L E Y E N D A

SIMBOLO DESCRIPCION

h=0.50m. S.N.V

DE 3/8"x.15 DE LARGO
ASA DE FIERRO CORRUGADO h=0.71 m.S.N.V.

.10
BORDE SUPERIOR
LAVANDERÍA

.40

.30

.60
T T h=1.80m. S.N.P.T

.10
-
TRAGALUZ
CONDUCTOR DESNUDO
.15 .30 .15 -
CONECTOR DE BRONCE TAPA DE CONCRETO ARMADO
DE 0.40x0.40 .10 .40 .10 h=2.10m.S.N.P.T.
T
ELECTRODO DE COBRE 35 mm Ø F° G° -

h=0.40m.,S.N.P.T.

0.50
P (eje)
T

.82
T h=0.40m.,S.N.P.T.
CONDUCTOR DE PUESTA A TIERRA (eje)
SALA 1x25/Tmm2 Cu. DESNUDO
h=0.40m.,S.N.P.T.
T

.10
T P h=2.10m.S.N.P.T.
T h=0.40m.,S.N.P.T.
CONECTOR DE PRESION h=1.10m.,S.N.P.T.
DE COBRE O BRONCE
COCINA T T h=0.40m.,S.N.P.T.
h=1.10m.,S.N.P.T.
C T
T h=0.40m.,S.N.P.T.
C-1 C-3 T h=1.80m.S.N.P.T.
T SANIK GEL, SULFATO DE S 2S 3S
C-2 h=1.20m.S.N.P.T.

3.42
T MAGNESIO O SUSTANCIA SIMILAR

S3 h=1.20m.S.N.P.T.
T.G. POZO DE TIERRA
CLOSET

2.50
ESC. 1/25
2 h=1.20m.S.N.P.T.
T
VARILLA DE COBRE DE 16mm.Ø x
2.50m. DE LONGITUD h=2.20m.S.N.P.T.

h=1.40m.S.N.P.T.

PASADIZO
DORMITORIO TABLERO
02 TIERRA CERNIDA
Y COMPACTADA TABLERO

TRAGALUZ

.20
BAÑO .80 X .80
CONECTOR DE PRESION
DE COBRE O BRONCE
T

T
T T CONSIDERANDO LA NATURALEZA DEL TERRENO, HUMEDAD, LA TEMPERATURA, SALINIDAD Y
ESTRATIGRAFIA DEL TERRENO, SE PREVEE QUE CON UN POZO A TIERRA SE PUEDE OBTENER
15 OHMIOS.
EN CASO CONTRARIO, SE CONSTRUIRÁN MAS POZOS Y SE CONECTARÁN EN PARALELO,
T TENIENDO EN CUENTA QUE LA DISTANCIA ENTRE ELECTRODOS NO DEBE SER MENOR DE
T 1.5 VECES LA LONGITUD DEL DISPERSOR.

VACIO HALL
DIAGRAMA UNIFILAR DEL TABLERO GENERAL TG
220V / 60 HZ / 3Ø / 23 POLOS

ESTAR 2x16A
2x16A
S=30mA
C-1 2-1x2.5mm2 TW -15mmØ PVC-P ALUMBRADO
T 2x25A
2x20A S=30mA
T C-2 2-1x4mm2TW+1x4mm2(T)-20mmØ PVC-P
TOMACORRIENTES
BAÑO T
2x25A
3x50A 2x20A S=30mA
3-1x6mm2 AWG C-3 2-1x4mm2TW+1x4mm2(T)-20mmØ PVC-P CALENTADOR DE AGUA
VIENE DEL SUMINISTRO ELECTRICO 18KA

C-4 RESERVA
BORNERA DE PUESTA

BAÑO A TIERRA

T
PODER DE RUPTURA 10 KA

T
DORMITORIO
PRINCIPAL DETALLE DE NICHOS
T T

CAJA TRIFASICA
TIPO LTR
CAJA TOMA
TIPO F1
CUADRO DE CARGAS TABLERO GENERAL TG
POTENCIA FACTOR DE MAXIMA
DESCRIPCION INSTALADA DEMANDA DEMANDA
(w) (%) (w)
CLOSET

ALUMB. + TOMAC. 1,005 Primeros 2,000w al 100% 1,005


DORMITORIO Area techada 40.20m2 X 25 w 0.00 x 0.35% --
CLOSET

T 01 T Pequeñas aplicaciones 1,500 1,500 35% 525


Cocina electrica 6,000 80% 4,800
Calentador electrico (1) 60Lts 1,500 100% 1,500
Lavadora (1) 250 100% 250

TOTAL 10,255 8,080

POTENCIA INSTALADA : 10.26 Kw


MAXIMA DEMANDA : 8.08 Kw
ACOMETIDA ELECTRICA SUMINISTRO SOLICITADO: Trifasico de 10kw
SUBTERRANEA
S.T. 2"Ø PVC SAP
EN TARIFA BT5B

PLANTA SEGUNDO NIVEL

POSESIONARIA:

SR. LOLIN VERDE ESPINOZA


PROFESIONAL : LAMINA:
CARLOS ENRIQUE CORREA CHAPA
ING. CIVIL CIP N° 238514
ESPECIALIDAD:
INST. ELECTRICAS (Segundo Piso)
CORPAL S.A.C.
DIRECCION: AA.HH. Portada de Manchay II-Ampliacion Sector Las Mercedes, Mza E1 , Lote 04
Dist. Pachacamac - Prov. y Dpto de Lima
IE-01
CONSTRUCTORA & INMOBILIARIA
REVISADO: DIBUJO: FECHA: ESCALA:
CEL. 934 117 481 C.C.C. J.D.C.P. MAYO 2020 1/50