DISEÑO DE RESERVORIO DE 10,00 M3.

DATOS :
0.01
VOLUMEN (V) = 10.00 m3.
ANCHO DE LA PARED (b) = 3.30 m.
ALTURA DEL AGUA (h) = 1.40 m.
BORDE LIBRE (B.L.) = 0.30 m.
ALTURA TOTAL (H) = 1.70 m.
PESO ESPECIFICO DEL AGUA (§a) = 1,000.00 Kg/m3.
PESO ESPECIFICO DEL TERRENO (§t) = 1,800.00 Kg/m3.
CAPACIDAD DE CARGA DEL TERRENO (öt) = 0.85 Kg/cm2.
PESO ESPECIFICO DEL CONCRETO (§c) = 2,400.00 Kg/m3.

A) CALCULO DE MOMENTOS Y ESPESORES

Los límites de relación de b/h son de 0.5 a 3.0 b/h = 2.36


COEFICIENTES
y=0 y = b/4 y = b/2
b/h x/h
Mx My Mx My Mx My
0 0.000 0.023 0.000 0.005 0.000 -0.042
¼ 0.011 0.021 0.004 0.006 -0.008 -0.046
1.80 ½ 0.017 0.016 0.010 0.008 -0.008 -0.043
¾ -0.001 0.008 -0.001 0.005 -0.005 -0.027
1 -0.064 -0.013 -0.042 -0.008 0.000 0.000

MOMENTOS

y=0 y = b/4 y = b/2


b/h x/h
Mx My Mx My Mx My
0 0.000 63.519 0.000 14.940 0.000 -114.333
¼ 30.395 57.743 11.433 17.562 -22.867 -125.759
2.36 ½ 46.831 43.904 27.440 22.226 -22.226 -118.496
¾ -1.372 22.867 -1.372 14.635 -13.720 -74.088
1 -174.723 -36.318 -116.271 -22.867 0.000 0.000

M = k x §a x h3 (01)

DEL CUADRO: M = 174.723 Kg-m.

CALCULO DEL ESPESOR DE LA PARED:

½
e= 6M (02)
ft x b

DONDE :
ft = 0.85(F'c)^½ = 11.24 Kg/cm2.
F'c = 175.00 Kg/cm2.
Mx = 174.72 Kg-m.
My = 125.76 Kg-m.
b = 100.00 cm.
REMPLAZANDO VALORES EN (02) TENEMOS:

e = 9.66 cm.

PARA EL DISEÑO SE ASUME, QUE:


e = 20.00 cm.
CALCULO DEL ESPESOR DE LA LOSA DE CUBIERTA

SE CALCULA COMO LOSA ARMADA EN DOS DIRECCIONES

Espesor e = L/36 (03)

L = b + ((2*e)/2) (04)

REMPLAZANDO VALORES EN (04):


L = 3.50 m.

LUEGO EN 03:
Espesor e = 0.10 m.

ASUMIENDO PARA EL PROYECTO

Espesor e = 0.15 m.

SEGÚN EL REGLAMENTO NACIONAL DE CONSTRUCCIONES, PARA LOSAS MACIZAS EN DOS DIRECCIONES 1:1

MA = MB = CW(L^2) (05)

DONDE: C = 0.036
PESO PROPIO = 0,10 x 2400 = 360.00 kg/m2
CARGA VIVA = 150.00 kg/m2
PESO TOTAL = Wtotal = 510.00 kg/m2

REEMPLAZANDO EN LA ECUACION 05:

MA = MB = 224.91 kg-m.

CALCULO DEL PERALTE:

d = M ½ (06)
Rb

SIENDO:
M = MA = MB = 224.91 kg-m.
b = 100.00 cm.

R = ½ * fc * j * k (07)

n = 9.28
k = 0.344

j = 1 - k/3 (08)

(1)n = (1)n = Es/Ec = (2.1 x 10^6)/(W^1.5 * Fy * (f'c)^½)

PARA W = 2.40 Tn/m3. Tn/m3.


f'c = 210.00 kg/cm2. kg/cm2.
Fy = 4,200.00 kg/cm2. kg/cm2.

(2)k = 1/(1+fs/(nf'c))

PARA fs = 1,400.00 kg/cm2.


fc = 79.00 kg/cm2.

EN LA ECUACION 08:
j = 0.885
EN LA ECUACION 09:
R = 12.02

REEMPLAZANDO VALORES EN 06:

d = 4.33 cm.

EL ESPESOR TOTAL (e), CONSIDERANDO UN RECUBRIMIENTO DE 2.5 CM.

Recubrimiento ( r ) = 2.50 cm.

e total = d + r e total = 6.83 cm. = 0.07 m.

SIENDO: 0.07 < 0.15 m. CONFORME OK


PARA EL DISEÑO SE CONSIDERA:

d = 12.50 cm.
A USAR = 15.00 cm. OK

CALCULO DEL ESPESOR DE LA LOSA DE FONDO

ASUMIENDO EL ESPESOR DE LA LOSA DE FONDO Y CONOCIDA LA ALTURA

e' = 0.15 m.
h = 1.40 m.

PESO PROPIO DEL AGUA (h x §a) = 1,400.00 kg/m2.


PESO PROPIO DEL CONCRETO (e' x §c) = 360.00 kg/m2.

w = 1,760.00 kg/m2.

DEBIDO A LA ACCION DE LAS CARGAS VERTICALES ACTUANTES PARA UNA LUZ INTERNA, SE PRODUCEN
SE PRODUCEN LOS SIGUIENTES MOMENTOS:

MOMENTO DE EMPOTRAMIENTO EN LOS EXTREMOS:

M = -(W x L^2 /192) (09) M = -99.83 kg-m.

MOMENTO EN EL CENTRO:
M = W x L^2 /384 (10) M = 49.91 kg-m.

CHEQUEO DEL ESPESOR DE LA LOSA:

EL ESPESOR SE CHEQUEA POR MEDIO DEL METODO ELASTICO, CONSIDERANDO EL MAXIMO MOMENTO ABSOLUTO:

e = 6M ½
ft x b (11)

ft = 0.85(F'c)^½ = 12.32 KG/CM2.


F'c = 210.00 KG/CM2.
M = 99.83 KG-M
b = 100.00 CM

REMPLAZANDO EN LA ECUACION 11:


e = 6.97 cm.

6.97 < 15.00 cm. CONFORME

POR LO TANTO CONSIDERANDO EL RECUBRIMIENTO:

r = 4.00 cm.
PERALTE:
d = 11.00 cm.
A USAR = 20.00 cm. OK

B) DISTRIBUCION DE LA ARMADURA DEL RESERVORIO

As = M (12)
fs x j x d

DONDE:
M = MOMENTO MAXIMO ABSOLUTO EN KG-M.
fs = FATIGA DE TRABAJO EN KG/CM2.
j = RELACION ENTRE LA DISTANCIA DE LA RESULTANTE DE LOS ESFUERZOS DE
DE COMPRESION AL CENTRO DE LA GRAVEDAD DE LOS ESFUERZOS DE TENSION.
d = PERALTE EFECTIVO EN CM.

CALCULO DE LA ARMADURA DE LA PARED:

M+ = 174.72 kg-m.
M- = 125.76 kg-m.
fs = 900.00 kg/cm2.
n = 9.00 Valores recomendado en las Normas Sanitarias - ACI-350
e = 20.00 cm.
r = 5.00 cm.
d efectivo = 15.00
j = 0.85
k = 0.441
b = 100.00 cm.
R = ½ * fs * j * k

n = 9.58
k = 0.46

j = 1 - k/3

(1)n = (1)n = Es/Ec = (2.1 x 10^6)/(W^1.5 * Fy * (f'c)^½)

PARA W = 2.40 Tn/m3. Tn/m3.


f'c = 210.00 kg/cm2. kg/cm2.
Fy = 4,200.00 kg/cm2. kg/cm2.

(2)k = 1/(1+fs/(nf'c))

PARA fs = 900.00 kg/cm2.


f'c = 79.00 kg/cm2.

EN LA ECUACION 08:
j = 0.85
EN LA ECUACION 09:
R = 17.43

REEMPLAZANDO VALORES EN 06:

d = 0.32 cm.

RESUMEN DEL CALCULO DEL ACERO


METODO ELASTICO
PARED LOSA LOSA
DESCRIPCION DE DE
VERTICAL HORIZONTAL CUBIERTA FONDO
Momento "M" (kg - m) 174.72 125.76 224.91 99.83
Recubrimiento (cm) 7.00 7.00 7.00 7.00
Espesor Util "d" (cm.) 13.00 13.00 8.00 8.00
fs (kg/cm2.) 900.00 900.00 1,400.00 900.00
n 9.00 9.00 10.00 9.00
f'c (kg/cm2.) 79.00 79.00 79.00 79.00
k = 1/(1+ fs / (n x f'c)) 0.441 0.441 0.361 0.441
j = 1 - (k/3) 0.853 0.853 0.880 0.853
Area de Acero
As = (100 x M)/(fs x j x d) (cm2.) 1.75 1.26 2.28 1.63
C 0.0018 0.0018 0.0018 0.0018
b (cm.) 100 100 100 100
e (cm.) 15 15 15 20
Cuantia Mínima
Asmín = C x b x e (cm2.) 2.7 2.7 2.7 3.6
Area Efectiva de As2. (cm2.) 2.70 2.70 2.70 3.60
Area Efectiva de Asmín2. (cm2.) 2.70 2.70 2.70 3.60
Ø de Acero 3/8" 3/8" 3/8" 3/8"
Numero de varrillas 3.80 3.80 3.80 5.07
Distribución 3/8"(Aacero/Aacero total) (m.) 26.30 26.30 26.30 19.72
A USAR 25.00 25.00 25.00 20.00