Está en la página 1de 15

LISTA DE BREAKER

FIJADOS A CHASIS 10 KA
HQC 10 KA GC EB 10 KA ICC KA
15 15 15 HQC 10 QC,QCHW
20 20 20 GC
25 25 25 EB 10 KA 10 GC,EHB
30 30 30 FDB 18KA 18 FB
35 35 35 JDB
40 40 40 KD
50 50 LB 42
55 LA 42
60 60 60 TRI PAC LA 200
70 70 70 NB 200
80 PB 200
90 90
100 100

TRI PAC
FDB 18KA JDB KD LB LA LA NB PB
15
20
25
30
35
40
45
50
60
70 70 70 70
80
90 90 90 90
100 100 100 100 100
110
125 125 125 125 125
150 150 150 150 150
175 175 175 175
200 200 200 200
225 225 225 225
250 250 250 250 250
300 300 300 300 300
350 350 350 350 350
400 400 400 400 400
500 500
600 600 600
700 700
800 800
900
1000
1200
1400
1600
TABLEROS
BARRA(A) PRINCIPAL
NLAB 225 HQC EB CA
NAB 400 EB CA DA
NHB 400 EHB FB HFB KA

CDP-1 600 EB HFB LA-400 HLA-400 LA-600 HLA-600


CDP-2 800 KA HKA LA-400 HLA-400 LA-600 HLA-600 MC
CDP-3 1200 NC MC LA-400 DA EB CA FB

SUB ALIMENTADOR
SECUNDARIOS
NLAB HQC EB
NAB EB CA
NHB EHB KA HFB
V
CDP-1 240 EB CA
CDP-2 480 EHB FB HFB
CDP-3 600 FB HFB
LA HLA

240V
MAXIMO (A) Icc(ka) SIMILAR
HQC 100 10
EB 100 10
EHB 100 18
FB 150 18 FDB
HFB 150 65
CA 225
DA 400
LA-400 42
HLA-400 65
LA-600 250-600 42
HLA-601 60
TRIPAC 200
FB 100
LA 400
NB 300-800
PB 600-1600
NC
CARGA MAXIMA POR CONDUCTORES

cable x cable x
awg TW THW Tuberia tuberia Prot THHN Tuberia tuberia
14 15 15 1/2 5 15 25 1/2 12
12 20 20 1/2 4 20 30 1/2 9
10 30 30 3/4 6 30 40 1/2 5
8 40 45 3/4 4 40 55 1/2 3
6 55 65 1 4 70 75 3/4 4
4 70 85 1,1/2 7 70 95 1 4
2 95 115 1,1/2 5 100 130 1 3
1/0 125 150 2 5 150 170 1,1/2 4
2/0 145 175 2 4 150 195 1,1/2 3
3/0 165 200 2 4 200 225 1,1/2 3
4/0 195 230 3 7 200 260 2 4
250 215 255 3 6 250 290 2 3
300 240 285 3 5 300 320 2 3
350 260 310 4 8 350 350 2,1/2 4
400 280 335 4 7 350 380 2,1/2 4
500 320 380 4 6 400 430 3 5
600 355 420 4 5 500 475 3 4
700 385 460 6 10 500 3 4
750 400 475 6 9 500 535 4 4
Prot tierra
20 14
30 12
40 10
50 10
70 10
90 8
120 8
150 6
175 6
200 6
250 6
300 6
300 4
350 4
350 4
400 4
400 2
500 2
500 2
Ing. Enrique Jubes G

PROYECTO:
CIRCUITO TRIFASICOS INCLUYE EL BIFASICO 208.00

VA
OJO SE ENTRA CON KVA 1,000.00
SERVICIO TRIFASICO 208 Y/120 V #REF! KVA
1.00
#REF!
TERNAS 1.00
2.95

DATOS DE CALCULO CALIBRE


FASES CONDUCTOR TIPO DUCTO ELEGIDO DUCTO f
1 COBRE THW MAGNETICO 12

CAIDA DE TENSION PERMISIBLE [%] = 3.0 CONDUCTORES / FASE = 1


FACTOR DE POTENCIA = 0.9 CARGA MAXIMA PERMITIDA = 82%
KW TOTAL KVA DISTANCIA KVAM Icc (Amp) TENSION CORRIENTE PROTECCION
2.66 2.95 36.00 106.28 1,736.7 208 14.19 3X20
ELECCION DE CONDUCTOR
CALIBRE POR CALIBRE POR CALIBRE POR CALIBRE CAIDA DE CALIBRE
CAIDA DE V. CARGA PROTECCION ELEGIDO TENSION NEUTRO
14 12 12 12 1.500% 12

Nota : Se elige el cable bajo condicion de carga de maximo 3 conductores por tuberia principal
Ing. Enrique Jubes G

PROYECTO:
CIRCUITO TRIFASICOS INCLUYE EL BIFASICO 208.00

VA
OJO SE ENTRA CON KVA 1,000.00
SERVICIO TRIFASICO 208 Y/120 V 54.79 KVA
1.00
54.79
TERNAS 1.00
54.79

DATOS DE CALCULO CALIBRE


FASES CONDUCTOR TIPO DUCTO ELEGIDO DUCTO f
1 COBRE THW MAGNETICO 3/0

CAIDA DE TENSION PERMISIBLE [%] = 3.0 CONDUCTORES / FASE = 1


FACTOR DE POTENCIA = 0.9 CARGA MAXIMA PERMITIDA = 82%
KW TOTAL KVA DISTANCIA KVAM Icc (Amp) TENSION CORRIENTE PROTECCION
49.31 54.79 20.00 1,095.89 1,736.7 208 263.43 3X20
ELECCION DE CONDUCTOR
CALIBRE POR CALIBRE POR CALIBRE POR CALIBRE CAIDA DE CALIBRE
CAIDA DE V. CARGA PROTECCION ELEGIDO TENSION NEUTRO
1 400 12 3/0 1.605% 3/0

Nota : Se elige el cable bajo condicion de carga de maximo 3 conductores por tuberia principal
200 8.4

TABLAS DE CARGA
PROYECTO
ALIMENTADOR TABLERO CON SECADORA Y AIRE

SISTEMA:2F,3H, 120/208V TIPO =


TABLERO: T1 N° DE CIRCUITOS =
FUNCION:ILUMINACION / FUERZA SALIDAS ACTIVAS =
MONTAJE: EMPOTRADO SALIDAS DE RESERVA =
UBICACION:IZQUIERDA SALIDAS BLOQUEADAS =
CTO TOMACORRIENTES CONDUCTOR KW
ALUMBRADO KW
N° T/C ESPECIAL N° TIPO CIRC
1 11 14 THHN 0.062 0.68
2 6 14 THHN 0.18 1.08
3 6 14 THHN 0.18 1.08
4 4 14 THHN 0.18 0.72
5.7 1 14 THHN 3 3.00
6 1 14 THHN 1 1.00
7 1 14 THHN 1.2 1.20
8.76

P FASE A : 4.26 KW FACTOR DE POTENCIA =


P FASE B : 4.50 KW
P FASE C : 0.00 KW LONGITUD DEL CIRCUITO =

CARGA TOTAL CONECTADA: 8.76 KW DIVISOR DE ACOMETIDA


PRIMEROS 3 KW 100% 3.00 KW CONDUCTOR POR CAPACIDAD DE CO
RESTA 5.76 KW
siguientes DE 3 KW A 12 KW 35% CONDUCTOR POR CAPACIDAD DE TE
2.02 CONDUCTOR SELE
suma 7.78 PROTECCION =
RESTA 0.00 ACOMETIDA =
A partir de 12 KW 25.00% DUCTO=
0.00 TIPO =
CARGA TOTAL DIVERSIFICADA: 7.78 KW
RESERVA 40% 3.11 KW NOTA : CALENTADOR DE AGUA y
CARGA TOTAL DEMANDADA: 10.89 KW
208
115

TABLAS DE CARGA
PROYECTO
LERO CON SECADORA Y AIRE ACONDICIONADO

NLAB AMP-BARRA = 225 A


8 FD- ILUMINACION = 1
6 FD- T/C = 1
2 FD- ESP. = 0.8
0
CARGA TOTAL KW AMPERIOS PROTECCION DESCRIPCION
A B C CONECT P Amp. Icc (Ka)
0.68 5.9 1 15 10 ALUMBRADO 56 W
1.08 9.4 1 15 10 T/C GENERALES
1.08 9.4 1 15 10 T/C GENERALES
0.72 6.3 1 15 10 T/C GENERALES
1.50 1.50 14.4 2 20 10 SECADORA NO COINCIDE CON PLAN
1.00 8.7 1 15 10 PLANCHA
1.20 10.4 1 15 10 AIRE ACONDICIONADO
4.26 4.50 0.00

DE POTENCIA = 0.9 CORRIENTE TOTAL DEMANDADA= 52,36 A

D DEL CIRCUITO = 36 MTS CARGA MAXIMA PERMITIDA = 82%

DIVISOR DE ACOMETIDA (TERNAS) = 1


CTOR POR CAPACIDAD DE CORRIENTE = 6
CAIDA DE TENSION %= 1.666
CTOR POR CAPACIDAD DE TENSION 3% = 8
CONDUCTOR SELECIONADO = 6 (75 A)
2X60A TIPO HQC 10 KA
F 2#6 + N1#6+ T1 #10 THHN-AWG
1 f 3/4"

CALENTADOR DE AGUA y COCINA DE GAS


NO COINCIDE CON PLANCHA
200 8.4

TABLAS DE CARGA
PROYECTO
ALIMENTADOR TABLERO APARTAMENTO SI

SISTEMA:2F,3H, 120/208V TIPO =


TABLERO: T1 N° DE CIRCUITOS =
FUNCION:ILUMINACION / FUERZA SALIDAS ACTIVAS =
MONTAJE: EMPOTRADO SALIDAS DE RESERVA =
UBICACION:IZQUIERDA SALIDAS BLOQUEADAS =
CTO TOMACORRIENTES CONDUCTOR KW
ALUMBRADO KW
N° T/C ESPECIAL N° TIPO CIRC
1 11 14 THHN 0.062 0.68
2 6 14 THHN 0.18 1.08
3 6 14 THHN 0.18 1.08
4 4 14 THHN 0.18 0.72
5.7 0 14 THHN 3 0.00
6 1 14 THHN 1 1.00
4.56

P FASE A : 2.76 KW FACTOR DE POTENCIA =


P FASE B : 1.80 KW
P FASE C : 0.00 KW LONGITUD DEL CIRCUITO =

CARGA TOTAL CONECTADA: 4.56 KW DIVISOR DE ACOMET


PRIMEROS 3 KW 100% 3.00 KW CONDUCTOR POR CAPACIDAD DE
RESTA 1.56 KW
siguientes DE 3 KW A 12 KW 35% CONDUCTOR POR CAPACIDAD DE
0.55
suma 2.11 PROTECCION =
RESTA 0.00 ACOMETIDA =
A partir de 12 KW 25.00% TUBERIA=
0.00
CARGA TOTAL DIVERSIFICADA: 2.11 KW
RESERVA 40% 0.84 KW NOTA : CALENTADOR DE AGUA y
CARGA TOTAL DEMANDADA: 2.95 KW SIN SECADORA
208
115

TABLAS DE CARGA
PROYECTO
TABLERO APARTAMENTO SIN SECADORA

NLAB AMP-BARRA = 225 A


8 FD- ILUMINACION = 1
5 FD- T/C = 1
3 FD- ESP. = 0.8
0
CARGA TOTAL KW AMPERIOS PROTECCION DESCRIPCION
A B C CONECT P Amp. Icc (Ka)
0.68 5.9 1 15 10 ALUMBRADO 56 W
1.08 9.4 1 15 10 T/C GENERALES
1.08 9.4 1 15 10 T/C GENERALES
0.72 6.3 1 15 10 T/C GENERALES
0.00 0.00 0.0 2 15 10 SECADORA
1.00 8.7 1 15 10 PLANCHA
2.76 1.80 0.00

DE POTENCIA = 0.9 CORRIENTE TOTAL DEMANDADA= 14,19 A

D DEL CIRCUITO = 36 MTS CARGA MAXIMA PERMITIDA = 82%

DIVISOR DE ACOMETIDA (TERNAS) = 1


DUCTOR POR CAPACIDAD DE CORRIENTE = 12
CAIDA DE TENSION %= 1.5
DUCTOR POR CAPACIDAD DE TENSION 3% = 14
CONDUCTOR SELECIONADO = 10 (55 A)
2X40A TIPO HQC 10 KA
F 2#10 + N1#10+ T1 #12 THHN-AWG
1 f 3/4 "

CALENTADOR DE AGUA y COCINA DE GAS


SIN SECADORA
200 8.4

TABLAS DE CARGA
PROYECTO
ALIMENTADOR TABLERO ASCENSORES -

SISTEMA:3F,4H, 120/208V TIPO =


TABLERO: T1 N° DE CIRCUITOS =
FUNCION:ILUMINACION / FUERZA SALIDAS ACTIVAS =
MONTAJE: EMPOTRADO SALIDAS DE RESERVA =
UBICACION:IZQUIERDA SALIDAS BLOQUEADAS =
CTO TOMACORRIENTES CONDUCTOR KW
ALUMBRADO KW
N° T/C ESPECIAL N° TIPO CIRC
1 5 12 THHN 0.062 0.31
2 2 12 THHN 0.18 0.36
3 12 THHN 0.18 0.00
4 12 THHN 0.18 0.00
5.7 1 8 THHN 8 8.00
6 1 8 THHN 8 8.00
16.67

P FASE A : 6.00 KW FACTOR DE POTENCIA =


P FASE B : 5.33 KW
P FASE C : 5.33 KW LONGITUD DEL CIRCUITO =

CARGA TOTAL CONECTADA: 16.67 KW DIVISOR DE ACOMETIDA


PRIMEROS 20 KW 100% 16.67 KW CONDUCTOR POR CAPACIDAD DE CO
RESTA 0.00 KW
siguientes DE 20 KW A 100 KW 40% CONDUCTOR POR CAPACIDAD DE TE
0.00 KW CONDUCTOR SELE
CARGA TOTAL DIVERSIFICADA: 16.67 KW PROTECCION =
RESERVA 40% 6.67 KW ACOMETIDA =
CARGA TOTAL DEMANDADA: 23.34 KW DUCTO=
TIPO =

***********
208
115

TABLAS DE CARGA
PROYECTO
R TABLERO ASCENSORES - AZOTEA

NLAB AMP-BARRA = 225 A


8 FD- ILUMINACION = 1
6 FD- T/C = 1
2 FD- ESP. = 0.8
0
CARGA TOTAL KW AMPERIOS PROTECCION DESCRIPCION
A B C CONECT P Amp. Icc (Ka)
0.31 2.7 1 20 10 ALUMBRADO 56 W
0.36 3.1 1 20 10 T/C GENERALES
0.00 0.0 1 20 10
0.00 0.0 1 20 10
2.67 2.67 2.67 38.5 2 20 10 ASCENSOR
2.67 2.67 2.67 38.5 1 20 10 ASCENSOR
6.00 5.33 5.33

DE POTENCIA = 0.9 CORRIENTE TOTAL DEMANDADA= 44,17 A


1.25 55.2125
D DEL CIRCUITO = 3X12 MTS CARGA MAXIMA PERMITIDA = 82%

DIVISOR DE ACOMETIDA (TERNAS) = 1


CTOR POR CAPACIDAD DE CORRIENTE = 6
CAIDA DE TENSION %= 2.703
CTOR POR CAPACIDAD DE TENSION 3% = 6
CONDUCTOR SELECIONADO = 6
3X90A TIPO EB 18 KA
F 3#1/0 + N1#4+ T1 #4 THHN-AWG
1 f 1 1/2"
NLAB408AB90_18KA

También podría gustarte