Está en la página 1de 15

Ubicación Tablero

QUINTO PISO STES-V

QUINTO PISO STES-V

QUINTO PISO STES-V

QUINTO PISO STES-V

QUINTO PISO STES-V

QUINTO PISO STES-V

QUINTO PISO STAA-V

QUINTO PISO STAA-V

QUINTO PISO STAA-V

AZOTEA STD-VI

AZOTEA STD-VI

AZOTEA STD-VI

AZOTEA STD-VI

AZOTEA STD-VI
AZOTEA STD-VI

AZOTEA STD-VI

AZOTEA STD-VI

AZOTEA STD-VI

AZOTEA STD-VI

AZOTEA STD-VI

AZOTEA STD-VI

AZOTEA STD-VI

AZOTEA STD-VI

AZOTEA STD-VI

AZOTEA STES-VI

AZOTEA STES-VI

AZOTEA STES-VI

AZOTEA STAA-VI

AZOTEA STAA-VI

AZOTEA STAA-VI

AZOTEA STAA-VI

AZOTEA STAA-VI

AZOTEA STAA-VI

AZOTEA STAA-VI

AZOTEA T-MONT 1

AZOTEA T-MONT 1

AZOTEA T-MONT 2
AZOTEA T-MONT 2

AZOTEA T-ASC 1

AZOTEA T-ASC 1

AZOTEA T-ASC 2

AZOTEA T-ASC 2
Máxima Voltaje
Circuito Demanda [kW] [kV] k

CES1,TOMACORRIENTES ESTABILIZADOS
OFICINA CONTABILIDAD,OFICINA 0.75 0.22 2.00
ADMINISTRATIVA

CES2,TOMACORRIENTES ESTABILIZADOS
0.50 0.22 2.00
CAFETIN,ESTAR MEDICO

CES3, CENTRAL DE MUSICA Y PERIFONEO 0.25 0.22 2.00

CES4,TOMACORRIENTES ESTABILIZADOS,
0.50 0.22 2.00
SALA DE USOS MULTIPLES

CES5, TOMACORRIENTES ESTABILIZADOS 1.00 0.22 2.00

SubTotal 2.40 0.38 1.73

C1,EXTRACTOR EA01-5P 0.30 0.22 2.00

C2, EXTRACTOR EA02-5P 0.30 0.22 2.00

SubTotal 0.48 0.38 1.73

C1,ALUMBRADO SALA DE ESPERA 0.44 0.22 2.00

S DE AIRE ACONDICIONADO,OFICINA VIDEO VIGILANCIA,SS.HH.MUJERES


0.41 0.22 Y2.00
HOMBRES

C3,ALUMBRADO CIRCULACION 0.28 0.22 2.00

DO OFICINA NUTRICIONISTA,CLASIFICACION,RECEPCION,HALL,DESPACHO
0.57 0.22 2.00

UMBRADO DISPENSA,ESTERILIZACION,ROPA LIMPIA, ROPA


0.54
SUCIA 0.22 2.00
C6,ALUMBRADO BAÑO+VESTUARIO HOMBRES Y MUJERES
0.16 0.22 2.00

C7,ALUMBRADO CIRCULACION TECNICA 0.44 0.22 2.00

C8,TOMACORRIENTES SALA DE ESPERA 0.75 0.22 2.00

C9,TOMACORRIENTES CIRCULACION TECNICA 0.75 0.22 2.00

C10,TOMACORRIENTES OFICINA VIDEO VIGILANCIA 1.25 0.22 2.00

ORRIENTES DESPENSA,OFICINA NUTRICIONISTA,RECEPCION,DESPACHO


1.25 0.22 2.00

,TOMACORRIENTES ESTERILIZACION, ROPA LIMPIA,DESPACHO


1.75 0.22 2.00

C13,ESTERILIZADOR 5.00 0.22 2.00

C14,ESTERILIZADOR 5.00 0.22 2.00

SubTotal 13.01 0.38 1.73

CES1,TOMACORRIENTES ESTABILIZADOS OFICINA NUTRICIONISTA,OFI 1.00 0.22 2.00

CES2, TOMACORRIENTES ESTABILIZADOS DESPENSA,ESTERILIZACION 1.25 0.22 2.00

SubTotal 1.80 0.38 1.73

C1,EA-06-I 0.85 0.22 2.00

C2,EA-01-S 0.40 0.22 2.00

C3,EAP01-S 3.40 0.38 1.73

C4,EA-01-S 0.80 0.22 2.00

C5,EA-07-IV 0.50 0.22 2.00

C6,UC-01-4P 1.60 0.22 2.00

SubTotal 6.04 0.38 1.73

C1,FUERZA MONTACARGA 8.00 0.38 1.73

SubTotal 6.40 0.38 1.73

C2,FUERZA MONTACARGA 8.00 0.38 1.73


SubTotal 6.40 0.38 1.73

C1,ASCENSOR 8.00 0.38 1.73

SubTotal 6.40 0.38 1.73

C1,ASCENSOR 8.00 0.38 1.73

SubTotal 6.40 0.38 1.73


L(m) Tipo de Uso del Calibre de
I [A] Id [A] [total] conductor conductor conductor [mm2] ΔV [%]

3.79 4.73 31.40 NH-80 Ducto 4.00 0.59

2.53 3.16 32.20 NH-80 Ducto 4.00 0.40

1.26 1.58 30.00 NH-80 Ducto 4.00 0.19

2.53 3.16 43.50 NH-80 Ducto 4.00 0.55

5.05 6.31 34.20 NH-80 Ducto 4.00 0.86

4.06 5.07 80.00 NH-80 Ducto 10.00 0.32

1.52 1.89 54.00 NH-80 Ducto 4.00 0.41

1.52 1.89 46.20 NH-80 Ducto 4.00 0.35

0.81 1.01 85.00 NH-80 Ducto 4.00 0.17

2.20 2.75 31.40 NH-80 Ducto 2.50 0.55

2.05 2.56 39.00 NH-80 Ducto 2.50 0.63

1.39 1.74 32.20 NH-80 Ducto 2.50 0.36

2.87 3.59 40.00 NH-80 Ducto 2.50 0.91

2.75 3.43 57.04 NH-80 Ducto 2.50 1.25


0.81 1.01 48.00 NH-80 Ducto 2.50 0.31

2.22 2.78 49.00 NH-80 Ducto 2.50 0.87

3.79 4.73 22.20 NH-80 Ducto 4.00 0.42

3.79 4.73 39.50 NH-80 Ducto 4.00 0.74

6.31 7.89 20.00 NH-80 Ducto 4.00 0.63

6.31 7.89 56.00 NH-80 Ducto 4.00 1.76

8.84 11.05 58.20 NH-80 Ducto 6.00 1.70

25.25 31.57 27.00 NH-80 Ducto 6.00 2.26

25.25 31.57 28.00 NH-80 Ducto 6.00 2.34

21.98 27.48 90.00 NH-80 Ducto 50.00 0.39

5.05 6.31 27.00 NH-80 Ducto 4.00 0.68

6.31 7.89 40.00 NH-80 Ducto 4.00 1.26

3.04 3.80 95.00 NH-80 Ducto 6.00 0.48

4.29 5.37 29.00 NH-80 Ducto 4.00 0.62

2.02 2.53 26.00 NH-80 Ducto 4.00 0.26

5.75 7.18 26.00 NH-80 Ducto 4.00 0.37

4.04 5.05 22.40 NH-80 Ducto 4.00 0.45

2.53 3.16 21.00 NH-80 Ducto 4.00 0.26

8.08 10.10 24.00 NH-80 Ducto 4.00 0.96

10.21 12.76 98.00 NH-80 Ducto 25.00 0.40

13.52 16.90 4.00 NH-80 Ducto 4.00 0.13

10.82 13.52 99.00 NH-80 Ducto 25.00 0.43

13.52 16.90 4.00 NH-80 Ducto 4.00 0.13


10.82 13.52 99.00 NH-80 Ducto 25.00 0.43

13.52 16.90 5.00 NH-80 Ducto 4.00 0.17

10.82 13.52 99.00 NH-80 Ducto 25.00 0.43

13.52 16.90 5.00 NH-80 Ducto 4.00 0.17

10.82 13.52 99.00 NH-80 Ducto 25.00 0.43


Intesidad de Corriente de Interruptor
ΣV [%] ΔV [V] llave térmica [A] ruptura [kA] Tipo de llave térmica diferencial

1.32 1.30 2 x 16 A 6 kA Riel Din 2 x 25 A

1.13 0.89 2 x 16 A 6 kA Riel Din 2 x 25 A

0.92 0.41 2 x 16 A 6 kA Riel Din 2 x 25 A

1.28 1.20 2 x 16 A 6 kA Riel Din 2 x 25 A

1.59 1.89 2 x 16 A 6 kA Riel Din 2 x 25 A

0.73 1.23 3 x 16 A 10 kA Riel Din

1.10 0.89 2 x 16 A 6 kA Riel Din 2 x 25 A

1.04 0.77 2 x 16 A 6 kA Riel Din 2 x 25 A

0.70 0.65 3 x 20 A 10 kA Caja Moldeable Fija

1.20 1.21 2 x 16 A 6 kA Riel Din 2 x 25 A

1.28 1.40 2 x 16 A 6 kA Riel Din 2 x 25 A

1.01 0.79 2 x 16 A 6 kA Riel Din 2 x 25 A

1.56 2.01 2 x 16 A 6 kA Riel Din 2 x 25 A

1.90 2.74 2 x 16 A 6 kA Riel Din 2 x 25 A


0.96 0.68 2 x 16 A 6 kA Riel Din 2 x 25 A

1.52 1.91 2 x 16 A 6 kA Riel Din 2 x 25 A

1.07 0.92 2 x 16 A 6 kA Riel Din 2 x 25 A

1.39 1.64 2 x 16 A 6 kA Riel Din 2 x 25 A

1.28 1.38 2 x 16 A 6 kA Riel Din 2 x 25 A

2.41 3.87 2 x 16 A 6 kA Riel Din 2 x 25 A

2.35 3.75 2 x 16 A 6 kA Riel Din 2 x 25 A

2.91 4.97 2 x 32 A 6 kA Riel Din 2 x 40 A

2.99 5.16 2 x 32 A 6 kA Riel Din 2 x 40 A

0.65 1.50 3 x 40 A 10 kA Caja Moldeable Fija

1.56 1.49 2 x 16 A 6 kA Riel Din 2 x 25 A

2.14 2.76 2 x 16 A 6 kA Riel Din 2 x 25 A

0.89 1.82 3 x 20 A 10 kA Caja Moldeable Fija

1.54 1.36 2 x 16 A 6 kA Riel Din 2 x 25 A

1.18 0.57 2 x 16 A 6 kA Riel Din 2 x 25 A

1.30 1.41 3 x 16 A 10 kA Riel Din 4 x 25 A

1.37 0.99 2 x 16 A 6 kA Riel Din 2 x 25 A

1.19 0.58 2 x 16 A 6 kA Riel Din 2 x 25 A

1.89 2.12 2 x 16 A 6 kA Riel Din 2 x 25 A

0.92 1.51 3 x 16 A 10 kA Riel Din

0.82 0.51 3 x 20 A 10 kA Riel Din

0.68 1.62 3 x 20 A 10 kA Riel Din

0.82 0.51 3 x 20 A 10 kA Riel Din 4 x 25 A


0.68 1.62 3 x 20 A 10 kA Riel Din

0.85 0.64 3 x 20 A 10 kA Riel Din 4 x 25 A

0.68 1.62 3 x 20 A 10 kA Riel Din

0.85 0.64 3 x 20 A 10 kA Riel Din

0.68 1.62 3 x 20 A 10 kA Riel Din


Tubo
PVC/Conduit
SAP (mm)

20 mm

20 mm

20 mm

20 mm

20 mm

40 mm

20 mm

20 mm

25 mm

20 mm

20 mm

20 mm

20 mm

20 mm
20 mm

20 mm

20 mm

20 mm

20 mm

20 mm

25 mm

25 mm

25 mm

80 mm

20 mm

20 mm

35 mm

20 mm

20 mm

25 mm

20 mm

20 mm

20 mm

65 mm

25 mm

65 mm

25 mm
65 mm

25 mm

65 mm

25 mm

65 mm

También podría gustarte