Está en la página 1de 15

ENCHUFE

T.D.A CTO TRIPLE 300W

CB1 5
CB2 8
CB3 6
CB4 5
1 CB5
CB6
CB7
CB8
CB9
TOTAL 24

ENCHUFE
Calculos Justificativos T.D.A CTO TRIPLE 300W

Calculo Alimentador CB1 9


S=2xLx𝞺xI CB2 10
6.6 CB3 7
S = 2 x 30 x 0,0018 x 80 CB4 7
6.6 CB5 8
S = 0,21mm2 CB6 9
CB7 4
Calculo Del Vp CB8
Vp= 2 x L x 𝞺 x I 2 CB9
S CB10
S = 2 x 30 x 0,0018 x 80 CB11
35mm2 CB12
VP = 0,24 Volt CB13
CB14
CB15
CB16
CB17
TOTAL 54
ENCHUFE
T.D.A CTO TRIPLE 300W ENCHUFE 150W

CB1 11
CB2 7
CB3 9
CB4 6 2
CB5
3 CB6
CB7
CB8
CB9
CB10
CB11
TOTAL 33 2

ENCHUFE
T.D.A CTO TRIPLE 300W

CB1 3
CB2 9
CB3 12
CB4 8
CB5 7
CB6 5
4 CB7
CB8
CB9
CB10
CB11
CB12
CB13
TOTAL 44

T.D.A CTO ENCHUFE ENCHUFE 150W


TRIPLE 300W

CB1 5
CB2 2 4

5
CB3 8
5 CB4
CB5
CB6
CB7
TOTAL 15 4

TOTAL DE EQUIPOS
ENCHUFE
TRIPLE 300W ENCHUFE 150W

170 6
CUAD
AIRE ACONDICIONADO
LUMINARIA
EQUIPO LED PROYECTOR LED TOTAL
2x18 W EQUIPO LED 18 W 50W ORNAMENTAL 80 9.000 12.000 18.000 24.000 CENTROS
W BTU BTU BTU BTU
5
8
6
5
12 2 4 18
7 2 9
3 3
1 1
1 1
19 4 4 0 4 0 0 1 56

CUAD
AIRE ACONDICIONADO
EQUIPO LED PROYECTOR LED LUMINARIA TOTAL
2x18 W EQUIPO LED 18 W 50W ORNAMENTAL 80 9.000 12.000 18.000 24.000 CENTROS
W BTU BTU BTU BTU
9
10
7
7
8
9
4
9 2 11
12 2 3 17
14 2 1 17
1 1
1 1
3 3
3 3
1 1
1 1
1 1
35 6 4 0 7 0 0 4 110

CUADRO DE
AIRE ACONDICIONADO
EQUIPO LED PROYECTOR LED LUMINARIA TOTAL
2x18 W EQUIPO LED 18 W 50W ORNAMENTAL 80 9.000 12.000 18.000 24.000 CENTROS
W BTU BTU BTU BTU
11
7
9
8
10 2 12
10 10
1 1
1 1
1 1
1 1
2 2
20 2 0 0 4 0 0 2 63

CUAD
AIRE ACONDICIONADO
EQUIPO LED PROYECTOR LED LUMINARIA TOTAL
2x18 W EQUIPO LED 18 W 50W ORNAMENTAL 80 9.000 12.000 18.000 24.000 CENTROS
W BTU BTU BTU BTU
3
9
12
8
7
5
14 14
11 2 13
2 2
1 1
1 1
3 3
2 2
25 2 0 0 5 2 2 0 80

CUADRO DE
AIRE ACONDICIONADO
LUMINARIA
EQUIPO LED EQUIPO LED 18 W PROYECTOR LED ORNAMENTAL 80 TOTAL
2x18 W 50W 9.000 12.000 18.000 24.000 CENTROS
W BTU BTU BTU BTU
5
6
8
8 2 10
6 6
1 1 2
1 1
14 2 0 0 1 0 0 2 38

AIRE ACONDICIONADO
EQUIPO LED PROYECTOR LED LUMINARIA
2x18 W EQUIPO LED 18 W 50W ORNAMENTAL 80 9.000 12.000 18.000 24.000
W BTU BTU BTU BTU
113 16 8 0 21 2 2 9 347
CUADRO DE CARGAS TDF-01
PROTECCION CANALIZACIÓN
POTENCIA FACTOR DE POTENCIA CORRIENTE TOTAL (A)
TOTAL (KW) UTILIZACIÓN (KW) CONDUCTOR DUCT
DIF. DISY.
R--N S--N T-N mm2 TIPO
1.50 0.6 0.90 4.1 16 A. 2.5 EMT
2.40 0.6 1.44 6.5 2X25A 30mA 16 A. 2.5 EMT
1.80 0.6 1.08 4.9 16 A. 2.5 EMT
1.50 0.6 0.90 4.1 2X25A 30mA 16 A. 2.5 EMT
0.67 1.0 0.67 3.0 10 A. 1.5 EMT
2X25A 30mA
0.29 1.0 0.29 1.3 10 A. 1.5 EMT
2.48 1.0 2.48 11.3 2X25A 30mA 16 A. 2.5 EMT
2.01 1.0 2.01 9.1 2X25A 30mA 16 A. 2.5 EMT
0.83 1.0 0.83 3.8 2X25A 30mA 16 A. 2.5 EMT
13.466 10.59 15.5 19.1 13.5

CUADRO DE CARGAS TDF-02


PROTECCION CANALIZACIÓN
POTENCIA FACTOR DE POTENCIA CORRIENTE TOTAL (A)
TOTAL (KW) UTILIZACIÓN (KW) CONDUCTOR DUCT
DIF. DISY.
R--N S--N T-N mm2 TIPO
2.70 0.5 1.35 6.1 16 A. 2.5 EMT
3.00 0.6 1.80 8.2 2X25A 30mA 16 A. 2.5 EMT
2.10 0.6 1.26 5.7 16 A. 2.5 EMT
2.10 0.6 1.26 5.7 16 A. 2.5 EMT
2X25A 30mA
2.40 0.6 1.44 6.5 16 A. 2.5 EMT
2.70 0.6 1.62 7.4 16 A. 2.5 EMT
2X25A 30mA
1.20 0.6 0.72 3.3 16 A. 2.5 EMT
0.36 0.8 0.29 1.3 2X25A 30mA 10 A. 1.5 EMT
0.62 0.8 0.49 2.2 2X25A 30mA 10 A. 1.5 EMT
0.59 0.8 0.47 2.1 2X25A 30mA 10 A. 1.5 EMT
2.01 1.0 2.01 9.1 16 A. 2.5 EMT
2X25A 30mA
2.01 1.0 2.01 9.1 16 A. 2.5 EMT
2.48 0.6 1.49 6.8 16 A. 2.5 EMT
2.48 0.6 1.49 6.8 2X25A 30mA 16 A. 2.5 EMT
2.01 0.8 1.61 7.3 16 A. 2.5 EMT
2.01 0.8 1.61 7.3 16 A. 2.5 EMT
2X25A 30mA
0.83 0.8 0.66 3.0 16 A. 2.5 EMT
31.58 21.57 35.6 32.4 30.1

CUADRO DE CARGAS TDF-03


PROTECCION CANALIZACIÓN
POTENCIA FACTOR DE POTENCIA CORRIENTE TOTAL (A)
TOTAL (KW) UTILIZACIÓN (KW) CONDUCTOR DUCT
DIF. DISY. mm2
R--N S--N T-N TIPO
3.30 0.5 1.65 7.5 2X25A 30mA 16 A. 2.5 EMT
2.10 0.6 1.26 5.7 16 A. 2.5 EMT
2.70 0.6 1.62 7.4 16 A. 2.5 EMT
2.10 0.6 1.26 5.7 2X25A 30mA 16 A. 2.5 EMT
0.40 0.7 0.28 1.3 2X25A 30mA 10 A. 1.5 EMT
0.36 0.7 0.25 1.1 10 A. 1.5 EMT
0.83 0.8 0.66 3.0 2X25A 30mA 16 A. 2.5 EMT
2.01 0.8 1.61 7.3 2X25A 30mA 16 A. 2.5 EMT
2.01 0.8 1.61 7.3 16 A. 2.5 EMT
0.83 0.8 0.66 3.0 16 A. 2.5 EMT
1.65 0.8 1.32 6.0 2X25A 30mA 16 A. 2.5 EMT
18.28 12.18 20.6 17.1 17.6

CUADRO DE CARGAS TDF-04


PROTECCION CANALIZACIÓN
POTENCIA FACTOR DE POTENCIA CORRIENTE TOTAL (A)
TOTAL (KW) UTILIZACIÓN (KW) CONDUCTOR DUCT
DIF. DISY. mm2
R--N S--N T-N TIPO
0.90 0.6 0.54 2.5 16 A. 2.5 EMT
2.70 0.6 1.62 7.4 2X25A 30mA 16 A. 2.5 EMT
3.60 0.6 2.16 9.8 16 A. 2.5 EMT
2.40 0.6 1.44 6.5 2X25A 30mA 16 A. 2.5 EMT
2.10 0.6 1.26 5.7 2X25A 30mA 16 A. 2.5 EMT
1.50 0.6 0.90 4.1 2X25A 30mA 16 A. 2.5 EMT
0.50 0.6 0.30 1.4 10 A. 2.5 EMT
2X25A 30mA
0.43 0.8 0.35 1.6 10 A. 1.5 EMT
1.65 0.8 1.32 6.0 16 A. 2.5 EMT
1.64 0.8 1.31 6.0 2X25A 30mA 16 A. 2.5 EMT
1.64 0.8 1.31 6.0 16 A. 2.5 EMT
2.48 0.8 1.98 9.0 16 A. 2.5 EMT
2X25A 30mA
2.18 0.8 1.74 7.9 16 A. 2.5 EMT
23.72 16.24 23.7 23.7 26.4

CUADRO DE CARGAS TDF-05


PROTECCION CANALIZACIÓN
POTENCIA FACTOR DE POTENCIA CORRIENTE TOTAL (A)
CONDUCTOR DUCT
TOTAL (KW) UTILIZACIÓN (KW) DIF. DISY.
R--N S--N T-N mm2 TIPO
1.50 0.6 0.90 4.1 16 A. 2.5 EMT
2X25A 30mA
1.20 0.6 0.72 3.3 16 A. 2.5 EMT
2.40 0.5 1.20 5.5 2X25A 30mA 16 A. 2.5 EMT
0.32 0.8 0.26 1.2 10 A. 1.5 EMT
2X25A 30mA
0.22 0.8 0.17 0.8 10 A. 1.5 EMT
2.84 0.6 1.70 7.7 2X25A 30mA 16 A. 2.5 EMT
2.01 0.7 1.41 6.4 2X25A 30mA 16 A. 2.5 EMT
10.49 6.36 7.4 13.2 8.4

97.531 0 66.9276 102.8 105.5 95.95


CANALIZACIÓN UBICACIÓN
DUCTO
DIAM
20 mm ENCHUFE JUZGADO DE POLICIA LOCAL
20 mm ENCHUFE JUZGADO DE POLICIA LOCAL
20 mm ENCHUFE DEPARTAMENTO DE TESORERÍA
20 mm ENCHUFE DEPARTAMENTO DE TESORERÍA
20 mm ALUMBRADO JUZGADO DE POLICIA LOCAL
20 mm ALUMBRADO DEPARTAMENTO DE TESORERÍA
20 mm AIRE ACONDICIONADO OFICINA JUZGADO
20 mm AIRE ACONDICIONADO TESORERÍA
20 mm AIRE ACONDICIONADO TESORERÍA

CANALIZACIÓN UBICACIÓN
DUCTO
DIAM
20 mm ENCHUFE OFICINA DIRECCIÓN DE OBRAS
20 mm ENCHUFE OFICINA DIRECCIÓN DE OBRAS
20 mm ENCHUFE OFICINA CONCEJALES
20 mm ENCHUFE OFICINAS
20 mm ENCHUFE OFICINAS
20 mm ENCHUFE SALON MULTIUSO
20 mm ENCHUFE COMEDOR
20 mm ALUMBRADO OFICINA DIRECCIÓN DE OBRAS
20 mm ALUMBRADO OFICINA CONCEJALES
20 mm ALUMBRADO SALON MULTIUSO
20 mm AIRE ACONDICIONADO OFICINA DIRECCION
20 mm AIRE ACONDICIONADO OFICINA DIRECCION
20 mm AIRE ACONDICIONADO OFICINA DIRECCION
20 mm AIRE ACONDICIONADO OFICINA CONCEJAL
20 mm AIRE ACONDICIONADO SALON MULTIUSO
20 mm AIRE ACONDICIONADO SALON MULTIUSO
20 mm AIRE ACONDICIONADO COMEDOR
CANALIZACIÓN UBICACIÓN
DUCTO
DIAM
20 mm ENCHUFE DEPARTAMENTO DE FINANZAS
20 mm ENCHUFE SECRETARIA MUNICIPAL
20 mm ENCHUFE OFICINAS
20 mm ENCHUFE OFICINAS
20 mm ALUMBRADO DEPARTAMENTO DE FINANZAS
20 mm ALUMBRADO SECRETARIA MUNICIPAL
20 mm AIRE ACONDICIONADO DEP. FINANZAS
20 mm AIRE ACONDICIONADO OFICINA
20 mm AIRE ACONDICIONADO SECRETARIA MUN.
20 mm AIRE ACONDICIONADO OFICINA
20 mm AIRE ACONDICIONADO OFICINA

CANALIZACIÓN UBICACIÓN
DUCTO
DIAM
20 mm ENCHUFE OFICINA SECPLAN
20 mm ENCHUFE OFICINA SECPLAN
20 mm ENCHUFE OFICINA SECPLAN
20 mm ENCHUFE OFICINA INFORMATICA
20 mm ENCHUFE DEP. DE COMUNICACIÓN
20 mm ENCHUFE OFICINAS
20 mm ALUMBRADO SECPLAN
20 mm ALUMBRADO DEP. DE COMUNICACIÓN
20 mm AIRE ACONDICIONADO SECPLAN
20 mm AIRE ACONDICIONADO SECPLAN
20 mm AIRE ACONDICIONADO SECPLAN
20 mm AIRE ACONDICIONADO INFORMATICA
20 mm AIRE ACONDICIONADO DEP. COMUNICACIONES

CANALIZACIÓN UBICACIÓN
DUCTO
DIAM
20 mm ENCHUFE OFICINA DE ALCALDÍA
20 mm ENCHUFE OFICINA
20 mm ENCHUFE ALCALDE
20 mm ALUMBRADO OFICINA DE ALCALDÍA
20 mm ALUMBRADO OFICINA DE ALCALDE
20 mm AIRE ACONDICIONADO ALCALDÍA
20 mm AIRE ACONDICIONADO ALCALDE
44.332

CUADRO DE CARGAS T.G


RESUMEN DE POTENCIA TABLERO POTENCIA (KW)
POTENCIA EXISTENTE 2.64 KW TDF - 01 10.586
POTENCIA DECLARADA KW TDF - 02 21.570
POTENCIA TOTAL KW TDF - 03 12.175
TDF - 04 16.24
TDF - 05 6.36
0 TOTAL 66.928
TDF - 01 20.105
TDF - 02 40.966
TDF - 03 23.123
TDF - 04 30.835
TDF - 05 12.079
TOTAL 127.107
CUADRO DE CARGAS T.GRAL
DESCRIPCIÓN
JUZGADO DE POLICIA
DIRECCIÓN DE OBRAS
DEPARTAMENTO DE FINANZAS
SECPLAN
ALCALDÍA
KW