ING. DAVID GONZALEZ M C.I.V: 152.808 SCI.

SISTEMA CONTRA INCENDIO


REG. CONSULTORES SENCAMER: 20578

CALCULOS HIDRAULICOS DE BIE (GABINETES CON MANGUERAS)


PROYECTO: LOCAL COMERCIAL RAMON BLADIMIR GONZALEZ MORENO
DIRECCION: CALLE VELASQUEZ CRUCE CALLE DOÑA ISABEL, PORLAMAR

SISTEMA DE MANGUERAS PAG. 1/2

TIPO DE RIESGO LIGERO


TIPO DE GABINETES TIPO I D: 1. 1/2 "
LONGITUD ENTRE GABINETE(m) 30.00 CAUDAL MINIMO (q1) 380 L/min SUPERFICIE TOTAL 163.8 m2
TIPO DE TUBERIA ACERO COEF RUGOSIDAD RELATIVA (K) 0.02 mm 1.0 ALTURA EDIF 10 m
CANTIDAD DE GABINETES 2.0 UND CAUDAL MINIMO 0.0063 m3/seg
COEFICIENTE (C) SEGÚN TIPO CAUDAL TOTAL (QT) 760.0 L/min DESCARGA DE BOMBA 2.6 m
TUBERIA HAZEN WILLIAMS 120.00 PRESION MINIMA (1,2) 75.0 PSI

ACCESORIOS factor
IDENTIFICACIO ESPESOR LONGITUD PERDIDA de
CAUDAL DIAM DIAM DIAM VELOC
TRAMOS N Y SITUACION
TUB.(PULG) TUB.(mm)
TUB.(mm)/(
TUB.(mts) L.Equiv EQUIVALENTE DE CARGA HF RE k/D OBSERVACIONES
DE LAS BIE (L/Min) mt) CANT TIPO TUBERIA bar/metro m/sg λ
Acces.

T LONG. C= 120 4.82


q1= 3.7
380.00 2 C 1.2 TRAMO 1.5 FLUJO TURBULENTO
1 1 2 1 1/2 " 40.9 0.0409
Va ACCES 2.4 0.0722 bMtr
0.423925 1.97E+05 0.0005 0.003753
0.0037
Q= 380 RED TOTAL 3.90
T LONG. C= 120 2.92
q= 3.9
380 C TRAMO 3 FLUJO TURBULENTO
2 2 3 2" 52.5 0.0525
Red ACCES 0 0.0214 bMtr
0.098562 1.54E+05 0.0004 0.003953
0.0039
Q= 380 Vc TOTAL 3.00
T LONG. C= 120 2.92
q= 3.9
380 C TRAMO 3 FLUJO TURBULENTO
3 3 4 2" 52.5 0.0525
Va ACCES 0 0.0214 bMtr
0.098562 1.54E+05 0.0004 0.003953
0.0039
Q= 380 Vc TOTAL 3.00
T LONG. C= 120 2.05
q= 5.2
380 C TRAMO 4 FLUJO TURBULENTO
4 5 6 2 1/2" 62.7 0.0627
Red ACCES 0 0.0090 bMtr
0.056196 1.29E+05 0.0003 0.004107
0.0052
Q= 380 Vc TOTAL 4.00
T LONG. C= 120 2.19
q= 5.2
380 C TRAMO 8 FLUJO TURBULENTO
5 7 8 2 1/2° 60.7 0.0607
Va ACCES 0 0.0106 bMtr
0.131240 1.33E+05 0.0003 0.004078
0.0052
Q= 380 Vc TOTAL 8.00

CALCULO HIDRAULICO SEGUN NORMA COVENIN 1376:1999


ING. DAVID GONZALEZ M C.I.V: 152.808 SCI. SISTEMA CONTRA INCENDIO
REG. CONSULTORES SENCAMER: 20578

L/min GPM m3 HORA PSI BAR N/M2


CAUDAL DE
380 114 23 PRESION MINIMA 75.00 5.17 517106.25
DEMANDA
NOTAS:

CALCULO DE BOMBEO
PRESION P2= 517106.25 BOMBA PARA EL SISTEMA
Q Caudal(lts) = 0.0063 HP = 5.612 Eficiencia = 75.00%
ρDensidad = 1000 HP = 7.482
Gravedad(m/seg2)= 9.80 Hf total 0.808485

Le del sistema (m) = 21.90


HB perdidas del sistema = 67.36
POTENCIA HP = 4180.75

CALCULO HIDRAULICO SEGUN NORMA COVENIN 1376:1999