CALCULO DE PROFUNDIDAD DE EXCAVACIÓN EN EDIFICACIÓN

DATOS:

LONGITUD DE TERRENO 300.00 m Área de Terreno 60000.00 m2


ANCHO TERRENO 200.00 m
TRAMOS X 40
TRAMOS Y 50 VIGAS Columnas
B 5.00 m DIMEN (X) DIMEN (xy) UNICA
L1 6.00 m Peralte= 0.30 m Ancho 0.25 m
TIPO DE SUELO 1 Ancho= 0.25 m Largo 0.30 m
RESIS. SUELO APROX. 22.00 Kg/cm2 Largo Total= 5.00 m Altura 3.00 m
# PISOS 200
ESPESOR LOSA 0.25 m DIMEN ( Y) TABIQUERIA
ANCHO DE ZAPATA PRE. 1.50 m Peralte= 0.30 m Altura 1.13 m
Pe. CONCRETO 2400 kg/m3 Ancho= 0.25 m Ancho o espesor 0.15 m
S/C POR NIEVE 40.00 Kg/m2 Largo Total= 6.00 m Largo 1.50 m
S/C POR USO 350.00 Kg/m2
Tabla N° 01
N° Tipo y condiciones de Suelo Resistencia
1 Roca dura 22.00 Kg/cm2
2 Roca blanda 9.00 Kg/cm2
3 Tosca o arenisca arcillosa 7.00 Kg/cm2
4 Grava conglomerada 6.00 Kg/cm2
5 Grava suelta 3.50 Kg/cm2
6 Arena de grano grueso 1.80 Kg/cm2
7 Arcilla compactada 1.30 Kg/cm2
8 Arena de grano fino 0.80 Kg/cm2
9 Arcilla humeda 0.50 Kg/cm2
Largo = 300.00 m 10 Fango o arcilla empapada 0.00 Kg/cm2

6.00 m

Ancho = 200.00 m 5.00 m

METRADO DE CARGAS DE EDIFICACIÓN

CARGA MUERTA O PERMANENTE (D):


Peso de losa aligerada (e = 0.17) = 350 (Kg/m2) x 5 (m) / 1000 = 1.75 T/m = 10.50 Tn
Peso de los Acabados = 100 (Kg/m2) x 5 (m) / 1000 = 0.50 T/m = 3.00 Tn
Peso de las Vigas sentido ( X) = 2400 (Kg/m3) x 0.3 (m) x 0.25 (m) x 5 (m) / 1000 = 0.90 T/m = 5.40 Tn
Peso de las Vigas sentido ( Y) = 2400 (Kg/m3) x 0.3 (m) x 0.25 (m) x 6 (m) / 1000 = 1.08 T/m = 6.48 Tn
Peso de las columna = 2400 (Kg/m3) x 0.25 (m) x 0.3 (m) x 3 (m) / 1000 = 0.54 T/m = 3.24 Tn
Peso de la Tabiquería = 150 (Kg/m2) x 1.5 (m) x 1.13 (m) / 1000 = 0.25 T/m = 1.53 Tn
Peso de la Cobertura = 0.01025 (Kg/m2) x 5 (m) / 1000 = 0.05 T/m = 0.01 Tn
D = 30.16 Tn
CARGA VIVA O SOBRE CARGA S/C (L):
Peso de la Sobre Carga por uso = 350 (Kg/m2) x 5 (m) x 6 (m) / 1000 L = 10.50 Tn
Peso de la Sobre Carga (S/C) por nieve = 40 (Kg/m2) x 5 (m) / 1000 L = 0.20 T/m L = 1.20 Tn
L = 11.70 Tn

Dtotal= 30.16 Tn Ltotal= 11.70 Tn Total 62.11 Ptotal 12422.33

Ancho zapata 751.43 cm


Ancho zapata 7.51 m

DF = 1.60 m

Profundidad de 12.87 m
P= Excavación
12.87 m

Z= 11.27 m

Hecho por:
CARRION YAUYO, Brayan Anthony
CALCULO DE CANTIDAD DE EXPLORACIONES EN
EDIFICACIONES SEGÚN NORMA E050

Area Techada 60000.00 m2


Descripción BASES DE MAQUINAS Y SIMILARES
# PISOS 200
TIPO DE EDIFICACIÓN -
# PTO. EXPLORACIÓN #N/A
Datos:

ℎ=𝐿𝑛/12 h= 0.46 m
h= 0.50 m

𝑏=ℎ/2 b= 0.25 m
b= 0.25 m

𝑒=𝐿𝑛/25 e= 0.22 m
e= 0.25 m

Sobrecargo por uso Oficinas S/C = 400.00 Kg/m2

Tabiqueria = S. Uso/2 Tabiqueria = 200.00 Kg/m2

Acabados, tableros y paneles ligeros Acabados = 100.00 Kg/m2

Peso de Concreto Armado W. Concreto = 2400.00 Kg/m3

Resistencia a la comprecion del concreto f'c = 350.00 Kg/cm2

Limite elastico del acero fy = 4200.00 Kg/cm2

β1 ≤ 280 kg/cm2 β1 = 0.80

Recubrimiento R= 6.00 cm

b= 0.25 m h= 0.50 m
e= 0.25 m β1 = 0.80
Acabado = 100.00 Kg/m2 Ø= 0.9
Tabiqueria = 200.00 Kg/m2 R= 6.00 cm
S/C = 400.00 Kg/m2 1" = 2.54 cm
f'c = 350.00 Kg/cm2 3/4" = 1.91 cm
fy = 4200.00 Kg/cm2 d= 0.44 m
W. Concreto = 2400 kg/m3 a = d/5 = 8.80 cm
5.50 m

5.50 m

5.50 m

5.50 m

5.50 m

5.00 m
5.00 m 5.00 m

Solución:

METRADO DE CARGAS DE EDIFICACIÓN

CARGA MUERTA O PERMANENTE (WD):


Peso de losa aligerada = 1.84 Tn
Peso de los Acabados = 0.55 Tn
Peso de las Vigas sentido = 0.30 Tn
Peso de la Tabiquería = 1.10 Tn
D = 3.79 Tn
CARGA VIVA O SOBRE CARGA S/C (WL):
Peso de la Sobre Carga (S/C) L = 2.20 Tn

Dtotal= 3.79 Tn Ltotal= 2.20 Tn Wu oTotal = 9.04 T/m


Momento positivo Momento negativos

TRAMO AB y (𝑊𝑢× 〖𝐿𝑛〗 ^2)/11 = 24.867 Tn-m (𝑊𝑢× 〖𝐿𝑛〗 ^2)/24 = 11.397 Tn-m
APOYO A y E =
DE =

TRAMO BC y (𝑊𝑢× 〖𝐿𝑛〗 ^2)/16 = 17.096 Tn-m (𝑊𝑢× 〖𝐿𝑛〗 ^2)/10 = 27.354 Tn-m
APOYO B y D =
CD =

(𝑊𝑢× 〖𝐿𝑛〗 ^2)/11 = 24.867 Tn-m


APOYO C =

APOYO A y E Mu+ = 11.397 Tn-m

As1 = 7.614 cm2


𝐴𝑠1=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 4.300 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As2 = 7.205 cm2


𝐴𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 4.069 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As3 = 7.185 cm2


𝐴𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 4.057 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As (A y E)= 7.18 cm2


APOYO B y D Mu+ = 27.354 Tn-m

As1 = 18.274 cm2


𝐴𝑠1=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 10.319 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As2 = 18.631 cm2


𝐴𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 10.521 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As3 = 18.680 cm2


𝐴𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 10.549 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As(B y D) = 18.68 cm2

APOYO C Mu+ = 24.867 Tn-m

As1 = 16.612 cm2


𝐴𝑠1=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 9.381 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As2 = 16.735 cm2


𝐴𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 9.451 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As3 = 16.750 cm2


𝐴𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 9.459 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As(C) = 16.75 cm2


TRAMO AB y DE Mu+ = 24.867 Tn-m

As1 = 16.612 cm2


𝐴𝑠1=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 9.381 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As2 = 16.735 cm2


𝐴𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 9.451 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As3 = 16.750 cm2


𝐴𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 9.459 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As(AB y DE) = 16.75 cm2

TRAMO BC y CD Mu+ = 17.096 Tn-m

As1 = 11.421 cm2


𝐴𝑠1=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 6.450 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As2 = 11.092 cm2


𝐴𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 6.264 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As3 = 11.067 cm2


𝐴𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 6.249 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As(BC y CD) = 11.07 cm2


PULGADAS ÁREA EN cm2
100.00% 95.00% ∅ 1/4 pulg 0.32cm2
APOYO A y E = 7.18 cm2 6.83 cm2 ∅ 3/8 pulg 0.71cm2
APOYO B y D = 18.68 cm2 17.75 cm2 ∅ 1/2 pulg 1.29cm2
APOYO C = 16.75 cm2 15.91 cm2 ∅ 5/8 pulg 1.99cm2
TRAMO AB y DE = 16.75 cm2 15.91 cm2 ∅ 3/4 pulg 2.84cm2
TRAMO BC y CD = 11.07 cm2 10.51 cm2 ∅ 1 pulg 5.10cm2
∅ 1 3/8 pulg 10.06cm2

Tomaremos el mayor valor de área para diseñar una viga uniforme: 17.746 cm2 =====> Ø= 3 Ø 1" + 2 Ø 3/4" 20.980 cm2

Acero Minimo

As min = 3.430 cm2


𝐴𝑠 𝑚𝑖𝑛=0.70×√(𝑓^′ 𝑐)/𝑓𝑦×𝑏×𝑑

El refuerzo superior sera de 3 Ø 1" entoda la viga y bastones de 2 Ø 3/4" en la zona de los apoyos (20.980 cm2) y refuerzo inferior sera de 3 Ø 1" en toda la viga y un refuerzo central
de 2 Ø 3/4" (20.980 cm2).

DATOS WU = 9.043 T/m


f´c = 350.00 Kg/cm2
Fy = 4200.00 Kg/cm2
WD = 3.79 Tn/m
WL = 2.20 Tn/m h = 0.50m d = 0.44m
arga Sismica = 1.30 Tn/m
cubrimiento = 5.00 cm A B
Ø= 0.85 cm b = 0.25m
5.50m

10.42 Tn

(−)
𝐃𝐅𝐂 (𝐖𝐃)
(+)
10.42 Tn
6.05 Tn

(−)
𝐃𝐅𝐂 (𝐖𝐋)
(+)
6.05 Tn
3.58 Tn

(−)
𝐃𝐅𝐂 (𝐂𝐒)
(+)
3.58 Tn

1) CORTANTES MAXIMOS A LA CARA DE APOYO.

V Max APOYO "A" APOYO "B" 24.87 Tn 𝐕_𝐔𝐀 20.89 Tn CORTANTES CRITICOS A LA DISTANCIA "d"
Vu1 24.87 Tn 24.87 Tn zona critica d = 0.44m VuA 20.89 Tn
Vu2 24.16 Tn 24.16 Tn VuB 20.89 Tn
A B
Vu3 17.01 Tn 17.01 Tn Vu 20.89 Tn d = 0.44m
Vu4 12.95 Tn 12.95 Tn espaciamiento 𝐕_𝐔𝐁 24.87 Tn
Vu5 5.80 Tn 5.80 Tn d = 0.44m 20.89 Tn

2) DISEÑO POR CORTE.


Cortante de Concreto.

Vc = 10906.93 kg/cm
𝑉𝑐=0.53√(𝑓^′ 𝑐)×𝑏𝑤×𝑑 Vc = 10.91 Tn/cm

Calculo de la Cortante de Acero

𝑉𝑠=𝑉𝑢/Ø−𝑉𝑐 Vs = 13.67 Tn/cm


𝑉𝑠=𝑉𝑢/Ø−𝑉𝑐

Espaciamiento considerando estribos de Ø 3/8" en Zona Critica

𝑆=(2𝐴𝑒𝑠𝑡 ×𝑓𝑦×𝑑)/𝑉𝑠 S = 19.16 cm 15.00 cm

Espaciamiento maximo de los Estribos fuera de la Zona Critica. Si: 13.67 Tn/cm ≤ 22.64 Tn/cm

Smax = d/2 Smax = 22.00 cm

Cortantes Resistentes de los Refuerzos a las siguientes distancias.

Zona Critica S = 15cm Vs = ### ØVs = ###


Zona medio S = 20cm Vs = 13120.8 Kg ØVs = 11152.68 Kg
Fuera de Critica S = 20cm Vs = 13120.8 Kg ØVs = 11152.68 Kg

Ubicando ØVs en el D.F.C. Si: Zona media = Fuera de critica


X2 = 0.00m
ØVs = 11642.50 Kg @ 15cm

ØVs = 11152.68 Kg @ 20cm


ØVs = 11152.68 Kg @ 20cm
d = 0.44m 0.10m 2.21m

X2 = 0.00m
X1 = 2.21m
2.31m
2.75m

Est : 1 @ 0.05m, 3 @ 0.15m, 11 @ 0.20m, Rto. @ 0.20m.


3) DISPOSICION DE LA ARMADURA.

1 @ 0.05m
3 @ 0.15m
Rto. @ 0.20m

A B
11 @ 0.20m
5.50m
N° ø (PULG.) AREA As (cm2) α

1 ∅ 1/4 pulg 0.317cm2 1 Muros de albañileria, vigas chatas, losas 1.00


2 ∅ 3/8 pulg 0.712cm2 2 Viga peraltada 0.90
3 ∅ 1/2 pulg 1.266cm2 3 Muro de concreto armado 0.80
4 ∅ 5/8 pulg 1.978cm2
5 ∅ 3/4 pulg 2.849cm2
6 ∅ 1 pulg 5.065cm2
7 ∅ 1 1/8 pulg 6.410cm2
8 ∅ 1 1/4 pulg 7.913cm2
9 ∅ 1 3/8 pulg 9.575cm2

DATOS:

t=𝐿𝑛/25 𝑜 t=𝐿𝑛/20 t= 0.20 m


t= 0.25 m

cos⁡(𝜃)=𝑃𝑎𝑠𝑜/√( 〖𝑃𝑎𝑠𝑜〗 ^2+ 〖𝐶𝑜𝑛𝑡𝑟𝑎𝑝𝑎𝑠𝑜〗 ^2 ) cos(Ө) = 0.8269

ℎ_𝐷=𝑡/cos⁡(𝜃) hD = 24.19 cm

ℎ_𝑚=ℎ_𝐷+𝐶𝑜𝑛𝑡𝑟𝑎𝑝𝑎𝑠𝑜/2 hm = 32.69 cm

Sobrecargo S/C S/C = 400.00 Kg/m2

Acabados, tableros y paneles ligeros Acabados = 100.00 Kg/m2

Peso de Concreto Armado W. Concreto = 2400.00 Kg/m3

Resistencia a la comprecion del concreto f'c = 350.00 Kg/cm2

Limite elastico del acero fy = 4200.00 Kg/cm2

Recubrimiento R= 3.00 cm
Ln = 5.00 m 500.00 cm Paso = 0.25 m 25.00 cm
t= 0.20 m 20.00 cm Contrapaso = 0.17 m 17.00 cm
Acabado = 100.00 Kg/cm2 0.10 Tn/m2 hD = 0.24 m 24.19 cm
S/C = 400.00 Kg/cm2 0.40 Tn/m2 hm = 0.33 m 32.69 cm
f'c = 350.00 Kg/cm2 0.35 Tn/m2 ancho = 1.00 m 100.00 cm
fy = 4200.00 Kg/cm2 4.20 Tn/m2 R= 0.03 m 3.00 cm
. Concreto = 2400 kg/m3 2.40 Tn/m3 d= 0.17 m 17.00 cm
h= 2.55 m 255.00 cm a = d/5 = 0.03 m 3.40 cm

METRADO DE CARGAS (TRAMO INCLINACION)

CARGA MUERTA O PERMANENTE (WD):


Peso propio W. concreto x ancho x hm = 0.78 Tn
Peso acabado acabado x ancho = 0.10 Tn
D = 0.88 T/m
CARGA VIVA O SOBRE CARGA S/C (WL):
Peso de la Sobre Carga (S/C) S/C x ancho L = 0.40 T/m

Dtotal = 0.88 Tn Ltotal = 0.40 Tn Wu1 = 1.92 T/m

METRADO DE CARGAS (DESCANSO)

CARGA MUERTA O PERMANENTE (WD):


Peso propio W. concreto x ancho x hm = 0.48 Tn
Peso acabado acabado x ancho = 0.10 Tn
D = 0.58 T/m
CARGA VIVA O SOBRE CARGA S/C (WL):
Peso de la Sobre Carga (S/C) S/C x ancho L = 0.40 T/m

Dtotal = 0.58 Tn Ltotal = 0.40 Tn Wu2 = 1.49 T/m

Wu2 = 1.92 T/m


Wu1 = 1.49 T/m Wu1 = 1.49 T/m

1.25m 2.50m 1.25m


L1 L2 L3
Calculando la reacción de A

RA = RB

RA = 4.26 Tn RB = 4.26 Tn

Momento ultimo máximo al centro del tramo de la escalera

𝑀_(𝑢
𝑚𝑎𝑥)=𝑅_𝐴×(𝐿_1+𝐿_2/2)−𝑊_𝑢1×𝐿_1×((𝐿_1+𝐿_2)/2)−𝑊_𝑢2×( 〖𝐿 _2 〗 ^2 Mu max = 5.662 Tn-m
/2)

Calculando el momento de diseño 2 Viga peraltada

Donde α = 0.9
+𝑀_𝑑𝑖𝑠𝑒ñ𝑜=𝛼𝑀_(𝑢 𝑚𝑎𝑥) (+) Mdiseño = 5.095 Tn-m

−𝑀_𝑑𝑖𝑠𝑒ñ𝑜=1/2 𝑀_𝑑𝑖𝑠𝑒ñ𝑜 (-) Mdiseño = 2.548 Tn-m

Acero positivo

As1 = 8.81 cm2


𝐴𝑠1=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 1.24 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As2 = 8.23 cm2


𝐴𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 1.16 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As3 = 8.21 cm2


𝐴𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 1.16 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

(+)As = 8.21 cm2

Usando ∅ 1/2 pulg 𝑠= (𝐴𝑡. 𝐴𝑐𝑒𝑟𝑜)/𝐴𝑠 s= 0.154 m


s= 0.125 m
Acero negativo

As1 = 4.41 cm2


𝐴𝑠1=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 0.62 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As2 = 4.04 cm2


𝐴𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 0.57 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As3 = 4.03 cm2


𝐴𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 0.57 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

(+)As = 4.03 cm2

Usando ∅ 3/8 pulg 𝑠= (𝐴𝑡. 𝐴𝑐𝑒𝑟𝑜)/𝐴𝑠 s= 0.177 m


s= 0.200 m

Acero Minimo

𝐴𝑠 𝑚𝑖𝑛=0.0018×𝐵×𝑡 As min = 3.600 cm2

Usando ∅ 3/8 pulg 𝑠= (𝐴𝑡. 𝐴𝑐𝑒𝑟𝑜)/𝐴𝑠 s= 0.198 m


s= 0.200 m
Diseño de Escalera

∅ 1/2 pulg @ 0.125m.

1.54 m

4.63 m

∅ 3/8 pulg @ 0.200m.

∅ 3/8 pulg @ 0.200m.

∅ 1/2 pulg @ 0.125m.


1.54 m

∅ 3/8 pulg @ 0.200m.


∅ 3/8 pulg @ 0.200m.
∅ 3/8 pulg @ 0.200m.

∅ 3/8 pulg @ 0.200m.


f´c = 350.00 Kg/cm2 0.35 Tn/m2 S. ult. Nivel = 250.00 Kg/cm2 0.25 Tn/m2
TIPO DE COLUMNA ʎ Ƞ
S/C = 400.00 Kg/cm2 0.40 Tn/m2 S. Tipica = 100.00 Kg/cm2 0.10 Tn/m2
Acabados = 100.00 Kg/cm2 0.10 Tn/m2 # Pisos = 5.00 CENTRAL 1.10 0.30
Tabiqueria T.= 100.00 Kg/cm2 0.10 Tn/m2 PERIMETRAL 1.25 0.25
abiqueria UN = 50.00 Kg/cm2 0.05 Tn/m2 ESQUINA 1.50 0.20
ꝩc = 2400 kg/m3 2.40 Tn/m3

COLUMNA CENTRAL Vigas en Y Vigas en X

2.35 m
0.40 m
2.45 m
0.60 m
0.30 m
4.90 m 5.50 m 15.50 m
0.30 m Columna

2.45 m
2.35 m 0.60 m
4.70 m
5.00 m 0.40 m

DESCRIPCION # PISOS ÁREA (m2) LONGITUD (m) PESO (t/m2) PESO (t)
Peso acabado 5.00 27.50 m2 0.10 Tn/m2 13.75 Tn
Peso Tabiqueria Tipica 4.00 27.50 m2 0.10 Tn/m2 11.00 Tn
Peso Tabiqueria Ultimo Nivel 1.00 27.50 m2 0.05 Tn/m2 1.38 Tn
Peso de Losa 5.00 27.50 m2 0.40 Tn/m2 55.00 Tn
CARGA
MUERT DESCRIPCION # PISOS SECCION (m2) LONGITUD (m) PESO (t/m2) PESO (t)
A Vigas en direccion X 5.00 0.12 m2 4.70 m 2.40 Tn/m3 6.77 Tn
Vigas en direccion Y 5.00 0.18 m2 4.90 m 2.40 Tn/m3 10.58 Tn
Columna 50 x 50 1.00 0.24 m2 15.50 m 2.40 Tn/m3 8.93 Tn

CARGA MUERTA 107.41 Tn

DESCRIPCION # PISOS SECCION (m2) LONGITUD (m) PESO (t/m2) PESO (t)
CARGA Sobrecarga Tipica 4.00 27.50 m2 0.10 Tn/m3 11.00 Tn
MUERT Sobrecarga Ultimo Nivel 1.00 27.50 m2 0.25 Tn/m3 6.88 Tn
A
CARGA VIVA 17.88 Tn
CARGA EN SERVICIO (CARGA VIVA + CARGA MUERTA) 125.28 Tn

CARGA ULTIMA (1.40 x CARGA MUERTA + 1.70 x CARGA VIVA) 180.75 Tn

Acolumna = 1312.46 cm2


𝐴𝑐𝑜𝑙𝑢𝑚𝑛𝑎=(ʎ×𝐶. 𝑆𝐸𝑅𝑉𝐼𝐶𝐼𝑂)/(Ƞ×𝑓^′ 𝑐)

LARGO ANCHO SECCION (cm2) CONDICIÓN


35.00 cm 45.00 cm 1575.00 cm2 CUMPLE
DIMENSIONES DE COLUMNA 35.00 cm 40.00 cm 1400.00 cm2 CUMPLE
(ASUMIENDO TOMANDO EN 40.00 cm 35.00 cm 1400.00 cm2 CUMPLE
BASE EL ÁREA DE COLUMNA) 40.00 cm 30.00 cm 1200.00 cm2 NO CUMPLE
45.00 cm 25.00 cm 1125.00 cm2 NO CUMPLE
45.00 cm 20.00 cm 900.00 cm2 NO CUMPLE

Por cuestion de economia tomaremos: (TOMAR VALORES


1400.00 cm2
QUE CUMPLAN)

COLUMNA PERIMETRAL Vigas en Y Vigas en X

0.40 m
2.45 m
0.60 m
0.30 m
4.90 m 5.50 m
0.30 m Columna

2.45 m
0.60 m
2.20 m
2.50 m 0.30 m

DESCRIPCION # PISOS ÁREA (m2) LONGITUD (m) PESO (t/m2) PESO (t)
Peso acabado 5.00 13.75 m2 0.10 Tn/m2 6.88 Tn
Peso Tabiqueria Tipica 4.00 13.75 m2 0.10 Tn/m2 5.50 Tn
Peso Tabiqueria Ultimo Nivel 1.00 13.75 m2 0.05 Tn/m2 0.69 Tn
Peso de Losa 5.00 13.75 m2 0.40 Tn/m2 27.50 Tn
CARGA
MUERT
A
CARGA
MUERT DESCRIPCION # PISOS SECCION (m2) LONGITUD (m) PESO (t/m2) PESO (t)
A Vigas en direccion X 5.00 0.12 m2 2.20 m 2.40 Tn/m3 3.17 Tn
Vigas en direccion Y 5.00 0.00 m2 4.90 m 2.40 Tn/m3 0.00 Tn
Columna 50 x 50 1.00 0.18 m2 15.50 m 2.40 Tn/m3 6.70 Tn

CARGA MUERTA 50.43 Tn

DESCRIPCION # PISOS SECCION (m2) LONGITUD (m) PESO (t/m2) PESO (t)
CARGA Sobrecarga Tipica 4.00 13.75 m2 0.10 Tn/m3 5.50 Tn
MUERT Sobrecarga Ultimo Nivel 1.00 13.75 m2 0.25 Tn/m3 3.44 Tn
A
CARGA VIVA 8.94 Tn

CARGA EN SERVICIO (CARGA VIVA + CARGA MUERTA) 59.36 Tn

CARGA ULTIMA (1.40 x CARGA MUERTA + 1.70 x CARGA VIVA) 85.79 Tn

Acolumna = 848.06 cm2


𝐴𝑐𝑜𝑙𝑢𝑚𝑛𝑎=(ʎ×𝐶. 𝑆𝐸𝑅𝑉𝐼𝐶𝐼𝑂)/(Ƞ×𝑓^′ 𝑐)

LARGO ANCHO SECCION (cm2) CONDICIÓN


20.00 cm 50.00 cm 1000.00 cm2 CUMPLE
DIMENSIONES DE COLUMNA 20.00 cm 45.00 cm 900.00 cm2 CUMPLE
(ASUMIENDO TOMANDO EN 25.00 cm 40.00 cm 1000.00 cm2 CUMPLE
BASE EL ÁREA DE COLUMNA) 25.00 cm 35.00 cm 875.00 cm2 CUMPLE
30.00 cm 30.00 cm 900.00 cm2 CUMPLE
30.00 cm 25.00 cm 750.00 cm2 NO CUMPLE

Por cuestion de economia tomaremos: (TOMAR VALORES


875.00 cm2
QUE CUMPLAN)

COLUMNA ESQUINA Vigas en Y Vigas en X

0.40 m
2.15 m
0.60 m
2.75 m
2.75 m
0.30 m

0.30 m Columna
2.20 m
2.50 m
0.40 m

0.40 m

DESCRIPCION # PISOS ÁREA (m2) LONGITUD (m) PESO (t/m2) PESO (t)
Peso acabado 5.00 6.88 m2 0.10 Tn/m2 3.44 Tn
Peso Tabiqueria Tipica 4.00 6.88 m2 0.10 Tn/m2 2.75 Tn
Peso Tabiqueria Ultimo Nivel 1.00 6.88 m2 0.05 Tn/m2 0.34 Tn
Peso de Losa 5.00 6.88 m2 0.40 Tn/m2 13.75 Tn
CARGA
MUERT DESCRIPCION # PISOS SECCION (m2) LONGITUD (m) PESO (t/m2) PESO (t)
A Vigas en direccion X 5.00 0.12 m2 2.20 m 2.40 Tn/m3 3.17 Tn
Vigas en direccion Y 5.00 0.18 m2 2.15 m 2.40 Tn/m3 4.64 Tn
Columna 50 x 50 1.00 0.16 m2 15.50 m 2.40 Tn/m3 5.95 Tn

CARGA MUERTA 34.05 Tn

DESCRIPCION # PISOS SECCION (m2) LONGITUD (m) PESO (t/m2) PESO (t)
CARGA Sobrecarga Tipica 4.00 6.88 m2 0.10 Tn/m3 2.75 Tn
MUERT Sobrecarga Ultimo Nivel 1.00 6.88 m2 0.25 Tn/m3 1.72 Tn
A
CARGA VIVA 4.47 Tn

CARGA EN SERVICIO (CARGA VIVA + CARGA MUERTA) 38.51 Tn

CARGA ULTIMA (1.40 x CARGA MUERTA + 1.70 x CARGA VIVA) 55.26 Tn

Acolumna = 825.30 cm2


𝐴𝑐𝑜𝑙𝑢𝑚𝑛𝑎=(ʎ×𝐶. 𝑆𝐸𝑅𝑉𝐼𝐶𝐼𝑂)/(Ƞ×𝑓^′ 𝑐)

LARGO ANCHO SECCION (cm2) CONDICIÓN


20.00 cm 50.00 cm 1000.00 cm2 CUMPLE
DIMENSIONES DE COLUMNA 20.00 cm 45.00 cm 900.00 cm2 CUMPLE
(ASUMIENDO TOMANDO EN
BASE EL ÁREA DE COLUMNA)
DIMENSIONES DE COLUMNA
(ASUMIENDO TOMANDO EN 25.00 cm 40.00 cm 1000.00 cm2 CUMPLE
BASE EL ÁREA DE COLUMNA) 25.00 cm 35.00 cm 875.00 cm2 CUMPLE
30.00 cm 30.00 cm 900.00 cm2 CUMPLE
30.00 cm 25.00 cm 750.00 cm2 NO CUMPLE

Por cuestion de economia tomaremos: (TOMAR VALORES 875.00 cm2


QUE CUMPLAN)
Datos:

b= 0.25 m h= 0.50 m
WD = 2.60 T/m β1 = 0.85
WL = 1.40 T/m Ø= 0.9
f'c = 210.00 Kg/cm2 Recubrimiento = 4.00 cm
fy = 4200.00 Kg/cm2 3/8" = 0.95 cm
1" = 2.54 cm L= 7.00 m

Solución:

Wu oTotal = 6.02 T/m

−𝑀𝑢 𝑚𝑎𝑥=(𝑊𝑢×𝐿^2)/12

-Mu max = 24.58 Tn-m

𝐴𝑠=𝑀_𝑈/(Ø×𝑓𝑦(0.9𝑑))

As = 17.52 cm2

d= 41.24 cm

b min = 27.06 cm

𝑃𝑏=β_1×0.85×(𝑓^′ 𝑐)/𝑓𝑦 (6000/(6000+𝑓𝑦)) Pb = 0.0213

P= 0.0170
𝑃=𝐴𝑠/(𝑏×𝑑)

Zona sismica: Pmax = 0.5 Pb Pmax = 0.0106

Se necesita A's

P1 = Pmax = 0.0106 As1 = P1 x b x d As1 = 10.95 cm2

a= 10.31 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

Mu1 = 14.94 Tn-m


𝑀_𝑈1=∅𝐴𝑠1×𝑓𝑦×(𝑑−𝑎/2)

Mu2 = 9.64 Tn-m


𝑀_𝑈2=𝑀𝑢−𝑀𝑢1
𝑀_𝑈2=𝑀𝑢−𝑀𝑢1

Usar 4 Ø 1" = 20.26 cm2 d' = 6.22 cm


o 3 Ø 1"+ 1 Ø 7/8" = 19.06 cm2

As2 = 7.28 cm2


𝐴2𝑠=𝑀_𝑈2/(∅𝑓𝑦(𝑑−𝑑^′))

As = As1 + As2 As = 18.24 cm2

c= 12.13 cm
𝑐=𝑎/𝛽1

f's = 2.92 Tn/cm2


𝑓′𝑠=6×((𝑐−𝑑^′))/𝑐

A's = 10.46 cm2


𝐴′𝑠=𝑀_𝑈2/(∅𝑓^′ 𝑠(𝑑−𝑑^′))

Usar 2 Ø 1"+ 1 Ø 5/8" = 12.11 cm2


Datos:

WD = 0.20 T/m h= 0.20 m


WL = 0.08 T/m β1 = 0.85
f'c = 210.00 Kg/cm2 Ø= 0.9
fy = 4200.00 Kg/cm2 Ln = 4.20 m

Solución:

Wu oTotal = 0.416 T/m

Momento positivo

(𝑊𝑢× 〖𝐿𝑛〗 ^2)/11 = 0.667 Tn-m

(𝑊𝑢× 〖𝐿𝑛〗 ^2)/16 = 0.459 Tn-m

Momento negativos

(𝑊𝑢× 〖𝐿𝑛〗 ^2)/24 = 0.306 Tn-m

(𝑊𝑢× 〖𝐿𝑛〗 ^2)/10 = 0.734 Tn-m

(𝑊𝑢× 〖𝐿𝑛〗 ^2)/11 = 0.667 Tn-m


Mu+ = 0.667 Tn-m

Ancho M. + = b = 40.00 cm Ancho M. - = bw = 10.00 cm Peralte efec = d = 0.17 m

a = d/5 a= 0.034 cm

As1 = 1.153 cm2


𝐴𝑠1=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 0.679 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As2 = 1.059 cm2


𝐴𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 0.623 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As3 = 1.058 cm2


𝐴𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 0.622 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

a < hf

Mu- = 0.306 Tn-m Mu- = 0.734 Tn-m Mu- = 0.667 Tn-m


a (cm) As (cm2) a (cm) As (cm2) a (cm) As (cm2)
3.400 0.529 3.400 1.269 3.400 1.153
1.244 0.494 2.986 1.252 2.714 1.128
1.162 0.493 2.946 1.250 2.655 1.126
1.159 0.493 2.942 1.250 2.650 1.126
1.159 0.493 2.942 1.250 2.650 1.126

Mu- = 0.667 Tn-m Mu- = 0.459 Tn-m


a (cm) As (cm2) a (cm) As (cm2)
3.400 1.153 3.400 0.793
0.678 1.059 0.467 0.724
0.623 1.058 0.426 0.723
0.622 1.057 0.425 0.723
0.622 1.057 0.425 0.723

As min = 0.469 cm2


𝐴𝑠 𝑚𝑖𝑛=0.80×√(𝑓^′ 𝑐)/𝑓𝑦×𝑏𝑤×𝑑
Fuerzas Cortantes

Vc = 1.310 Tn
𝑉𝑐=1.50×(1/2)×𝑊𝑢×𝐿𝑛

Vc = 0.874 Tn
𝑉𝑐=(1/2)×𝑊𝑢×𝐿𝑛

h= 0.20 m bw = 0.10 m f'c = 210.00 Kg/cm2

Vc = 1.306 Tn ØVc = 1.110 Tn

Observamos que el cortante ultimo excede al cortante resistido por el alma de la vigueta; es necesario colocar ensanche.

bw = 0.25 m

Vc = 3.264 Tn ØVc = 2.775 Tn


Datos:

b= 0.35 m h= 0.70 m a=
f'c = 210.00 Kg/cm2 β1 = 0.85
fy = 4200.00 Kg/cm2 Ø= 0.90
Mu- = 37.00 Tn-m L= 8.00 m
Mu+ = 40.00 Tn-m d= 0.64 m

Solución:

As1 =
𝐴𝑠1=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a=
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As2 =
𝐴𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))
𝐴𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a=
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As3 =
𝐴𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a=
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

Por lo tanto el área de acero a utilizar para los apoyos sera: As =

Considerando d= 0.64 m a= 0.13 m

A's1 =
𝐴′𝑠1=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a=
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

A's2 =
𝐴′𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a=
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

A's3 =
𝐴′𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a=
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

Por lo tanto el área de acero a utilizar para los apoyos sera: A's =

Acero Minimo

As min =
𝐴𝑠 𝑚𝑖𝑛=0.70×√(𝑓^′ 𝑐)/𝑓𝑦×𝑏𝑤×𝑑

2 Ø 1" + 3 Ø 3/4" 18.675 cm2

El refuerzo superior sera de 2 Ø 1" entoda la viga y bastones de 3 Ø 3/4" en la zona de los apoyos (18.675 cm2) y
refuerzo inferior sera de 2 Ø 1" en toda la viga y un refuerzo central de 3 Ø 3/4" (18.675 cm2).

Diseño por Corte Vu = 33.000 Tn

𝑉𝑐=0.53√(𝑓^′ 𝑐)×𝑏𝑤×𝑑
Vc =
𝑉𝑐=0.53√(𝑓^′ 𝑐)×𝑏𝑤×𝑑

Cortante Nominal

Vn =
𝑉𝑛=𝑉𝑢/Ø

Calculando el cortante de acero

Vs =
𝑉𝑠=𝑉𝑢/Ø−𝑉𝑐

Tenemos Vn ≥ Vc y Vs ≤ 2Vc

Considerando estribos de Ø 3/8"

S=
𝑆=(2𝐴𝑒𝑠𝑡 ×𝑓𝑦×𝑑)/𝑉𝑠

De la recomendaciones del ACI tenemos que el espaciamiento maximo en la zona de confinamiento es:

d/4 =
𝑆𝑚𝑎𝑥≤(𝑑/4;6Ø𝑏𝑙 𝑚𝑖𝑛;15𝑐𝑚) 6 Ø bl min =
15 cm =

Espaciamiento maximo en la zona central

S = d/2 d/2 =

Por lo tanto consideramos la longitud de confinamiento Lo = 2h = 1.40 m, nuestra distribución de estribos


serala siguiente:

Est : Ø3/8": 1@0.05,14@0.10,3@0.15,Rto@0.25m c/e


0.13 m

16.994 cm2

11.424 cm

16.793 cm2
11.290 cm

16.774 cm2

11.276 cm

16.774 cm2

18.372 cm2

12.351 cm

18.300 cm2

12.303 cm

18.293 cm2

12.298 cm

18.293 cm2

5.410 cm2

los apoyos (18.675 cm2) y


4" (18.675 cm2).
17.204 Tn

38.824 Tn

21.619 Tn

17.617 cm

a zona de confinamiento es:

16.000 cm
11.430 cm
15.000 cm

32.000 cm

estra distribución de estribos


LOSAS ALIGERADAS

DEFINICION

Las losas son elementos encargados de recibir las cargas de gravedad y transmitirlas a
las vigas.
tambien tienen la funcion de diagrama rigido que conecta los elementos estructurales
garantizando un desplazamiento compatible.

ELEMENTOS DE LOSAS ALIGERADAS

SON 3:

LADRILLO DE TECHO ACERO

CONCRETO

F'c = 210 kg/m2

F'y = 4200 kg/m2

Peralte = H = 20 cm

Base = b = 10 cm

Peralte efectivo = d = 17 cm

Ancho Tributario = 40 cm
EJERCICIO 01

LUZ MENOR

LUZ MENOR

EJERCICIO 02

LUZ MENOR
b) METRADO DE CARGAS

CARGA MUERTA (WD)

TABIQUERIA = 150 kg/m2 x 0.40 m 60 kg/m


ACABADO = 100 kg/m2 x 0.40 m 40 kg/m
CIELO RASO = 50 kg/m2 x 0.40 m 20 kg/m
ALIGERADO = 300 kg/m2 x 0.40 m 120 kg/m
TOTAL = 240 kg/m

CARGA VIVA (WL)

S/C = 200 kg/m2 x 0.4 m = 80 kg/m

CARGA ULTIMA (WU)

Wu = 1.5 240 kg/m + 1.8 80 kg/m

Wu = 504 kg/m
1.20 > = LUZ MAYOR
LUZ MENO

4.50 = 1.1 4.20 = 1.05


4.00 4.00

4.20 = 1.11
3.80
APOYO A = 4.50

APOYO A = 4.5 + 4.0 = 4.25


2
APOYO A = 4.2 + 4.0 = 4.10
2
APOYO A = 4.2 + 3.8 = 4.00
2
APOYO E = 3.80

MA = 504 x 20.25 = 425 kg.m = 0.43 Tn-m


24

MB = 504 x 18.06 = 910 kg.m = 0.91 Tn-m


10

MC = 504 x 16.81 = 770 kg.m = 0.77 Tn-m


11

MD = 504 x 16 = 806 kg.m = 0.81 Tn-m


10

ME = 504 x 14.44 = 303 kg.m = 0.30 Tn-m


24
MAB = 504 x 20.25 = 928 kg.m = 0.93 Tn-m
11

MBC = 504 x 16 = 504 kg.m = 0.50 Tn-m


16

MCD = 504 x 17.64 = 556 kg.m = 0.56 Tn-m


16

MDE = 504 x 14.44 = 662 kg.m = 0.66 Tn-m


11

RESUMEN DE MOMENTOS
Datos
fy = 4200.00 Kg/cm2
f'c = 210.00 Kg/cm2
h= 0.20 m 20.00 cm
b= 0.10 m 10.00 cm
d= 0.17 m 17.00 cm
a = d/5 = 0.03 cm 3.40 cm
Ø= 0.9 0.9

Momentos Negativos Momentos Positivos


MA = 0.43 Tn-m MAB = 0.93 Tn-m
MB = 0.91 Tn-m MBC = 0.50 Tn-m
MC = 0.77 Tn-m MCD = 0.56 Tn-m
MD = 0.81 Tn-m MDE = 0.66 Tn-m
ME = 0.30 Tn-m

Para el apoyo A

As1 = 0.74 cm2


𝐴𝑠1=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 1.73 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As2 = 0.70 cm2


𝐴𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 1.64 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As3 = 0.70 cm2


𝐴𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 1.64 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As(A) = 0.70 cm2

Para el apoyo B

As1 = 1.57 cm2


𝐴𝑠1=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 3.70 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As2 = 1.59 cm2


𝐴𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 3.74 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As3 = 1.59 cm2


𝐴𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 3.74 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)
As(B) = 1.59 cm2
Para el apoyo C

As1 = 1.33 cm2


𝐴𝑠1=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 3.13 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As2 = 1.32 cm2


𝐴𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 3.11 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As3 = 1.32 cm2


𝐴𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 3.10 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As(C) = 1.32 cm2

Para el apoyo D

As1 = 1.39 cm2


𝐴𝑠1=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 3.28 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As2 = 1.39 cm2


𝐴𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 3.27 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As3 = 1.39 cm2


𝐴𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 3.27 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As(D) = 1.39 cm2

Para el apoyo E

As1 = 0.52 cm2


𝐴𝑠1=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 1.23 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As2 = 0.49 cm2


𝐴𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 1.15 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As3 = 0.49 cm2


𝐴𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 1.15 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)
As(E) = 0.49 cm2
Para el tramo AB

As1 = 1.60 cm2


𝐴𝑠1=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 3.77 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As2 = 1.62 cm2


𝐴𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 3.82 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As3 = 1.63 cm2


𝐴𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 3.83 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As(AB) = 1.63 cm2

Para el tramo BC

As1 = 0.87 cm2


𝐴𝑠1=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 2.05 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As2 = 0.83 cm2


𝐴𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 1.96 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As3 = 0.83 cm2


𝐴𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 1.96 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As(BC) = 0.83 cm2

Para el tramo CD

As1 = 0.96 cm2


𝐴𝑠1=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 2.26 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As2 = 0.93 cm2


𝐴𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 2.18 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As3 = 0.92 cm2


𝐴𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 2.17 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)
As(CD) = 0.92 cm2
Para el tramo DE

As1 = 1.14 cm2


𝐴𝑠1=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 2.69 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As2 = 1.12 cm2


𝐴𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 2.63 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As3 = 1.12 cm2


𝐴𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

a= 2.63 cm
𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

As(DE) = 1.12 cm2


100.00% 95.00% Ø
As(A) = 0.70 cm2 0.66 cm2 3/8 pulg
As(B) = 1.59 cm2 1.51 cm2 1/2 pulg 3/8 pulg
As(C) = 1.32 cm2 1.25 cm2 1/2 pulg
As(D) = 1.39 cm2 1.32 cm2 1/2 pulg 3/8 pulg
As(E) = 0.49 cm2 0.46 cm2 3/8 pulg

100.00% 95.00% Ø
As(AB) = 1.63 cm2 1.55 cm2 1/2 pulg 3/8 pulg
As(BC) = 0.83 cm2 0.79 cm2 1/2 pulg
As(CD) = 0.92 cm2 0.88 cm2 1/2 pulg
As(DE) = 1.12 cm2 1.06 cm2 1/2 pulg

L1 L2 L3 L4
CORTE DE VARILLAS:
LUZ = 4.50 m 4.00 m 4.20 m 3.80 m

Varilla Coeficiente Longitud Varilla Coeficiente Longitud


a1 L1/5 0.90 m c4 L3/3 1.40 m
a2 L1/7-Lo 0.45 m c5 L3/4 1.05 m
b1 L1/3 1.50 m c6 L3/6-Lo 0.70 m
b2 L1/4 1.15 m d1 L3/3 1.40 m
b3 L1/6-Lo 0.55 m d2 L3/4 1.05 m
b4 L2/3 1.35 m d3 L3/6-Lo 0.70 m
b5 L2/4 1.00 m d4 L4/3 1.30 m
b6 L2/6-Lo 0.45 m d5 L4/4 0.95 m
c1 L2/3 1.35 m d6 L4/6-Lo 0.60 m
c2 L2/4 1.00 m e1 L4/5 0.80 m
c3 L2/6-Lo 0.65 m e2 L4/7-Lo 0.35 m
Criterio Personal

Donde la máxima separación de varillas en 5t o 5 veces el espesor del recubrimiento de la losa

Rec. Losa = 5.00 cm

Sep. Var. = 25.00 cm

Ø 1/4 @ 0.25 m
Diseñar la loza maciza para cubrir los paños de la estructura mostrada en la figura, considerar:

f´c = 210.00 Kg/cm2


Fy = 4200.00 Kg/cm2
SOBRE CARGA S/C = 500.00 Kg/cm2
P. Acabados = 100.00 Kg/cm2
P. Tabiqueria = 100.00 Kg/cm2
B= 1.00 m
ꝩc = 2400 kg/m3
Ø= 0.90

1) CALCULO DEL ESPESOR DE LOSA MACIZA.

Un extremo continuo: h=Ln/24 0.166666666667 0.15 m


Ambos extremos continuos: h=Ln/28 0.160714285714 0.15 m

2) METRADO DE CARGAS.

CARGA MUERTA O PERMANENTE (WD):


Peso de losa maciza h x B x ꝩc = 360.00 Kg/m
Peso de los Acabados B x P. Acabados = 100.00 Kg/m
Peso de la Tabiquería B x P. Tabiqueria = 100.00 Kg/m
560.00 Kg/m
CARGA VIVA O SOBRE CARGA S/C (WL):
Peso de la Sobre Carga (S/C) Sobre Carga S/C x B = 500.00 Kg/m

Dtotal= 560.00 Kg/m Ltotal= 500.00 Kg/m Wu o Total = 1634.00 Kg/m


Wu o Total = 1.63 T/m

3) CALCULO DE LOS MOMENTOS MAXIMOS USANDO METODO DE LOS COEFICIENTES.

WU = 1.634 T/m

4.00 m 4.50 m 4.00 m

2.96 Tn.m 2.96 Tn.m


1.09 Tn.m 1.09 Tn.m

1.87 Tn.m 1.87 Tn.m

2.07 Tn.m

4) DISEÑO POR FLEXION.

15.00cm 12.00cm

1.00 m
Calculo de refuerzo negativo

Apoyo A = Apoyo D

𝑃𝑚=0.85−√(0.7225−(1.7×𝑀𝑢)/(∅×𝑓^′
Cuantia Mecanica𝑐×𝑏×𝑑^2 ))

Pm = 0.041

Cuantia Maxima 𝑃𝑚𝑎𝑥=𝑃𝑚×(𝑓^′ 𝑐)/𝑓𝑦

Pmax = 0.002

Verificanto tipo de falla: P = 0.007


P > Pmax FALLA DUCTIL

Área del acero

𝐴𝑠=𝑃𝑚𝑎𝑥×𝐵×𝑑 As = 2.461 cm2

Acero Minimo

𝐴𝑠 𝑚𝑖𝑛=0.0018×𝐵×ℎ As min = 2.700 cm2

Cuando Asmin > As; entonces:

𝐴𝑠𝐷=4/3×𝐴𝑠 AsD = 3.281 cm2

Ø del Acero: 2

N° ø (PULG.) AREA As (cm2) Espaciamiento de barras


1 1/4 pulg 0.32cm2
2 3/8 pulg 0.71cm2
𝑆∅=(𝐴𝑠𝑏×𝐵)/𝐴𝑠𝐷 SØ = 21.71 cm
3 1/2 pulg 1.27cm2
4 5/8 pulg 1.98cm2 SØ = 22.00 cm

5 3/4 pulg 2.85cm2


6 1 pulg 5.06cm2
7 1 1/8 pulg 6.41cm2 Usaremos: ∅ 3/8 pulg @ 0.22m
8 1 1/4 pulg 7.91cm2
9 1 3/8 pulg 9.58cm2

Apoyo B = Apoyo C

Cuantia Mecanica𝑃𝑚=0.85−√(0.7225−(1.7×𝑀𝑢)/(∅×𝑓^′
𝑐×𝑑^2 ))

Pm = 0.117

Cuantia Maxima 𝑃𝑚𝑎𝑥=𝑃𝑚×(𝑓^′ 𝑐)/𝑓𝑦

Pmax = 0.006

Verificanto tipo de falla: P = 0.007


P > Pmax FALLA DUCTIL
Área del acero

𝐴𝑠=𝑃𝑚𝑎𝑥×𝐵×𝑑 As = 7.011 cm2

Acero Minimo

𝐴𝑠 𝑚𝑖𝑛=0.0018×𝐵×ℎ As min = 2.700 cm2

Ø del Acero: 3

N° ø (PULG.) AREA As (cm2) Espaciamiento de barras


1 1/4 pulg 0.317cm2
2 3/8 pulg 0.712cm2
𝑆∅=(𝐴𝑠𝑏×𝐵)/𝐴𝑠 SØ = 18.06 cm
3 1/2 pulg 1.266cm2
4 5/8 pulg 1.978cm2 SØ = 18.00 cm

5 3/4 pulg 2.849cm2


6 1 pulg 5.065cm2
7 1 1/8 pulg 6.410cm2 Usaremos: ∅ 1/2 pulg @ 0.18m
8 1 1/4 pulg 7.913cm2
9 1 3/8 pulg 9.575cm2

Tramo AB = Tramo CD

𝑃𝑚=0.85−√(0.7225−(1.7×𝑀𝑢)/(∅×𝑓^′
Cuantia Mecanica𝑐×𝑑^2 ))

Pm = 0.072

Cuantia Maxima 𝑃𝑚𝑎𝑥=𝑃𝑚×(𝑓^′ 𝑐)/𝑓𝑦

Pmax = 0.004

Verificanto tipo de falla: P = 0.007


P > Pmax FALLA DUCTIL

Área del acero

𝐴𝑠=𝑃𝑚𝑎𝑥×𝐵×𝑑 As = 4.298 cm2

Acero Minimo

𝐴𝑠 𝑚𝑖𝑛=0.0018×𝐵×ℎ As min = 2.700 cm2

Ø del Acero: 2

N° ø (PULG.) AREA As (cm2) Espaciamiento de barras


1 1/4 pulg 0.32cm2
2 3/8 pulg 0.71cm2
𝑆∅=(𝐴𝑠𝑏×𝐵)/𝐴𝑠𝐷 SØ = 16.57 cm
3 1/2 pulg 1.27cm2
4 5/8 pulg 1.98cm2 SØ = 17.00 cm

5 3/4 pulg 2.85cm2


6 1 pulg 5.06cm2
7 1 1/8 pulg 6.41cm2 Usaremos: ∅ 3/8 pulg @ 0.17m
8 1 1/4 pulg 7.91cm2
9 1 3/8 pulg 9.58cm2
Tramo BC

𝑃𝑚=0.85−√(0.7225−(1.7×𝑀𝑢)/(∅×𝑓^′
Cuantia Mecanica𝑐×𝑑^2 ))

Pm = 0.080

Cuantia Maxima 𝑃𝑚𝑎𝑥=𝑃𝑚×(𝑓^′ 𝑐)/𝑓𝑦

Pmax = 0.004

Verificanto tipo de falla: P = 0.007


P > Pmax FALLA DUCTIL

Área del acero

𝐴𝑠=𝑃𝑚𝑎𝑥×𝐵×𝑑 As = 4.783 cm2

Acero Minimo

𝐴𝑠 𝑚𝑖𝑛=0.0018×𝐵×ℎ As min = 2.700 cm2

Ø del Acero: 3

N° ø (PULG.) AREA As (cm2) Espaciamiento de barras


1 1/4 pulg 0.32cm2
2 3/8 pulg 0.71cm2
𝑆∅=(𝐴𝑠𝑏×𝐵)/𝐴𝑠 SØ = 26.47 cm
3 1/2 pulg 1.27cm2
4 5/8 pulg 1.98cm2 SØ = 26.00 cm

5 3/4 pulg 2.85cm2


6 1 pulg 5.06cm2
7 1 1/8 pulg 6.41cm2 Usaremos: ∅ 1/2 pulg @ 0.26m
8 1 1/4 pulg 7.91cm2
9 1 3/8 pulg 9.58cm2

Calculo de Refuerzo de Temperatura

Acero Minimo

𝐴𝑠 𝑚𝑖𝑛=0.0018×𝐵×ℎ As min = 2.700 cm2

Ø del Acero: 2

N° ø (PULG.) AREA As (cm2) Espaciamiento de barras


1 1/4 pulg 0.32cm2
2 3/8 pulg 0.71cm2
𝑆∅=(𝐴𝑠𝑏×𝐵)/𝐴𝑠 SØ = 26.38 cm
3 1/2 pulg 1.27cm2
4 5/8 pulg 1.98cm2 SØ = 26.00 cm

5 3/4 pulg 2.85cm2


6 1 pulg 5.06cm2
7 1 1/8 pulg 6.41cm2 Usaremos: ∅ 3/8 pulg @ 0.26m
8 1 1/4 pulg 7.91cm2
9 1 3/8 pulg 9.58cm2
5) DISPOSICION DE LA ARMADURA.

∅ 3/8 pulg @ 0.26m ∅ 3/8 pulg @ 0.26m ∅ 3/8 pulg @ 0.26m

∅ 3/8 pulg @ 0.22m ∅ 1/2 pulg @ 0.18m ∅ 1/2 pulg @ 0.18m ∅ 3/8 pulg @ 22.00m
0.80m 1.00m 1.13m 1.13m 1.00m 0.80m

∅ 1/2 pulg @ 0.26m


∅ 3/8 pulg @ 0.17m ∅ 3/8 pulg @ 0.17m

X X

*CORTE X - X.
0.800m 1.000m 1.125m 1.125m 1.000m 0.800m
∅ 3/8 pulg @ 0.22m ∅ 1/2 pulg @ 0.18m ∅ 1/2 pulg @ 0.18m ∅ 3/8 pulg @ 22.00m

0.15m ∅ 3/8 pulg


@ 0.26m
4.00m 4.50m 4.00m
∅ 3/8 pulg @ 0.17m ∅ 1/2 pulg @ 0.26m ∅ 3/8 pulg @ 0.17m
DATOS WU = 9.570 T/m
f´c = 280.00 Kg/cm2
Fy = 4200.00 Kg/cm2
WD = 3.80 Tn/m
WL = 2.50 Tn/m h = 0.50m d = 0.44m
Carga Sismica = 1.30 Tn/m
Recubrimiento = 5.00 cm A B
Ø= 0.85 cm b = 0.30m
6.60m

12.54 Tn

(−)
𝐃𝐅𝐂 (𝐖𝐃)
(+)
12.54 Tn
8.25 Tn

(−)
𝐃𝐅𝐂 (𝐖𝐋)
(+)
8.25 Tn
4.29 Tn

(−)
𝐃𝐅𝐂 (𝐂𝐒)
(+)
4.29 Tn
1) CORTANTES MAXIMOS A LA CARA DE APOYO.

V Max APOYO "A" APOYO "B" 31.58 Tn 𝐕_𝐔𝐀27.37 Tn CORTANTES CRITICOS A LA DISTANCIA "d"
Vu1 31.58 Tn 31.58 Tn zona critica d = 0.44m VuA 27.37 Tn
Vu2 30.28 Tn 30.28 Tn VuB 27.37 Tn
A B
Vu3 21.70 Tn 21.70 Tn Vu 27.37 Tn d = 0.44m
Vu4 15.58 Tn 15.58 Tn espaciamiento 𝐕_𝐔𝐁 31.58 Tn
Vu5 7.00 Tn 7.00 Tn d = 0.44m 27.37 Tn

2) DISEÑO POR CORTE.


Cortante de Concreto.

Vc = 11706.55 kg/cm
𝑉𝑐=0.53√(𝑓^′ 𝑐)×𝑏𝑤×𝑑
Vc = 11.71 Tn/cm

Calculo de la Cortante de Acero

𝑉𝑠=𝑉𝑢/Ø−𝑉𝑐 Vs = 20.49 Tn/cm

Espaciamiento considerando estribos de Ø 3/8" en Zona Critica

𝑆=(2𝐴𝑒𝑠𝑡 ×𝑓𝑦×𝑑)/𝑉𝑠 S = 12.78 cm 10.00 cm


𝑆=(2𝐴𝑒𝑠𝑡 ×𝑓𝑦×𝑑)/𝑉𝑠

Espaciamiento maximo de los Estribos fuera de la Zona Critica. Si: 20.49 Tn/cm ≤ 24.30 Tn/cm

Smax = d/2 Smax = 22.00 cm

Cortantes Resistentes de los Refuerzos a las siguientes distancias.

Zona Critica S = 10cm Vs = ### ØVs = ###


Zona medio S = 15cm Vs = 17494.4 Kg ØVs = 14870.24 Kg
Fuera de Critica S = 20cm Vs = 13120.8 Kg ØVs = 11152.68 Kg

Ubicando ØVs en el D.F.C.

ØVs = 17457.44 Kg @ 10cm

ØVs = 14870.24 Kg @ 15cm


ØVs = 11152.68 Kg @ 20cm
d = 0.44m 0.42m 0.61m

X2 = 1.83m
X1 = 2.44m
2.86m
3.30m

Est : 1 @ 0.05m, 9 @ 0.10m, 4 @ 0.15m, Rto. @ 0.20m.


3) DISPOSICION DE LA ARMADURA.

1 @ 0.05m
9 @ 0.10m
Rto. @ 0.20m

A B
4 @ 0.15m
6.60m
N° ø (PULG.)
1 ∅ 1/4 pulg
2 ∅ 3/8 pulg
3 ∅ 1/2 pulg
4 ∅ 5/8 pulg
5 ∅ 3/4 pulg
6 ∅ 1 pulg
7 ∅ 1 1/8 pulg
8 ∅ 1 1/4 pulg
9 ∅ 1 3/8 pulg

Muros de albañileria, vigas


1
chatas, losas
2 Viga peraltada
3 Muro de concreto armado

DATOS:

t=𝐿𝑛/25 𝑜 t=𝐿𝑛/20

cos⁡(𝜃)=𝑃𝑎𝑠𝑜/√( 〖𝑃𝑎𝑠𝑜〗 ^2+ 〖𝐶𝑜𝑛𝑡𝑟𝑎𝑝𝑎𝑠𝑜〗 ^2 )

ℎ_𝐷=𝑡/cos⁡(𝜃)

ℎ_𝑚=ℎ_𝐷+𝐶𝑜𝑛𝑡𝑟𝑎𝑝𝑎𝑠𝑜/2

Sobrecargo S/C

Acabados, tableros y paneles ligeros

Peso de Concreto Armado

Resistencia a la comprecion del concreto

Limite elastico del acero

Recubrimiento

Ln = 4.90 m 490.00 cm Paso =


t= 0.20 m 20.00 cm Contrapaso =
Acabado = 100.00 Kg/cm2 0.10 Tn/m2 hD =
S/C = 500.00 Kg/cm2 0.50 Tn/m2 hm =
f'c = 210.00 Kg/cm2 0.21 Tn/m2 ancho =
fy = 4200.00 Kg/cm2 4.20 Tn/m2 R=
W. Concreto = 2400 kg/m3 2.40 Tn/m3 d=
h= 1.87 m 187.00 cm a = d/5 =

METRADO DE CARGAS (TRAMO INCLINACION)

CARGA MUERTA O PERMANENTE (WD):


Peso propio W. concreto x ancho x hm
Peso acabado acabado x ancho

CARGA VIVA O SOBRE CARGA S/C (WL):


Peso de la Sobre Carga (S/C) S/C x ancho

Dtotal = 0.88 Tn Ltotal = 0.50 Tn

METRADO DE CARGAS (DESCANSO)

CARGA MUERTA O PERMANENTE (WD):


Peso propio W. concreto x ancho x hm
Peso acabado acabado x ancho

CARGA VIVA O SOBRE CARGA S/C (WL):


Peso de la Sobre Carga (S/C) S/C x ancho

Dtotal = 0.58 Tn Ltotal = 0.50 Tn

Wu2 = 2.09 T/m


Wu1 = 1.66 T/m

1.20m 2.50m
L1 L2

Calculando la reacción de A

RA = RB

RA = 4.60 Tn

Momento ultimo máximo al centro del tramo de la escalera

𝑀_(𝑢
𝑚𝑎𝑥)=𝑅_𝐴×(𝐿_1+𝐿_2/2)−𝑊_𝑢1×𝐿_1×((𝐿_1+𝐿_2)/2)−𝑊_𝑢2×( 〖𝐿 _2 〗 ^2/
2)
𝑀_(𝑢
𝑚𝑎𝑥)=𝑅_𝐴×(𝐿_1+𝐿_2/2)−𝑊_𝑢1×𝐿_1×((𝐿_1+𝐿_2)/2)−𝑊_𝑢2×( 〖𝐿 _2 〗 ^2/
2)

Calculando el momento de diseño 2

Donde α = 0.9
+𝑀_𝑑𝑖𝑠𝑒ñ𝑜=𝛼𝑀_(𝑢 𝑚𝑎𝑥)

-𝑀_𝑑𝑖𝑠𝑒ñ𝑜=1/2 𝑀_𝑑𝑖𝑠𝑒ñ𝑜

Acero positivo

𝐴𝑠1=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

𝐴𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

𝐴𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

Usando ∅ 1/2 pulg 𝑠= (𝐴𝑡. 𝐴𝑐𝑒𝑟𝑜)/𝐴𝑠

Acero negativo

𝐴𝑠1=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

𝐴𝑠2=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

𝐴𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))
𝐴𝑠3=𝑀_𝑈/(Ø×𝑓𝑦(𝑑−𝑎/2))

𝑎=(𝐴𝑠×𝑓𝑦)/(0.85𝑓^′ 𝑐×𝑏)

Usando ∅ 3/8 pulg 𝑠= (𝐴𝑡. 𝐴𝑐𝑒𝑟𝑜)/𝐴𝑠

Acero Minimo

𝐴𝑠 𝑚𝑖𝑛=0.0018×𝐵×𝑡

Usando ∅ 3/8 pulg 𝑠= (𝐴𝑡. 𝐴𝑐𝑒𝑟𝑜)/𝐴𝑠

Diseño de Escalera

1.04 m

3.12 m

∅ 1/2 pulg
1.04 m

∅ 3/8 pulg @ 0.200m.


∅ 3/8 pulg @ 0.150m.
∅ 3/8 pulg @ 0.150m.

∅ 3/8 pulg @ 0.200m.


ø (PULG.) AREA As (cm2)
∅ 1/4 pulg 0.317cm2
∅ 3/8 pulg 0.712cm2
∅ 1/2 pulg 1.266cm2
∅ 5/8 pulg 1.978cm2
∅ 3/4 pulg 2.849cm2
∅ 1 pulg 5.065cm2
∅ 1 1/8 pulg 6.410cm2
∅ 1 1/4 pulg 7.913cm2
∅ 1 3/8 pulg 9.575cm2

α
Muros de albañileria, vigas
1.00
hatas, losas
iga peraltada 0.90
Muro de concreto armado 0.80

t= 0.20 m
t= 0.25 m

cos(Ө) = 0.8269

hD = 24.19 cm

hm = 32.69 cm

S/C = 500.00 Kg/m2

Acabados = 100.00 Kg/m2

W. Concreto = 2400.00 Kg/m3

f'c = 210.00 Kg/cm2

fy = 4200.00 Kg/cm2

R= 3.00 cm

0.25 m 25.00 cm
0.17 m 17.00 cm
0.24 m 24.19 cm
0.33 m 32.69 cm
1.00 m 100.00 cm
0.03 m 3.00 cm
0.17 m 17.00 cm
0.03 m 3.40 cm

CION)

ancho x hm = 0.78 Tn
x ancho = 0.10 Tn
D = 0.88 T/m

ncho L = 0.50 T/m

Wu1 = 2.09 T/m

ancho x hm = 0.48 Tn
x ancho = 0.10 Tn
D = 0.58 T/m

ncho L = 0.50 T/m

Wu2 = 1.66 T/m

Wu1 = 1.66 T/m

1.20m
L3

RB = 4.60 Tn

Mu max = 5.960 Tn-m


Viga peraltada

(+) Mdiseño = 5.364 Tn-m

(-) Mdiseño = 2.682 Tn-m

As1 = 9.28 cm2

a= 2.18 cm

As2 = 8.92 cm2

a= 2.10 cm

As3 = 8.90 cm2

a= 2.09 cm

(+)As = 8.90 cm2

s= 0.142 m
s= 0.125 m

As1 = 4.64 cm2

a= 1.09 cm

As2 = 4.31 cm2

a= 1.01 cm
As3 = 4.30 cm2

a= 1.01 cm

(+)As = 4.30 cm2

s= 0.166 m
s= 0.150 m

As min = 3.600 cm2

s= 0.198 m
s= 0.200 m

∅ 1/2 pulg @ 0.125m.

∅ 3/8 pulg @ 0.150m.

∅ 3/8 pulg @ 0.200m.

@ 0.125m.
Hallar las dimensiones de la columna central, perimetral y de esquina.

5.00 m

6.00 m

6.00 m

5.00 m

5.00 m 5.00 m 5.00 m

f´c = 210.00 Kg/cm2 0.21 Tn/m2 S. ult. Nivel = 250.00 Kg/cm2 0.25 Tn/m2 TIPO DE
S/C = 350.00 Kg/cm2 0.35 Tn/m2 S. Tipica = 100.00 Kg/cm2 0.10 Tn/m2 COLUMNA
Acabados = 100.00 Kg/cm2 0.10 Tn/m2 # Pisos = 5.00 CENTRAL
Tabiqueria T.= 100.00 Kg/cm2 0.10 Tn/m2 PERIMETRAL
Tabiqueria UN = 50.00 Kg/cm2 0.05 Tn/m2 ESQUINA
ꝩc = 2400 kg/m3 2.40 Tn/m3

COLUMNA CENTRAL Vigas en Y Vigas en X

2.35 m
0.40 m
2.70 m
0.60 m
0.30 m
5.40 m 6.00 m
0.30 m Columna

2.70 m
2.35 m 0.60 m
4.70 m
5.00 m 0.40 m

DESCRIPCION # PISOS ÁREA (m2) LONGITUD (m) PESO (t/m2) PESO (t)
Peso acabado 5.00 30.00 m2 0.10 Tn/m2 15.00 Tn
Peso Tabiqueria Tipica 4.00 30.00 m2 0.10 Tn/m2 12.00 Tn
Peso Tabiqueria Ultimo Nivel 1.00 30.00 m2 0.05 Tn/m2 1.50 Tn
Peso de Losa 5.00 30.00 m2 0.35 Tn/m2 52.50 Tn
CARGA SECCION
MUERTA DESCRIPCION # PISOS (m2) LONGITUD (m) PESO (t/m2) PESO (t)
Vigas en direccion X 5.00 0.12 m2 4.70 m 2.40 Tn/m3 6.77 Tn
Vigas en direccion Y 5.00 0.18 m2 5.40 m 2.40 Tn/m3 11.66 Tn
Columna 50 x 50 1.00 0.24 m2 15.50 m 2.40 Tn/m3 8.93 Tn

CARGA MUERTA 108.36 Tn


DESCRIPCION # PISOS SECCION LONGITUD (m) PESO (t/m2) PESO (t)
(m2)
CARGA Sobrecarga Tipica 4.00 30.00 m2 0.25 Tn/m3 30.00 Tn
MUERTA Sobrecarga Ultimo Nivel 1.00 30.00 m2 0.10 Tn/m3 3.00 Tn

CARGA VIVA 33.00 Tn

CARGA EN SERVICIO (CARGA VIVA + CARGA MUERTA) 141.36 Tn

CARGA ULTIMA (1.40 x CARGA MUERTA + 1.70 x CARGA VIVA) 207.80 Tn

Acolumna = 2468.19 cm2


𝐴𝑐𝑜𝑙𝑢𝑚𝑛𝑎=(ʎ×𝐶. 𝑆𝐸𝑅𝑉𝐼𝐶𝐼𝑂)/(Ƞ×𝑓^′ 𝑐)

LARGO ANCHO SECCION (cm2) CONDICIÓN


40.00 cm2 60.00 cm2 2400.00 cm2 NO CUMPLE
DIMENSIONES DE 45.00 cm2 55.00 cm2 2475.00 cm2 CUMPLE
COLUMNA (ASUMIENDO 50.00 cm2 50.00 cm2 2500.00 cm2 CUMPLE
TOMANDO EN BASE EL 55.00 cm2 45.00 cm2 2475.00 cm2 CUMPLE
ÁREA DE COLUMNA)
60.00 cm2 40.00 cm2 2400.00 cm2 NO CUMPLE
65.00 cm2 35.00 cm2 2275.00 cm2 NO CUMPLE

Por cuestion de economia tomaremos: 2475.00 cm2


(TOMAR VALORES QUE CUMPLAN)

COLUMNA PERIMETRAL Vigas en Y Vigas en X

0.40 m
2.70 m
0.60 m
0.30 m
5.40 m 6.00 m
0.30 m Columna

2.70 m
0.60 m
2.20 m
2.50 m 0.30 m

DESCRIPCION # PISOS ÁREA (m2) LONGITUD (m) PESO (t/m2) PESO (t)
Peso acabado 5.00 15.00 m2 0.10 Tn/m2 7.50 Tn
Peso Tabiqueria Tipica 4.00 15.00 m2 0.10 Tn/m2 6.00 Tn
Peso Tabiqueria Ultimo Nivel 1.00 15.00 m2 0.05 Tn/m2 0.75 Tn
Peso de Losa 5.00 15.00 m2 0.35 Tn/m2 26.25 Tn

CARGA SECCION
MUERTA DESCRIPCION # PISOS
(m2)
LONGITUD (m) PESO (t/m2) PESO (t)
Vigas en direccion X 5.00 0.12 m2 2.20 m 2.40 Tn/m3 3.17 Tn
Vigas en direccion Y 5.00 0.18 m2 5.40 m 2.40 Tn/m3 11.66 Tn
Columna 50 x 50 1.00 0.18 m2 15.50 m 2.40 Tn/m3 6.70 Tn

CARGA MUERTA 62.03 Tn


SECCION
DESCRIPCION # PISOS (m2) LONGITUD (m) PESO (t/m2) PESO (t)

CARGA Sobrecarga Tipica 4.00 15.00 m2 0.25 Tn/m3 15.00 Tn


MUERTA Sobrecarga Ultimo Nivel 1.00 15.00 m2 0.10 Tn/m3 1.50 Tn

CARGA VIVA 16.50 Tn

CARGA EN SERVICIO (CARGA VIVA + CARGA MUERTA) 78.53 Tn

CARGA ULTIMA (1.40 x CARGA MUERTA + 1.70 x CARGA VIVA) 114.89 Tn

Acolumna = 1869.71 cm2


𝐴𝑐𝑜𝑙𝑢𝑚𝑛𝑎=(ʎ×𝐶. 𝑆𝐸𝑅𝑉𝐼𝐶𝐼𝑂)/(Ƞ×𝑓^′ 𝑐)

LARGO ANCHO SECCION (cm2) CONDICIÓN


25.00 cm2 70.00 cm2 1750.00 cm2 NO CUMPLE
DIMENSIONES DE 30.00 cm2 65.00 cm2 1950.00 cm2 CUMPLE
COLUMNA (ASUMIENDO 35.00 cm2 60.00 cm2 2100.00 cm2 CUMPLE
TOMANDO EN BASE EL
40.00 cm2 55.00 cm2 2200.00 cm2 CUMPLE
ÁREA DE COLUMNA)
45.00 cm2 50.00 cm2 2250.00 cm2 CUMPLE
50.00 cm2 45.00 cm2 2250.00 cm2 CUMPLE

Por cuestion de economia tomaremos:


1950.00 cm2
(TOMAR VALORES QUE CUMPLAN)

COLUMNA ESQUINA Vigas en Y Vigas en X

0.40 m
1.90 m
0.60 m
2.50 m
0.30 m

0.30 m Columna
2.20 m
2.50 m
0.40 m

0.40 m

DESCRIPCION # PISOS ÁREA (m2) LONGITUD (m) PESO (t/m2) PESO (t)
Peso acabado 5.00 6.25 m2 0.10 Tn/m2 3.13 Tn
Peso Tabiqueria Tipica 4.00 6.25 m2 0.10 Tn/m2 2.50 Tn
Peso Tabiqueria Ultimo Nivel 1.00 6.25 m2 0.05 Tn/m2 0.31 Tn
Peso de Losa 5.00 6.25 m2 0.35 Tn/m2 10.94 Tn

CARGA SECCION
MUERTA DESCRIPCION # PISOS (m2) LONGITUD (m) PESO (t/m2) PESO (t)
Vigas en direccion X 5.00 0.12 m2 2.20 m 2.40 Tn/m3 3.17 Tn
Vigas en direccion Y 5.00 0.18 m2 1.90 m 2.40 Tn/m3 4.10 Tn
Columna 50 x 50 1.00 0.16 m2 15.50 m 2.40 Tn/m3 5.95 Tn

CARGA MUERTA 30.10 Tn


SECCION
DESCRIPCION # PISOS (m2) LONGITUD (m) PESO (t/m2) PESO (t)

CARGA Sobrecarga Tipica 4.00 6.25 m2 0.25 Tn/m3 6.25 Tn


MUERTA Sobrecarga Ultimo Nivel 1.00 6.25 m2 0.10 Tn/m3 0.63 Tn

CARGA VIVA 6.88 Tn

CARGA EN SERVICIO (CARGA VIVA + CARGA MUERTA) 36.97 Tn

CARGA ULTIMA (1.40 x CARGA MUERTA + 1.70 x CARGA VIVA) 53.83 Tn

Acolumna = 1320.50 cm2


𝐴𝑐𝑜𝑙𝑢𝑚𝑛𝑎=(ʎ×𝐶. 𝑆𝐸𝑅𝑉𝐼𝐶𝐼𝑂)/(Ƞ×𝑓^′ 𝑐)

LARGO ANCHO SECCION (cm2) CONDICIÓN


25.00 cm2 50.00 cm2 1250.00 cm2 NO CUMPLE
DIMENSIONES DE 30.00 cm2 45.00 cm2 1350.00 cm2 CUMPLE
COLUMNA (ASUMIENDO 35.00 cm2 40.00 cm2 1400.00 cm2 CUMPLE
TOMANDO EN BASE EL 40.00 cm2 35.00 cm2 1400.00 cm2 CUMPLE
ÁREA DE COLUMNA)
45.00 cm2 30.00 cm2 1350.00 cm2 CUMPLE
50.00 cm2 25.00 cm2 1250.00 cm2 NO CUMPLE

Por cuestion de economia tomaremos:


(TOMAR VALORES QUE CUMPLAN) 1350.00 cm2
CARRION YAUYO, Brayan Anthony

Columna = 40.00cm 60.00cm


f'c = 210.00 Kg/cm2 0.21 Tn/m2 Ø=
fy = 4200.00 Kg/cm2 4.20 Tn/m2

Ag = 2400.000cm2 As = 28.488cm2

Ac = Ag - As As = 2371.512cm2

Pn = 0.80 (0.85 x f'c x Ac + fy x As) Pn = 434371.10 Kg

Pu = Ø x Pn Pu = 304.06 T
ony

AREA As
ø (PULG.)
(cm2)
∅ 1/4 pulg 0.317cm2
∅ 3/8 pulg 0.712cm2
∅ 1/2 pulg 1.266cm2
∅ 5/8 pulg 1.978cm2
∅ 3/4 pulg 2.849cm2
∅ 1 pulg 5.065cm2
∅ 1 1/8 pulg 6.410cm2
∅ 1 1/4 pulg 7.913cm2
∅ 1 3/8 pulg 9.575cm2

0.70

434.37 T
Hallar Padm y Madm

σadm =
σadm =

Base A=
Altura
10.00cm I=
0.10m
10.00cm
0.10m
0.05m

Solución

Padm =
𝑷𝒂𝒅𝒎= 𝝈𝒂𝒅𝒎 ×𝑨 Padm =
Padm =

Madm =
𝑴𝒂𝒅𝒎= (𝝈𝒂𝒅𝒎 ×𝑰)/𝑪 Madm =
Madm =

Chart Title
250000.00 Kgf

200000.00 Kgf 3399.07 Kgf.m 0


3399.07 Kgf.m 203944.00 Kgf
150000.00 Kgf
Padm (Kgf)

0 203944.00 Kgf
3399.07 Kgf.m 203944.00 Kgf
100000.00 Kgf

50000.00 Kgf

0
0.00 Kgf
0.00 Kgf.m 1000.00 Kgf.m 2000.00 Kgf.m 3000.00 Kgf.m 4000.00 Kgf.m
Madm (Kgf.m)
200.00 MPa
200000000.00 Pa

0.01m2

0.00001m4

2000000.00 N
203944.00 Kgf
203.94 Tn

33333.33 N.m
3399.07 Kgf.m
3.40 Tn.m

0
m 4000.00 Kgf.m