VIENE DE TABLERO EXISTENTE VIENE DE TABLERO EXISTENTE

(VER PLANO ALIMENTADORES) (VER PLANO ALIMENTADORES)

3x40A
10kA
DIAGRAMA UNIFILAR 3x40A
10kA
CL 2 # 17-10 OFC 211 PQ. IND SAN JORGE
MOSQUERA - CUNDINAMARCA
TOMAS PUESTOS DE TOMAS PUESTOS DE

LSG CARACOLÍ PISO 14


TRABAJO TRABAJO Y SERVICIO
TOMAS PUESTOS DE TOMAS PUESTOS DE
TOMAS PUESTOS DE TRABAJO TOMAS PUESTOS DE TRABAJO
TRABAJO TRABAJO
TOMAS PUESTOS DE TOMA NEVERA
TOMAS PUESTOS DE TRABAJO TOMA CAFETERA
TRABAJO
TOMAS DE SERVICIO Y TOMA MICROONDAS
MANAGER
RESERVA RESERVA
DEPARTAMENTO SANTANDER

BUCARAMANGA
RESERVA TOMA HIDROSPOT

DPS HOME LINE DPS HOME LINE ENCHUFABLE


RESERVA TOMA DE SERVICIOS DATA
CENTER

MUNICIPIO BUCARAMANGA
TABLERO NORMAL (TN1) TABLERO NORMAL (TN2)
3Ø-12 CIRCUITOS 3Ø-12 CIRCUITOS EDIFICIO CARACOLÍ OFICINA
CARGA INSTALADA: 7,02kVA CARGA INSTALADA: 7,35kVA DIRECCION 14-02, 14-03, 14-06 Y 14-07
CARGA DEMANDADA: 6,31kVA CARGA DEMANDADA: 6,61kVA

VIENE DE TABLERO EXISTENTE VIENE DE TABLERO EXISTENTE


OBSERVACIONES
(VER PLANO DE ALIMENTADORES) (VER PLANO DE ALIMENTADORES)
FECHA VERSIÒN

1 26-01-2022 Versión 01 Geardo Herrera González


2 23-02-2022 Versión 02 Geardo Herrera González
3 16-03-2022 Versión 03 Geardo Herrera González
4 07-04-2022 Versión 04 Geardo Herrera González
TABLERO REGULADO 1 TABLERO REGULADO 2 5
(TR1) 3x40A
10kA
(TR2) 2x40A
10kA
6
CARGA INSTALADA: 9,5 kVA CARGA INSTALADA: 4,6 kVA 7
CARGA DEMANDADA: 9,5 kVA 3F, 1N, 1T,In=250 Amp, Icc=30 kA CARGA DEMANDADA: 4,6 kVA 2F, 1N, 1T,In=125 Amp, Icc=25 kA

3x40 A 3x40 A 3x30 A 2x40 A 2x40 A 2x30 A


10kA 10kA 10kA 10kA 10kA 10kA

3x40 A 2x40 A
10kA 10kA CONVENCIONES
S TOMA DE SERVICIO

TOMA BIFÁSICA

D TOMA TRIFÁSICA

ENTRADA A MUEBLE

TUBERIA POR TECHO Y MURO


P

DT TUBERIA POR PISO

CANALETA BAJANDO
SE CONMUTA EL NEUTRO SE CONMUTA EL NEUTRO
TUBERIA BAJANDO
P

TOMA NORMAL TECHO CAJA DE PASO 10X10


T

TOMA NORMAL PISO DUCTO ELÉCTRICO PROYECTADO


P DESDE PISO ANTERIOR
TOMA GFCI DUCTO ELÉCTRICO EN TECHO

TOMA GFCI PISO CIRCUITO ELÉCTRICO


P NORMAL (F,N,T)
3x40 A 2x40 A CIRCUITO ELÉCTRICO
TOMA REGULADA PISO
REGULADO (F,N,T)
10kA 10kA P

TOMA REGULADA TECHO TABLERO ELÉCTRICO


T
TOMA REGULADA CUATRUPLE EN
CANALETA METÁLICA 12x5cm
T TECHO SIEMPRE EN CAJA 10X10cm

MÓDULO DE TOMAS REGULADAS 120V:


(TR2)

3F, In=80 Amp, Icc=25 kA 3F, In=80 Amp, Icc=25 kA


1x20A 1x20A 1x20A 1x20A 1x20A 1x20A 1x20A 1x20A 1x20A 1x20A 1x20A 1x20A 1x20A 1x20A 1x20A 1x20A 1x20A 1x20A 1x20A 1x20A 1x20A 1x20A 1x20A 1x20A 1x20A 1x20A 1x20A
10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA
1x12 F + 1x12 F + 1x12 F + 1x12 F + 1x12 F + 1x12 F + 1x12 F + 1x12 F + 1x12 F + 1x12 F + 1x12 F + 1x12 F + 1x12 F + 1x12 F + 1x12 F + 1x12 F + 1x12 F + 1x12 F + 1x12 F + 1x12 F +
1x2 N 1x2 N 1x2 N 1x2 N 1x2 N 1x2 N 1x2 N 1x2 N 1x2 N 1x2 N 1x2 N 1x2 N 1x2 N 1x2 N 1x2 N 1x2 N 1x2 N 1x2 N 1x2 N 1x2 N
1x12 T 1x12 T 1x12 T 1x12 T 1x12 T 1x12 T 1x12 T 1x12 T 1x12 T 1x12 T 1x12 T 1x12 T 1x12 T 1x12 T 1x12 T 1x12 T 1x12 T 1x12 T 1x12 T 1x12 T

01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 01 02 03 04 05 06 07 08 09 10 11 12
TOMAS TOMAS TOMAS TOMAS TOMAS TOMAS TOMAS TOMAS TOMAS TOMAS PDU PANEL DE RESERVA TOMA RESERVA TOMAS TOMAS TOMAS TOMAS TOMAS PDU PANEL DE RESERVA RESERVA RESERVA RESERVA RESERVA
PUESTOS PUESTOS PUESTOS PUESTOS PUESTOS PUESTOS PUESTOS PUESTOS PUESTOS PUESTOS GABINETE 1 CONTROL DE EQUIPADA IMPRESORA EQUIPADA PUESTOS PUESTOS PUESTOS PUESTOS PUESTOS GABINETE 2 CONTROL DE EQUIPADA EQUIPADA EQUIPADA EQUIPADA EQUIPADA
DE TRABAJO DE TRABAJO DE TRABAJO DE TRABAJO DE TRABAJO DE TRABAJO DE TRABAJO DE TRABAJO DE TRABAJO DE TRABAJO ACCESO 1 DE TRABAJO DE TRABAJO DE TRABAJO DE TRABAJO DE TRABAJO ACCESO 2

NORMAL REGULADO DISEÑÓ


NORMAL REGULADO ING. GERARDO HERRERA GONZALEZ
MP: CN205-83681

CONSTRUYÓ

CONTENIDO

DIAGRAMA UNIFILAR LSG CARACOLÍ PISO 14

ESCALA ANEXO

SIN ESCALA

FECHA
ABRIL DE 2022
4/9