25m)
P = 8 Ton
0.25
1.05
2.00
0.25
METRADO DE CARGAS
f'c = 210.00
Mu = 937,968.75
b = 100.00
d = 22.00
0.36125f'cba2 - 0.7225f'cbda + Mu = 0
a1 = 3.0168662419
a2 = 40.983133758
Ø N de Barras @ (cm.)
As = (0.85f'cab) / fy 3/8" 18.06 18.00 5.56
1/2" 9.94 10.00 10.00
As = 12.82 cm2 5/8" 6.41 6.00 16.67
3/4" 4.50 4.00 25.00
1" 2.53 3.00 33.33
Con la finalidad de resistir el momento flector debido al empuje del suelo y sobrecargas consideramos
una cuantía mínima de 14/fy
As = (14/4200)xbxd
As = 6.67 cm2
P = 8 Ton
0.20
0.70
0.15
METRADO DE CARGAS
CARGAS DE SERVICIO
P.P.LOSA WD WL
0.29 8.00
0.29 8.00
WD = 0.29 Ton/m
WL = 8.00 Ton/m
Mu = (WDxL²/8)+ (PL/2)+(PL/2)*0.30
Mu = 3.92 Tn-m
1 CALCULO DE ACERO DE LA LOSA DE TECHO
f'c = 210.00
Mu = 392,025.00
b = 100.00
d = 17.00
0.36125f'cba2 - 0.7225f'cbda + Mu = 0
a1 = 1.594667453
a2 = 32.40533255
Donde:
As = (0.85f'cab) / fy
As = 6.78 cm2
Ø N de Barras @ (cm.)
3/8" 9.55 10.00 10.00
1/2" 5.25 5.00 20.00
5/8" 3.39 3.00 33.33
3/4" 2.38 2.00 50.00
1" 1.34 1.00 100.00
Con la finalidad de resistir el momento flector debido al empuje del suelo y sobrecargas consideramos
una cuantía mínima de 14/fy
As = (14/4200)xbxd
As = 5.67 cm2