Está en la página 1de 9

RIA B, VILLA VICTORIA C, VILLA VICTORIA D Y TRES ESTRELLAS CANTÓN CRUZ PLAYA - CARANAVI

PLANILLA PARA DETERMINAR LA CURVA DIARIA DE CARGA ELÉCTRICA CUADRO 4.1


COM. VILLA VICTORIA B
,
Nº P. Unit. P. Tot. Factor Factor P. Unit.
Categoria y Uso de la Energía 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Cons. Inst. W Inst. W Util(%) Simul(%) Inst. W
1 Cat. Residencial 9
2 Ilum. Residencial 9 200 1.8 70% 85% 1.1 1.1 1.1 1.1 1.1 1.1 1.1
3 Radio 9 20 0.18 100% 70% 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
4 Televisor 2 70 0.14 100% 60% 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
5 Refrigerador 1 180 0.2 100% 100% 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9
6 Ducha 0 4000 0 100% 50% 0.0 0.0 0.0 0.0 0.0
7 Alum. Público 2 70 0.14 100% 100% 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
8 Cat. General 3
9 Escuelas y/o Colegios 0 2000 0 40% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
10 Alcaldia 0 2000 0 60% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
kw
11 Iglesias y/o Templos 0 300 0 60% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
12 Sindicato / SEDE 1 1000 1 50% 100% 0.5 0.5 0.5 0.5 0.5 0.5
13 Posta Sanitaria 0 2000 0 70% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
14 Punto ENTEL 0 1200 0 70% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
15 Tiendas y/o negocioas 2 1000 2 60% 70% 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
16 Cat. Pequeña Industria 1
17 Carpinteria 0 3000 0 70% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
18 Gomería 0 1000 0 50% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
19 Talleres 1 2500 2.5 70% 70% 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
20 Total Usuarios 13
21 Total Potencia [kW] 1.0 1.0 1.0 1.0 1.0 2.1 4.7 3.6 3.1 3.1 3.2 3.2 3.2 2.0 1.8 3.0 3.0 4.9 4.9 4.9 3.2 2.1 1.1 1.0 63.03

Diaría en kWh/día 63.0


Energia Anual (MWh/año) 23.01
CURVA DE CARGA DIARIA
Potencia Media kW 2.63 10.0
Potencia Máxima kW 4.89
9.0
Factor de Carga 54%
8.0

7.0

6.0

5.0
Demanda
kW

4.0

3.0

2.0

1.0

0.0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Horas del día


PLANILLA PARA DETERMINAR LA CURVA DIARIA DE CARGA ELÉCTRICA CUADRO 4.1
COM. VILLA VICTORIA C
,
Nº P. Unit. P. Tot. Factor Factor P. Unit.
Categoria y Uso de la Energía 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Cons. Inst. W Inst. W Util(%) Simul(%) Inst. W
1 Cat. Residencial 44
2 Ilum. Residencial 44 200 8.8 70% 85% 5.2 5.2 5.2 5.2 5.2 5.2 5.2
3 Radio 44 20 0.88 100% 70% 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6
4 Televisor 10 70 0.7 100% 60% 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4
5 Refrigerador 3 180 0.5 100% 100% 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
6 Ducha 2 4000 8 100% 50% 4.0 4.0 4.0 4.0 4.0
7 Alum. Público 4 70 0.28 100% 100% 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
8 Cat. General 3
9 Escuelas y/o Colegios 0 2000 0 40% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
10 Alcaldia 0 2000 0 60% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
kw
11 Iglesias y/o Templos 1 300 0.3 60% 100% 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2
12 Sindicato / SEDE 1 1000 1 50% 100% 0.5 0.5 0.5 0.5 0.5 0.5
13 Posta Sanitaria 0 2000 0 70% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
14 Punto ENTEL 0 1200 0 70% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
15 Tiendas y/o negocioas 1 1000 1 60% 70% 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4
16 Cat. Pequeña Industria 1
17 Carpinteria 0 3000 0 70% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
18 Gomería 0 1000 0 50% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
19 Talleres 1 2500 2.5 70% 70% 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
20 Total Usuarios 48
21 Energía vendida [kWh] 0.8 0.8 0.8 0.8 0.8 6.4 8.5 7.5 7.0 3.0 3.4 3.4 3.2 2.0 1.6 2.4 2.4 9.4 13.4 13.4 7.7 2.3 1.2 0.8 103.1

Diaría en kWh/día 103.06


Energia Anual (MWh/año) 37.62 CURVA DE CARGA DIARIA 2020
15.0
Potencia Media kW 4.29
Potencia Máxima kW 13.42
13.0
Factor de Carga 32%

11.0
Potencia kW

9.0

7.0

5.0

3.0

1.0

-1.0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Horas del día


PLANILLA PARA DETERMINAR LA CURVA DIARIA DE CARGA ELÉCTRICA CUADRO 4.1
COM. VILLA VICTORIA D
,
Nº P. Unit. P. Tot. Factor Factor P. Unit.
Categoria y Uso de la Energía 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Cons. Inst. W Inst. W Util(%) Simul(%) Inst. W
1 Cat. Residencial 27
2 Ilum. Residencial 27 200 5.4 70% 85% 3.2 3.2 3.2 3.2 3.2 3.2 3.2
3 Radio 27 20 0.54 100% 70% 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4
4 Televisor 6 70 0.42 100% 60% 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
5 Refrigerador 2 180 0.4 100% 100% 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4
6 Ducha 1 4000 4 100% 50% 2.0 2.0 2.0 2.0 2.0
7 Alum. Público 3 70 0.21 100% 100% 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2
8 Cat. General 5
9 Escuelas y/o Colegios 1 2000 2 40% 100% 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
10 Alcaldia 0 2000 0 60% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
kw
11 Iglesias y/o Templos 1 300 0.3 60% 100% 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2
12 Sindicato / SEDE 1 1000 1 50% 100% 0.5 0.5 0.5 0.5 0.5 0.5
13 Posta Sanitaria 0 2000 0 70% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
14 Punto ENTEL 0 1200 0 70% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
15 Tiendas y/o negocioas 2 1000 2 60% 70% 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
16 Cat. Pequeña Industria 3
17 Carpinteria 1 3000 3 70% 100% 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
18 Gomería 0 1000 0 50% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
19 Talleres 2 2500 5 70% 70% 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
20 Total Usuarios 35
21 Energía vendida [kWh] 0.6 0.6 0.6 0.6 0.6 4.0 9.8 9.6 9.1 7.1 7.4 7.4 6.4 1.8 2.4 6.7 6.7 11.3 11.2 10.4 5.4 2.0 0.8 0.6 123

Diaría en kWh/día 123.00


Energia Anual (MWh/año) 44.90 CURVA DE CARGA DIARIA 2020
15.0
Potencia Media kW 5.13
Potencia Máxima kW 11.28
Factor de Carga 45% 13.0

11.0
Potencia kW

9.0

7.0

5.0

3.0

1.0

-1.0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Horas del día


PLANILLA PARA DETERMINAR LA CURVA DIARIA DE CARGA ELÉCTRICA CUADRO 4.1
COM. TRES ESTRELLAS
,
Nº P. Unit. P. Tot. Factor Factor P. Unit.
Categoria y Uso de la Energía 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Cons. Inst. W Inst. W Util(%) Simul(%) Inst. W
1 Cat. Residencial 60
2 Ilum. Residencial 60 200 12 70% 85% 7.1 7.1 7.1 7.1 7.1 7.1 7.1
3 Radio 60 20 1.2 100% 70% 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
4 Televisor 14 70 0.98 100% 60% 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6
5 Refrigerador 4 180 0.7 100% 100% 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
6 Ducha 3 4000 12 100% 50% 6.0 6.0 6.0 6.0 6.0
7 Alum. Público 6 70 0.42 100% 100% 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4
8 Cat. General 4
9 Escuelas y/o Colegios 0 2000 0 40% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
10 Alcaldia 0 2000 0 60% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
kw
11 Iglesias y/o Templos 1 300 0.3 60% 100% 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2
12 Sindicato / SEDE 1 1000 1 50% 100% 0.5 0.5 0.5 0.5 0.5 0.5
13 Posta Sanitaria 0 2000 0 70% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
14 Punto ENTEL 0 1200 0 70% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
15 Tiendas y/o negocioas 2 1000 2 60% 70% 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
16 Cat. Pequeña Industria 4
17 Carpinteria 1 3000 3 70% 100% 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
18 Gomería 1 1000 1 50% 100% 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
19 Talleres 2 2500 5 70% 70% 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
20 Total Usuarios 68
21 Energía vendida [kWh] 1.1 1.1 1.1 1.1 1.1 8.7 15.1 14.1 13.6 7.6 8.2 8.2 8.0 3.0 2.3 6.8 6.8 16.3 20.2 19.7 10.7 3.4 1.7 1.1 181.4

Diaría en kWh/día 181.39


Energia Anual (MWh/año) 66.21 CURVA DE CARGA DIARIA 2020
25.0
Potencia Media kW 7.56
Potencia Máxima kW 20.18
Factor de Carga 37%
20.0
Potencia kW

15.0

10.0

5.0

0.0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Horas del día
PLANILLA PARA DETERMINAR LA CURVA DIARIA DE CARGA ELÉCTRICA CUADRO 4.1
DATOS CENTRALIZADOS
,
Nº P. Unit. P. Tot. Factor Factor P. Unit.
Categoria y Uso de la Energía 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Cons. Inst. W Inst. W Util(%) Simul(%) Inst. W
1 Cat. Residencial 140
2 Ilum. Residencial 140 200 28 70% 85% 16.7 16.7 16.7 16.7 16.7 16.7 16.7
3 Radio 140 20 2.8 100% 70% 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
4 Televisor 32 70 2.24 100% 60% 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
5 Refrigerador 10 180 1.8 100% 100% 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
6 Ducha 7 4000 28 100% 50% 14.0 14.0 14.0 14.0 14.0
7 Alum. Público 15 70 1.05 100% 100% 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1
8 Cat. General 15
9 Escuelas y/o Colegios 1 2000 2 40% 100% 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
10 Alcaldia 1 2000 2 60% 100% 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
kw
11 Iglesias y/o Templos 1 300 0.3 60% 100% 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2
12 Sindicato / SEDE 1 1000 1 50% 100% 0.5 0.5 0.5 0.5 0.5 0.5
13 Posta Sanitaria 1 2000 2 70% 100% 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
14 Punto ENTEL 1 1200 1.2 70% 100% 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
15 Tiendas y/o negocioas 4 1000 4 60% 70% 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
16 Cat. Pequeña Industria 9
17 Carpinteria 1 3000 3 70% 100% 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
18 Gomería 1 1000 1 50% 100% 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
19 Talleres 3 2500 7.5 70% 70% 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
20 Total Usuarios 164
21 Energía vendida [kWh] 4.3 4.3 4.3 4.3 4.3 21.8 31.1 30.6 30.1 16.1 17.5 17.5 15.3 9.0 9.2 14.2 14.2 35.7 47.6 45.1 26.9 10.1 6.4 4.3 424

Diaría en kWh/día 424.00


Energia Anual (MWh/año) 154.76 CURVA DE CARGA DIARIA 2020
60.0
Potencia Media kW 17.67
Potencia Máxima kW 47.59
Factor de Carga 37%
50.0
Potencia kW

40.0

30.0

20.0

10.0

0.0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Horas del día
PLANILLA PARA DETERMINAR LA CURVA DIARIA DE CARGA ELÉCTRICA CUADRO 4.1
PROYECCION A 20 AÑOS
,
Nº P. Unit. P. Tot. Factor Factor P. Unit.
Categoria y Uso de la Energía 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Cons. Inst. W Inst. W Util(%) Simul(%) Inst. W
1 Cat. Residencial 208
2 Ilum. Residencial 208 200 41.6 70% 85% 24.8 24.8 24.8 24.8 24.8 24.8 24.8
3 Radio 208 20 4.16 100% 70% 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.9
4 Televisor 48 70 3.36 100% 60% 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
5 Refrigerador 15 180 2.7 100% 100% 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
6 Ducha 10 4000 40 100% 50% 20.0 20.0 20.0 20.0 20.0
7 Alum. Público 22 70 1.5602 100% 100% 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
8 Cat. General 21
9 Escuelas y/o Colegios 4 2000 8 40% 100% 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2
10 Alcaldia 0 2000 0 60% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
kw
11 Iglesias y/o Templos 4 300 1.2 60% 100% 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
12 Sindicato / SEDE 3 1000 3 50% 100% 1.5 1.5 1.5 1.5 1.5 1.5
13 Posta Sanitaria 2 2000 4 70% 100% 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8
14 Punto ENTEL 0 1200 0 70% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
15 Tiendas y/o negocioas 6 1000 6 60% 70% 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
16 Cat. Pequeña Industria 11
17 Carpinteria 6 3000 18 70% 100% 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6 12.6
18 Gomería 0 1000 0 50% 100% 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
19 Talleres 6 2500 15 70% 70% 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4 7.4
20 Total Usuarios 240
21 Energía vendida [kWh] 7.1 7.1 7.1 7.1 7.1 33.2 57.1 56.3 54.8 34.8 36.8 36.8 32.9 12.9 14.0 31.9 31.9 64.6 72.0 68.8 40.0 14.5 9.1 7.1 744.8

Diaría en kWh/día 744.84


Energia Anual (MWh/año) 271.87 CURVA DE CARGA DIARIA 2020
80.0
Potencia Media kW 31.03
Potencia Máxima kW 72.03
70.0
Factor de Carga 43%

60.0

Potencia kW
50.0

40.0

30.0

20.0

10.0

0.0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Horas del día
DOMESTICA

AÑOS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Número de consumidores 140 143 146 149 152 155 158 161 164 167 171 174 178 181 185 188 192 196 200 204
Consumo específico (KWh/Mes-usu) 52 54 56 57 59 61 63 64 66 68 70 73 75 77 79 82 84 87 89 92
Consumo anual(Mwh) 88066 92522 97203 102122 107289 112718 118422 124414 130709 137323 144271 151572 159241 167299 175764 184658 194001 203818 214131 224966
Factor de carga (%) 37% 38% 38% 39% 39% 40% 40% 40% 40% 41% 41% 41% 42% 42% 42% 42% 42% 43% 43% 43%
Facto de difersidad (%)
Factor de potencia 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Demanda máxima (kVA) 88066 92522 97203 102122 107289 112718 118422 124414 130709 137323 144271 151572 159241 167299 175764 184658 194001 203818 214131 224966
Demanda diversificada (kVA)

GENERAL

AÑOS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Número de consumidores 15 15 16 16 16 16 17 17 17 18 18 18 19 19 19 20 20 20 21 21
Consumo específico (KWh/Mes-usu) 202 206 210 214 218 223 227 232 236 241 246 251 256 261 266 271 277 282 288 294
Consumo anual(Mwh) 36284 37676 39122 40622 42181 43799 45479 47223 49035 50916 52869 54897 57003 59189 61460 63817 66265 68807 71447 74188
Factor de carga (%) 37% 38% 38% 39% 39% 40% 40% 40% 40% 41% 41% 41% 42% 42% 42% 42% 42% 43% 43% 43%
Facto de difersidad (%)
Factor de potencia 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Demanda máxima (kVA) 36284 37676 39122 40622 42181 43799 45479 47223 49035 50916 52869 54897 57003 59189 61460 63817 66265 68807 71447 74188
Demanda diversificada (kVA)

ALUMBRADO PÚBLICO

AÑOS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Número de consumidores 15 15 16 16 16 17 17 17 18 18 18 19 19 19 20 20 21 21 21 22
Consumo específico (KWh/Mes-usu) 25.58 25.58 25.58 25.58 25.58 25.58 25.58 25.58 25.58 25.58 25.58 25.58 25.58 25.58 25.58 25.58 25.58 25.58 25.58 25.58
Consumo anual(Mwh) 4604.4 4696.5 4790.4 4886.2 4984 5083.6 5185.3 5289 5394.8 5502.7 5612.7 5725 5839.5 5956.3 6075.4 6196.9 6320.9 6447.3 6576.2 6707.7
Factor de carga (%) 37% 38% 38% 39% 39% 40% 40% 40% 40% 41% 41% 41% 42% 42% 42% 42% 42% 43% 43% 43%
Facto de difersidad (%)
Factor de potencia 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Demanda máxima (kVA) 4604.4 4696.5 4790.4 4886.2 4984 5083.6 5185.3 5289 5394.8 5502.7 5612.7 5725 5839.5 5956.3 6075.4 6196.9 6320.9 6447.3 6576.2 6707.7
Demanda diversificada (kVA)

PEQUEÑA INDUSTRIA
AÑOS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Número de consumidores 9 9 9 9 9 9 10 10 10 10 10 10 10 10 10 10 11 11 11 11
Consumo específico (KWh/Mes-usu) 238.58 242.87 247.25 251.7 256.23 260.84 265.53 270.31 275.18 280.13 285.18 290.31 295.53 300.85 306.27 311.78 317.39 323.11 328.92 334.84
Consumo anual(Mwh) 25767 26493 27239 28007 28796 29608 30442 31300 32182 33089 34021 34980 35966 36979 38021 39093 40194 41327 42492 43689
Factor de carga (%) 37% 38% 38% 39% 39% 40% 40% 40% 40% 41% 41% 41% 42% 42% 42% 42% 42% 43% 43% 43%
Facto de difersidad (%)
Factor de potencia 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Demanda máxima (kVA) 25767 26493 27239 28007 28796 29608 30442 31300 32182 33089 34021 34980 35966 36979 38021 39093 40194 41327 42492 43689
Demanda diversificada (kVA)

TOTAL DEMANDA

AÑOS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Número de consumidores 179 182 186 190 193 197 201 205 209 213 217 221 225 230 234 239 243 248 253 258
Consumo p/específico (MWh/Año) 154721 161387 168355 175637 183250 191208 199527 208226 217320 226830 236774 247173 258049 269423 281320 293765 306782 320399 334646 349550
Demanda máxima (kVA) 154721 161387 168355 175637 183250 191208 199527 208226 217320 226830 236774 247173 258049 269423 281320 293765 306782 320399 334646 349550
Demanda diversificada (kVA)
CUADRO 4.3
- El Boletin REA 45-2 Tabla de demanda proporciona un método de cálculo, para consumos
especificos menores a 50 kWh/mes-consumidor.

C = Número de consumidores


FactorA  C * 1  0,4 * C  0,4 * C 2  40  0, 5

0 ,885
 kwh 
FactorB  0.005925 *  
 mes  usuario 
D max FactorA* FactorB

Consumo Especifico Año = 2041 52.08 (kWh/mes-usurio)

Número de Número de Número de


Nº Poblacion Factor A Factor B Demanda kW
Habitantes Familias Consumidores
1 COM. VILLA VICTORIA B 45 9 9 16.2 0.196 3.17
2 COM. VILLA VICTORIA C 220 44 44 52.0 0.196 10.18
3 COM. VILLA VICTORIA D 135 27 27 34.9 0.196 6.83
4 COM. TRES ESTRELLAS 300 60 60 68.0 0.196 13.31

DEMANDA RESIDENCIAL TOTAL 700 140 140 33.50