CUADRO DE CARGAS ALUM

LAMPA TOTAL POTENCIA PROTECCION

In
APLI ENCHU ENCH

TDA CTO N° RA
QUE FES
ESP. CENTROS W KW FASE
DISYUNTOR
18 18 150 1000

C 1 7 1 8 144.0 0.1 KW 0.65 A 1 X 10 A.


C 2 1 1 18.0 0.0 KW 0.08 A 1 X 10 A.
C 3 2 4 6 108.0 0.1 KW 0.49 A 1 X 10 A.
C 4 2 6 8 144.0 0.1 KW 0.65 A 1 X 10 A.
C 5 9 9 162.0 0.2 KW 0.74 A 1 X 10 A.
C 6 19 2 21 378.0 0.4 KW 1.72 A 1 X 10 A.
1 C 7 9 9 1350.0 1.4 KW 6.14 A
C 8 10 10 1500.0 1.5 KW 6.82 A
C 9 2 2 2000.0 2.0 KW 9.09 A
C 10 3 3 3000.0 3.0 KW 13.64 A
C 11 15 15 2250.0 2.3 KW 10.23 A
C 12 19 19 2850.0 2.9 KW 12.95 A
TOTAL 12 31 22 53 5 111 13904 W 13.9 KW 63.20 A

10000
12000
220 15000
13904.0 13904.00 63.20 A 18000
20000
3000 3000 13.64 A
30000
10904.0 3816.4 17.35 A
SEGÚN TABLA N° 7.5 30.98 A 15000
NCH ELECT 4/2003
6816.4 30.98 A

30000

10 5 50
3.5 2.5 8.75
7 7 49
6 4 24
0
0
0
0
0
0
0
0

131.75
LUMBRADO
CCIONES CANALIZACION

DIFERENCIAL CONDUCTOR
DUCTO UBICACIONES
Ø
EVAFLEX 1,5 mm² t.p.r.e. 16 mm² VIVIENDA CUADRO DE CARGAS'!DA110
EVAFLEX 1,5 mm² t.p.r.e. 16 mm² VIVIENDA
EVAFLEX 1,5 mm² t.p.r.e. 16 mm² VIVIENDA
EVAFLEX 1,5 mm² t.p.r.e. 16 mm² VIVIENDA
EVAFLEX 1,5 mm² t.p.r.e. 16 mm² VIVIENDA
EVAFLEX 1,5 mm² t.p.r.e. 16 mm² VIVIENDA
2 X25 A 30 mA. EVAFLEX 2,5 mm² t.p.r.e. 20 mm² VIVIENDA
2 X25 A 30 mA. EVAFLEX 2,5 mm² t.p.r.e. 20 mm² VIVIENDA
2 X25 A 30 mA. EVAFLEX 4 mm² t.p.r.e. 20 mm² VIVIENDA
2 X25 A 30 mA. EVAFLEX 4 mm² t.p.r.e. 20 mm² VIVIENDA
2 X25 A 30 mA. EVAFLEX 2,5 mm² t.p.r.e. 20 mm² VIVIENDA
2 X25 A 30 mA. EVAFLEX 2,5 mm² t.p.r.e. 20 mm² VIVIENDA

$1,110,000
$1,332,000 bandejas
$1,665,000
$1,998,000
$2,220,000

$3,330,000
131.75
DUCTO
DUCTO
PVC FLEX.
16 mm² 16
20 mm² 20
25 mm² 25
32 mm² 32
40 mm²
50 mm²
63 mm²
75 mm²
90 mm²
110 mm²
111 mm²
112 mm²
113 mm²
114 mm²
115 mm²
25 25 32 1 Ø ¾ 3 12
32 32 1¼ Ø 10

40 40 1½ Ø 1,5 mm² 1.5 8

50 50 2 Ø 2,5 mm² 2.5 6

63 2½ Ø 4 mm² 4 4
75 3 Ø 6 mm² 6 2
90 4 Ø 10 mm² 10 1/0
110 8 Ø 16 mm² 16 2/0
25 mm² 25 3/0
35 mm² 35 4/0
50 mm² 50 250
R Cobre 0.018 70 mm² 70 300
S Aluminio 0.028 95 mm² 95 350
T Plata 0.016 120 mm² 120 400
R-S-T Oro 0.023 150 mm² 150 500
Cinc 0.006 185 mm² 185
Latón 0.070 240 mm² 240
6 A.W.G. 13.30
5 A.W.G. 16.80
4 A.W.G. 21.20
3 A.W.G. 26.70
2 A.W.G. 33.60
1 A.W.G. 42.40
1/0 A.W.G. 53.50
2/0 A.W.G. 67.40
3/0 A.W.G. 85.00
4/0 A.W.G. 107.00
3 250 A.W.G. 126.70
6 300 A.W.G.
9 350 A.W.G. 177.30
12 400 A.W.G. 203.00
15 500 A.W.G. 253.00
18
21
24
27
30
33
36
39
42
45
25 2 x 25 + 1 x 25 2 X25 A 30 mA.
30 3 x 25 + 1 x 25 2 X 25 A 300 mA. 16 A.

40 3 x 16 + 1 x 50 2 X 40 A 30 mA. 20 A.

55 3 x 50 + 1 x 50 2 X 40 A 300 mA. 25 A.

70 3 x 70 + 1 x 50 2 X 63 A 30 mA. 30 A.
95 3 x 70 + 1 x 50 2 X 63 A 300 mA. 32 A.
125 3 x 95 + 1 x 50 35 A.
145 40 A.
165 88 A.
195 89 A.
215 90 A.
240 91 A.
260 92 A.
280 93 A.
320 94 A.
95 A.
96 A.
2 X 25 A 30 mA. NYY
2 X 40 A 30 mA. PT
2 X 63 A 30 mA. PW
4 X 25 A 30 mA. THW
4 X 40 A 30 mA. THWN
4 X 63 A 30 mA. TTMU
4 X 80 A 30 mA. TTU
2 X 25 A 300 mA. TW
2 X 40 A 300 mA. UF
2 X 63 A 300 mA. USE - RHH
4 X 25 A 300 mA. USE - RHHM
4 X 40 A 300 mA. XPLE
4 X 63 A 300 mA. XTMU
4 X 80 A 300 mA. XTU
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
½ 15 16 mm²
1 X 6 A. ¾ 20 20 mm²

1 X 10 A. 1 25 25 mm²

1 X 13 A. 1¼ 32 32 mm²

1 X 16 A. 1½ 40 40 mm²
1 X 20 A. 2 50 50 mm²
1 X 25 A. 2½ 65 63 mm²
1 X 32 A. 3 80 75 mm²
1 X 40 A. 3½ 90 90 mm²
1 X 50 A. 4 100 110 mm²
1 X 63 A. 4½ 115 140 mm²
1 X 80 A. 5 125 ⅛" Ø
1 X 100 A. 8 ¼" Ø
1 X 125 A. ⅜" Ø
1 X 150 A. ½" Ø
1 X 160 A. ⅝" Ø
1 X 180 A. ¾" Ø
2 ½" Ø
2 ⅝" Ø
2 ¾" Ø
2 ⅞" Ø
3" Ø
3 ⅛" Ø
3 ¼" Ø
3 ⅜" Ø
3 ½" Ø
3 ⅝" Ø
3 ¾" Ø
4" Ø
5" Ø
8" Ø
5 X 150
6 X 10
6 X 15
6 X 20
10 X 20
10 X 30
10 X 40
10 X 41
10 X 50
10 X 60
13 X 7
20 X 10
20 X 12
32 X 12
35 X 56
40 X 10
40 X 16
40 X 25
40 X 60
45 X 100
49 X 36
50 X 100
60 X 100
60 X 150
60 X 200
60 X 300
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
Tubo deformable t.d.
Tubería metálica flexible t.m.f
Tubería de pared gruesa galvanizado c.g.

Tubería plástica flexible de PVC t.p.f.

Tubería plástica rígida de PVC t.p.r.


Tubería plástica rígida de PVC t.p.r.e.
Tubería plástica de polietileno t.p.p.
Canaleta ranurada c.r.
a.a
a.b
a.c
a.d
a.f
a.g

NOMINAL PIPE SIZE NPS


DIAMETRO NOMINAL DN
POLICLORURO DE VINILO PVC
ELECTTICAL METALIC TUBING EMT
NYA H07 V- U GENLIS ECO 1,5-2,5-4-6-10 mm
XTU (MONOCONDUCTOR ) 12-10-8-6-4-2-1-1/0-2/0-3/0-4/0-250-300-350-400-500-750-1000 AWG
XTMU (MULTICONDUCTOR ) 12-10-8-6-4-2-1-1/0-2/0-3/0-4/0-250-300-350-400-500-750-1000 AWG
XAT (MONOCONDUCTOR ) 2-1-1/0-2/0-3/0-4/0-250-300-350-400-500 AWG
EAT (MONOCONDUCTOR ) 2-1-1/0-2/0-3/0-4/0-250-300-350-400-500 AWG
GPT ( TAC) 14-12-10 AWG
SUPERFLEX / EVA ( MONOCONDUCTOR ) 14-12-10-8 AWG
SUPERFLEX / EVA ( MULTICONDUCTOR ) 14-12-10 X 3 AWG - 14-12-10 X 4 AWG - 14-12-10 X 5 AWG
SUPERFLEX / RV-K ( MONOPOLAR ) 16-14-12-10-8-6-4-2-1-1/0-2/0-3/0-4/0-250-300-350-400-500 AWG
SUPERFLEX / RV-K ( MULTIPOLAR ) 16-14-12-10-8-4-3-2-1 X 16-14-12-10-8-4-3-2-1 X 3 16-14-12-10-8-4-3-2-1 X 5

EVAFLEX 1,5 - 2,5 - 4 mm


exZhellent XXL (MONOCONDUCTOR ) 1,5 - 2,5 - 4 - 10 - 16 - 25 - 35 - 50 - 70 - 95 - 120 - 150 - 240 mm
exZhellent XXL (MULTICONDUCTOR ) 1,5 - 2,5 - 4 - 10 - 16 - 25 - 35 - 50 - 70 - 95 - 120 - 150 - 240 mm
DLO LOC 14-12-10-8-6-4-3-2-1-1/0-2/0-3/0-4/0-262,6-313,3-373,3-444,4-535,3-646,4-777,7-929,9-111,1 AWG
THHN 14-12-10-8-6-4-3-2-1-1/0-2/0-3/0-4/0-250-300-350-400-500 AWG
GENLIS ECO 1,5-2,5-4-6-10 mm
TOXFREE 1,5-2,5-4-6-10 mm
POWERFLEX 4-6-10 mm
CALECO ( NYIFY) 2 X 1,5 - 2 X 2,5 - 3 X 1,5 - 3 X 2,5
ALAMBRE COBRE DURO REDONDO 12-10-9-8-7-6-5-4-2 AWG
PW 4-6-10 mm -- 8-6-4 AWG
CABLE COBRE DESNUDO 6-4-3-2-1-1/0-2/0-3/0-4/0 AWG
THW
NSYA
NYY
PREENSAMBLADO
CU. DESNUDO
COCINA
ALUMBRADO DORMITORIO
ALUMBRADO COCINA
ALUMBRADO 1er PISO
ALUMBRADO 2do PISO
ALUMBRADO COCINA - BAÑOS
ALUMBRADO COMEDOR - SALA DE ESTAR - DORMITORIOS
BAÑO
BODEGA
COCINA - BAÑO
COMEDOR
COMEDOR - SALA DE ESTAR - DORMITORIOS
DORMITORIOS
ENCHUFES COCINA
ENCHUFES COCINA - BAÑO
ENCHUFES DORMITORIO
ENCHUFES 1er PISO
ENCHUFES 2do PISO
ENCHUFES COMEDOR - SALA DE ESTAR - DORMITORIOS
GALPON
SALA DE ESTAR - COMEDOR
SALA DE ESTAR
VIVIENDA - BODEGA
DORMITORIO _PASILLO
ALUMBRADO PRIMER PISO
ALUMBRADO SEGUNDO PISO
ALUMBRADO EXTERIOR
LAVADORA CUADRO DE CARGAS'!AM10
SECADORA
BAÑOS PRIMER PISO SEGUNDO PISO
ENCHUFES COMUNES VIVIENDA
ENCHUFES COCINA
ENCHUFES COCINA
VIVIENDA
Z 1028
13 2.62
12 3.31
11 4.17

10 5.26

9 6.63
8 8.37
7 10.50
6 13.30
5 16.80
4 21.20
3 26.70
2 33.60
1 42.40
0(1/0) 53.50
00(2/0) 67.40
000(3/0) 85.00
0000(4/0) 107.00
valor U.F. valor certificacion TE 1
$28,667.44 0.5 $14,334
0.6 $17,200
0.7 $20,067
0.8 $22,934
0.9 $25,801 PLANOS PRECIO POR METRO
1 $28,667
1.1 $31,534 por metro
132
1.2 $34,401 cuadrado
1.3 $37,268
1.4 $40,134 131.75
1.5 $43,001

PLANOS PRECIO POR METRO


$10,000
14 $12,500
$15,000

VALOR POR CENTROS


$8,000
$10,000
111 $12,500
$15,000
$18,000

VALOR TABLERO
$10,000
DISYUNTORES $12,500
$15,000
$10,000
DIFERENCIALES $12,500
$15,000
$10,000
TABLERO $12,500
$15,000
NOS PRECIO POR METRO
$1,000 $131,750
$1,500 $197,625
$2,000 $263,500
$2,500 $329,375

NOS PRECIO POR METRO


$139,040
$173,800
$208,560

VALOR POR CENTROS


$888,000
$1,110,000
$1,387,500
$1,665,000
$1,998,000

VALOR TABLERO
130000 $250,000
13 162500
195000
$110,000
11 $137,500 $312,500
$165,000
$10,000
1 $12,500
$15,000 $375,000
POTENCIA W = 13904.00 w

CAIDA DE TENSION δ = 4.19 V 1.91 %

RESISTENCA METAL ρ = Cobre 0.018

LARGO CONDUCTOR L = 25 m.

CORRIENTE I = 63.20 A.

MONOFASICO IGUAL 1 COS ϕ = 0.98

CALIBRE CONDUCTOR s = 8.45


CALCULADO

CALIBRE CONDUCTOR s = 6 A.W.G. 13.3 mm²


SUGERIDO

13904.00
I =
220
= 63.20
POTENCIA W =
CAIDA DE TENSION δ = 0.00

RESISTENCA METAL ρ = 0.01786

LARGO CONDUCTOR L = 25 m.

CORRIENTE I = 33.5 A.

MONOFASICO IGUAL 1 COS ϕ = 0.98

CALIBRE CONDUCTOR s = 0.00


CALCULADO

CALIBRE CONDUCTOR s = 4 mm²


SUGERIDO
CALCULO CONDUCTOR

2 * 0.01800 * 25 * 63.2 * 0.98 = 8.45


s= 6.6
mm²

CAIDA DE TENSION

2 * 0.01800 * 25 * 63.2 * 0.98 = 4.19 V


δ= 13.30
88 mm cuadrado
Cobre 0.018 1,5 mm² 1.5
Aluminio 0.028 2,5 mm² 2.5
Plata 0.016 4 mm² 4
Oro 0.023 6 mm² 6
Cinc 0.006 10 mm² 10
Latón 0.070 16 mm² 16
Hierro 0.100 25 mm² 25
Estaño 0.110 35 mm² 35
Platino 0.106 50 mm² 50
Plomo 0.208 70 mm² 70
95 mm² 95
120 mm² 120
150 mm² 150
185 mm² 185
240 mm² 240
300 mm² 300
400 mm² 400
500 mm² 500
16 A.W.G. 1.31
15 A.W.G. 1.65
14 A.W.G. 2.08
13 A.W.G. 2.62
12 A.W.G. 3.31
11 A.W.G. 4.17
10 A.W.G. 5.26
9 A.W.G. 6.63
8 A.W.G. 8.37
7 A.W.G. 10.50
6 A.W.G. 13.30
5 A.W.G. 16.80
4 A.W.G. 21.20
3 A.W.G. 26.70
2 A.W.G. 33.60
1 A.W.G. 42.40
1/0 A.W.G. 53.50
2/0 A.W.G. 67.40
3/0 A.W.G. 85.00
4/0 A.W.G. 107.00
250 A.W.G. 126.70
300 A.W.G. 146.50
350 A.W.G. 177.30
400 A.W.G. 203.00
500 A.W.G. 253.00
0.01786
0.02810
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
POTENCIA W = 6816.4 w

=
δ
s=
CAIDA DE TENSION 0.29 V 0.13 %

RESISTENCA METAL ρ = 0.02810

LARGO CONDUCTOR L = 25 m.

CORRIENTE I = 30.98 A.

MONOFASICO IGUAL 1 COS ϕ = 0.98

CALIBRE CONDUCTOR
CALCULADO
s = 6.46
δ=
CALIBRE CONDUCTOR s = 300 A.W.G. 146.5 mm²
SUGERIDO

6816.4
I =
220
= 30.98
POTENCIA W =
CAIDA DE TENSION δ = 0.00

RESISTENCA METAL ρ = 0.01786

LARGO CONDUCTOR L = 25 m.

CORRIENTE I = 33.5 A.

MONOFASICO IGUAL 1 COS ϕ = 0.98

CALIBRE CONDUCTOR s = 0.00


CALCULADO

CALIBRE CONDUCTOR s = 4 mm²


SUGERIDO
CALCULO CONDUCTOR

2 * 0.02810 * 25 * 31.0 * 0.98 = 6.46 mm²


6.6

CAIDA DE TENSION

0.02810 25
2 * * * 31.0 * 0.98 = 0.29 V
146.50
88 mm cuadrado
Cobre 0.018 1,5 mm² 1.5 0.01786
Aluminio 0.028 2,5 mm² 2.5 0.02810
Plata 0.016 4 mm² 4 0.00000
Oro 0.023 6 mm² 6 0.00000
Cinc 0.006 10 mm² 10 0.00000
Latón 0.070 16 mm² 16 0.00000
Hierro 0.100 25 mm² 25 0.00000
Estaño 0.110 35 mm² 35 0.00000
Platino 0.106 50 mm² 50 0.00000
Plomo 0.208 70 mm² 70 0.00000
95 mm² 95
120 mm² 120
150 mm² 150
185 mm² 185
240 mm² 240
300 mm² 300
400 mm² 400
500 mm² 500
16 A.W.G. 1.31
15 A.W.G. 1.65
14 A.W.G. 2.08
13 A.W.G. 2.62
12 A.W.G. 3.31
11 A.W.G. 4.17
10 A.W.G. 5.26
9 A.W.G. 6.63
8 A.W.G. 8.37
7 A.W.G. 10.50
6 A.W.G. 13.30
5 A.W.G. 16.80
4 A.W.G. 21.20
3 A.W.G. 26.70
2 A.W.G. 33.60
1 A.W.G. 42.40
1/0 A.W.G. 53.50
2/0 A.W.G. 67.40
3/0 A.W.G. 85.00
4/0 A.W.G. 107.00
250 A.W.G. 126.70
300 A.W.G. 146.50
350 A.W.G. 177.30
400 A.W.G. 203.00
500 A.W.G. 253.00
S =
2 =
√3 =
L =
ρ =
I =
cos ϕ =
Δ V =

√ 3∗¿L∗ρ∗I∗cosϕ
S= ¿
ΔV
S= 5.02 mm²

L= 90 metros
ρ= 0.018
I= 40 A
cos ϕ = 0.85 VAR
380 5 Δ V= 19 V
√3 = 1.7321
Sección del cable
Monofasica
Trifasica
Longitud del cable o circuito
Resistividad del cable (0,018 CU ; 0,029 AL )
Intensidad de corriente
Factor de potencia
Caida de Tensión ( 6,6 220 V. 19 380 V.)

S∗ΔV 2∗L∗
L= ¿ S=
√ 3∗¿ ρ∗I∗cos ϕV
L = 71.70 m

S = 4 mm²
ρ = 0.018 Ω mm 2

I = 40 A m
cos ϕ = 0.85 VAR
Δ V = 19 V
√3 = 1.7321
2∗L∗ρ∗I∗cos ϕ
S=
ΔV
S = 1.85
L= 10
ρ= 0.018
I= 40
cos ϕ = 0.85
Δ V= 6.6
WATT AMPERES

WATTS 2200 2200 10

AMPERES 40 8800 40

HP CV K WATT
HP 3 3 2.208 2.238

CV 2 1.9726 2 1.47

K WATT 1 1.341 1.35962 1


P = V * I
P = 2200

P = 220 * I
I = 16
I = P / V
V = 220
I = P / 220
P = V * I 3520.00 W

I = P / V 10.00 A

V = P / I 137.50 V
Plata 0.016 Plata 0.016
Cobre 0.01786 Cobre 0.018
Brone 0.018..0.056 Oro 0.023
Oro 0.023 Aluminio 0.028
Aluminio 0.02857 Cinc 0.006
Magnesio 0.045 Latón 0.070
Grafito 0.046 Hierro 0.100
Tungsteno 0.055 Estaño 0.110
Wolframio 0.055 Platino 0.106
Cinc 0.063 Plomo 0.208
Latón 0.07..0.09
Niquel 0.08..0.11
Hierro 0.1..0.15
Estaño 0.11
Platino 0.11..0.14
Plomo 0.21
Maillechort 0.3
Orocromo 0.33
Niquelina 0.43
Manganina 0.43
Novocosntat 0.45
1 T
2 H
3 HH
4 W
5 LS
6 SPT
(Thermoplastic): Aislamiento termoplástico (este lo tienen todos los cables.
(Heat resistant): Resistente al calor hasta 75° centígrados (167° F)
(Heat resistant): Resistente al calor hasta 90° centígrados (194° F).
(Water resistant): Resistente al agua y a la humedad.
(Low smoke): Este cable tiene baja emisión de humos y bajo contenido de gases contaminantes. 
(Service paralell thermoplastic): Esta nomenclatura se usa para identificar un cordón que se compone de dos
mpone de dos cables flexibles y paralelos con aislamiento de plástico y que están unidos entre sí. También se denomina co
mbién se denomina cordón dúplex.
DUCTO DUCTO DUCTO conduit
DUCTO
PVC FLEX. PVC E.M.T. met flex
16 mm² 16 16 16 20
20 mm² 20 20 20 25
25 mm² 25 25 25 32
32 mm² 32 32 32
40 mm² 40 40
50 mm² 50 50
63 mm² 63
75 mm² 75
90 mm² 90
110 mm² 110
111 mm²
112 mm²
113 mm²
114 mm²
115 mm²
116 mm²
117 mm²

0.01786 6.6
ρ 0.028
ΔV 11.4

R
S
T
R-S-T

mm²
A.W.G.
EXPRESIÓN MATEMÁTICA:

A.- Cálculo de Corriente Nominal:


Fórmula In = P / (V * Cos Fi)
B.- Cálculo de sección de alimentador:
Fórmula S= (2 * L * Rho* In) / Vp
C.- Cálculo de tensión de pérdida:
Fórmula Vp= (2 * L* Rho * In) / S
D.- Medida de puesta a tierra:
Medida en terreno con método de caída
de potencial.
E.- Rho = 0.01782 [(O*mm2)/m]
DUCTO
t.G
½ Ø 1,5 mm² 16
¾ Ø 2,5 mm² 15
1 Ø 4 mm² 14 20
1¼ Ø 6 mm² 13
1½ Ø 10 mm² 12 25
2 Ø 16 mm² 10 30
2½ Ø 25 mm² 8 40
3 Ø 35 mm² 6 55
4 Ø 50 mm² 4 70
8 Ø 70 mm² 2 95
95 mm² 1/0 125
120 mm² 2/0 145
150 mm² 3/0 165
185 mm² 4/0 195
240 mm² 250 215
300 mm² 300 240
400 mm² 350 260
500 mm² 400 280
16 A.W.G. 500 320
15 A.W.G.
14 A.W.G.
13 A.W.G.
12 A.W.G.
Cobre 0.018 10 A.W.G.
Aluminio 0.028 8 A.W.G.
Plata 0.016 6 A.W.G.
Oro 0.023 4 A.W.G.
Cinc 0.006 2 A.W.G.
Latón 0.070 1/0 A.W.G.
Hierro 0.100 2/0 A.W.G.
Estaño 0.110 3/0 A.W.G.
Platino 0.106 4/0 A.W.G.
Plomo 0.208 250 A.W.G.
300 A.W.G.
350 A.W.G.
400 A.W.G.
500 A.W.G.
barra copperweld DISYUNTOR B DISYUNTOR C
½ 1 6 A. 6 A.
⅝ 1.5 15 A. 10 A.
¾ 3 16 A. 13 A.
20 A. 16 A.
25 A. 20 A.
PREEMSAMBLADO 30 A. 25 A.
1 x 16 + 1 x 16 32 A. 32 A.
1 x 25+ 1 x 25 35 A. 40 A.
3 x 16 + 1 x 16 40 A. 50 A.
2 x 25 + 1 x 25 88 A. 63 A.
3 x 25 + 1 x 25 89 A. 80 A.
3 x 16 + 1 x 50 90 A. 100 A.
3 x 50 + 1 x 50 91 A. 125 A.
3 x 70 + 1 x 50 92 A. 150 A.
3 x 70 + 1 x 50 93 A. 160 A.
3 x 95 + 1 x 50 94 A. 180 A.
95 A. 200 A.
96 A. 225 A.
250 A.
99 A.
DIFERENCIAL 99 A.
2 X 25 A 30 99 A.
2 X 40 A 30 99 A.
2 X 63 A 30 99 A.
4 X 25 A 30
4 X 40 A 30
4 X 63 A 30
4 X 80 A 30
2 X 25 A 300
2 X 40 A 300
2 X 63 A 300
4 X 25 A 300
4 X 40 A 300
4 X 63 A 300
4 X 80 A 300
NPS DN PVC
TUBO PVC
⅜ 10 16 mm²
½ 15 20 mm²
¾ 20 25 mm²
1 25 32 mm²
1¼ 32 40 mm²
1½ 40 50 mm²
2 50 63 mm²
2½ 65 75 mm²
3 80 90 mm²
3½ 90 110 mm²
4 100 140 mm²
4½ 115 ⅛" Ø
5 125 ¼" Ø
8 ⅜" Ø
½" Ø
⅝" Ø
¾" Ø
⅞" Ø
1" Ø
1 ⅛" Ø
1 ¼" Ø
1 ⅜" Ø
1 ½" Ø
1 ⅝" Ø
1 ¾" Ø
1 ⅞" Ø
2" Ø
2 ⅛" Ø
2 ¼" Ø
2 ⅜" Ø
2 ½" Ø
2 ⅝" Ø
2 ¾" Ø
2 ⅞" Ø
3" Ø
3 ⅛" Ø
3 ¼" Ø
3 ⅜" Ø
3 ½" Ø
3 ⅝" Ø
3 ¾" Ø
4" Ø
5" Ø
8" Ø
Tubería de acero t.a.
Tubería de acero galvanizado t.a.g
Tubería de bronce t.b.
Tubería de cobre t.c.
Tubo deformable t.d.
Tubería metálica flexible t.m.f
Tubería de pared gruesa galvanizado c.g.
Tubería plástica flexible de PVC t.p.f.
Tubería plástica rígida de PVC t.p.r.
Tubería plástica rígida de PVC t.p.r.e.
Tubería plástica de polietileno t.p.p.

NOMINAL PIPE SIZE NPS


DIAMETRO NOMINAL DN
POLICLORURO DE VINILO PVC
ELECTTICAL METALIC TUBING EMT
NYA H07 V- U GENLIS ECO 1,5-2,5-4-6-10 mm
XTU (MONOCONDUCTOR ) 12-10-8-6-4-2-1-1/0-2/0-3/0-4/0-250-300-350-400-500-750-1000
XTMU (MULTICONDUCTOR ) 12-10-8-6-4-2-1-1/0-2/0-3/0-4/0-250-300-350-400-500-750-1000
XAT (MONOCONDUCTOR ) 2-1-1/0-2/0-3/0-4/0-250-300-350-400-500 AWG
EAT (MONOCONDUCTOR ) 2-1-1/0-2/0-3/0-4/0-250-300-350-400-500 AWG
GPT ( TAC) 14-12-10 AWG
SUPERFLEX / EVA ( MONOCONDUCTOR ) 14-12-10-8 AWG
SUPERFLEX / EVA ( MULTICONDUCTOR ) 14-12-10 X 3 AWG - 14-12-10 X 4 AWG - 14-12-10 X 5 A
SUPERFLEX / RV-K ( MONOPOLAR ) 16-14-12-10-8-6-4-2-1-1/0-2/0-3/0-4/0-250-300-350-400-500 A
SUPERFLEX / RV-K ( MULTIPOLAR ) 16-14-12-10-8-4-3-2-1 X 16-14-12-10-8-4-3-2-1 X 3 16-14-1
EVAFLEX 1,5 - 2,5 - 4 mm
exZhellent XXL (MONOCONDUCTOR ) 1,5 - 2,5 - 4 - 10 - 16 - 25 - 35 - 50 - 70 - 95 - 120 - 150 - 240 mm
exZhellent XXL (MULTICONDUCTOR ) 1,5 - 2,5 - 4 - 10 - 16 - 25 - 35 - 50 - 70 - 95 - 120 - 150 - 240 mm
DLO LOC 14-12-10-8-6-4-3-2-1-1/0-2/0-3/0-4/0-262,6-313,3-373,3-444,4-535,3-646,4-777,7-929,9
THHN 14-12-10-8-6-4-3-2-1-1/0-2/0-3/0-4/0-250-300-350-400-500 AW
GENLIS ECO 1,5-2,5-4-6-10 mm
TOXFREE 1,5-2,5-4-6-10 mm
POWERFLEX 4-6-10 mm
CALECO ( NYIFY) 2 X 1,5 - 2 X 2,5 - 3 X 1,5 - 3 X 2,5
ALAMBRE COBRE DURO REDONDO 12-10-9-8-7-6-5-4-2 AWG
PW 4-6-10 mm -- 8-6-4 AWG
CABLE COBRE DESNUDO 6-4-3-2-1-1/0-2/0-3/0-4/0 AWG
THW
NSYA
NYY
PREENSAMBLADO
CU. DESNUDO
-4/0-250-300-350-400-500-750-1000 AWG
-4/0-250-300-350-400-500-750-1000 AWG
-350-400-500 AWG
-350-400-500 AWG

2-10 X 4 AWG - 14-12-10 X 5 AWG


/0-3/0-4/0-250-300-350-400-500 AWG
6-14-12-10-8-4-3-2-1 X 3 16-14-12-10-8-4-3-2-1 X 5

5 - 50 - 70 - 95 - 120 - 150 - 240 mm


5 - 50 - 70 - 95 - 120 - 150 - 240 mm
62,6-313,3-373,3-444,4-535,3-646,4-777,7-929,9-111,1 AWG
0-3/0-4/0-250-300-350-400-500 AWG
3 X 2,5

AWG
Corriente
admisible
AWG Área
a en cobre
40 °C al aire libre4​
(mm²) (mm) (kcmil) (mm²) (A)
1000 507.00 25.400 1000.000 507.000 870
900 456.00 24.100 900.000 456.000 800
750 380.00 22.000 750.000 380.000 740
600 304.00 19.670 600.000 304.000 650
500 253.00 17.960 500.000 253.000 580
400 203.00 16.060 400.000 203.000 500
350 177.30 15.030 350.000 177.300 460
250 126.70 12.700 250.000 126.700 370
0000(4/0) 107.00 11.680 211.600 107.000 335
000(3/0) 85.00 10.400 167.800 85.000 287
00(2/0) 67.40 9266.000 133.100 67.400 247
0(1/0) 53.50 8251.000 105.500 53.500 214
1 42.40 7348.000 83.690 42.400 180
2 33.60 6544.000 66.370 33.600 150
3 26.70 5827.000 52.630 26.700 125
4 21.20 5189.000 41.740 21.200 117
5 16.80 4621.000 33.100 16.800
6 13.30 4115.000 26.250 13.300 89
7 10.50 3665.000 10.500
8 8.37 3264.000 8.370 66
9 6.63 2906.000 6.630
10 5.26 2588.000 5.260 30
11 4.17 2305.000 4.170 25
12 3.31 2053.000 3.310 20
13 2.62 1828.000 2.620 17
14 2.08 1628.000 2.080 15
15 1.65 1450.000 1.650 12
16 1.31 1291.000 1.310 10
17 1.04 1150.000 1.040 7
18 0.82 102362.000 0.823 5
19 0.65 0.912 0.653
20 0.52 0.813 0.518
21 0.41 0.723 0.410
22 0.33 0.644 0.326
23 0.26 0.573 0.258
24 0.21 0.511 0.205
25 0.16 0.455 0.162
26 0.13 0.405 0.129
27 0.10 0.361 0.102
28 0.08 0.321 0.081
29 0.06 0.286 0.064
30 0.05 0.255 0.051
31 0.04 0.227 0.040
32 0.03 0.202 0.032
33 0.03 0.180 0.025
34 0.02 0.160 0.020
35 0.02 0.143 0.016
36 0.01 0.127 0.013
37 0.01 0.113 0.010
38 0.01 0.101 0.008
39 0.01 0.090 0.006
40 0.01 0.080 0.005
Resistencia eléctrica en Resistencia
AWG Diámetro Área cobre eléctrica en
cobre
(in) (mm) (kcmil) (mm²) (Ω/1 km) (Ω/1000 ft)
1000 10,000 25.40 1000 507 0.0339434602425
900 0.9487 24.10 900 456 0.0377397682959
750 0.8660 22.00 750 380 0.0452877219551
600 0.7746 19.67 600 304 0.0566096524439
500 0.7071 17.96 500 253 0.0680210843595
400 0.6325 16.06 400 203 0.0847750460244
350 0.5916 15.03 350 177.3 0.0970633634684
250 0.5000 12.70 250 126.7 0.135827421807
0000(4/0) 0.4600 11.68 211.6 107 0.160834900401
000(3/0) 0.4096 10.40 167.8 85 0.202462756976
00(2/0) 0.3648 9,266 133.1 67.4 0.255331370073
0(1/0) 0.3249 8,251 105.5 53.5 0.324704421565 ~0.1
1 0.2893 7,348 83.69 42.4 0.405880526956
2 0.2576 6,544 66.37 33.6 0.512182569731
3 0.2294 5,827 52.63 26.7 0.644544357414
4 0.2043 5,189 41.74 21.2 0.811761053913
5 0.1819 4,621 33.10 16.8 102,436,513,946
6 0.1620 4,115 26.25 13.3 1,293,934,913
7 0.1443 3,665 10.5 163,898,422,314
8 0.1285 3,264 8.37 20,560,733,982
9 0.1144 2,906 6.63 259,567,637,149
10 0.1019 2,588 5.26 32,772 0.9989
11 0.0907 2,305 4.17 41,339 1,260
12 0.0808 2,053 3.31 5,210 1,588
13 0.0720 1,828 2.62 6,572 2,003
14 0.0641 1,628 2.08 8,284 2,525
15 0.0571 1,450 1.65 10.45 3,184
16 0.0508 1,291 1.31 13.18 4,016
17 0.0453 1,150 1.04 16,614 5,064
18 0.0403 102,362 0.823 20,948 6,385
19 0.0359 0.9116 0.653 26,414 8,051
20 0.0320 0.8128 0.518 33,301 10.15
21 0.0285 0.7229 0.410 41,995 12.80
22 0.0253 0.6438 0.326 52,953 16.14
23 0.0226 0.5733 0.258 66,798 20.36
24 0.0215 0.5106 0.205 84,219 25.67
25 0.0179 0.4547 0.162 106,201 32.37
26 0.0159 0.4049 0.129 133,891 40.81
27 0.0142 0.3606 0.102 168,865 51.47
28 0.0126 0.3211 0.081 212,927 64.90
29 0.0113 0.2859 0.0642 268,471 81.83
30 0.0100 0.2546 0.0509 338,583 103.2
31 0.0089 0.2268 0.0404 426,837 130.1
32 0.0080 0.2019 0.0320 538,386 164.1
33 0.0071 0.1798 0.0254 678,806 206.9
34 0.0063 0.1601 0.0201 833 260.9
35 0.0056 0.1426 0.0160 1,085,958 331.0
36 0.0050 0.1270 0.0127 1,360,892 414.8
37 0.0045 0.1131 0.0100 1,680,118 512.1
38 0.0040 0.1007 0.00797 2,127,953 648.6
39 0.0035 0.08969 0.00632 2,781,496 847.8
40 0.0031 0.07987 0.00501 3,543,307 1080.0
Corriente Equivalencia
admisible en aproximada
cobre
a 40 °C en estándar
al aire libre4​
métrico
(A)
870
800
740
650
580
500
460
370
335
287
247
214
180
150
125 196/0.4
117
126/0.4
89
80/0.4
66
>84/0.3
30 <84/0.3
25 56/0.3
20
17 50/0.25
15
12 >30/0.25
10 <30/0.25
7 32/0.2
5 >24/0.2
<24/0.2
16/0.2

7/0.25

1/0.5, 7/0.2,
30/0.1

7/0.15
1/0.25, 7/0.1

1/0.2, 7/0.08
Longitud Intensidad de AWG / MCM (mm²) (Ω / 100 m)
(m) Corriente (A)
5 318 1,5 mm² 1.5
2,5 mm² 2.5
COS ϕ ρ 4 mm² 4
1 Cobre 6 mm² 6
0.018 10 mm² 10
16 mm² 16
Tensión de Alimentación (V) 95 mm² 95
220 Volt 120 mm² 120
AMPERES 150 mm² 150
70 KW 318.18 240 mm² 240
300 mm² 300
400 mm² 400
500 mm² 500
16 A.W.G. 1.31
15 A.W.G. 1.65
14 A.W.G. 2.08
13 A.W.G. 2.62
12 A.W.G. 3.31
10 A.W.G. 5.26
8 A.W.G. 8.37
6 A.W.G. 13.30
4 A.W.G. 21.20
3 A.W.G. 26.70
2 A.W.G. 33.60
1 A.W.G. 42.40
1/0 A.W.G. 53.50
2/0 A.W.G. 67.40
3/0 A.W.G. 85.00
4/0 A.W.G. 107.00
250 A.W.G. 126.70
300 A.W.G. 151.8
350 A.W.G. 177.30
400 A.W.G. 203.00
500 A.W.G. 253.00
303.60
354.70
379.50
405.40
456.00
506.70
633.40
750.10
886.70
1013.00
9999.00
(Ampere) (Ampere) Corriente (A) (m) Tensión (V)
90 ° grupo A 90 ° grupo B
15 318 5 38.160
20 318 5 22.896
25 318 5 14.310
33 318 5 9.540
45 318 5 5.724
61 318 5 3.578
197 318 5 0.603
235 318 5 0.477
318 5 0.382
318 5 0.239
318 5 0.191
318 5 0.143
318 5 0.114
318 5 43.695
318 5 34.691
25 35 318 5 27.519
27 40 318 5 21.847
30 55 318 5 17.293
40 80 318 5 10.882
55 105 318 5 6.839
75 140 318 5 4.304
95 318 5 2.700
110 318 5 2.144
130 318 5 1.704
150 318 5 1.350
170 318 5 1.070
195 318 5 0.849
225 318 5 0.673
260 318 5 0.535
290 318 5 0.452
320 318 5 0.377
350 318 5 0.323
380 318 5 0.282
430 318 5 0.226
475 318 5 0.189
475 318 5 0.161
520 318 5 0.151
535 318 5 0.141
555 318 5 0.126
585 318 5 0.113
615 318 5 0.090
665 318 5 0.076
705 318 5 0.065
735 318 5 0.057
750 318 5 0.006
100 metro

0.018
0.028
0.016
0.023
0.106
0.208
1,5 mm² 1.5 1.2 Cobre 0.018
2,5 mm² 2.5 0.72 Aluminio 0.028
4 mm² 4 0.45 Plata 0.016
6 mm² 6 0.3 Oro 0.023
10 mm² 10 0.18 Cinc 0.006
16 mm² 16 0.1125 Latón 0.070
95 mm² 95 0.01894737
120 mm² 120 0.015
150 mm² 150 0.012
240 mm² 240 0.0075
300 mm² 300 0.006
400 mm² 400 0.0045
500 mm² 500 0.0036
16 A.W.G. 1.31 1.3740458
15 A.W.G. 1.65 1.09090909
14 A.W.G. 2.08 0.86538462
13 A.W.G. 2.62 0.6870229
12 A.W.G. 3.31 0.54380665
10 A.W.G. 5.26 0.34220532
8 A.W.G. 8.37 0.21505376
6 A.W.G. 13.30 0.13533835
4 A.W.G. 21.20 0.08490566

2 A.W.G. 33.60 0.05357143

1/0 A.W.G. 53.50 0.03364486


2/0 A.W.G. 67.40 0.02670623
3/0 A.W.G. 85.00 0.02117647
4/0 A.W.G. 107.00 0.01682243
250 A.W.G. 126.70 0.01420679
300 A.W.G. #DIV/0!
350 A.W.G. 177.30 0.01015228
400 A.W.G. 203.00 0.008867
500 A.W.G. 253.00 0.00711462

253.2 0.0089 2.25348


3.31 0.656 2.17136
Longitud Intensidad de AWG / MCM (mm²) (Ampere) Tensión (V)
(m) Corriente (A) 90 ° grupo A
60 132.94 1,5 mm² 1.5 15 165.789
2,5 mm² 2.5 20 99.474
COS ϕ ρ 4 mm² 4 25 62.171
1 Cobre 6 mm² 6 33 41.447
0.018 10 mm² 10 45 24.868
16 mm² 16 61 15.543
Tensión de Alimentación (V) 95 mm² 95 197 2.618
380 Volt 120 mm² 120 235 2.072
150 mm² 150 1.658
0.8 AMPERES 240 mm² 240 1.036
300 mm² 300 0.829
70 KW 132.94 400 mm² 400 0.622
500 mm² 500 0.497
16 A.W.G. 1.31 189.835
15 A.W.G. 1.65 150.718
14 A.W.G. 2.08 25 119.560
13 A.W.G. 2.62 27 94.918
12 A.W.G. 3.31 30 75.131
10 A.W.G. 5.26 40 47.278
8 A.W.G. 8.37 55 29.711
6 A.W.G. 13.30 75 18.698
4 A.W.G. 21.20 95 11.730
3 A.W.G. 26.70 110 9.314
2 A.W.G. 33.60 130 7.401
1 A.W.G. 42.40 150 5.865
1/0 A.W.G. 53.50 170 4.648
2/0 A.W.G. 67.40 195 3.690
3/0 A.W.G. 85.00 225 2.926
4/0 A.W.G. 107.00 260 2.324
250 A.W.G. 126.70 290 1.963
300 A.W.G. 151.8 320 1.638
350 A.W.G. 177.30 350 1.403
400 A.W.G. 203.00 380 1.225
500 A.W.G. 253.00 430 0.983
303.60 475 0.819
354.70 475 0.701
379.50 520 0.655
405.40 535 0.613
456.00 555 0.545
506.70 585 0.491
633.40 615 0.393
750.10 665 0.332
886.70 705 0.280
1013.00 735 0.245
9999.00 750 0.025
100

0.018
0.028
0.016
0.023
0.106
0.208
metro 1,5 mm² 1.5 1.2
2,5 mm² 2.5 0.72
4 mm² 4 0.45
6 mm² 6 0.3
10 mm² 10 0.18
16 mm² 16 0.1125
95 mm² 95 0.01894737
120 mm² 120 0.015
150 mm² 150 0.012
240 mm² 240 0.0075
300 mm² 300 0.006
400 mm² 400 0.0045
500 mm² 500 0.0036
16 A.W.G. 1.31 1.3740458
15 A.W.G. 1.65 1.09090909
14 A.W.G. 2.08 0.86538462
13 A.W.G. 2.62 0.6870229
12 A.W.G. 3.31 0.54380665
10 A.W.G. 5.26 0.34220532
8 A.W.G. 8.37 0.21505376
6 A.W.G. 13.30 0.13533835
4 A.W.G. 21.20 0.08490566

2 A.W.G. 33.60 0.05357143

1/0 A.W.G. 53.50 0.03364486


2/0 A.W.G. 67.40 0.02670623
3/0 A.W.G. 85.00 0.02117647
4/0 A.W.G. 107.00 0.01682243
250 A.W.G. 126.70 0.01420679
300 A.W.G. #DIV/0!
350 A.W.G. 177.30 0.01015228
400 A.W.G. 203.00 0.008867
500 A.W.G. 253.00 0.00711462

253.2 0.0089 2.25348


3.31 0.656 2.17136
Cobre 0.018
Aluminio 0.028
Plata 0.016
Oro 0.023
Cinc 0.006
Latón 0.070
Sección Nominal
Sección Nominal Intensidad de corriente admisible [Amperes] [mm2]

[mm2] En cañería Sobre bandeja


0.35 1 1 1x4
0.5 3 3 1x6
0.75 8 10 1 x 10
1 10.5 12 1 x 16
1.5 13 15.5 1 x 25
2.5 18 21 1 x 35
4 24 28 1 x 50
6 31 36 1 x 70
10 42 50 1 x 95
16 56 68 1 x 120
25 73 89 1 x 150
35 89 111 1 x 185
50 108 134 2 x 1,50
70 136 171 2 x 2,50
95 164 207 2x4
120 188 239 2x6
150 310 385 2 x 10
2 x 16
3 x 1,50
3 x 2,50
3x4
3x6
3 x 10
3 x 16
3 x 25
3 x 35
4 x 1,50
4 x 2,50
4x4
4x6
4 x 10
4 x 16
3 x 25 + 16
3 x 35 + 16
3 x 50 + 25
Intensidad de corriente admisible
[Amperes]

Aire Tierra
41 54
53 68
89 89
97 116
121 148
149 177
181 209
221 258
272 307
316 349
360 390
410 440
15 24
21 32
28 44
37 56
50 72
64 94
15 24
21 32
28 44
37 56
50 72
64 94
86 120
105 144
15 24
21 32
28 44
37 56
50 72
64 94
86 120
105 144
128 172