ING. DAVID GONZALEZ M C.I.V: 152.808
REG. CONSULTORES SENCAMER: 20578 SCI. SISTEMA CONTRA INCENDIO

CALCULOS HIDRAULICOS DE BIE (GABINETES CON MANGUERAS)


PROYECTO: REMODELACION LOCAL COMERCIAL 4/3/2017

DIRECCION: AV ANDOLZA MANRIQUE, URB PLAYA EL ANGEL, MUNICIPIO MANEIRO. E.N.E

SISTEMA DE MANGUERAS PAG. 1/2

TIPO DE RIESGO LIGERO


TIPO DE GABINETES TIPO I D: 1. 1/2 "
LONGITUD ENTRE GABINETE(m) 30.00 CAUDAL MINIMO (q1) 380 L/min SUPERFICIE TOTAL 177 m2
TIPO DE TUBERIA ACERO COEF RUGOSIDAD RELATIVA (K) 0.02 mm 1.0 ALTURA EDIF 3 m
CANTIDAD DE GABINETES 2.0 UND CAUDAL MINIMO 0.0063 m3/seg
COEFICIENTE (C) SEGÚN TIPO CAUDAL TOTAL (QT) 760.0 L/min DESCARGA DE BOMBA 2.6 m
TUBERIA HAZEN WILLIAMS 120.00 PRESION MINIMA (1,2) 65.0 PSI

ACCESORIOS factor
IDENTIFICACIO CAUDAL ESPESOR LONGITUD PERDIDA de VELOC
DIAM TUB. DIAM DIAM
TRAMOS N Y SITUACION TUB. L.Equi EQUIVALENTE DE CARGA HF RE k/D OBSERVACIONES
DE LAS BIE (L/Min) (PULG) TUB.(mm)
(mm)/(mt)
TUB.(mts)
CANT TIPO vAcces TUBERIA bar/metro m/sg λ
.
T LONG. C= 120 4.82
q1= 3.7
380.00 C TRAMO 2 FLUJO TURBULENTO
1 1 2 1 1/2 " 40.9 0.0409 Va ACCES 0 0.0722 bMtr 0.217397 1.97E+05 0.0005 0.003753
0.0037
Q= 380 RED TOTAL 2.00
T LONG. C= 120 4.82
q= 3.7
380 C TRAMO 5 FLUJO TURBULENTO
2 2 3 1 1/2 " 40.9 0.0409 Red ACCES 0 0.0722 bMtr 0.543493 1.97E+05 0.0005 0.003753
0.0037
Q= 380 Vc TOTAL 5.00
T LONG. C= 120 4.82
q= 3.9
380 C TRAMO 5 FLUJO TURBULENTO
3 3 4 1 1/2 " 40.9 0.0409
Va ACCES 0 0.0722 bMtr
0.543493 1.97E+05 0.0005 0.003753
0.0039
Q= 380 Vc TOTAL 5.00
T LONG. C= 120 2.92
q= 380 3.9 C 5
TRAMO FLUJO TURBULENTO
4 5 6 2" 52.5 0.0525
Red ACCES 0 0.0214 bMtr
0.164270 1.54E+05 0.0004 0.003953
Q= 380 0.0039 Vc 5.00
TOTAL
T LONG. C= 120 2.92
q= 3.9
380 C TRAMO 5 FLUJO TURBULENTO
5 7 8 2" 52.5 0.0525
Va ACCES 0 0.0214 bMtr
0.164270 1.54E+05 0.0004 0.003953
0.0039
Q= 380 Vc TOTAL 5.00

CALCULO HIDRAULICO SEGUN NORMA COVENIN 1376:1999


ING. DAVID GONZALEZ M C.I.V: 152.808
REG. CONSULTORES SENCAMER: 20578 SCI. SISTEMA CONTRA INCENDIO

L/min GPM m3 HORA PSI BAR N/M2


CAUDAL DE
DEMANDA 380 114 23 PRESION MINIMA 65.00 4.48 448158.75

NOTAS: ACEPTADO 65.00

CALCULO DE BOMBEO
PRESION P2= 448158.75 BOMBA PARA EL SISTEMA
Q Caudal = 0.0063 HP = 4.511 Eficiencia = 85.00%
ρDensidad = 1000 HP = 5.307
Gravedad = 9.80 Hf total 1.632924

Le del sistema = 22.00


HB perdidas del sistema = 54.15
POTENCIA WATTS = 3360.79

CALCULO HIDRAULICO SEGUN NORMA COVENIN 1376:1999