SONDAJES EL MOLINO LLAYLLAY LLAYLLAY TAG: SMOLIN_EVAP TWIDO 10.200.80.111

RANGO Y/O SCADA PLC


ELEMENTO TIPO TAG DESCRIPCION
UNIDAD WORD :BIT WORD :BIT
ESTANQUE UCUKER ANA ESC AAAAAA_AAAAAA_ENPR1_EST01 NIVEL PARADA ESTANQUE UCUKER 0-500CM 40013 12
ANA ESC AAAAAA_AAAAAA_ENPT1_EST01 NIVEL PARTIDA 1 ESTANQUE UCUKER 0-500CM 40014 13
ANA ESC AAAAAA_AAAAAA_ENPT2_EST01 NIVEL PARTIDA 2 ESTANQUE UCUKER 0-500CM 40015 14
ANA ESC AAAAAA_AAAAAA_EREFE_EST01 NIVEL REFERENCIA PID ESTANQUE UCUKER 0-500CM 40016 15
SONDAJE 1 (938) ANA LEC AAAAAA_AAAAAA_LHORO_SON01 HOROMETRO SONDAJE 1 H 40004 3
DIG LEC AAAAAA_AAAAAA_LFUNC_SON01 FUNCIONANDO SONDAJE 1 40001 0 0 0
DIG LEC AAAAAA_AAAAAA_LFALL_SON01 FALLA SONDAJE 1 40001 1 0 1
DIG LEC AAAAAA_AAAAAA_LRGN_SON01 NIVEL BAJO RGN SONDAJE 1 40001 2 0 2
DIG ESC AAAAAA_AAAAAA_EHOPU_SON01 SWITCH HORA PUNTA SONDAJE 1 40003 6 2 6
SONDAJE 2 (939) ANA LEC AAAAAA_AAAAAA_LHORO_SON02 HOROMETRO SONDAJE 2 H 40005 4
DIG LEC AAAAAA_AAAAAA_LFUNC_SON02 FUNCIONANDO SONDAJE 2 40001 3 0 3
DIG LEC AAAAAA_AAAAAA_LFALL_SON02 FALLA SONDAJE 2 40001 4 0 4
DIG LEC AAAAAA_AAAAAA_LRGN_SON02 NIVEL BAJO RGN SONDAJE 2 40001 5 0 5
DIG ESC AAAAAA_AAAAAA_EHOPU_SON02 SWITCH HORA PUNTA SONDAJE 2 40003 7 2 7
VARIADOR 1 ANA LEC AAAAAA_AAAAAA_LFREC_VFR01 FRECUENCIA VARIADOR 1 0-50,0HZ 40006 5
ANA LEC AAAAAA_AAAAAA_LPOTE_VFR01 POTENCIA VARIADOR 1 0-45KW 40007 6
DIG LEC AAAAAA_AAAAAA_LFUNC_VFR01 FUNCIONANDO VARIADOR 1 40001 6 0 6
DIG LEC AAAAAA_AAAAAA_LFALL_VFR01 FALLA VARIADOR 1 40001 7 0 7
DIG LEC AAAAAA_AAAAAA_LAUTO_VFR01 AUTOMATICO VARIADOR 1 40001 8 0 8
DIG LEC AAAAAA_AAAAAA_LMLOC_VFR01 MANUAL LOCAL VARIADOR 1 40001 9 0 9
DIG ESC AAAAAA_AAAAAA_EMREM_VFR01 MANUAL REMOTO VARIADOR 1 40003 0 2 0
DIG ESC AAAAAA_AAAAAA_EPAPA_VFR01 PARTIR PARAR VARIADOR 1 40003 1 2 1
DIG ESC AAAAAA_AAAAAA_ERESE_VFR01 RESET VARIADOR 1 40003 2 2 2
VARIADOR 2 ANA LEC AAAAAA_AAAAAA_LFREC_VFR02 FRECUENCIA VARIADOR 2 0-50,0HZ 40008 7
ANA LEC AAAAAA_AAAAAA_LPOTE_VFR02 POTENCIA VARIADOR 2 0-45KW 40009 8
DIG LEC AAAAAA_AAAAAA_LFUNC_VFR02 FUNCIONANDO VARIADOR 2 40001 10 0 10
DIG LEC AAAAAA_AAAAAA_LFALL_VFR02 FALLA VARIADOR 2 40001 11 0 11
DIG LEC AAAAAA_AAAAAA_LAUTO_VFR02 AUTOMATICO VARIADOR 2 40001 12 0 12
DIG LEC AAAAAA_AAAAAA_LMLOC_VFR02 MANUAL LOCAL VARIADOR 2 40001 13 0 13
DIG ESC AAAAAA_AAAAAA_EMREM_VFR02 MANUAL REMOTO VARIADOR 2 40003 3 2 3
DIG ESC AAAAAA_AAAAAA_EPAPA_VFR02 PARTIR PARAR VARIADOR 2 40003 4 2 4
DIG ESC AAAAAA_AAAAAA_ERESE_VFR02 RESET VARIADOR 2 40003 5 2 5
GENERADOR DIG LEC AAAAAA_AAAAAA_LFUNC_GRE01 FUNCIONANDO GENERADOR 40010 0 9 0
DIG LEC AAAAAA_AAAAAA_LFALL_GRE01 FALLA GENERADOR 40010 1 9 1
DIG LEC AAAAAA_AAAAAA_LBCOM_GRE01 BAJO NIVEL COMBUSTIBLE GENERADOR 40010 2 9 2
DIG LEC AAAAAA_AAAAAA_LDINCE_GRE01 DETECCION DE INCENDIO GENERADOR 40010 3 9 3
DIG ESC AAAAAA_AAAAAA_EHOPU_GRE01 HORA PUNTA GENERADOR 40003 8 2 8
BASE 24 ENTRADAS DIGITALES, 16 SALIDAS DIGITALES. TWDLCAE40DRF MODULO 8 ENTRADA
%I0.0 SONDAJE 1 MODO AUTOMATICO %Q0.0 %IW1.0
%I0.1 SONDAJE 1 FUNCIONANDO %Q0.1 %IW1.1
%I0.2 SONDAJE 1 FALLA %Q0.2 PARTIR SONDAJE 1 %IW1.2
%I0.3 SONDAJE 1 NIVEL BAJO RGN %Q0.3 RESET SONDAJE 1 %IW1.3
%I0.4 SONDAJE 2 MODO AUTOMATICO %Q0.4 PARTIR SONDAJE 2 %IW1.4
%I0.5 SONDAJE 2 FUNCIONANDO %Q0.5 RESET SONDAJE 2 %IW1.5
%I0.6 SONDAJE 2 FALLA %Q0.6 PARTIR GENERADOR %IW1.6
%I0.7 SONDAJE 2 NIVEL BAJO RGN %Q0.7 %IW1.7
%I0.8 GENERADOR FUNCIONANDO %Q0.8
%I0.9 GENERADOR FALLA %Q0.9
%I0.10 GENERADOR BAJO COMBUSTIBLE %Q0.10
%I0.11 GENERADOR DETECCION INCENDIO %Q0.11
%I0.12 %Q0.12
%I0.13 %Q0.13
%I0.14 %Q0.14
%I0.15 %Q0.15
%I0.16
%I0.17
%I0.18
%I0.19
%I0.20
%I0.21
%I0.22
%I0.23
MODULO 8 ENTRADAS ANALOGAS. TM2AMI8HT MODULO 1 SALIDA ANALOGA. TM2AMO1HT
FRECUENCIA VARIADOR 1. 0-50HZ %QW2.0 REFERENCIA NIVEL UCUKER. 0-10V
POTENCIA VARIADOR 2. 0-45KW
FRECUENCIA VARIADOR 3. 0-50HZ
POTENCIA VARIADOR 2. 0-45KW