02 Pase Aereo 81 M
02 Pase Aereo 81 M
Fc = 9m
11.30
0.5
1.8
LP = 81 m
10 10.00 1.049
4.000
11 11.00 1.164
12 12.00 1.290
3.000
13 13.00 1.427
14 14.00 1.575
2.000
15 15.00 1.735
16 16.00 1.905 1.000
17 17.00 2.086
18 18.00 2.278 0.000
19 19.00 2.481 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00
0. 2. 4. 6. 8. 10. 12. 14. 16. 18. 20. 22. 24. 26. 28. 30. 32. 34. 36. 38.
20 20.00 2.695
21 21.00 2.920
22 22.00 3.156
23 23.00 3.403
24 24.00 3.660
25 25.00 3.929
26 26.00 4.209
27 27.00 4.500
28 28.00 4.802
29 29.00 5.115
30 30.00 5.438
31 31.00 5.773
32 32.00 6.119
33 33.00 6.475
34 34.00 6.843
35 35.00 7.222
36 36.00 7.611
37 37.00 8.012
38 38.00 8.423
39 39.00 8.846
40
132.70
Longitud Total de Péndolas 265.40
Diseño de Cable
Factor de seguridad a la tension (2 -5) 5.0
Tmax.rotr = Tmax.ser x Fs 22.4 Tn < 50.3 OK!
Se adopta Cable de 1 '' Cable tipo Boa ( 6x19 )
CALCULOS DESCRIPCION
d= 1.026
d= 1.0 m
b =1.85
e d
b/2
e (excentricidad de la resultante de fuerzas)
e= -0.101 < b/3 = 0.6 OK !
q ( presion con que actua la estructura sobre el terreno)
q =(suma Fzas. verticales/ Area)*(1 ± 6* e/ b)
q1=[(Wp-Tmax.ser*SEN(o) )/(b*prof)]*(1+6* e/ b)
q1= 0.2005 < 0.4 kg/cm2 OK!
q2=[(Wp-Tmax.ser*SEN(o) )/(b*prof)]*(1-6* e/ b)
q2= 0.3960 < 0.4 kg/cm2 OK!
CIMENTACIÓN
DIMENSIONAMIENTO
CALCULOS DESCRIPCION
Sobre carga piso 150.00 kg/m2
Profundiadad de desplante (Df) 2.20 m.
Diametro de Acero Columna 1 "
Calculo del peralte (ld) Ld=0.08xdbxfy/√/f´c 23.19 cm.
Altura de Zapata teorica 31.19 cm
Altura de Zapata Asumida (hc) 0.90 m
ht 1.30 m
Calculo de Presion de suelo (qm) qm = qa - gtxht - gcxhc - s/c 0.34 kg/cm2 ht = 1.30
Tension Vertical = TH*Sen (0) 2871.28853637119 Kg Df = 2.20
Peso de la Columna 27120 Kg Lv
Peso sobre la columna (Ps) 29991.29 kg
Calculo de Area de Zapata
A'z = Ps A'z = 88209.67 cm2 hc = 0.90
qm T = 297.00 cm
T = Az^.5 + ( t - b ) B = 297.00 cm T = 6.40
2 B = 6.00
B = Az^.5 - ( t - b )
2 b = 1.00
Dimensiones a Usar
T = 640.00 cm
B = 600.00 cm t = 1.00
VERIFICACION POR CORTE ( Ø = 0.85 )
CALCULOS DESCRIPCION
DIRECCION TRANSVERSAL
CALCULOS DESCRIPCION
Lv = ( B - b ) / 2 250.00 cm T = 6.40
Mu = qmu x T x Lv²/2 2,186,864.79 kg-cm
Fs1 =0.82
Ht/3
6.00
Nivel hi wixhi Fs ( i )
3 11.3 204.304 2.45 Ton
2 7.5 136.20 1.63 Ton
1 3.8 68.10 0.82 Ton
408.608
Fs = (S.U.C.Z / Rd )*Peso de toda la estructura Fs (fuerza sismica total en la base)
Fs = 4.89 Ton
ANALISIS DE ESTABILIDAD
b/2= d + e Wp
e=b/2-d < b/3
d=( suma de momentos)/(suma de fuerzas verticales)
d = (Wp*2b/3+Wz*b/2+Tmax.ser*SEN(o2)*2b/3+Tmax.ser*SEN(o)*2b/3-[ Tmax.ser*COS(o2)-
Tmax.ser*COS(o) ]*(H+hz)-Fs3*(H+hz)-Fs2*2*(H+hz)/3-Fs1*(H+hz)/3) /
(Wp+Wz+Tmax.ser*SEN(o)+Tmax.ser*SEN(o2))
d = (Wp*2b/3+Wz*b/2+Tmax.ser*SEN(o2)*2b/3+Tmax.ser*SEN(o)*2b/3-[ Tmax.ser*COS(o2)-
Tmax.ser*COS(o) ]*(H+hz)-Fs3*(H+hz)-Fs2*2*(H+hz)/3-Fs1*(H+hz)/3) /
(Wp+Wz+Tmax.ser*SEN(o)+Tmax.ser*SEN(o2))
q2 q1
d = 3.0 m
b =6.4
q ( presion con que actua la estructura sobre el terreno) e d
q =(suma Fzas. verticales/ Area)*(1+ 6* e/ b)
q1=[(Wp+Wz+Tmax.ser*SEN(o2)+Tmax.ser*SEN(o) ))/ (b*prof)]*(1+6* e/ b) b/2
q1= 0.40 < 0.4 kg/cm2 OK!
q2=[(Wp+Wz+Tmax.ser*SEN(o2)+Tmax.ser*SEN(o) ))/ (b*prof)]*(1-6* e/ b)
q2= 0.24 < 0.4 kg/cm2 OK!
ANALISIS DE LOS FACTORES DE SEGURIDAD
11.3
Wp
A A
1
1
Diámetro Ø
Area as cm2 Cantidad de varillas Area Total As cm2
Pulg
1 5.07 4 20.28 B Cal B asum
1 5.07 4 20.28 34.00 100 Ok
TOTAL 40.56 Ok
Tmax.rot/columna=1.5*Tmax.ser/columna
VU (cortante ultimo)
Vu= Tmax.rot*COS(o2)-Tmax.rot*COS(o)+Fs3+Fs2+Fs1
RESULTADOS DE DISEÑO
DIMENSIONES DE PASE AÉREO
Fc = 9m
11.30
0.5
1.8
LP = 81 m
1.70m
1.50m
1.85m
Dimensiones de Cimentación
Largo 6.40 m
Ancho 6.00 m
Altura 0.90 m
Profundidad de Desplante 2.20 m
6.40 m 0.90 m
6.00 m
Detalle de Armado de Acero
10 m
11.3 m
Nivel de Terreno
0.9 m
2.7 m 1m 2.7 m