Ejercicio N°1
CALCULOS ELECTRICOS PARA UN CONDUCTOR DE ALEACION DE ALUMINIO AAA

CALCULO DE LA RESISTENCIA A = 40 ºC

Datos de la tabla de especificaciones tecnicas

R20ºc (Ohm/Km) 0.9651


T1 (ºC) 20
T2 (ºC) 40
a (1/ºC) 0.0036
R40ºC (Ohm/Km) 1.0346

CALCULO DEL FACTOR CAIDA DE TENSION (K)

Cos (Ø) 0.9


Sen (Ø) 0.4360
R40º C (Ohm/Km) 1.0346
XL (Ohm/Km) 0.4621
K (Ohm/Km) 1.9617

ANALISIS DE CAIDA DE TENSION EN LA RED PRIMARIA

PROYECTO : SISTEMA DE DISTRIBUCION PRIMARIA Y

DISTRITO : NUEVO CHIMBOTE


PROVINCIA : SANTA
DEPARTAMENTO : ANCASH

P
U SECCION POTENCIA SUMA
N CONDUCTOR DE POTENCIA
T AAAC TRANSF. TRANSF.
O (mm²) (KVA) (KVA)
PA 35 0.0 460.0
1 35 0.0 460.0
2 35 0.0 460.0
3 35 0.0 385.0
4 35 0.0 235.0
5 35 0.0 235.0
6 35 0.0 160.0
7 35 0.0 160.0
SAB N° 01 8 35 160.0 160.0

2.1 35 0.0 75.0


2.2 35 0.0 75.0
2.3 35 0.0 75.0
SAB N° 02 2.4 35 75.0 75.0

3.1 35 0.0 150.0


3.2 35 0.0 100.0
SAB N° 03 3.3 35 100.0 100.0

SAB N° 04 3.1.1 35 50.0 50.0

SAB N° 05 5.1 35 75.0 75.0

Se considera una Caida de tension en el punto de alimentacion = 3%

% ∆V ≤ 3.5%
% ∆V ≤ 6%
% ∆V ≤ 5%
PRACTICA S07-2

EACION DE ALUMINIO AAAC 35 mm2

CALCULO DE LA REACTANCIA INDUCTIVA

Datos de la tabla de especificaciones tecnicas de conductores de AAAC

d1 (m) 1.00 DMG (m) 1.260


d2 (m) 1.00 RMG (m) 0.0027479
d3 (m) 2.00 XL (ohm/Km) 0.4621
r (m) 0.003785

NORMA DGE 018-2003 EM

DISTRIBUCION PRIMARIA Y SECUNDARIA

SISTEMA TRIFASICO
Tensio(KV):
13.2

I L K ∆V ∑∆V %∑∆V
INTENSIDAD LONGITUD FACTOR CAIDA CAIDA DE CAIDA DE TENSION CAIDA DE TENSION
DE CORRIENTE DE TENSION TENSION ACUMULADA ACUMULADA %
(AMP.) (m) (ohm/Km) (V) (V) (%)
20.12 0.0 1.9617 396.00 396.000 3.000
20.12 70.0 1.9617 2.763 398.763 3.021
20.12 90.0 1.9617 3.552 402.315 3.048
16.84 60.0 1.9617 1.982 404.297 3.063
10.28 70.0 1.9617 1.412 405.709 3.074
10.28 100.0 1.9617 2.017 407.725 3.089
7.00 100.0 1.9617 1.373 409.099 3.099
7.00 60.0 1.9617 0.824 409.923 3.105
7.00 70.0 1.9617 0.961 410.884 3.113

3.28 100.0 1.9617 0.643 402.959 3.053


3.28 80.0 1.9617 0.515 403.473 3.057
3.28 90.0 1.9617 0.579 404.052 3.061
3.28 80.0 1.9617 0.515 404.567 3.065

6.56 90.0 1.9617 1.158 405.455 3.072


4.37 90.0 1.9617 0.772 406.227 3.077
4.37 80.0 1.9617 0.686 406.913 3.083

2.19 40.0 1.9617 0.172 405.627 3.073

3.28 80.0 1.9617 0.515 408.240 3.093


1350.0 TOTAL PERDIDAS
mentacion = 3%

Zona Urbana CNE IV (1978)


Zona rural NTCSR
Zona Urbana CNE SUMINISTRO 2011
(7 hilos)
Pp
PERDIDA DE
POTENCIA
(W)
0.00 0.0
87.95 343000.0
113.08 729000.0
52.81 216000.0
22.96 343000.0
32.80 1000000.0
15.21 1000000.0
9.13 216000.0
10.65 343000.0
0.0
3.34 1000000.0
2.67 512000.0
3.01 729000.0
2.67 512000.0
0.0
12.02 729000.0
5.33 729000.0
4.74 512000.0
0.0
0.60 64000.0
0.0
2.67 512000.0
381.64 9489000.0

83.83846903
PRÁCTICA S07-2
Ejercicio N°2
CALCULOS ELECTRICOS PARA UN CONDUCTOR DE ALEACION DE ALUMINIO AAAC

CALCULO DE LA RESISTENCIA A = 40 ºC

Datos de la tabla de especificaciones tecnicas

R20ºc (Ohm/Km) 0.6755


T1 (ºC) 20
T2 (ºC) 40
a (1/ºC) 0.0036
R40ºC (Ohm/Km) 0.7241

CALCULO DEL FACTOR CAIDA DE TENSION (K)

Cos (Ø) 0.9


Sen (Ø) 0.4360
R40º C (Ohm/Km) 0.7241
XL (Ohm/Km) 0.4496
K (Ohm/Km) 1.4683

ANALISIS DE CAIDA DE TENSION EN LA RED PRIMARIA


PROYECTO : SISTEMA DE DISTRIBUCION PRIMARIA Y SECUNDAR

DISTRITO : NUEVO CHIMBOTE


PROVINCIA : SANTA
DEPARTAMENTO : ANCASH

P
U SECCION POTENCIA SUMA I
N CONDUCTOR DE POTENCIA INTENSIDAD
T AAAC TRANSF. TRANSF. DE CORRIENTE
O (mm²) (KVA) (KVA) (AMP.)
PA 50 0.0 720.0 18.15
1 50 0.0 720.0 18.15
2 50 0.0 670.0 16.89
3 50 0.0 410.0 10.34
4 50 0.0 250.0 6.30
5 50 0.0 250.0 6.30
6 50 0.0 250.0 6.30
7 50 0.0 250.0 6.30
8 50 0.0 250.0 6.30
SAB B 9 50 250.0 250.0 6.30

SAB F 1.1 50 50.0 50.0 1.26

3.1 50 0.0 160.0 4.03


3.2 50 0.0 160.0 4.03
3.3 50 0.0 160.0 4.03
SAB A 3.4 50 160.0 160.0 4.03

2.1 50 0.0 260.0 6.56


2.2 50 0.0 210.0 5.29
2.3 50 0.0 210.0 5.29
2.4 50 0.0 50.0 1.26
2.5 50 0.0 50.0 1.26
2.6 50 0.0 50.0 1.26
SAB D 2.7 50 50.0 50.0 1.26

2.1.1 50 0.0 50.0 1.26


2.1.2 50 0.0 50.0 1.26
SAB C 2.1.3 50 50.0 50.0 1.26

SAB E 2.3.1 50 160.0 160.0 4.03

Se considera una Caida de tension en el punto de alimentacion = 3%


% ∆V ≤ 3.5% Zona Urbana
% ∆V ≤ 6% Zona rural
% ∆V ≤ 5% Zona Urbana
PRÁCTICA S07-2

N DE ALUMINIO AAAC 50 mm2

CALCULO DE LA REACTANCIA INDUCTIVA

Datos de la tabla de especificaciones tecnicas de conductores de AAAC

d1 (m) 1.22 DMG (m) 1.277


d2 (m) 1.22 RMG (m) 0.0032852 (7 hilos)
d3 (m) 1.40 XL (ohm/Km) 0.4496
r (m) 0.004525

NORMA DGE 018-2003 EM


PRIMARIA Y SECUNDARIA DE LA LOCALIDAD SANTA DORALIZA

SISTEMA TRIFASICO
Tensio(KV):
22.9

L K ∆V ∑∆V %∑∆V Pp
LONGITUD FACTOR CAIDA CAIDA DE CAIDA DE TENSION CAIDA DE TENSION PERDIDA DE
DE TENSION TENSION ACUMULADA ACUMULADA % POTENCIA
(m) (ohm/Km) (V) (V) (%) (W)
0.0 1.4683 687.00 687.000 3.000 0.00
100.0 1.4683 2.665 689.665 3.012 71.56
90.0 1.4683 2.232 691.897 3.021 55.78
100.0 1.4683 1.518 693.415 3.028 23.23
110.0 1.4683 1.018 694.433 3.032 9.48
80.0 1.4683 0.740 695.173 3.036 6.90
90.0 1.4683 0.833 696.005 3.039 7.76
95.0 1.4683 0.879 696.884 3.043 8.19
85.0 1.4683 0.786 697.670 3.047 7.33
90.0 1.4683 0.833 698.503 3.050 7.76

80.0 1.4683 0.148 689.813 3.012 0.28

90.0 1.4683 0.533 693.948 3.030 3.18


80.0 1.4683 0.473 694.421 3.032 2.82
70.0 1.4683 0.414 694.835 3.034 2.47
60.0 1.4683 0.355 695.190 3.036 2.12

110.0 1.4683 1.060 692.956 3.026 10.28


80.0 1.4683 0.621 693.578 3.029 4.86
90.0 1.4683 0.699 694.277 3.032 5.47
100.0 1.4683 0.185 694.462 3.033 0.34
90.0 1.4683 0.167 694.628 3.033 0.31
80.0 1.4683 0.148 694.776 3.034 0.28
70.0 1.4683 0.130 694.906 3.035 0.24

90.0 1.4683 0.167 693.123 3.027 0.31


80.0 1.4683 0.148 693.271 3.027 0.28
40.0 1.4683 0.074 693.345 3.028 0.14

80.0 1.4683 0.473 694.750 3.034 2.82


2130.0 TOTAL PERDIDAS 234.19
CNE IV (1978)
NTCSR
CNE SUMINISTRO 2011
0.0
1000000.0
729000.0
1000000.0
1331000.0
512000.0
729000.0
857375.0
614125.0
729000.0
0.0
512000.0
0.0
729000.0
512000.0
343000.0
216000.0
0.0
1331000.0
512000.0
729000.0
1000000.0
729000.0
512000.0
343000.0
0.0
729000.0
512000.0
64000.0
0.0
512000.0
16786500.0

88.77491715