Está en la página 1de 19

PROYECTO :

MEJORAMIENTO Y CONSTRUCCION DE AGUA POTABLE Y LETRINAS-PAUCARBAMBILLA -EL CARMEN

PROYECTISTA: ING. YANETT MAGALI DELGADILLO GAMBOA


DISTRITO : EL CARMEN
PROVINCIA: CHURCAMPA DEPARTAMENTO: HUANCAVELICA
FECHA: SETIEMBRE 2008

MEMORIA DE CÁLCULO - LINEA DE CONDUCCION

CUADRO 2.1
A.- POBLACION ACTUAL 1800 hab. Coeficiente de crecimiento lineal por departamento ( r )
CRECIMIENTO CRECIMIENTO
B.- TASA DE CRECIMIENTO (r%) 1.80 % DEPART. ANUAL % DEPARTAMENTO ANUAL %
HAB. ( r ) HAB. ( r )
C.- PERIODO DE DISEÑO (AÑOS) 20 años Piura 3 Cusco 1.5
Cajamarca 2.5 Apúrimac 1.5
D.- POBLACION FUTURA 2448 hab. Lambayeque 3.5 Arequipa 1.5
rt La Libertad 2 Puno 1.5
Pf =Pa( 1+ ) Ancash 1 Moquegua 1
100
Huánuco 2.5 Tacna 4
E.- DOTACION (LT/HAB/DIA) 100 lt/hab/dia Huancavelica 2.5 Loreto 1
Pasco 2.5 San Martin 3
F.- CONSUMO PROMEDIO ANUAL (LT/SEG) Lima 2.5 Amazonas 4
Pf . D 2.83 lps. Ica 3.2 Madre de Dios 4
Qm=
864000
CUADRO 01.01 CUADRO 01.02
G.- CONSUMO MAXIMO DIARIO (LT/SEG) 3.68 lps. Periodo de diseño recomendado para Periodo de diseño recomendado según
k1 = 1.30 poblaciones rurales la población
Qmd=k 1 Qm COMPONENTE PERIODO DE POBLACIÓN PERIODO DE
como 1.33 > 0.50 ok DISEÑO DISEÑO
El valor de K1 para pob. rurales varia entre 1.2 y 1.5. Obras de captación 20 años 2,000 - 20,000 15 años
(dependiendo de la población de diseño y de la región) Conduccion 10 a 20 años Mas de 20,000 10 años
Reservorio 20 años
H.- CAUDAL DE LA FUENTE (LT/SEG) 1.33 lt/seg. Red principal 20 años
Red secundaria 10 años
I.- CONSUMO MAXIMO HORARIO (LT/SEG) 5.67 lt/seg.
k2 = 2.00 CUADRO 02.01 CUADRO 02.02
Qmh=k 2 Qm Dotación por números de habitantes Dotación según Región
POBLACIÓN DOTACIÓN REGIÓN DOTACIÓN
El valor de k2 varían desde 1 hasta 4. (habitantes) (l/hab/día) (l/hab/día)
(dependiendo de la población de diseño y de la región) Hasta 500 60 Selva 70
500 - 1000 60 - 80 Costa 60
J.- VOLUMEN DEL RESERVORIO (M3) 1000 - 2000 80 - 100 Sierra 50
VOL. ALM. = VREG. + VINCENDIO + VRESERVA. Fuente: Ministerio de Salud Fuente: Ministerio de Salud

V = 0.25 * Qmd *86400/1000 Poblacion Vol. Extincion de Incendio


< 10000 -
Vol. Reg. = 25% ( Consumo Medio Diario) 10000 < P < 100000 2 grifos (hidrantes) tmin=2horas(Q=15lt/seg)
Vol Reg. =0.25*Qmx86400seg/1000 79.56 m3. > 100000 tmin.=2horas; zona resid.: 2 grifos; zona industrial:3 grifos.
Vol. Incendio = 0.00 m3 Coef. de Hanzen-Williams: Tub. de diametros comerciales
MATERIAL C Diametro D(cm)
- VRESERVA = 25 % Vol. Total. 26.52 m3 F°F° - F°G° 100 0.75 3/4" 0.75 1.905
- VRESERVA = 33 % ( Vol.Regulacion + Vol. Incendio). 26.25 m3 Concreto 110 1 1" 1 2.54
- VRESERVA = Qp x t ---------> 2 horas < t < 4 horas 30.60 m3 Acero 120 1.5 1 1/2" 1.5 3.81
-VRESERVA = 30.60 m3 Asbesto cemento 140 2 2" 2 5.08
P.V.C 150 3 3" 2.5 6.35
Vol. Almac.= 110.16 m3 4 4" 3 7.62
(El proyectista asume un volumen razonable) 5 5" 4 10.16
6 6" 6 15.24
Calculo Linea de Conducción
Q
Ecuación de Hazen Williams D=( )1/ 2 .63
4 , 26∗10−4∗C∗S 0. 54 Pf = Po + ^h -hf

CÁLCULO HIDRAULICO DE LA LINEA DE CONDUCCIÓN


LONGITUD CAUDAL COTA DEL TERRENO DESNIVEL PERDIDA DIAM. DIAM. Pf
TRAMO DEL CARGA UNIT. CALC. COMER. Po (m.c.a)
L Qmd INICIAL FINAL TERRENO DISPONIBLE
hf D D
(Km) (l/s) (m.s.n.m) (m.s.n.m) (m) (m) (Pulg.) (Pulg.)
CRP. - RESERV. 2.00 3.68 7.200 5.200 2.00 17.26 2.41 3 0.00 32.74
EJERCICIO 2
1 65 1.9 2.875 2.81 65 18.39 1.54 2 0.00 46.61
2 55 1.9 2.875 2.82 55 18.39 1.59 2 0 36.61

Hf=Sr * L
Q
Sr =( )1/ 0 .54
4 ,26∗10 ∗C∗D 2 .63
−4
PROYECTO :
MEJORAMIENTO Y CONSTRUCCION DE AGUA POTABLE Y LETRINAS-PAUCARBAMBILLA -EL CARMEN

PROYECTISTA: ING. YANETT MAGALI DELGADILLO GAMBOA


DISTRITO : EL CARMEN
PROVINCIA: CHURCAMPA DEPARTAMENTO: HUANCAVELICA
FECHA: SETIEMBRE 2008

MEMORIA DE CÁLCULO - CAPTACIÓN


DATOS GENERALES DEL PROYECTO AFORO MANANTIAL PAMPALCO
Tiempo 3 seg.
Población Actual : 1800 hab. Vol. Recip. 4 lts. Cadal de Diseño : 3.68 l/s
Población Futura : 2448 hab. Caudal 5.00 lts/seg Caudal Máximo : 5.67 l/s

DISEÑO DE LA CAPTACION - MANANTIAL DE LADERA Y CONCENTRADO

PROTECCIÓN CÁM ARA CÁM ARA


CANASTILLA
DE SALIDA AFLORAMIENTO HUMEDA SECA
TU BERIA
DE SALIDA

AFLORO
0 2
1 b AFLORO
A A C ANASTILLA
L DE SALIDA
0 h0 TUBERIA
TUBERÍA D E
1 2 DE SALIDA
REBOSE Y LIMPIA L

TUBERÍA DE
REBOSE Y LIMPIA

PROTECCIÓN CÁMARA CÁMARA


AFLORAMIENTO HUMEDA SECA

PLANTA DE CAPTACIÓN ELEVACIÓN: CORTE A-A

A .- CÁLCULO DE LA DISTANCIA ENTRE EL AFLORAMIENTO Y LA CAMARA HÚMEDA (L):


MEMORIA DE CÁLCULO - CAPTACIÓN
FÓRMULA:

L = 3.33 (ho - 1.56V2 /2g)


2

ho DONDE:
ho : Se recomienda valores entre 0.40 y 0.50m.
V2: Velocidad de salida.recommendable menor
a 0.60 m/s.
ho = 0.4 m.
Considerando: g = 9.81 m/seg2
V2 = 0.6 m/seg.

L= 1.24 m.
L= 1.20 m.
L

B .- CÁLCULO DEL ANCHO DE LA PANTALLA (b):

CÁLCULO DEL DIÁMETRO DE LA TUBERIA


DE INGRESO A LA CAPTACIÓN:

A = Qmax / Cd * V
Donde:
Cd: Coeficiente de descarga(0.6 - 0.8)
V : Velocidad de descarga ≤ 0.6m/seg.
Qmax. : Caudal máximo del manantial (m3/seg)
A : Área total de las tuberias de salida.
MEMORIA DE CÁLCULO - CAPTACIÓN
Tomando valores:
V : 0.5 m/s A= 0.01417 m2
Qmax: 0.00567 m3/s D= 13.43 cm.
Cd : 0.8 Asumiendo:
D= 2 Pulgadas

; Aasumido= 0.002 m2

NA = Area Dobtenido + 1 Donde:


Area Dasumido NA : Número de orificios
ASUMIR
NA = 7.99 ≈ SEGÚN
2 Unidades
CRITERIO

b = ( 9 + 4 NA ) * D b= 0.85 m

C .- DETERMINACION DE LA ALTURA DE LA CÁMARA HÚMEDA ( Ht ):

a Ht = A + B + H + D + E
DONDE:
A = 10.00 cm.(Mínimo)
B = 1/2 Diámetro de la canastilla.
D = Desnivel mínimo (3.00 cm)
E = Borde Libre ( 10 - 30 cm.)
H = Altura del agua que permita una velocidad determinada a la
Ht salida de la tuberia a la linea de conducción.(min 30cm.)

1. 56 . V
2 Q md
H= V=
2g Ac

Qmd = 0.003683 m3/seg V = 12.92949 m/seg


MEMORIA DE CÁLCULO - CAPTACIÓN
g= 9.81 m/seg2 H = 13.29194 m.
Ac = 0.0003 m2

Por lo tanto H= 13.29 m. (altura mim. Recomendado 0.30m)


Asumiendo :
Dc = 0.75 Pulg.
E= 0.30 m.
D= 0.03 m. Ht = 13.74 m.
A= 0.10 m.
B= 0.019 m.

D .- DISEÑO DE LA CANASTILLA :

CONDICIONES:
At = 2 Ac At
N° ranura =
3 Dc < L < 6 Dc. Área de una ranura
At ≤ 0.50 * Dg * L
MEMORIA DE CÁLCULO - CAPTACIÓN
Donde :
At : Área total de las ranuras
Ag : Área de la granada.

At = 0.00057 m2

CÁLCULO DE L:
3*Dc = 5.715 cm
6*Dc = Asumircm
11.43 según el
rango anterior

L= 0.10 m
Ag = 0.00029 m2
At = 0.00057 m2
0.5*Dg*L = 0.00598 m2

0.00598 > 0.00057 -------- OK!

N° ranuras = 16.2871

Por lo tanto :

N° ranuras = 16 Ranuras

E .- DIMENSIONAMIENTO DE LA TUBERIA DE REBOSE Y LIMPIEZA :

FÓRMULA: Donde :
Q = Caudal máximo de la fuente en m3/seg
nQ 3 /8 S = Pendiente mínima (1 - 1.5 %) m/m
D=1 . 548[ ( ] n = coeficiente de rugosidad de manning
√S D = diámetro de la tuberia en m.

Datos:
n= 0.01 PVC
S= 0.5 %
Q= 5.67 lt/seg (caudal maximo)

n*Q = 5.7E-05
Asumir según criterio
√S= 0.07071
D= 0.11 m. ≈ 4.21 Pulg. Pulg. 2 Pulg.
PROYECTO :
MEJORAMIENTO Y CONSTRUCCION DE AGUA POTABLE Y LETRINAS-PAUCARBAMBILLA -EL CARMEN

PROYECTISTA: ING. YANETT MAGALI DELGADILLO GAMBOA


DISTRITO : EL CARMEN
PROVINCIA: CHURCAMPA DEPARTAMENTO: HUANCAVELICA
FECHA: SETIEMBRE 2008

DISEÑO DE RESERVORIO DE 12 M3. VALORES DE LOS COEFICIENTES (K) PARA EL CALCULO DE MOMENTOS - TAPA LIBRE Y FONDO EMPOTRADO

Nota: Para calculo de momentos, se debe tener presente la relacion b/h


Obra: Agua Potable Ingenio el resultado debe relacionarse con la aproximacion del cuadro en y=0, y=b/4 y y=b/2
Distrito : Palca tanto en momento x y momento y , en relacion a las distancias de 0, 1/4, 1/2, 3/4 y 1 tanto en x-y
Provincia : Huancavelica en la parte baja se obtendra el ancho del muro.
Departamento : Huancavelica

DATOS :

VOLUMEN (V) = 12.00 m3.


ANCHO DE LA PARED (b) = 2.50 m. y=0 y = b/4 y = b/2
ALTURA DEL AGUA (h) = 1.90 m. b/h x/h
BORDE LIBRE (B.L.) = 0.30 m. Mx My Mx My Mx My
ALTURA TOTAL (H) = 2.20 m. 0 0.000 0.025 0.000 0.014 0.000 -0.082
PESO ESPECIFICO DEL AGUA (§a) = 1,000.00 Kg/m3. ¼ 0.010 0.019 0.007 0.013 -0.014 -0.071
PESO ESPECIFICO DEL TERRENO (§t) = 1,800.00 Kg/m3. 3.00 ½ 0.005 0.010 0.008 0.010 -0.011 -0.055
CAPACIDAD DE CARGA DEL TERRENO (öt) = 2.10 Kg/cm2. ¾ -0.033 -0.004 -0.018 0.000 -0.006 -0.028
PESO ESPECIFICO DEL CONCRETO (§c) = 2,400.00 Kg/m3. 1 -0.126 -0.025 -0.092 -0.018 0.000 0.000

A) CALCULO DE MOMENTOS Y ESPESORES 0 0.000 0.027 0.000 0.013 0.000 -0.074


¼ 0.012 0.022 0.007 0.013 -0.013 -0.066
Los límites de relación de b/h son de 0.5 a 3.0 2.50 ½ 0.011 0.014 0.008 0.010 -0.011 -0.053
b/h = 1.32 ¾ -0.021 -0.001 -0.010 0.001 -0.005 -0.027
1 -0.108 -0.022 -0.077 -0.015 0.000 0.000
y=0 y = b/4 y = b/2 0 0.000 0.027 0.000 0.009 0.000 -0.060
b/h x/h ¼ 0.013 0.023 0.006 0.010 -0.012 -0.059
Mx My Mx My Mx My 2.00 ½ 0.015 0.016 0.010 0.010 -0.010 -0.049
0 0.000 185.19 0.00 61.73 0.00 -411.54 ¾ -0.008 0.003 -0.002 0.003 -0.005 -0.027
¼ 89.167 157.76 41.15 68.59 -82.31 -404.68 1 -0.086 -0.017 -0.059 -0.012 0.000 0.000
1.32 ½ 102.885 109.74 68.59 68.59 -68.59 -336.09 0 0.000 0.025 0.000 0.007 0.000 -0.050
¾ -54.872 20.58 -13.72 20.58 -34.30 -185.19 ¼ 0.012 0.022 0.005 0.008 -0.010 -0.052
1 -589.874 -116.60 -404.68 -82.31 0.00 0.00 1.75 ½ 0.016 0.022 0.010 0.009 -0.009 -0.046
¾ -0.002 0.022 0.001 0.004 -0.005 -0.027
1 -0.074 0.022 -0.050 -0.010 0.000 0.000
M = k x §a x h3 (01) 0 0.000 0.022 0.000 0.005 0.000 -0.040
¼ 0.008 0.022 0.004 0.007 -0.009 -0.044
DEL CUADRO: Mx = 589.874 Kg-m. 1.50 ½ 0.016 0.022 0.010 0.008 -0.008 -0.042
¾ 0.003 0.022 0.003 0.004 -0.005 -0.026
CALCULO DEL ESPESOR DE LA PARED: 1 -0.060 0.022 -0.041 -0.008 0.000 0.000

½ 0 0.000 0.015 0.000 0.003 0.000 -0.029


e= 6M (02) ¼ 0.005 0.015 0.002 0.005 -0.007 -0.034
ft x b 1.25 ½ 0.014 0.015 0.008 0.007 -0.007 -0.037
¾ 0.006 0.007 0.005 0.005 -0.005 -0.024
1 -0.047 -0.009 -0.031 -0.006 0.000 0.000
DONDE : 0 0.000 0.009 0.000 0.002 0.000 -0.018
ft = 0.85(F'c)^½ = 12.32 Kg/cm2. ¼ 0.002 0.011 0.000 0.003 -0.005 -0.023
F'c = 210.00 Kg/cm2. 1.00 ½ 0.009 0.013 0.005 0.005 -0.006 -0.029
Mx = 589.87 Kg-m. ¾ 0.008 0.008 0.005 0.004 -0.004 -0.020
My = 404.68 Kg-m. 1 -0.035 -0.007 -0.022 -0.005 0.000 0.000
b = 100.00 cm. 0 0.000 0.004 0.000 0.001 0.000 -0.007
¼ 0.001 0.008 0.000 0.002 -0.002 -0.011
REMPLAZANDO VALORES EN (02) TENEMOS: 0.75 ½ 0.005 0.010 0.002 0.003 -0.003 -0.017
¾ 0.007 0.007 0.003 0.003 -0.003 -0.013
e = 16.95 cm. 1 -0.024 -0.005 -0.015 -0.003 0.000 0.000
0 0.000 0.001 0.000 0.000 0.000 -0.002
PARA EL DISEÑO SE ASUME, QUE: ¼ 0.000 0.005 0.000 0.001 -0.001 -0.004
e = 20.00 cm. 0.50 ½ 0.002 0.006 0.001 0.001 -0.002 -0.009
d = 15.00 ¾ 0.004 0.006 0.001 0.001 -0.001 -0.007
1 -0.015 -0.003 -0.008 -0.002 0.000 0.000
CALCULO DEL ESPESOR DE LA LOSA DE CUBIERTA

SE CALCULA COMO LOSA ARMADA EN DOS DIRECCIONES

Espesor e = L/36 (03)

L = b + ((2*e)/2) (04)

REMPLAZANDO VALORES EN (04):


L = 2.70 m.

LUEGO EN 03:
Espesor e = 0.08 m.

ASUMIENDO PARA EL PROYECTO

Espesor e = 0.15 m.
d = 12.50
SEGÚN EL REGLAMENTO NACIONAL DE CONSTRUCCIONES, PARA LOSAS MACIZAS EN DOS DIRECCIONES 1:1

MA = MB = CW(L^2) (05)

DONDE: C = 0.036
PESO PROPIO = 0,10 x 240 = 360.00 kg/m2
CARGA VIVA = 150.00 kg/m2
PESO TOTAL = Wtotal = 510.00 kg/m2

REEMPLAZANDO EN LA ECUACION 05:


MA = MB = 133.84 kg-m.

CALCULO DEL PERALTE:

d = M ½ (06)
Rb

SIENDO:
M = MA = MB = 133.84 kg-m.
b = 100.00 cm.

R = ½ * fc * j * k (07)

n = 10.17
k = 0.365

j = 1 - k/3 (08)

(1)n = (1)n = Es/Ec = (2.1 x 10^6)/(W^1.5 * Fy * (f'c)^½)

PARA W = 2.40 Tn/m3. Tn/m3.


f'c = 175.00 kg/cm2. kg/cm2.
Fy = 4,200.00 kg/cm2. kg/cm2.

(2)k = 1/(1+fs/(nf'c))

PARA fs = 1,400.00 kg/cm2.


fc = 79.00 kg/cm2.

EN LA ECUACION 08:
j = 0.878
EN LA ECUACION 09:
R = 12.65

REEMPLAZANDO VALORES EN 06:

d = 3.25 cm.

EL ESPESOR TOTAL (e), CONSIDERANDO UN RECUBRIMIENTO DE 2.5 CM.

Recubrimiento ( r ) = 2.50 cm.

e total = d + r e total = 5.75 cm. = 0.06 m.

SIENDO: 0.06 < 0.15 m. CONFORME

PARA EL DISEÑO SE CONSIDERA:


d = 12.50 cm.
CALCULO DEL ESPESOR DE LA LOSA DE FONDO

ASUMIENDO EL ESPESOR DE LA LOSA DE FONDO Y CONOCIDA LA ALTURA

e' = 0.15 m.
h = 1.90 m.

PESO PROPIO DEL AGUA (h x §a) = 1,900.00 kg/m2.


PESO PROPIO DEL CONCRETO (e' x §c) = 360.00 kg/m2.

w = 2,260.00 kg/m2.

DEBIDO A LA ACCION DE LAS CARGAS VERTICALES ACTUANTES PARA UNA LUZ INTERNA, SE PRODUCEN
SE PRODUCEN LOS SIGUIENTES MOMENTOS:

MOMENTO DE EMPOTRAMIENTO EN LOS EXTREMOS:

M = -(W x L^2 /192) (09) M = -73.57 kg-m.

MOMENTO EN EL CENTRO:
M = W x L^2 /384 (10) M = 36.78 kg-m.

CHEQUEO DEL ESPESOR DE LA LOSA:

EL ESPESOR SE CHEQUEA POR MEDIO DEL METODO ELASTICO, CONSIDERANDO EL MAXIMO MOMENTO ABSOLUTO:

e = 6M ½
ft x b (11)

ft = 0.85(F'c)^½ = 11.24 KG/CM2.


F'c = 175.00 KG/CM2.
M = 73.57 KG-M
b = 100.00 CM

REMPLAZANDO EN LA ECUACION 11:


e = 6.27 cm.

6.27 < 15.00 cm. CONFORME

POR LO TANTO CONSIDERANDO EL RECUBRIMIENTO:


Espesort de losa para diseño e = 20.00 cm.
r = 2.50 cm.
PERALTE:
d = 12.50 cm.
B) DISTRIBUCION DE LA ARMADURA DEL RESERVORIO

As = M (12)
fs x j x d

DONDE:
M = MOMENTO MAXIMO ABSOLUTO EN KG-M.
fs = FATIGA DE TRABAJO EN KG/CM2.
j = RELACION ENTRE LA DISTANCIA DE LA RESULTANTE DE LOS ESFUERZOS DE
DE COMPRESION AL CENTRO DE LA GRAVEDAD DE LOS ESFUERZOS DE TENSION.
d = PERALTE EFECTIVO EN CM.

CALCULO DE LA ARMADURA DE LA PARED:

M+ = 589.87 kg-m.
M- = 404.68 kg-m.
fs = 900.00 kg/cm2.
n = 9.00 Valores recomendado en las Normas Sanitarias - ACI-350
e = 20.00 cm.

r = 10.00 cm.
d efectivo = 7.50
j = 0.85
k = 0.441
b = 100.00 cm.

R = ½ * fs * j * k

n = 10.50
k = 0.48

j = 1 - k/3

(1)n = (1)n = Es/Ec = (2.1 x 10^6)/(W^1.5 * Fy * (f'c)^½)

PARA W = 2.40 Tn/m3. Tn/m3.


f'c = 175.00 kg/cm2. kg/cm2.
Fy = 4,200.00 kg/cm2. kg/cm2.

(2)k = 1/(1+fs/(nf'c))

PARA fs = 900.00 kg/cm2.


f'c = 79.00 kg/cm2.

EN LA ECUACION 08:
j = 0.84
EN LA ECUACION 09:
R = 18.13

REEMPLAZANDO VALORES EN 06:

d = 0.57 cm.

RESUMEN DEL CALCULO DEL ACERO


(RESERVORIO DE 12.00 M3.)
PARED LOSA LOSA
DESCRIPCION DE DE
VERTICALHORIZONTAL CUBIERTA FONDO
Momento "M" (kg - m) 589.87 411.54 133.84 -73.57
Espesor Util "d" (cm.) 15.00 15.00 12.50 12.50
fs (kg/cm2.) 900.00 900.00 1,400.00 900.00
n 9.00 9.00 10.00 9.00
f'c (kg/cm2.) 79.00 79.00 79.00 79.00
k = 1/(1+ fs / (n x f'c)) 0.441 0.441 0.361 0.441
j = 1 - (k/3) 0.853 0.853 0.880 0.853
Area de Acero
As = (100 x M)/(fs x j x d) (cm2.) 5.12 3.57 0.87 -0.77
C 0.0015 0.0015 0.0017 0.0017
b (cm.) 100 100 100 100
e (cm.) 20.00 20.00 15.00 20.00
Cuantia Mínima
Asmín = C x b x e (cm2.) 3 3 2.55 3.4
Area Efectiva de As2. (cm2.) 5.12 3.57 2.55 3.4
Area Efectiva de Asmín2. (cm2.) 1.27 0.71 0.71 0.71
Distribución 3/8"(Aacero/Aacero total) 0.25 0.20 0.28 0.21

C) CHEQUEO POR ESFUERZO CORTANTE Y ADHERENCIA

CHEQUEO DE LA PARED

1. - ESFUERZO CORTANTE MAXIMA (V), SERA:

V = (§a x h^2) /2 (13)

REEMPLAZANDO VALORES EN LA ECUACION 13:

V = 1,805.00 kg.
ESFUERZO CORTANTE NOMINAL

v = V/(j x b x d) (14)

DATOS J = 7/8 = 0.88

POR LO TANTO:
v = 1.38 kg/cm2.

EL ESFUERZO PERMISIBLE NOMINAL EN EL CONCRETO PARA MUROS NO EXCEDERA DE:

Vmáx = 0,02 * f'c (15)

Para f'c = ### kg/cm2.

Vmáx = 3.50 kg/cm2.

1.38 < 3.50 CONFORME

2.- CHEQUEO POR ADHERENCIA


18.9645
MEJORAMIENTO Y CONSTRUCCION DE AGUA POTABLE Y LETRINAS-PAUCARBAMBILLA -EL CARMEN
PROYECTO :
MEJORAMIENTO Y CONSTRUCCION DE AGUA POTABLE Y LETRINAS-PAUCARBAMBILLA -EL CARMEN

PROYECTISTA: ING. YANETT MAGALI DELGADILLO GAMBOA


DISTRITO : EL CARMEN
PROVINCIA: CHURCAMPA DEPARTAMENTO: HUANCAVELICA
FECHA: SETIEMBRE 2008

PROYECTO :

Evaluado: Ing° Moises Inga Alarcon

MEMORIA DE CÁLCULO - CAMARA ROMPEPRESIÓN

REBOSE
TUB. PVC 1" TAPA METALICA

VALVULA NIVEL DE
AGUA

ENTRADA SALIDA
TUB. PVC 1" TUB. PVC 1"
SALIDA
TUB. PVC 1"
A A

PLANTA
SECCION A-A
Para determinar la altura de la cámara rompe presion, es necesario conocer la carga requerida ( H ) para que el
gasto de salida pueda fluir. Este valor se determina mediante la ecuacion experimental de Bernoulli.

HT = A + B.L. + H DONDE: A = 10.00 cm.(Mínimo)


BL= Borde libre mínimo 40 cm.
2 H = Carga de agua
1. 56 . V
H= HT = Altura total de la cámara rompe presión.
2g
Q
V =1. 9765 .
D2
Qmd = 0.2500 lt/seg
g = 9.81 m/seg2
D = 0.75 Pulg.
SACAR DE CAL. L.
CONDUCCION
V = 0.87720467 m/seg
H = 0.06118253 m.
Por lo tanto H= 0.30 m.

Asumiendo :
B.L. = 0.40 m.
A= 0.30 m.

Ht = 1.00 m.

POR LA FACILIDAD, EN EL PROCESO CONSTRUCTIVO Y EN LA INSTALACION DE ACCESORIOS,


SE CONSIDERARÁ UNA SECCION INTERNA DE 0.60 m. x 0.60 m.
PROYECTO :
MEJORAMIENTO Y CONSTRUCCION DE AGUA POTABLE Y LETRINAS-PAUCARBAMBILLA -EL CARMEN

PROYECTISTA: ING. AGÜERO PITTMAN

MEMORIA DE CÁLCULO - RED DE DISTRIBUCIÓN


DATOS GENERALES DEL PROYECTO:
Población Futura : 1125 hab.
Cota del Reservorio : 3916.921 m.s.n.m Caudal Máximo horario Qmh: 1.758 l/s

CALCULO DE LOS GASTOS POR TRAMO:


Qmh
Para propositos de diseño se concidera: Consumo Unitario: Qunit .=
Ecuación de Hazen Williams PoblaciónFutura
2. 64
Q=0. 0004264 CD h 0 . 54 Qunit.: 0.001563 l/s/hab.

f
Calculo de los gastos por tramos
Donde: D : Diametro de la tuberia (Pulg) Nº HABITANTES GASTO
Q : Caudal de diseño (l/s) TRAMO
POBLACIÓN FUTURA POR TRAMO
hf : Perdida de carga unitaria (m/Km) POR TRAMO (l/s/hab.)
C : Coefic. de Hanzen -Williams (pie^1/2/seg) A-B 122 0.191
B-C 161 0.252
Coef. de Hanzen-Williams: Tub. de diametros comerciales C-D 160 0.250
MATERIAL C Diametro D(num) C-E 157 0.245
Fierro Fundido 100 0.75 3/4" 0.75 B - CRP 100 0.156
Concreto 110 1 1" 1 CRP- F 103 0.161
Acero 120 1.5 1 1/2" 1.5 F-G 119 0.186
Asbesto cemento 140 2 2" 2 F-H 105 0.164
P.V.C 140 3 3" 2.5 H-I 98 0.153
TRAMO 1125 1.758
Coeficiente de Hanzeb-Williams: 140

RESUMEN DEL CÁLCULO HIDRAÚLICO DE LA RED DE DISTRIBUCIÓN . SISTEMA RAMIFICADO


GASTO LONGITUD DIAM. VELOC. PERDIDA DE CARGA COTA PIEZOMETRICA COTA DEL TERRENO PRESION
TRAMO (l/s) D V (m.s.n.m) (m.s.n.m) (m)
TRAMO DISEÑO L (Pulg.) (m/s) UNIT. TRAMO INICIAL FINAL INICIAL FINAL INICIAL FINAL
O/OO (m)
RES - A 1.758 60.00 2.00 0.868 17.911 1.07 2462.000 2460.925 2462.00 2443.00 0.00 17.93
A-B 0.191 1.758 125.00 2.00 0.868 17.911 2.24 2460.925 2458.686 2443.00 2432.00 17.93 26.69
B-C 0.252 0.747 97.00 1.50 0.655 14.905 1.45 2458.686 2457.241 2432.00 2430.00 26.69 27.24
C-D 0.250 0.250 67.00 0.75 0.877 57.367 3.84 2457.241 2453.397 2430.00 2424.00 27.24 29.40
C-E 0.245 0.245 105.00 0.75 0.861 55.393 5.82 2457.241 2451.424 2430.00 2434.00 27.24 17.42
B - CRP 0.156 0.820 109.00 1.50 0.720 17.729 1.93 2458.686 2456.754 2432.00 2412.00 26.69 44.75
CRP- F 0.161 0.664 98.00 1.50 0.583 11.992 1.18 2412.000 2410.825 2412.00 2392.00 0.00 18.82
F-G 0.186 0.186 86.00 1.50 0.163 1.138 0.10 2410.825 2410.727 2392.00 2369.00 18.82 41.73
F-H 0.164 0.317 100.00 1.00 0.626 21.980 2.20 2410.825 2408.627 2392.00 2385.00 18.82 23.63
H-I 0.153 0.153 120.00 0.75 0.537 23.164 2.78 2408.627 2405.847 2385.00 2372.00 23.63 33.85
1.758