Relés Inteligentes - Eaton C441

Application Configuration Ground Fault

Alimentador kW CT Multiplier ** Motor FLA ** Trip Class** Trip Level Delay

Rango de Ajuste Ajuste Rango de Ajuste Ajuste Rango de Ajuste Ajuste Rango de Ajuste Ajuste Rango de Ajuste Ajuste

H-4136
(0.3...2.0 A)
Sistema de Calibración Correa 0.75 kW (1...600) 2 - 1.71 A (NEMA 5…30) 20 0.4 A (1…60s) 1s
(3...20 A)
Transportadora de Producto

P-4151-A (0.3...2.0 A)
5.50 kW (1…4) 2 - 11.10 A (NEMA 5…30) 20 2.3 A (1…60s) 1s
Bomba Agua de Procesos (3...20 A)

P-4151-B (0.3...2.0 A)
5.50 kW (1…4) 2 - 11.10 A (NEMA 5…30) 20 2.3 A (1…60s) 1s
Bomba Agua de Procesos (3...20 A)

P-4151-C (0.3...2.0 A)
5.50 kW (1…4) 2 - 11.10 A (NEMA 5…30) 20 2.3 A (1…60s) 1s
Bomba Agua de Procesos (3...20 A)

F-4101-M1 (0.3...2.0 A)
5.50 kW (1…4) 2 - 11.10 A (NEMA 5…30) 20 2.3 A (1…60s) 1s
Separador Magnético (3...20 A)

H-4137-M2
(0.3...2.0 A)
Sistema de Calibración Alimentador 0.75 kW (1…600) 2 - 1.71 A (NEMA 5…30) 20 0.4 A (1…60s) 1s
(3...20 A)
Pesometrico

N-4101-M1
(0.3...2.0 A)
Agitador Estanque Preparación 2.20 kW (1…4) 4 - 4.76 A (NEMA 5…30) 10 1.0 A (1…60s) 1s
(3...20 A)
Criscell

N-4142-M1
(0.3...2.0 A)
Agitador Estanque Preparación 2.20 kW (1…4) 4 - 4.76 A (NEMA 5…30) 10 1.0 A (1…60s) 1s
(3...20 A)
Crisamine

P-4140 (0.3...2.0 A)
7.50 kW (1…4) 2 - 15.18 A (NEMA 5…30) 20 3.1 A (1…60s) 1s
Bomba Preparación Criscell (3...20 A)

P-4142 (0.3...2.0 A)
7.50 kW (1…4) 2 - 15.18 A (NEMA 5…30) 20 3.1 A (1…60s) 1s
Bomba Preparación Crisamine (3...20 A)

H-4138-M1 (0.3...2.0 A)
11.00 kW (1…4) 1 - 21.56 A (NEMA 5…30) 20 4.4 A (1…60s) 1s
Correa Transportadora Silvinita (3...20 A)

H-4131-M1
(0.3...2.0 A)
Segunda Correa Transportadora 18.60 kW (1…4) 1 - 36.00 A (NEMA 5…30) 20 7.2 A (1…60s) 1s
(3...20 A)
Silvinita

Configuraciones generales de protección

Current Unbalance Current Phase Loss Low Power

Trip Level Delay Trip Level Delay Trip Level

(1...30% FLA) (0.3...6.0 kW)/Off


20% (1…20s) 3s Fijo - (1…20s) 3s Off
Off (3.30...59.9 kW)

Motor Jam Under Current High Power

- - Trip Level Delay Trip Level Delay Trip Level

(10 ... 90% FLA) (0.8...8.3 kW)


(150...400% FLA) 200% (1…20s) 2s 15% (1…60s) 3s Off
Off (8.3...82.3 kW)

Voltage Unbalance Power-up Restart Delay Phase Rotation **

Trip Level Delay Delay Trip Level Delay

(1...20%) 5% (1…60s) 3s (0…500s) Off 1, 2 and Off 2.0 NA -

**Este ajuste debe ser confirmado en campo con los datos de placa del motor.