REFUERZO DE ACERO EN ELEMENTOS

LOSAS

PARA TODOS LOS PISOS:

LOSA H=0.20m

ACERO INFERIOR Ø 3/8"

ACERO SUPERIOR Ø 1/2" Y Ø 3/8" (Según plano)

ACERO DE TEMPERATURA 1/4"@0.25

VIGAS

VIGA 1 PISO 1, 2, 3, 4, 5
EXTREMOS CENTRO ESTRIBOS
SUPERIOR SUPERIOR Ø 3/8", 1@0.05, 8@0.10, rto @0.20
V-25X30 3Ø 1/2" 2Ø 1/2"
INFERIOR INFERIOR
2Ø 1/2" 2Ø 1/2"
VIGA 2 PISO 1, 2, 3 PISO 4,5
EXTREMOS CENTRO EXTREMOS CENTRO ESTRIBOS
SUPERIOR SUPERIOR SUPERIOR SUPERIOR Ø 3/8", 1@0.05, 8@0.10, rto @0.20
V-25X40 3Ø 1/2" 3Ø 1/2" 2Ø 1/2"+1Ø 3/8" 2Ø 1/2"+1Ø 3/8"
INFERIOR INFERIOR INFERIOR INFERIOR
2Ø 1/2"+1Ø 3/8" 2Ø 1/2"+1Ø 3/8" 2Ø 1/2"+1Ø 3/8" 2Ø 1/2"+1Ø 3/8"
VIGA 3 PISO 2,3 PISO 4,5
EXTREMOS CENTRO EXTREMOS CENTRO ESTRIBOS
SUPERIOR SUPERIOR SUPERIOR SUPERIOR Ø 3/8", 1@0.05, 8@0.10, rto @0.20
V-30X40 3Ø 1/2"+2Ø 3/8" 3Ø 1/2" 3Ø 1/2" 3Ø 1/2"
INFERIOR INFERIOR INFERIOR INFERIOR
3Ø 1/2" 3Ø 1/2" 3Ø 1/2" 3Ø 1/2"
VIGA 4 (EJE 8 A-C) PISO 2,3 PISO 4,5
EXTREMOS CENTRO EXTREMOS CENTRO ESTRIBOS
SUPERIOR SUPERIOR SUPERIOR SUPERIOR Ø 3/8", 1@0.05, 8@0.10, rto @0.20
V-30X40 5Ø 5/8" 3Ø 5/8" 5Ø 1/2" 3Ø 1/2"
INFERIOR INFERIOR INFERIOR INFERIOR
3Ø 5/8" 3Ø 5/8" 3Ø 1/2" 3Ø 1/2"
VIGA 5 PISO 1
EXTREMOS CENTRO ESTRIBOS
SUPERIOR SUPERIOR Ø 3/8", 1@0.05, 8@0.10, rto @0.20
V-30X60 3Ø 5/8" 3Ø 5/8"
INFERIOR INFERIOR
3Ø 5/8" 3Ø 5/8"
VIGA 6 (EJE 8 A-C) PISO 1
EXTREMOS CENTRO ESTRIBOS
SUPERIOR SUPERIOR Ø 3/8", 1@0.05, 8@0.10, rto @0.20
V-30X60 3Ø 3/4"+2Ø 5/8" 3Ø 3/4"
INFERIOR INFERIOR
2Ø 3/4"+2Ø 5/8" 2Ø 3/4"+2Ø 5/8"
VIGA 7 PISO 1, 2, 3, 4, 5
EXTREMOS CENTRO ESTRIBOS
SUPERIOR SUPERIOR Ø 3/8", 1@0.05, 8@0.10, rto @0.20
VCH25X20 2Ø 1/2" 2Ø 1/2"
INFERIOR INFERIOR
2Ø 1/2" 2Ø 1/2"
VIGA 8 PISO 1, 2, 3, 4, 5
EXTREMOS CENTRO ESTRIBOS
SUPERIOR SUPERIOR Ø 1/4", 1@0.05, 8@0.10, rto @0.20
VCH15X20 2Ø 3/8" 2Ø 3/8"
INFERIOR INFERIOR
2Ø 3/8" 2Ø 3/8"
MUROS DE ALBAÑILERÍA CONFINADA

TODOS LOS MUROS DE SOGA LADRILLO KING KONG 18 HUECOS

MURO 1 MURO 2 MURO 3


ESFUERZO AXIAL ESFUERZO AXIAL ESFUERZO AXIAL
CARGA AXIAL 26.21 TON CARGA AXIAL 30.14 TON CARGA AXIAL 27.9 TON
LARGO DE MURO 1.97 M LARGO DE MURO 3.29 M LARGO DE MURO 3.21 M
ESPESOR 0.13 M ESPESOR 0.13 M ESPESOR 0.13 M
ESFUERZO AXIAL 102.342835 TON/M2 ESFUERZO AXIAL 70.4699556 TON/M2 ESFUERZO AXIAL 66.8583753 TON/M2
ESFUERZO ADMISIBLE ESFUERZO ADMISIBLE ESFUERZO ADMISIBLE
F'M 650 TON/M2 F'M 650 TON/M2 F'M 650 TON/M2
ALTURA 3.2 M ALTURA 3.2 M ALTURA 3.2 M
ESFUERZO ADMISIBLE 129.981635 TON/M2 ESFUERZO ADMISIBLE 129.981635 TON/M2 ESFUERZO ADMISIBLE 129.981635 TON/M2
102.342835 < 129.981635 OK 70.4699556 < 129.981635 OK 66.8583753 < 129.981635 OK

MURO 4 MURO 5 MURO 6


ESFUERZO AXIAL ESFUERZO AXIAL ESFUERZO AXIAL
CARGA AXIAL 27.51 TON CARGA AXIAL 28.02 TON CARGA AXIAL 36.56 TON
LARGO DE MURO 3.21 M LARGO DE MURO 3.21 M LARGO DE MURO 3.2 M
ESPESOR 0.13 M ESPESOR 0.13 M ESPESOR 0.13 M
ESFUERZO AXIAL 65.9237958 TON/M2 ESFUERZO AXIAL 67.1459382 TON/M2 ESFUERZO AXIAL 87.8846154 TON/M2
ESFUERZO ADMISIBLE ESFUERZO ADMISIBLE ESFUERZO ADMISIBLE
F'M 650 TON/M2 F'M 650 TON/M2 F'M 650 TON/M2
ALTURA 3.2 M ALTURA 3.2 M ALTURA 3.2 M
ESFUERZO ADMISIBLE 129.981635 TON/M2 ESFUERZO ADMISIBLE 129.981635 TON/M2 ESFUERZO ADMISIBLE 129.981635 TON/M2
65.9237958 < 129.981635 OK 67.1459382 < 129.981635 OK 87.8846154 < 129.981635 OK

MURO 7 MURO 8 MURO 9


ESFUERZO AXIAL ESFUERZO AXIAL ESFUERZO AXIAL
CARGA AXIAL 34.63 TON CARGA AXIAL 34.52 TON CARGA AXIAL 27.05 TON
LARGO DE MURO 2.97 M LARGO DE MURO 3.18 M LARGO DE MURO 3.2 M
ESPESOR 0.13 M ESPESOR 0.13 M ESPESOR 0.13 M
ESFUERZO AXIAL 89.6917897 TON/M2 ESFUERZO AXIAL 83.5026609 TON/M2 ESFUERZO AXIAL 65.0240385 TON/M2
ESFUERZO ADMISIBLE ESFUERZO ADMISIBLE ESFUERZO ADMISIBLE
F'M 650 TON/M2 F'M 650 TON/M2 F'M 650 TON/M2
ALTURA 3.2 M ALTURA 3.2 M ALTURA 3.2 M
ESFUERZO ADMISIBLE 129.981635 TON/M2 ESFUERZO ADMISIBLE 129.981635 TON/M2 ESFUERZO ADMISIBLE 129.981635 TON/M2
89.6917897 < 129.981635 OK 83.5026609 < 129.981635 OK 65.0240385 < 129.981635 OK

MURO 10 MURO 11 MURO 12


ESFUERZO AXIAL ESFUERZO AXIAL ESFUERZO AXIAL
CARGA AXIAL 26.94 TON CARGA AXIAL 26.56 TON CARGA AXIAL 25.37 TON
LARGO DE MURO 3.2 M LARGO DE MURO 3.2 M LARGO DE MURO 3.2 M
ESPESOR 0.13 M ESPESOR 0.13 M ESPESOR 0.13 M
ESFUERZO AXIAL 64.7596154 TON/M2 ESFUERZO AXIAL 63.8461538 TON/M2 ESFUERZO AXIAL 60.9855769 TON/M2
ESFUERZO ADMISIBLE ESFUERZO ADMISIBLE ESFUERZO ADMISIBLE
F'M 650 TON/M2 F'M 650 TON/M2 F'M 650 TON/M2
ALTURA 3.2 M ALTURA 3.2 M ALTURA 3.2 M
ESFUERZO ADMISIBLE 129.981635 TON/M2 ESFUERZO ADMISIBLE 129.981635 TON/M2 ESFUERZO ADMISIBLE 129.981635 TON/M2
64.7596154 < 129.981635 OK 63.8461538 < 129.981635 OK 60.9855769 < 129.981635 OK

MURO 13
ESFUERZO AXIAL
CARGA AXIAL 31.81 TON
LARGO DE MURO 3.2 M
ESPESOR 0.13 M
ESFUERZO AXIAL 76.4663462 TON/M2
ESFUERZO ADMISIBLE
F'M 650 TON/M2
ALTURA 3.2 M
ESFUERZO ADMISIBLE 129.981635 TON/M2
76.4663462 < 129.981635 OK