Está en la página 1de 49

HOSPITAL NAVAL DOS BOCAS

RESUMEN DE CARGAS TÉRMICAS


PLANTA BAJA EDIFICIO A

Nivel Zona Cant. Area M2 Cant. Personas Temperatura TR Cálculo


Interior Diseño ºC

EDIFICIO A
APLICACIÓN DE VACUNAS Y TAMIZ AUDITIVO 1 13.97 3.00 22.80 0.39
ARCHIVO CLINICO 1 30.94 3.00 22.80 1.38
AREA Y PROCEDIMIENTOS GINECOLOGIA 1 25.23 2.00 22.80 0.65
DEPARTAMENTO CONSULTA EXTERNA 1 11.12 3.00 22.80 0.49
DESPACHO MEDICAMENTOS AL PUBLICO 1 73.92 3.00 22.80 1.35
ENTREGA EXPEDIENTES 1 23.94 2.00 22.80 0.57
ENTREVISTA TRAUMA Y ORTOPEDIA 1 14.62 3.00 22.80 0.32
ENTREVISTAS GINECOLOGIA Y COLPOSCOPIA 1 14.87 3.00 22.80 0.40
ENTREVISTAS OFTAMOLOGIA 1 12.48 3.00 22.80 0.29
ENTREVISTAS OTORRINO 1 13.04 3.00 22.80 0.30
EXPLORACION MED PREVENTIVA 1 8.72 2.00 22.80 0.25
EXPLORACION OTORRINO 1 26.56 3.00 22.80 0.80
EXPLORACION TRAUMA Y ORTOPEDIA 1 12.52 2.00 22.80 0.24
IDF 1 13.58 3.00 22.80 0.40
LACTARIO 1 16.82 4.00 22.80 0.34
MED PREVENTIVA 1 10.90 3.00 22.80 0.28
OFICINA RESPONSABLE FARMACIAS 1 11.36 3.00 22.80 0.28
OFTALMOLOGIA 1 24.53 4.00 22.80 0.81
PASILLO CONSULTA EXTERNA 1 13.19 2.00 22.80 0.33
PASILLO TECNICO 1 1 32.66 6 22.80 2.48
PASILLO TECNICO 2 1 42.22 8.00 22.80 1.89
RECEPCION DEPTO CONSULTA EXTERNA 1 11.15 4.00 22.80 0.31
SALA DE ESPERA CONSULTA EXTERNA 1 235.10 72.00 22.80 4.11
TRATAMIENTO TRAUMA Y ORTOPEDIA 1 14.42 2.00 22.80 0.52
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Aplicación de Vacunas y Tamiz Auditivo
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
- Subtotal Btu/Hr : 0.00
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
4.05 2.8 2 11.34 13.284 9.184 122.00 84 0.294 789.10
3.45 2.8 2 9.66 11.316 9.184 103.926144 84 0.294 672.19
- Subtotal Btu/Hr : 1,461.29
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
4.05 3.45 13.9725 13.284 11.316 150.321744 13.97
- Subtotal Sqt M: 13.97
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Sedentary Work 3 280 270 840 810 1650
Electric -
watts/m2 20.00
m2 13.97
Total Watts 279.45
btu/hr 952.92
-
-
-
-
-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Aplicación de Vacunas y Tamiz Auditivo
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 4,064.22
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 609.63
- Total Btu/hr : 4,673.85
- Refrigerant Tons : 0.39
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Archivo Clinico
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
3.28 2.8 S 9.184 10.7584 9.184 98.8051456 16 -6 0.294 28.6 830.79
4.42 2.8 E 12.376 14.4976 9.184 133.1459584 24 0 0.294 42.6 1,667.57
- Subtotal Btu/Hr : 2,498.37
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
1.58 1.2 E 1 1.896 5.1824 3.936 20.3979264 203 0.95 3,933.74
1.8 1.2 S 1 2.16 5.904 3.936 23.238144 65 0.95 1,434.96
- Subtotal Btu/Hr : 5,368.70
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
1.58 1.2 E 1 1.896 5.1824 3.936 20.40 14 0.95 31.2 604.59
1.8 1.2 S 1 2.16 5.904 3.936 23.238144 14 0.95 31.2 688.78
- Subtotal Btu/Hr : 1,293.37
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
3.88 2.8 1 10.864 12.7264 9.184 116.88 84 0.294 377.99
7 2.8 1 19.6 22.96 9.184 210.86464 84 0.294 681.94
4.42 2.8 1 12.376 14.4976 9.184 133.1459584 84 0.294 430.59
- Subtotal Btu/Hr : 1,490.52
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
7 4.42 30.94 22.96 14.4976 332.864896 30.94
- Subtotal Sqt M: 30.94
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Sedentary Work 3 280 270 840 810 1650
Electric -
watts/m2 20.00
m2 30.94
Total Watts 618.80
btu/hr 2110.11
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Archivo Clinico
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
-
-
-
-
-
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 14,411.06
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 2,161.66
- Total Btu/hr : 16,572.72
- Refrigerant Tons : 1.38
DIMENSIONES
Customer : HOSPITAL NAVAL DOS BOCAS, TABASCO Date: 03/02/2023
item : Balance térmico
Area: PB - ÁREA DE PROCEDIMIENTOS
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
- Subtotal Btu/Hr : 0.00
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
3.45 2.8 1 9.66 11.316 9.184 103.93 84 0.294 336.10
5.2 2.8 1 14.56 17.056 9.184 156.642304 84 0.294 506.58
1.99 2.8 1 5.572 6.5272 9.184 59.9458048 84 0.294 193.86
2.08 2.8 1 5.824 6.8224 9.184 62.6569216 84 0.294 202.63
1.5 28 1 42 4.92 91.84 451.8528 84 0.294 1,461.29
7.22 2.8 1 20.216 23.6816 9.184 217.4918144 84 0.294 703.37
- Subtotal Btu/Hr : 3,403.84
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
21.28 1 21.28 69.7984 3.28 228.94 84.6 0.294 5,694.26
- Subtotal Btu/Hr : 5,694.26
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
21.28 1 21.28 69.7984 3.28 228.938752 21.28
- Subtotal Sqt M: 21.28
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Sedentary Work 3 280 270 840 810 1650
Electric -
watts/m2 30.00
m2 21.28
Total Watts 638.40
btu/hr 2176.94
-
-
Customer : HOSPITAL NAVAL DOS BOCAS, TABASCO Date: 03/02/2023
item : Balance térmico
Area: PB - ÁREA DE PROCEDIMIENTOS
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
-
-
-
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 12,925.04
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 1,938.76
- Total Btu/hr : 14,863.79
- Refrigerant Tons : 1.24
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Departamento Consulta Externa
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
2.95 2.8 S 8.26 9.676 9.184 88.864384 16 -6 0.294 28.6 747.21
- Subtotal Btu/Hr : 747.21
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
1.45 1.2 S 1 1.74 4.756 3.936 18.719616 65 0.95 1,155.94
- Subtotal Btu/Hr : 1,155.94
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
1.45 1.2 S 1 1.74 4.756 3.936 18.72 14 0.95 31.2 554.85
- Subtotal Btu/Hr : 554.85
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
3.77 2.8 2 10.556 12.3656 9.184 113.57 84 0.294 734.54
2.95 2.8 1 8.26 9.676 9.184 88.864384 84 0.294 287.39
- Subtotal Btu/Hr : 1,021.93
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
3.77 2.95 11.1215 12.3656 9.676 119.6495456 11.12
- Subtotal Sqt M: 11.12
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Seated at Rest 3 230 120 690 360 1050
Electric -
watts/m2 15.00
m2 11.12
Total Watts 166.82
btu/hr 568.86
-
-
-
-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Departamento Consulta Externa
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
-
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 5,098.79
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 764.82
- Total Btu/hr : 5,863.61
- Refrigerant Tons : 0.49
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Despacho Medicamentos al Publico
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
9.6 2.8 S 26.88 31.488 9.184 289.185792 16 -6 0.294 28.6 2,431.59
- Subtotal Btu/Hr : 2,431.59
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
- Subtotal Btu/Hr : 0.00
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
7.7 2.8 2 21.56 25.256 9.184 231.95 84 0.294 1,500.26
9.6 2.8 1 26.88 31.488 9.184 289.185792 84 0.294 935.23
- Subtotal Btu/Hr : 2,435.49
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
7.7 9.6 73.92 25.256 31.488 795.260928 73.92
- Subtotal Sqt M: 73.92
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Sedentary Work 3 280 270 840 810 1650
Electric -
watts/m2 30.00
m2 73.92
Total Watts 2217.60
btu/hr 7562.02
-
-
-
-
-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Despacho Medicamentos al Publico
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 14,079.09
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 2,111.86
- Total Btu/hr : 16,190.96
- Refrigerant Tons : 1.35
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Entrega Expedientes
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
3.42 2.8 E 9.576 11.2176 9.184 103.0224384 24 0 0.294 42.6 1,290.29
- Subtotal Btu/Hr : 1,290.29
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
- Subtotal Btu/Hr : 0.00
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
3.42 2.8 1 9.576 11.2176 9.184 103.02 84 0.294 333.17
7 2.8 2 19.6 22.96 9.184 210.86464 84 0.294 1,363.87
2.63 2.8 1 7.364 8.6264 9.184 79.2248576 84 0.294 256.21
- Subtotal Btu/Hr : 1,953.26
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
7 3.42 23.94 22.96 11.2176 257.556096 23.94
- Subtotal Sqt M: 23.94
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Sedentary Work 2 280 270 560 540 1100
Electric -
watts/m2 20.00
m2 23.94
Total Watts 478.80
btu/hr 1632.71
-
-
-
-
-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Entrega Expedientes
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 5,976.26
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 896.44
- Total Btu/hr : 6,872.70
- Refrigerant Tons : 0.57
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Entrevistas Trauma y Ortopedia
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
- Subtotal Btu/Hr : 0.00
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
4.12 2.8 2 11.536 13.5136 9.184 124.11 84 0.294 802.74
3.55 2.8 2 9.94 11.644 9.184 106.938496 84 0.294 691.68
- Subtotal Btu/Hr : 1,494.41
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
4.12 3.55 14.626 13.5136 11.644 157.3523584 14.63
- Subtotal Sqt M: 14.63
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Seated at Rest 3 230 120 690 360 1050
Electric -
watts/m2 15.00
m2 14.63
Total Watts 219.39
btu/hr 748.12
-
-
-
-
-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Entrevistas Trauma y Ortopedia
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 3,292.53
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 493.88
- Total Btu/hr : 3,786.41
- Refrigerant Tons : 0.32
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Entrevistas Ginecologia y Colposcopia
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
4.11 2.8 W 11.508 13.4808 9.184 123.8076672 18 -3 0.294 33.6 1,223.02
- Subtotal Btu/Hr : 1,223.02
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
- Subtotal Btu/Hr : 0.00
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
4.11 2.8 1 11.508 13.4808 9.184 123.81 84 0.294 400.39
3.62 2.8 2 10.136 11.8736 9.184 109.0471424 84 0.294 705.32
- Subtotal Btu/Hr : 1,105.71
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
3.62 4.11 14.8782 11.8736 13.4808 160.0656269 14.88
- Subtotal Sqt M: 14.88
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Seated at Rest 3 230 120 690 360 1050
Electric -
watts/m2 15.00
m2 14.88
Total Watts 223.17
btu/hr 761.02
-
-
-
-
-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Entrevistas Ginecologia y Colposcopia
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 4,139.75
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 620.96
- Total Btu/hr : 4,760.72
- Refrigerant Tons : 0.40
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Entrevistas Oftalmologia
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
- Subtotal Btu/Hr : 0.00
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
3.62 2.8 2 10.136 11.8736 9.184 109.05 84 0.294 705.32
3.45 2.8 2 9.66 11.316 9.184 103.926144 84 0.294 672.19
- Subtotal Btu/Hr : 1,377.51
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
3.62 3.45 12.489 11.8736 11.316 134.3616576 12.49
- Subtotal Sqt M: 12.49
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Seated at Rest 3 230 120 690 360 1050
Electric -
watts/m2 15.00
m2 12.49
Total Watts 187.34
btu/hr 638.81
-
-
-
-
-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Entrevistas Oftalmologia
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 3,066.32
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 459.95
- Total Btu/hr : 3,526.27
- Refrigerant Tons : 0.29
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Entrevistas Otorrino
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
- Subtotal Btu/Hr : 0.00
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
3.77 2.8 2 10.556 12.3656 9.184 113.57 84 0.294 734.54
3.46 2.8 2 9.688 11.3488 9.184 104.2273792 84 0.294 674.14
- Subtotal Btu/Hr : 1,408.69
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
3.77 3.46 13.0442 12.3656 11.3488 140.3347213 13.04
- Subtotal Sqt M: 13.04
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Seated at Rest 3 230 120 690 360 1050
Electric -
watts/m2 15.00
m2 13.04
Total Watts 195.66
btu/hr 667.21
-
-
-
-
-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Entrevistas Otorrino
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 3,125.90
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 468.88
- Total Btu/hr : 3,594.78
- Refrigerant Tons : 0.30
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Exploracion Med. Preventiva
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
- Subtotal Btu/Hr : 0.00
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
2.53 2.8 2 7.084 8.2984 9.184 76.21 84 0.294 492.94
3.45 2.8 2 9.66 11.316 9.184 103.926144 84 0.294 672.19
- Subtotal Btu/Hr : 1,165.14
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
2.53 3.45 8.7285 8.2984 11.316 93.9046944 8.73
- Subtotal Sqt M: 8.73
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Sedentary Work 2 280 270 560 540 1100
Electric -
watts/m2 10.00
m2 8.73
Total Watts 87.29
btu/hr 297.64
-
-
-
-
-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Exploracion Med. Preventiva
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 2,562.78
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 384.42
- Total Btu/hr : 2,947.20
- Refrigerant Tons : 0.25
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Exploracion Otorrino
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
- Subtotal Btu/Hr : 0.00
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
7.7 2.8 2 21.56 25.256 9.184 231.95 84 0.294 1,500.26
3.45 2.8 2 9.66 11.316 9.184 103.926144 84 0.294 672.19
- Subtotal Btu/Hr : 2,172.45
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
7.7 3.45 26.565 25.256 11.316 285.796896 26.57
- Subtotal Sqt M: 26.57
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Sedentary Work 3 280 270 840 810 1650
Electric -
watts/m2 50.00
m2 26.57
Total Watts 1328.25
btu/hr 4529.33
-
-
-
-
-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Exploracion Otorrino
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 8,351.79
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 1,252.77
- Total Btu/hr : 9,604.55
- Refrigerant Tons : 0.80
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Exploracion Trauma y Ortopedia
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
- Subtotal Btu/Hr : 0.00
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
3.48 2.8 2 9.744 11.4144 9.184 104.83 84 0.294 678.04
3.6 2.8 2 10.08 11.808 9.184 108.444672 84 0.294 701.42
- Subtotal Btu/Hr : 1,379.46
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
3.48 3.6 12.528 11.4144 11.808 134.7812352 12.53
- Subtotal Sqt M: 12.53
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Seated at Rest 2 230 120 460 240 700
Electric -
watts/m2 10.00
m2 12.53
Total Watts 125.28
btu/hr 427.20
-
-
-
-

-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Exploracion Trauma y Ortopedia
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 2,506.66
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 376.00
- Total Btu/hr : 2,882.66
- Refrigerant Tons : 0.24
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 31/12/2022
item : Balance térmico
Area: P.Baja IDF
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
3.95 2.8 S 11.06 12.956 9.184 118.987904 16 -6 0.294 28.6 1,000.50
- Subtotal Btu/Hr : 1,000.50
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
- Subtotal Btu/Hr : 0.00
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
3.95 2.8 1 11.06 12.956 9.184 118.99 84 0.294 384.81
3.44 2.8 2 9.632 11.2832 9.184 103.6249088 84 0.294 670.25
- Subtotal Btu/Hr : 1,055.05
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
3.95 3.44 13.588 12.956 11.2832 146.1851392 13.59
- Subtotal Sqt M: 13.59
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Sedentary Work 3 280 270 840 810 1650
Electric -
watts/m2 10.00
m2 13.59
Total Watts 135.88
btu/hr 463.35
-
-
-
-
-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 31/12/2022
item : Balance térmico
Area: P.Baja IDF
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 4,168.90
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 625.34
- Total Btu/hr : 4,794.24
- Refrigerant Tons : 0.40
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Lactario
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
- Subtotal Btu/Hr : 0.00
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
4.26 2.8 2 11.928 13.9728 9.184 128.33 84 0.294 830.01
3.95 2.8 2 11.06 12.956 9.184 118.987904 84 0.294 769.61
- Subtotal Btu/Hr : 1,599.63
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
4.26 3.95 16.827 13.9728 12.956 181.0315968 16.83
- Subtotal Sqt M: 16.83
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Seated at Rest 4 230 120 920 480 1400
Electric -
watts/m2 10.00
m2 16.83
Total Watts 168.27
btu/hr 573.80
-
-
-
-
-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Lactario
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 3,573.43
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 536.01
- Total Btu/hr : 4,109.44
- Refrigerant Tons : 0.34
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Med. Preventiva
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
- Subtotal Btu/Hr : 0.00
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
3.17 2.8 2 8.876 10.3976 9.184 95.49 84 0.294 617.64
3.44 2.8 2 9.632 11.2832 9.184 103.6249088 84 0.294 670.25
- Subtotal Btu/Hr : 1,287.89
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
3.17 3.44 10.9048 10.3976 11.2832 117.3182003 10.90
- Subtotal Sqt M: 10.90
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Seated at Rest 3 230 120 690 360 1050
Electric -
watts/m2 15.00
m2 10.90
Total Watts 163.57
btu/hr 557.78
-
-
-
-
-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Med. Preventiva
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 2,895.67
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 434.35
- Total Btu/hr : 3,330.02
- Refrigerant Tons : 0.28
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Oficina Responsable Farmacia
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
- Subtotal Btu/Hr : 0.00
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
3.03 2.8 2 8.484 9.9384 9.184 91.27 84 0.294 590.36
3.75 2.8 2 10.5 12.3 9.184 112.9632 84 0.294 730.65
- Subtotal Btu/Hr : 1,321.01
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
3.03 3.75 11.3625 9.9384 12.3 122.24232 11.36
- Subtotal Sqt M: 11.36
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Seated at Rest 3 230 120 690 360 1050
Electric -
watts/m2 15.00
m2 11.36
Total Watts 170.44
btu/hr 581.19
-
-
-
-
-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Oficina Responsable Farmacia
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 2,952.20
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 442.83
- Total Btu/hr : 3,395.03
- Refrigerant Tons : 0.28
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Oftalmologia
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
- Subtotal Btu/Hr : 0.00
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
7.05 2.8 2 19.74 23.124 9.184 212.37 84 0.294 1,373.61
3.48 2.8 2 9.744 11.4144 9.184 104.8298496 84 0.294 678.04
- Subtotal Btu/Hr : 2,051.65
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
7.05 3.48 24.534 23.124 11.4144 263.9465856 24.53
- Subtotal Sqt M: 24.53
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Sedentary Work 4 280 270 1120 1080 2200
Electric -
watts/m2 50.00
m2 24.53
Total Watts 1226.70
btu/hr 4183.05
-
-
-
-
-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Oftalmologia
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 8,434.70
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 1,265.21
- Total Btu/hr : 9,699.91
- Refrigerant Tons : 0.81
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 31/12/2022
item : Balance térmico
Area: P.Baja Pasillo Consulta Externa
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
- Subtotal Btu/Hr : 0.00
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
7.9 2.8 2 22.12 25.912 9.184 237.98 84 0.294 1,539.23
1.67 2.8 2 4.676 5.4776 9.184 50.3062784 84 0.294 325.38
- Subtotal Btu/Hr : 1,864.61
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
7.9 1.67 13.193 25.912 5.4776 141.9355712 13.19
- Subtotal Sqt M: 13.19
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Sedentary Work 2 280 270 560 540 1100
Electric -
watts/m2 10.00
m2 13.19
Total Watts 131.93
btu/hr 449.88
-
-
-
-
-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 31/12/2022
item : Balance térmico
Area: P.Baja Pasillo Consulta Externa
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 3,414.49
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 512.17
- Total Btu/hr : 3,926.66
- Refrigerant Tons : 0.33
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 02/01/2023
item : Balance térmico
Area: P. Baja Pasillo Tecnico 2
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
36.4 2.8 N 101.92 119.392 9.184 1096.496128 11 1 0.294 30.6 9,864.52
1.16 2.8 W 3.248 3.8048 9.184 34.9432832 18 -3 0.294 33.6 345.18
- Subtotal Btu/Hr : 10,209.70
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
- Subtotal Btu/Hr : 0.00
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
36.4 2.8 1 101.92 119.392 9.184 1096.50 84 0.294 3,546.07
1.16 2.8 1 3.248 3.8048 9.184 34.9432832 84 0.294 113.01
- Subtotal Btu/Hr : 3,659.08
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
36.4 1.16 42.224 119.392 3.8048 454.2626816 42.22
- Subtotal Sqt M: 42.22
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Sedentary Work 8 280 270 2240 2160 4400
Electric -
watts/m2 10.00
m2 42.22
Total Watts 422.24
btu/hr 1439.84
-
-
-
-
-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 02/01/2023
item : Balance térmico
Area: P. Baja Pasillo Tecnico 2
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 19,708.61
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 2,956.29
- Total Btu/hr : 22,664.91
- Refrigerant Tons : 1.89
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 31/12/2022
item : Balance térmico
Area: P.Baja Pasillo Tecnico
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
25.13 2.8 S 70.364 82.4264 9.184 757.0040576 16 -6 0.294 28.6 6,365.19
1.3 2.8 W 3.64 4.264 9.184 39.160576 18 -3 0.294 33.6 386.84
- Subtotal Btu/Hr : 6,752.04
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
0.54 1.2 S 19 0.648 1.7712 3.936 6.9714432 65 0.95 8,179.25
- Subtotal Btu/Hr : 8,179.25
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
0.54 1.2 S 19 0.648 1.7712 3.936 6.97 14 0.95 31.2 3,926.04
- Subtotal Btu/Hr : 3,926.04
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
25.13 2.8 1 70.364 82.4264 9.184 757.00 84 0.294 2,448.15
1.3 2.8 1 3.64 4.264 9.184 39.160576 84 0.294 126.65
- Subtotal Btu/Hr : 2,574.80
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
25.13 1.3 32.669 82.4264 4.264 351.4661696 32.67
- Subtotal Sqt M: 32.67
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Sedentary Work 6 280 270 1680 1620 3300
Electric -
watts/m2 10.00
m2 32.67
Total Watts 326.69
btu/hr 1114.01
-
-
-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 31/12/2022
item : Balance térmico
Area: P.Baja Pasillo Tecnico
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
-
-
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 25,846.13
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 3,876.92
- Total Btu/hr : 29,723.05
- Refrigerant Tons : 2.48
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Recepcion Depto Consulta Externa
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
- Subtotal Btu/Hr : 0.00
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
3.78 2.8 2 10.584 12.3984 9.184 113.87 84 0.294 736.49
2.95 2.8 2 8.26 9.676 9.184 88.864384 84 0.294 574.77
- Subtotal Btu/Hr : 1,311.27
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
3.78 2.95 11.151 12.3984 9.676 119.9669184 11.15
- Subtotal Sqt M: 11.15
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Seated at Rest 4 230 120 920 480 1400
Electric -
watts/m2 15.00
m2 11.15
Total Watts 167.27
btu/hr 570.37
-
-
-
-
-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Recepcion Depto Consulta Externa
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 3,281.64
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 492.25
- Total Btu/hr : 3,773.89
- Refrigerant Tons : 0.31
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Sala de Espera Consulta Externa
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
6.45 2.8 W 18.06 21.156 9.184 194.296704 18 -3 0.294 33.6 1,919.34
- Subtotal Btu/Hr : 1,919.34
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
- Subtotal Btu/Hr : 0.00
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
6.45 2.8 1 18.06 21.156 9.184 194.30 84 0.294 628.36
36.45 2.8 2 102.06 119.556 9.184 1098.002304 84 0.294 7,101.88
- Subtotal Btu/Hr : 7,730.23
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
36.45 6.45 235.1025 119.556 21.156 2529.326736 235.10
- Subtotal Sqt M: 235.10
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Seated at Rest 72 230 120 16560 8640 25200
Electric -
watts/m2 10.00
m2 235.10
Total Watts 2351.03
btu/hr 8017.00
-
-
-
-
-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Sala de Espera Consulta Externa
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 42,866.57
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 6,429.99
- Total Btu/hr : 49,296.56
- Refrigerant Tons : 4.11
DIMENSIONES
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Tratamiento Trauma y Ortopedia
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO

Wall Length Width Direction Area Length Width Area CLTD c Latitude U value CLTDc Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Solar Length Width Direction Qty Area Length Width Area SHGF SC & CLF Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Window Conduction Length Width Direction Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 DTCE DTCEc Btu/hr
- Subtotal Btu/Hr : 0.00
Partitions Length Width Qty Area Length Width Area Schedule U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
4.12 2.8 2 11.536 13.5136 9.184 124.11 84 0.294 802.74
3.5 2.8 2 9.8 11.48 9.184 105.43232 84 0.294 681.94
- Subtotal Btu/Hr : 1,484.67
Roof Length Width Area Length Width Area CLTDc U value Total
Mts Mts M2 Ft Ft Ft2 Btu/hr
- Subtotal Btu/Hr : 0.00
Floor Length Width Area Length Width Area °F ESPACE U value Total
Mts Mts M2 Ft Ft Ft2 NOT/ACOND. Btu/hr
- Subtotal Btu/Hr : 0.00
Electric gains by area Length Width Area Length Width Area Total Sqt. M
Mts Mts M2 Ft Ft Ft2
4.12 3.5 14.42 13.5136 11.48 155.136128 14.42
- Subtotal Sqt M: 14.42
-
- Sensible Latent Total SensibleTotal Latent Total Heat
People Quantity btu/hr btu/hr btu/Hr
Medium Work 2 295 455 590 910 1500
Electric -
watts/m2 50.00
m2 14.42
Total Watts 721.00
btu/hr 2458.61
-
-
-
-
-
Customer : HOSPITAL NAVAL DE DOS BOCAS, TABASCO Date: 30/12/2022
item : Balance térmico
Area: P.Baja Tratamiento Trauma y Ortopedia
Outdoor Dry Bulb : 98.6 °F
Indoor Dry Bulb : 73 °F
DT : 25.6 °F
BALANCE TÉRMICO
Heat Gain for Gas appliances
-
- Total Sensible Total Latent Total Heat
Quantity Large Width Ft2 btu/hr btu/hr btu/Hr
Gas, No hod req.-
- Total : 0 0
-
-
-
Prepared By Ing. Hipólito Sánchez Pérez Sub-total Btu/hr : 5,443.28
- PE, RUBSA Enterprises, Inc. 15% Safety Factor : 816.49
- Total Btu/hr : 6,259.78
- Refrigerant Tons : 0.52
DIMENSIONES