Documentos de Académico
Documentos de Profesional
Documentos de Cultura
CURSO ACS2000
MINERA EL BROCAL
© ABB Drives Services
© ABB Group
May 16, 2017 | Slide 1
Objetivos
Especificaciones técnicas
Etapas del drive
Componentes principales
© ABB Drives Services
© ABB Group
May 16, 2017 | Slide 2
ACS 2000 ABB MV Drives
Switching
Drive Type Power Front end / Topology / Motor type Other
switch Operation Inverter features
Output
ACS1000 VSI-NPC MV IGCT Diode, 12 p / 3 levels / 5 induction Sine filter
Fuseless 2 quadrants levels on motor
output
ACS 2000 VSI-ANPC HV IGBT Active, 6 pulses 5 levels / 9 induction DTL for
/ 4 quadrants levels Trafo-
less
ACS5000 VSI-NPC MV IGCT Diode, 36 p / 5 levels / 9 Induction
Fuseless 2 quadrants levels synchronous
PM
ACS6000 VSI-NPC MC IGCT Diode 12 p or 3 levels / 5 Induction Multidrive
Fuseless Active 6 p / levels synchronous config.
2 or 4 quadrants PM possible
LCI CSI MV Active Load synchronous
Thyristor commutated
(SCR)
© ABB Drives Services
Overview
ACS 2000 ABB MV Drives
© ABB Drives Services
Overview
ACS 2000 ABB MV Drives
ACS 2000 0.3 – 1MVA 4.0; 4.16; 6.0; 6.6 5L-ANPC-VSC IGBT Direct Torque Control
© ABB Drives Services
Familia de Productos ACS2000
© ABB Group
May 16, 2017 | Slide 6
ACS2000 Tipos y configuraciones
Sistema de alimentación:
• 6 kV
• 4 kV
Tipo de rectificador:
• AFE: IBGT
• DFE: Diodo
Tamaño según su potencia:
• Frame 1: 1MVA
• Frame 2: 2MVA
• Frame 3: 3MVA
Conexión a la red:
© ABB Drives Services
• Directo a la línea
• Transformador de entrada integrado
© ABB Group
• Transformador de entrada externo
May 16, 2017 | Slide 7
ACS2000 Tamaños
Rango:
- Hasta 3MVA
- Frame 1, 2 y 3
© ABB Drives Services
© ABB Group
May 16, 2017 | Slide 8
Aplicaciones ACS 2000
© ABB Drives Services
© ABB Group
May 16, 2017 | Slide 9
Conexiones Sistema Eléctrico
Transformador
© ABB Drives Services
© ABB Group
May 16, 2017 | Slide 10
Conexiones Sistema Eléctrico
MV Switchgear
© ABB Group
May 16, 2017 | Slide 11
Sistema ACS 2000 4kV DTL
© ABB Drives Services
© ABB Group
May 16, 2017 | Slide 12
Generalidades ACS 2000
La etapa de rectificación,
puede estar basado en
diodos (DFE) o igbts (AFE).
La etapa de inversión esta
basado en igbts (INU), y
constan de 03 módulos de
fase, al igual que el AFE.
© ABB Drives Services
© ABB Group
May 16, 2017 | Slide 13
IGBT Semiconductor de potencia
- Rango de alto voltaje de operación (1200 a 1500 V)
- Bajas pérdidas por conmutación (menos del 20%)
- Cortos tiempos de retardos al encendido y apagado
© ABB Drives Services
© ABB Group
May 16, 2017 | Slide 14
IGBT Semiconductor de potencia
Los IGBT hacen que el diseño del
drive ACS 2000 sea compacto.
Tanto el rectificador como el inversor
constan de 03 módulos de fase cada
etapa, a su vez cada módulo de fase
consta de 06 módulos o packs de
IGBT (una fase del motor por módulo
de fase).
© ABB Drives Services
© ABB Group
May 16, 2017 | Slide 15
IGBT Semiconductor de potencia
© ABB Group
May 16, 2017 | Slide 16
IGBT Semiconductor de potencia
© ABB Group
May 16, 2017 | Slide 17
5 Niveles – Voltaje fase a fase
© ABB Group
May 16, 2017 | Slide 19
5 Niveles – Voltaje fase a fase
© ABB Drives Services
© ABB Group
May 16, 2017 | Slide 20
5 Niveles – Voltaje fase a fase
© ABB Drives Services
© ABB Group
May 16, 2017 | Slide 21
5 Niveles – Voltaje fase a fase
© ABB Drives Services
© ABB Group
May 16, 2017 | Slide 22
ACS 2000 Topologia
Lado red (AFE)
Phase A Phase B Phase C Clamp DC-link
© ABB Group
May 16, 2017 | Slide 23
ACS 2000 Topologia
Lado motor (INU)
Clamp Phase A Phase B Phase C EMC filter
NP to GND
potential tie
© ABB Drives Services
Point of
grounding
© ABB Group
May 16, 2017 | Slide 24
ACS 2000 Topologia
El ACS 2000 debe pasar por una secuencia de carga antes de que el MCB
pueda cerrarse.
Objetivo de la secuencia de carga es cargar todos los condensadores de
DC (enlace DC, condensadores de fase) a la tensión nominal.
La carga consiste en una secuencia de fases, ver las siguientes
diapositivas:
© ABB Drives Services
© ABB Group
May 16, 2017 | Slide 26
Procedimiento de carga
Fase 1
IGBTs conmutados
© ABB Drives Services
Carga transformador
© ABB Group
May 16, 2017 | Slide 27
Procedimiento de carga
Fase 2
© ABB Group
May 16, 2017 | Slide 28
Procedimiento de carga
AFE
sincronización
[V]
DC Charging Level (17.02)
MCB Close
Command
Charging started
DC Link Level ≥
On Cmd = TRUE
DC Charging Level
[s]
© ABB Group
May 16, 2017 | Slide 29
Procedimiento de carga
© ABB Drives Services
© ABB Group
May 16, 2017 | Slide 30
ACS 2000 Gabinete
© ABB Group
May 16, 2017 | Slide 31
ACS 2000 Gabinete
© ABB Group
May 16, 2017 | Slide 32
ACS 2000 Gabinete
INU
U2 módulo de fase
V2 módulo de fase
W2 módulo de fase
AFE
L1 módulo de fase
L2 módulo de fase
L3 módulo de fase
© ABB Drives Services
© ABB Group
May 16, 2017 | Slide 33
ACS 2000 Características y beneficios
Adecuado uso con o sin transformador Adaptable para varios líneas de entrada del
de entrada cliente
© ABB Group
May 16, 2017 | Slide 34
ACS 2000 Esquemas
© ABB Drives Services
Sensor de corriente
Sensor de voltaje
© ABB Group
May 16, 2017 | Slide 35
ACS 2000 Esquemas
MCB, IFU
3 Ph
Sensor de corriente
Sensor de voltaje
NP
© ABB Drives Services
gnd
© ABB Group
May 16, 2017 | Slide 36
ACS 2000 Esquemas
Módulo de fase - AFE
+DC
Sensor de corriente
Sensor de voltaje
NP
3 Ph
© ABB Drives Services
-DC
© ABB Group
May 16, 2017 | Slide 37
ACS 2000 Esquemas
Bus DC, Filtro NP, Crowbar y Gnd Sw
Sensor de corriente
Sensor de voltaje
© ABB Drives Services
© ABB Group
May 16, 2017 | Slide 38
ACS 2000 Esquemas
Módulo de fase - INU
+DC
Sensor de corriente
Sensor de voltaje
NP
3 Ph
© ABB Drives Services
© ABB Group
May 16, 2017 | Slide 39 -DC
ACS 2000 Esquemas
Filtro dV/dt
© ABB Drives Services
Sensor de corriente
Sensor de voltaje
© ABB Group
May 16, 2017 | Slide 40
ACS 2000 IFU
El IFU reduce los voltajes armónicos inyectados a la red de
suministro y se utiliza en combinación con el AFE
El IFU es un filtro sintonizado situado entre el transformador de
distribución y el AFE
© ABB Drives Services
© ABB Group
May 16, 2017 | Slide 41
ACS 2000 Modulo de fase
Gate Drivers Phase INT Board
© ABB Group
May 16, 2017 | Slide 43
ACS 2000 Enfriamiento
El sistema de refrigeración por aire, mantiene refrigerado los
componentes asociados a la alimentación principal y transfiere el calor
hacia el exterior de los cubículos.
© ABB Drives Services
© ABB Group
May 16, 2017 | Slide 44