.
Todos los archivos están en binario y se definen los detalles de los archivos XXXXXXXX.DAT en base a la referencia [5] del
capítulo 12 de esta especificación.
E.2 OBJETIVO
Definir los archivos necesarios para integrar la información de los SISCOPROMM al SIPASD.
E.3 ALCANCE
Esta interfaz contempla el envío de señales analógicas y digitales que permitan recabar información paramétrica necesaria para
integrar o complementar los módulos de:
- control,
- protección,
- medición,
- inventario,
- mantenibilidad,
- análisis de falla,
- costos,
- seguridad.
E.4 PROCEDIMIENTO
Con la finalidad de integrar información entre los SISCOPROMM y el SIPASD se requiere que los SISCOPROMM definan una
tarea que consiste en compartir archivos que se actualizan o re-escriben en sí mismos cada 15 minutos.
80 de 166
El programa de aplicación SIPASD hace uso del “IP” de SISCOPROMM para utilizar los archivos que comparte; en cada
SISCOPROMM se definen archivos de señales analógicas así como archivos que contienen la información digital.
Con la identificación de su número de “IP” el programa de aplicación hace uso de esos archivos para integrar la información de
diferentes SISCOPROMM y proveedores.
- líneas,
- barras,
- transformadores,
- alimentadores.
Se adjunta el contenido que deben de tener cada uno de los archivos de las diferentes áreas de la subestación:
b) Las variables analógicas que estarán en el archivo tomando en cuenta que el archivo es en binario a 32 bits y los valores
son por fase.
c) El archivo de estados y alarmas digitales están indicados en las seis máscaras que forman el archivo con la información
digital.
81 de 166
De acuerdo a la configuración de la subestación serán los archivos que se generan. La configuración indicará cuáles archivos serán
consultados.
Como complemento a la información de la máscara de configuración se define un filtraje de los archivos requeridos para cada
SISCOPROMM en un valor analógico de 32 bits interpretado en los 8 campos de un carácter (4 bits) como sigue:
82 de 166
LSB Bit 0
Bit 1 Número de alimentadores en línea 5.
Bit 2
Bit 3
Bit 4
Bit 5 Número de alimentadores en línea 4.
Bit 6
Bit 7
Bit 8
Valores en los diferentes campos
Esta es una descripción compacta de la subestación y ayuda a identificar los archivos tanto analógicos como digitales a generarse
y actualizarse en el SISCOPROMM.
El valor analógico resultante se guarda en las variables analógicas de la línea 1 adom1aadom1badom1c, ya que siempre existirá al
menos una línea.
Los valores de cada variable adomxa, adomxb, adomxc, donde la x puede ir de 1 a 4 son F0F0F0F0, valor en hexadecimal, con
excepción del archivo de la línea 1 que lleva la descripción compata de la subestación.
Los SISCOPROMM tendrán tarea dedicada a la actualización (re-escribirse en sí mismos) la cual será cada 15 minutos.
83 de 166
El valor que se actualizará en los archivos viene de las tablas *circulares de minutos de cada SISCOPROMM con el donde se
tomarán en cuenta los 15 puntos más recientes de cada una tabla circular con los siguientes algoritmos:
*(para versiones que no tienen tablas circulares se define una tarea similar que actualice valores cada 15 minutos).
Para todas las tablas circulares digitales se dará la condición “OR”. Esto servirá de bandera para indicar cambio de estado en un
intervalo.
El documento base para el formato de archivos es el indicado en la referencia [5] del capítulo 12 de esta especificación.
La información en los archivos con extensiones (XXXXXXXX.HDR, CFG, INF casi no cambian, se actualizan cuando haya cambios.
En lo referente a los archivos de datos que se caracterizan por la extensión .DAT se definen las características en este documento.
a) Binarias a 32 “bits” en complemento a 2. Su expresión es en exadecimal a cuatro bytes expresándose primero el “byte”
menos significativos y así sucesivamente, por ejemplo el número “12345678” se almacena como “78563412”,
b) Las características no especificadas se toman de la referencia [5] del capítulo 12 de esta especificación, por ejemplo al
ser binarias no existe separadores entre señales.
84 de 166
g) El valor crítico para cumplir con la clase es el valor mínimo por ejemplo para kWatts:
para cumplir con clase de 0,1 % se debe representar 277 kW con 277 000 cuentas.
h) En base a las cuentas para el valor mínimo se define cual es, el valor de cuentas para el valor máximo. Es necesario
verificar que no se salga de intervalo.
b) Los estados están en máscaras y el complemento de esta información se encuentra en otra máscara.
c) Se tiene una máscara de configuración el estado de cada elemento utilizado será “1”.
85 de 166
ANEXO
Estructura de Información,
Máscaras y
Formatos de Archivos
86 de 166
Estructura de información
L í n e a s
Asignación Descripción
l 11,j,k k VAr
l 12,j,k k Wd
l 13,j,k k VArd
l 14,j,k k Wh
l 15,j,k k VArh
l 16,j,k Frecuencia (f)
2
l 17,j,k I t Interruptor línea
l 18,j,k N total de operaciones interruptor línea
l 19,j,k Ángulo = f (kVAr/kW)
l 20,j,k 87 L
l 21,j,k 67 F, N
l 22,j,k 50 FI
Protección
l 23,j,k 79
l 24,j,k 25*
l 25,j,k 27*
l 26,j,k 21 F, N
l 27,j,k 79 Interruptor amarre línea
l 28,j,k 25 Sincronía Interruptor amarre
l 29,j,k
87 de 166
L í n e a s
adom1aadom1badom1c
IaIbIc
VaVbVc
AnguloaAngulobAnguloc
kWakWbkWc
adom2aadom2badom2c
kVarakVarbkVarc
kWdakWdbkWdc
kWhakWhbkWhc
kVardakVardbkVardc
adom3aadom3badom3c
kWhakWhbkWhc
kVarhakVarhbkVarhc
i2tai2tbi2tc
NoperaNoperbNoperc
adom4aadom4badom4c
Como los archivos están en binario se envían los cuatro “bytes” de cada variable, a continuación se manda la siguiente señal sin
utilizar signos de separación ni “CR/LF”.
88 de 166
Estados lógicos
L í n e a s
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 87 L
Bit 21,j,k 67 F, N
Bit 22,j,k 50 FI
Bit 23,j,k 79
Bit 24,j,k 25*
Bit 25,j,k 27*
Bit 26,j,k 21 F, N
Bit 27,j,k 79 Interruptor amarre línea
Bit 28,j,k 25 Sincronía interruptor amarre
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
89 de 166
L í n e a s
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 87 L
Bit 21,j,k 67 F, N
Bit 22,j,k 50 FI
Bit 23,j,k 79
Bit 24,j,k 25*
Bit 25,j,k 27*
Bit 26,j,k 21 F, N
Bit 27,j,k 79 Interruptor amarre línea
Bit 28,j,k 25 Sincronía interruptor amarre
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
90 de 166
L í n e a s
Bit 10,j,k
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 87 L
Bit 21,j,k 67 F, N
Bit 22,j,k 50 FI
Bit 23,j,k 79
Bit 24,j,k 25*
Bit 25,j,k 27*
Bit 26,j,k 21 F, N
Bit 27,j,k 79 Interruptor amarre línea
Bit 28,j,k 25 Sincronía interruptor amarre
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
91 de 166
Decodificación funciones
L í n e a s
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 87 L
Bit 21,j,k 67 F, N
Bit 22,j,k 50 FI
Bit 23,j,k 79
Bit 24,j,k 25*
Bit 25,j,k 27*
Bit 26,j,k 21 F, N
Bit 27,j,k 79 Interruptor amarre línea
Bit 28,j,k 25 Sincronía interruptor amarre
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
92 de 166
L í n e a s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k
Bit 21,j,k
Bit 22,j,k
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
93 de 166
L í n e a s
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k
Bit 21,j,k
Bit 22,j,k
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
94 de 166
Estructura de información
Barra de alta
Asignación Descripción
Ba 23,j,k
Ba 24,j,k
Ba 25,j,k
Ba 26,j,k
Ba 27,j,k
Ba 28,j,k
Ba 29,j,k
95 de 166
Barra de alta
adom1aadom1badom1c
IaIbIc
VaVbVc
AnguloaAngulobAnguloc
kWakWbkWc
adom2aadom2badom2c
kVarakVarbkVarc
kWdakWdbkWdc
kWhakWhbkWhc
kVardakVardbkVardc
adom3aadom3badom3c
kWhakWhbkWhc
kVarhakVarhbkVarhc
i2tai2tbi2tc
NoperaNoperbNoperc
adom4aadom4badom4c
Como los archivos están en binario se envían los cuatro “bytes” de cada variable, a continuación se manda la siguiente señal sin
utilizar signos de separación ni “CR/LF”.
96 de 166
Estados lógicos
Barra en alta
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 87 B
Bit 21,j,k
Bit 22,j,k
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k Paquete alarmas (32 “bits”)
MSB Bit 31,j,k Máscara eventos (32 “bits”)
97 de 166
Barra en alta
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 87 B
Bit 21,j,k
Bit 22,j,k
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k Paquete alarmas (32 “bits”)
MSB Bit 31,j,k Máscara eventos (32 “bits”)
98 de 166
Barra en alta
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 87 B
Bit 21,j,k
Bit 22,j,k
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k Paquete alarmas (32 “bits”)
MSB Bit 31,j,k Máscara eventos (32 “bits”)
99 de 166
Decodificación funciones
Barra en alta
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 87 B
Bit 21,j,k
Bit 22,j,k
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k Paquete alarmas (32 “bits”)
MSB Bit 31,j,k Máscara eventos (32 “bits”)
100 de 166
Barra en alta
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k
Bit 21,j,k
Bit 22,j,k
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
101 de 166
Barra en alta
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k
Bit 21,j,k
Bit 22,j,k
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
102 de 166
Estructura de información
ta 8,j,k
ta 9,j,k Ángulo = f (k Var / k W)
ta 10,j,k kW
Señales Calculadas
ta 11,j,k k VAR
ta 12,j,k k Wd
ta 13,j,k k VArd
ta 14,j,k k Wh
ta 15,j,k k VArh
ta 16,j,k N número total de operaciones interrup. al transf.
ta 17,j,k I2t Interruptor transformador de alta
ta 18,j,k A Corriente por fase en capacitores
ta 19,j,k V Tensión residual
ta 20,j,k 87 T
BANCO CAPACITORESFI
ta 22,j,k 50
tata21,j,k 50 / 51
protección
26,j,k
27
tata 28,j,k 81
23,j,k 50 / 51
ta 24,j,k 59
ta 25,j,k 64 N
ta 27,j,k 50 FI
ta 29,j,k 86
103 de 166
adom1aadom1badom1c
IaIbIc
VaVbVc
AnguloaAngulobAnguloc
kWakWbkWc
adom2aadom2badom2c
kVarakVarbkVarc
kWdakWdbkWdc
kWhakWhbkWhc
kVardakVardbkVardc
adom3aadom3badom3c
kWhakWhbkWhc
kVarhakVarhbkVarhc
i2tai2tbi2tc
NoperaNoperbNoperc
adom4aadom4badom4c
Como los archivos están en binario se envían los cuatro “bytes” de cada variable, a continuación se manda la siguiente señal sin
utilizar signos de separación ni “CR/LF”.
104 de 166
Estados lógicos
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 87 T
Bit 21,j,k 27
Bit 22,j,k 50 FI
Bit 23,j,k 50 / 51
Bit 24,j,k 59
Bit 25,j,k 64 N
Bit 26,j,k 50 / 51
Bit 27,j,k 50 FI
Bit 28,j,k 81
Bit 29,j,k 86
Bit 30,j,k
MSB Bit 31,j,k
105 de 166
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 87 T
Bit 21,j,k 27
Bit 22,j,k 50 FI
Bit 23,j,k 50 / 51
Bit 24,j,k 59
Bit 25,j,k 64 N
Bit 26,j,k 50 / 51
Bit 27,j,k 50 FI
Bit 28,j,k 81
Bit 29,j,k 86
Bit 30,j,k
MSB Bit 31,j,k
106 de 166
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 87 T
Bit 21,j,k 27
Bit 22,j,k 50 FI
Bit 23,j,k 50 / 51
Bit 24,j,k 59
Bit 25,j,k 64 N
Bit 26,j,k 50 / 51
Bit 27,j,k 50 FI
Bit 28,j,k 81
Bit 29,j,k 86
Bit 30,j,k
MSB Bit 31,j,k
107 de 166
Decodificación funciones
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 87 T
Bit 21,j,k 27
Bit 22,j,k 50 FI
Bit 23,j,k 50 / 51
Bit 24,j,k 59
Bit 25,j,k 64 N
Bit 26,j,k 50 / 51
Bit 27,j,k 50 FI
Bit 28,j,k 81
Bit 29,j,k 86
Bit 30,j,k
MSB Bit 31,j,k
108 de 166
Al armas de transformador
109 de 166
110 de 166
Estructura de información
tb 8,j,k
tb 9,j,k Ángulo = f (k VAr/kW)
tb 10,j,k kW
Señales Calculadas
tb 11,j,k k VAr
tb 12,j,k k Wd
tb 13,j,k k VArd
tb 14,j,k k Wh
tb 15,j,k k VArh
tb 16,j,k N número total de operaciones interrup.transf.baja
tb 17,j,k I2t Interruptor transformador lado baja
tb 18,j,k
tb 19,j,k Tensión residual por fase
tb 20,j,k 50 / 51
tb 21,j,k 51 NT
tb 22,j,k 59 N
protección
tb 23,j,k 81
tb 24,j,k
tb 25,j,k
tb 26,j,k
tb 27,j,k
tb 28,j,k
tb 29,j,k
111 de 166
adom1aadom1badom1c
IaIbIc
VaVbVc
AnguloaAngulobAnguloc
kWakWbkWc
adom2aadom2badom2c
kVarakVarbkVarc
kWdakWdbkWdc
kWhakWhbkWhc
kVardakVardbkVardc
adom3aadom3badom3c
kWhakWhbkWhc
kVarhakVarhbkVarhc
i2tai2tbi2tc
NoperaNoperbNoperc
adom4aadom4badom4c
Como los archivos están en binario se envían los cuatro “bytes” de cada variable, a continuación se manda la siguiente señal sin
utilizar signos de separación ni “CR/L”
112 de 166
Estados lógicos
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 50 / 51
Bit 21,j,k 51 NT
Bit 22,j,k 59 N
Bit 23,j,k 81
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
113 de 166
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 50 / 51
Bit 21,j,k 51 NT
Bit 22,j,k 59 N
Bit 23,j,k 81
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
114 de 166
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 50 / 51
Bit 21,j,k 51 NT
Bit 22,j,k 59 N
Bit 23,j,k 81
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
115 de 166
Decodificación funciones
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 50 / 51
Bit 21,j,k 51 NT
Bit 22,j,k 59 N
Bit 23,j,k 81
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
116 de 166
Al armas generales
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k
Bit 21,j,k
Bit 22,j,k
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
117 de 166
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k
Bit 21,j,k
Bit 22,j,k
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
118 de 166
Estructura de información
bb 20,j,
bb 21,j,k
bb 22,j,k
protección
bb 23,j,k
bb 24,j,k 27
bb 25,j,k 50 / 51
bb 26,j,k 59 Banco de capacitores
bb 27,j,k 64 N
bb 28,j,k 50 F1
bb 29,j,k
119 de 166
adom1aadom1badom1c
IaIbIc
VaVbVc
AnguloaAngulobAnguloc
kWakWbkWc
adom2aadom2badom2c
kVarakVarbkVarc
kWdakWdbkWdc
kWhakWhbkWhc
kVardakVardbkVardc
adom3aadom3badom3c
kWhakWhbkWhc
kVarhakVarhbkVarhc
i2tai2tbi2tc
NoperaNoperbNoperc
adom4aadom4badom4c
Como los archivos están en binario se envían los cuatro “bytes” de cada variable, a continuación se manda la siguiente señal sin
utilizar signos de separación ni “CR/LF”.
120 de 166
Estados lógicos
121 de 166
122 de 166
123 de 166
Decodificación funciones
124 de 166
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k
Bit 21,j,k
Bit 22,j,k
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
125 de 166
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k
Bit 21,j,k
Bit 22,j,k
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
126 de 166
Estructura de información
bt 1,j,k TC Alimentador 1
Señales Primarias
bt 2,j,k ..............
bt 3,j,k ..............
bt 4,j,k Cuchillas de transferencia del alimentador 1
bt 5,j,k
bt 6,j,k
bt 7,j,k
Medición
bt 8,j,k
bt 9,j,k
bt 10,j,k kW
Señales Calculadas
bt 11,j,k k VAr
bt 12,j,k k Wd
bt 13,j,k k VArd
bt 14,j,k k Wh
bt 15,j,k k VArh
bt 16,j,k N Número operaciones interruptor alimentador
bt 17,j,k I2t Interruptor alimentador
bt 18,j,k
bt 19,j,k Ángulo = f (kVAr/kW)
bt 20,j,k 50 / 51
bt 21,j,k 79
bt 22,j,k 81
Protección
bt 23,j,k
bt 24,j,k
bt 25,j,k
bt 26,j,k
bt 27,j,k
bt 28,j,k
bt 29,j,k
eventos
127 de 166
adom1aadom1badom1c
IaIbIc
VaVbVc
AnguloaAngulobAnguloc
kWakWbkWc
adom2aadom2badom2c
kVarakVarbkVarc
kWdakWdbkWdc
kWhakWhbkWhc
kVardakVardbkVardc
adom3aadom3badom3c
kWhakWhbkWhc
kVarhakVarhbkVarhc
i2tai2tbi2tc
NoperaNoperbNoperc
adom4aadom4badom4c
Como los archivos están en binario se envían los cuatro “bytes” de cada variable, a continuación se manda la siguiente señal sin
utilizar signos de separación ni “CR/LF”.
128 de 166
Estados lógicos
Bit 10,j,k
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 50 / 51
Bit 21,j,k 79
Bit 22,j,k 81
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
129 de 166
Bit 10,j,k
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 50 / 51
Bit 21,j,k 79
Bit 22,j,k 81
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
130 de 166
Bit 10,j,k
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 50 / 51
Bit 21,j,k 79
Bit 22,j,k 81
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
131 de 166
Decodificación funciones
Bit 10,j,k
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 50 / 51
Bit 21,j,k 79
Bit 22,j,k 81
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
132 de 166
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k
Bit 21,j,k
Bit 22,j,k
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
133 de 166
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k
Bit 21,j,k
Bit 22,j,k
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
134 de 166
Estructura de información
bt 42,j,k ..............
bt 43,j,k ..............
bt 44,j,k Cuchillas de transferencia del alimentador 2
bt 45,j,k
bt 46,j,k
bt 47,j,k
Medición
bt 48,j,k
bt 49,j,k
bt 50,j,k kW
Señales Calculadas
bt 51,j,k k VAr
bt 52,j,k k Wd
bt 53,j,k k VArd
bt 54,j,k k Wh
bt 55,j,k k VArh
bt 56,j,k N Número operaciones interruptor alimentador
2
bt 57,j,k I t Interruptor alimentador
bt 58,j,k
bt 59,j,k Ángulo = f (kVAr/kW)
bt 60,j,k 50 / 51
bt 61,j,k 79
bt 62,j,k 81
Protección
bt 63,j,k
bt 64,j,k
bt 65,j,k
bt 66,j,k
bt 67,j,k
bt 68,j,k
bt 69,j,k
bt 70,j,k Paquete alarmas (32 "bits")
bt 71,j,k Máscara eventos (32 "bits")
Alarmas
eventos
135 de 166
adom1aadom1badom1c
IaIbIc
VaVbVc
AnguloaAngulobAnguloc
kWakWbkWc
adom2aadom2badom2c
kVarakVarbkVarc
kWdakWdbkWdc
kWhakWhbkWhc
kVardakVardbkVardc
adom3aadom3badom3c
kWhakWhbkWhc
kVarhakVarhbkVarhc
i2tai2tbi2tc
NoperaNoperbNoperc
adom4aadom4badom4c
Como los archivos están en binario se envían los cuatro “bytes” de cada variable, a continuación se manda la siguiente señal sin
utilizar signos de separación ni “CR/LF”.
136 de 166
Estados lógicos
Bit 10,j,k
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 50 / 51
Bit 21,j,k 79
Bit 22,j,k 81
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
137 de 166
Bit 10,j,k
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 50 / 51
Bit 21,j,k 79
Bit 22,j,k 81
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
138 de 166
Bit 10,j,k
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 50 / 51
Bit 21,j,k 79
Bit 22,j,k 81
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
139 de 166
Decodificación funciones
Bit 10,j,k
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 50 / 51
Bit 21,j,k 79
Bit 22,j,k 81
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
140 de 166
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k
Bit 21,j,k
Bit 22,j,k
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
141 de 166
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k
Bit 21,j,k
Bit 22,j,k
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
142 de 166
Estructura de información
bt 81,j,k TC Alimentador 3
Señales Primarias
bt 82,j,k ..............
bt 83,j,k ..............
bt 84,j,k Cuchillas de transferencia del alimentador 3
bt 85,j,k
bt 86,j,k
bt 87,j,k
Medición
bt 88,j,k
bt 89,j,k
bt 90,j,k kW
Señales Calculadas
bt 91,j,k k VAr
bt 92,j,k k Wd
bt 93,j,k k VArd
bt 94,j,k k Wh
bt 95,j,k k VArh
bt 96,j,k N Total operaciones interruptor alimentador
2
bt 97,j,k I t Interruptor alimentador
bt 98,j,k
bt 99,j,k Ángulo = f (kVAr/kW)
bt 100,j,k 50 / 51
bt 101,j,k 79
bt 102,j,k 81
Protección
bt103,j,k
bt 104,j,k
bt 105,j,k
bt 106,j,k
bt 107,j,k
bt 108,j,k
bt 109,j,k
bt 110,j,k Paquete alarmas (32 "bits")
bt 111,j,k Máscara eventos (32 "bits")
Alarmas
eventos
143 de 166
adom1aadom1badom1c
IaIbIc
VaVbVc
AnguloaAngulobAnguloc
kWakWbkWc
adom2aadom2badom2c
kVarakVarbkVarc
kWdakWdbkWdc
kWhakWhbkWhc
kVardakVardbkVardc
adom3aadom3badom3c
kWhakWhbkWhc
kVarhakVarhbkVarhc
i2tai2tbi2tc
NoperaNoperbNoperc
adom4aadom4badom4c
Como los archivos están en binario se envían los cuatro “bytes” de cada variable, a continuación se manda la siguiente señal sin
utilizar signos de separación ni “CR/LF”.
144 de 166
Estados lógicos
Bit 10,j,k
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 50 / 51
Bit 21,j,k 79
Bit 22,j,k 81
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
145 de 166
Bit 10,j,k
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 50 / 51
Bit 21,j,k 79
Bit 22,j,k 81
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
146 de 166
Bit 10,j,k
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 50 / 51
Bit 21,j,k 79
Bit 22,j,k 81
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
147 de 166
Decodificación funciones
Bit 10,j,k
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 50 / 51
Bit 21,j,k 79
Bit 22,j,k 81
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
148 de 166
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k
Bit 21,j,k
Bit 22,j,k
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
149 de 166
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k
Bit 21,j,k
Bit 22,j,k
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
150 de 166
Estructura de información
bt 121,j,k TC Alimentador 4
Señales Primarias
bt 122,j,k ..............
bt 123,j,k ..............
bt 124,j,k Cuchillas de transferencia del alimentador 4
bt 125,j,k
bt 126,j,k
bt 127,j,k
Medición
bt 128,j,k
bt 129,j,k
bt 130,j,k kW
Señales Calculadas
bt 131,j,k k VAr
bt 132,j,k k Wd
bt 133,j,k k VArd
bt 134,j,k k Wh
bt 135,j,k k VArh
bt 136,j,k No Total operaciones interruptor alimentador
bt 137,j,k I2t Interruptor alimentador
bt 138,j,k
bt 139,j,k Ángulo = f (kVAr/kW)
bt 140,j,k 50 / 51
bt 141,j,k 79
bt 142,j,k 81
Protección
bt 143,j,k
bt 144,j,k
bt 145,j,k
bt 146,j,k
bt 147,j,k
bt 148,j,k
bt 149,j,k
eventos
151 de 166
adom1aadom1badom1c
IaIbIc
VaVbVc
AnguloaAngulobAnguloc
kWakWbkWc
adom2aadom2badom2c
kVarakVarbkVarc
kWdakWdbkWdc
kWhakWhbkWhc
kVardakVardbkVardc
adom3aadom3badom3c
kWhakWhbkWhc
kVarhakVarhbkVarhc
i2tai2tbi2tc
NoperaNoperbNoperc
adom4aadom4badom4c
Como los archivos están en binario se envían los cuatro “bytes” de cada variable, a continuación se manda la siguiente señal sin
utilizar signos de separación ni “CR/LF”.
152 de 166
Estados lógicos
Bit 10,j,k
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 50 / 51
Bit 21,j,k 79
Bit 22,j,k 81
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
153 de 166
Bit 10,j,k
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 50 / 51
Bit 21,j,k 79
Bit 22,j,k 81
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
154 de 166
Bit 10,j,k
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 50 / 51
Bit 21,j,k 79
Bit 22,j,k 81
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
155 de 166
Decodificación funciones
Bit 10,j,k
Bit 11,j,k
Bit 12,j,k
Bit 13,j,k
Bit 14,j,k
Bit 15,j,k
Bit 16,j,k
Bit 17,j,k
V a l o r e s
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k 50 / 51
Bit 21,j,k 79
Bit 22,j,k 81
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
156 de 166
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k
Bit 21,j,k
Bit 22,j,k
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
157 de 166
Bit 18,j,k
Bit 19,j,k
Bit 20,j,k
Bit 21,j,k
Bit 22,j,k
Bit 23,j,k
Bit 24,j,k
Bit 25,j,k
Bit 26,j,k
Bit 27,j,k
Bit 28,j,k
Bit 29,j,k
Bit 30,j,k
MSB Bit 31,j,k
158 de 166
APÉNDICE F
CAPACITACIÓN
- se debe garantizar que al termino del mismo los participantes estén capacitados para operar y mantener los sistemas
SISCOPROMM ofrecidos.
159 de 166
160 de 166
161 de 166
APÉNDICE G
Los trabajos de la “puesta a punto” y “puesta en servicio”, deben cotizarse conforme se indique en las bases de la licitación.
Se debe indicar programa, equipo de prueba, especialidad y experiencia del personal que intervendrá en la puesta a punto y cotizar
por separado.
En las etapas de puesta a punto y puesta en servicio, los representantes en la obra por parte del proveedor y CFE deben llevar una
bitácora de obra, en la cual se deben asentar los trabajos realizados y cualquier acuerdo que autorice la Gerencia de Distribución
de CFE que no esté contemplado en estas especificaciones.
La bitácora de obra es la referencia para juzgar cualquier atraso en los trabajos indicados por el proveedor, en el programa de
puesta a punto y puesta en servicio que previamente ha sido aprobado por CFE.
La puesta a punto del sistema son todas aquellas actividades para montar, cablear, ajustar y probar, para dejar en condiciones
operativas comerciales el SISCOPROMM con la UCM correspondiente, considerando todos los protocolos de comunicaciones
solicitados. Esto incluye: Montaje, alambrado, ajustes y pruebas de aceptación en campo. En esta etapa el proveedor debe tener
un supervisor quien será responsable de éstos trabajos. En estos trabajos, el proveedor debe de proporcionar la mano de obra y
material misceláneo requerido para la conexión de los tableros con los equipos.
Es responsabilidad del proveedor, el obtener de los fabricantes correspondientes, la información de los protocolos propietarios y
respectivas las licencias. Para el caso de protocolos abiertos, debe contactar al fabricante de la UTM, para obtener la información
que requiera.
Durante esta etapa, CFE dispondrá como mínimo de un residente quien la representará en estos trabajos. Asimismo del personal
que CFE considere necesario para la capacitación respectiva.
Las pruebas de aceptación en campo del sistema forman parte de este concepto.
La puesta en servicio del sistema, es aquella etapa en donde el personal operativo de CFE efectúa conjuntamente con el
proveedor, las pruebas definitivas necesarias para garantizar la confiabilidad operativa del sistema y así proceder a su puesta en
operación. La puesta en servicio se considerará concluida con la entrada en operación del sistema.
162 de 166
APÉNDICE H
División: _______________________________________________________________________
Subestación:____________________________________________________________________
a) Datos generales.
Ubicación: ____________________________________________________________
Líneas de subtransmisión (Se debe llenar para cada una de las líneas):
163 de 166
TRANSFORMADOR DE POTENCIA
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
_________________________________________________________________________
164 de 166
Puertos SCADA (Utilizar esta configuración para cada puerto SCADA seleccionado)
Aplicación:____________________
Protocolo: ____________________
Estandares___________________
165 de 166
Puerto para UTRp (Utilizar esta configuración para cada puerto UTRp seleccionado)
Protocolo: ____________________
Modem______________________ Radiomodem____________________________
Estandares___________________
Puerto “ethernet” (Utilizar esta configuración para cada puerto “ethernet” seleccionado)
IP:___________
f) Simulador.
g) Equipo de comunicación.
_________________________________________________________________________
166 de 166
Antena ___________________________________________________________________
Cable ____________________________________________________________________
Alimentación ______________________________________________________________
_________________________________________________________________________
Antena ___________________________________________________________________
Cable ____________________________________________________________________
Alimentación ______________________________________________________________
h) Otros requerimientos: