Tabla 1. Demanda del alimentador para el día 24 de julio del 2019 a las 15h30.
MATRIZ DE ESTADO
T01 T02 T03 T04 T05 T06 T07 T08 T09 T10 L01 L02 L03 L04 L05 L06 L07 L08 L09 L10
T01 I I I I I I I I I I I I I I I I I I I I
T02 N I I I I I I I I I N I I I I I I I I I
T03 N R I I I I I I I I N R I I I I I I I I
T04 N R R I I I I I I I N R R I I I I I I I
T05 N R R R I I I I I I N R R R I I I I I I
T06 N R R R R I I I I I N R R R R I I I I I
T07 N R R R R R I I I I N R R R R R I I I I
T08 N R R R R R R I I I N R R R R R R I I I
T09 N R R R R R R R I I N R R R R R R R I I
T10 N R R R R R R R R I N R R R R R R R R I
L01 N N N N N N N N N N I N N N N N N N N N
L02 N N N N N N N N N N N I N N N N N N N N
L03 N N N N N N N N N N N N I N N N N N N N
L04 N N N N N N N N N N N N N I N N N N N N
L05 N N N N N N N N N N N N N N I N N N N N
L06 N N N N N N N N N N N N N N N I N N N N
L07 N N N N N N N N N N N N N N N N I N N N
L08 N N N N N N N N N N N N N N N N N I N N
L09 N N N N N N N N N N N N N N N N N N I N
L10 N N N N N N N N N N N N N N N N N N N I
PARAMETROS CONFIABILIDAD
TRAMOS λEi rT (horas) UiTOTAL Tabla 9. Indices de confiabilidad del alimentador con un
reconectador en tramo 2.
(fallas/año) (horas/año)
T01 0,17 3,00 0,508 INDICES DE CONFIABILIDAD
T02 1,69 1,00 1,692 Denominación Unidades Valor
T03 1,69 1,25 2,115 FMIK Fallas/KVA/año 3,359
T04 1,69 1,50 2,538 TTIK Horas/KVA/año 4,420
T05 1,69 1,75 2,961 ENS KWH/año 14.021
T06 1,69 2,00 3,384
T07 1,69 2,25 3,807
T08 1,69 2,50 4,230 Se muestra en la Tabla 8 y Tabla 9 los parámetros
T09 1,69 2,75 4,653 de confiabilidad del alimentador y los índices de
T10 1,69 3,000 5,076 confiabilidad respectivamente del segundo tramo,
L01 2,11 1,161 2,444 obteniendo un índice de pérdida de energía no
L02 3,63 1,000 3,629
suministrada ENS= 14.021 kWh/año, siendo este
L03 3,63 1,117 4,052
L04 3,63 1,233 4,475
el parámetro a considerar para la comparación con
L05 3,63 1,350 4,898 los demás tramos.
L06 3,63 1,466 5,321
L07 3,63 1,583 5,744
L08 3,63 1,699 6,167
L09 3,63 1,816 6,590
L10 3,63 1,933 7,013
Análisis para un reconectador en la posición 3
MATRIZ DE ESTADO
T01 T02 T03 T04 T05 T06 T07 T08 T09 T10 L01 L02 L03 L04 L05 L06 L07 L08 L09 L10
I I I I I I I I I I I I I I I I I I I I
R I I I I I I I I I R I I I I I I I I I
N N I I I I I I I I N N I I I I I I I I
N N R I I I I I I I N N R I I I I I I I
N N R R I I I I I I N N R R I I I I I I
N N R R R I I I I I N N R R R I I I I I
N N R R R R I I I I N N R R R R I I I I
N N R R R R R I I I N N R R R R R I I I
N N R R R R R R I I N N R R R R R R I I
N N R R R R R R R I N N R R R R R R R I
N N N N N N N N N N I N N N N N N N N N
N N N N N N N N N N N I N N N N N N N N
N N N N N N N N N N N N I N N N N N N N
N N N N N N N N N N N N N I N N N N N N
N N N N N N N N N N N N N N I N N N N N
N N N N N N N N N N N N N N N I N N N N
N N N N N N N N N N N N N N N N I N N N
N N N N N N N N N N N N N N N N N I N N
N N N N N N N N N N N N N N N N N N I N
N N N N N N N N N N N N N N N N N N N I
PARAMETROS CONFIABILIDAD
TRAMOS
λEi (fallas/año) rT (horas) UiTOTAL (horas/año) Tabla 12. Indices de confiabilidad del alimentador con un
T01 0,34 1,75 0,592 reconectador en tramo 3.
T02 0,34 3,00 1,015
T03 1,69 1,25 2,115 INDICES DE CONFIABILIDAD
T04 1,69 1,50 2,538 Denominación Unidades Valor
T05 1,69 1,75 2,961 FMIK Fallas/KVA/año 3,161
T06 1,69 2,00 3,384 TTIK Horas/KVA/año 4,321
T07 1,69 2,25 3,807 ENS KWH/año 13.723
T08 1,69 2,50 4,230
T09 1,69 2,75 4,653 Se muestra en la Tabla 11 y Tabla 12 los parámetros
T10 1,69 3,000 5,076
de confiabilidad del alimentador y los índices de
L01 2,27 1,112 2,529
L02 2,27 1,298 2,952
confiabilidad respectivamente del tercer tramo,
L03 3,63 1,117 4,052 obteniendo un índice de pérdida de energía no
L04 3,63 1,233 4,475 suministrada ENS= 13.723 kWh/año, siendo este el
L05 3,63 1,350 4,898 parámetro a considerar para la comparación con los
L06 3,63 1,466 5,321 demás tramos.
L07 3,63 1,583 5,744
L08 3,63 1,699 6,167
L09 3,63 1,816 6,590
L10 3,63 1,933 7,013
Análisis para un reconectador en la posición 4
MATRIZ DE ESTADO
T01 T02 T03 T04 T05 T06 T07 T08 T09 T10 L01 L02 L03 L04 L05 L06 L07 L08 L09 L10
T01 I I I I I I I I I I I I I I I I I I I I
T02 R I I I I I I I I I R I I I I I I I I I
T03 R R I I I I I I I I R R I I I I I I I I
T04 N N N I I I I I I I N N N I I I I I I I
T05 N N N R I I I I I I N N N R I I I I I I
T06 N N N R R I I I I I N N N R R I I I I I
T07 N N N R R R I I I I N N N R R R I I I I
T08 N N N R R R R I I I N N N R R R R I I I
T09 N N N R R R R R I I N N N R R R R R I I
T10 N N N R R R R R R I N N N R R R R R R I
L01 N N N N N N N N N N I N N N N N N N N N
L02 N N N N N N N N N N N I N N N N N N N N
L03 N N N N N N N N N N N N I N N N N N N N
L04 N N N N N N N N N N N N N I N N N N N N
L05 N N N N N N N N N N N N N N I N N N N N
L06 N N N N N N N N N N N N N N N I N N N N
L07 N N N N N N N N N N N N N N N N I N N N
L08 N N N N N N N N N N N N N N N N N I N N
L09 N N N N N N N N N N N N N N N N N N I N
L10 N N N N N N N N N N N N N N N N N N N I
PARAMETROS CONFIABILIDAD
TRAMOS
λEi (fallas/año) rT (horas) UiTOTAL (horas/año)
T01 0,51 1,33 0,677 Tabla 15. Indices de confiabilidad del alimentador con un
T02 0,51 2,17 1,100 reconectador en tramo 4.
T03 0,51 3,00 1,523
INDICES DE CONFIABILIDAD
T04 1,69 1,50 2,538
Denominación Unidades Valor
T05 1,69 1,75 2,961
FMIK Fallas/KVA/año 3,079
T06 1,69 2,00 3,384
TTIK Horas/KVA/año 4,280
T07 1,69 2,25 3,807
ENS KWH/año 13.605
T08 1,69 2,50 4,230
T09 1,69 2,75 4,653
T10 1,69 3,000 5,076
L01 2,44 1,069 2,613
Se muestra en la Tabla 14 y Tabla 15 los parámetros
L02 2,44 1,242 3,036 de confiabilidad del alimentador y los índices de
L03 2,44 1,415 3,459 confiabilidad respectivamente del cuarto tramo,
L04 3,63 1,233 4,475 obteniendo un índice de pérdida de energía no
L05 3,63 1,350 4,898 suministrada ENS= 13.605 kWh/año, siendo este el
L06 3,63 1,466 5,321
parámetro a considerar para la comparación con los
L07 3,63 1,583 5,744
L08 3,63 1,699 6,167
demás tramos.
L09 3,63 1,816 6,590
L10 3,63 1,933 7,013
Análisis para un reconectador en la posición 5
MATRIZ DE ESTADO
T01 T02 T03 T04 T05 T06 T07 T08 T09 T10 L01 L02 L03 L04 L05 L06 L07 L08 L09 L10
T01 I I I I I I I I I I I I I I I I I I I I
T02 R I I I I I I I I I R I I I I I I I I I
T03 R R I I I I I I I I R R I I I I I I I I
T04 R R R I I I I I I I R R R I I I I I I I
T05 N N N N I I I I I I N N N N I I I I I I
T06 N N N N R I I I I I N N N N R I I I I I
T07 N N N N R R I I I I N N N N R R I I I I
T08 N N N N R R R I I I N N N N R R R I I I
T09 N N N N R R R R I I N N N N R R R R I I
T10 N N N N R R R R R I N N N N R R R R R I
L01 N N N N N N N N N N I N N N N N N N N N
L02 N N N N N N N N N N N I N N N N N N N N
L03 N N N N N N N N N N N N I N N N N N N N
L04 N N N N N N N N N N N N N I N N N N N N
L05 N N N N N N N N N N N N N N I N N N N N
L06 N N N N N N N N N N N N N N N I N N N N
L07 N N N N N N N N N N N N N N N N I N N N
L08 N N N N N N N N N N N N N N N N N I N N
L09 N N N N N N N N N N N N N N N N N N I N
L10 N N N N N N N N N N N N N N N N N N N I
PARAMETROS CONFIABILIDAD
TRAMOS
λEi (fallas/año) rT (horas) UiTOTAL (horas/año)
T01 0,68 1,13 0,761 Tabla 18. Indices de confiabilidad del alimentador con un
T02 0,68 1,75 1,184 reconectador en tramo 5.
T03 0,68 2,38 1,607
INDICES DE CONFIABILIDAD
T04 0,68 3,00 2,030
Denominación Unidades Valor
T05 1,69 1,75 2,961
FMIK Fallas/KVA/año 3,043
T06 1,69 2,00 3,384
TTIK Horas/KVA/año 4,262
T07 1,69 2,25 3,807
ENS KWH/año 13.542
T08 1,69 2,50 4,230
T09 1,69 2,75 4,653
T10 1,69 3,000 5,076 Se muestra en la Tabla 17 y Tabla 18 los parámetros
L01 2,61 1,032 2,698 de confiabilidad del alimentador y los índices de
L02 2,61 1,194 3,121 confiabilidad respectivamente del quinto tramo,
L03 2,61 1,356 3,544 obteniendo un índice de pérdida de energía no
L04 2,61 1,518 3,967
suministrada ENS= 13.542 kWh/año, siendo este el
L05 3,63 1,350 4,898
L06 3,63 1,466 5,321
parámetro a considerar para la comparación con los
L07 3,63 1,583 5,744 demás tramos.
L08 3,63 1,699 6,167
L09 3,63 1,816 6,590
L10 3,63 1,933 7,013
Análisis para un reconectador en la posición 6
MATRIZ DE ESTADO
T01 T02 T03 T04 T05 T06 T07 T08 T09 T10 L01 L02 L03 L04 L05 L06 L07 L08 L09 L10
T01 I I I I I I I I I I I I I I I I I I I I
T02 R I I I I I I I I I R I I I I I I I I I
T03 R R I I I I I I I I R R I I I I I I I I
T04 R R R I I I I I I I R R R I I I I I I I
T05 R R R R I I I I I I R R R R I I I I I I
T06 N N N N N I I I I I N N N N N I I I I I
T07 N N N N N R I I I I N N N N N R I I I I
T08 N N N N N R R I I I N N N N N R R I I I
T09 N N N N N R R R I I N N N N N R R R I I
T10 N N N N N R R R R I N N N N N R R R R I
L01 N N N N N N N N N N I N N N N N N N N N
L02 N N N N N N N N N N N I N N N N N N N N
L03 N N N N N N N N N N N N I N N N N N N N
L04 N N N N N N N N N N N N N I N N N N N N
L05 N N N N N N N N N N N N N N I N N N N N
L06 N N N N N N N N N N N N N N N I N N N N
L07 N N N N N N N N N N N N N N N N I N N N
L08 N N N N N N N N N N N N N N N N N I N N
L09 N N N N N N N N N N N N N N N N N N I N
L10 N N N N N N N N N N N N N N N N N N N I
MATRIZ DE ESTADO
T01 T02 T03 T04 T05 T06 T07 T08 T09 T10 L01 L02 L03 L04 L05 L06 L07 L08 L09 L10
T01 I I I I I I I I I I I I I I I I I I I I
T02 R I I I I I I I I I R I I I I I I I I I
T03 R R I I I I I I I I R R I I I I I I I I
T04 R R R I I I I I I I R R R I I I I I I I
T05 R R R R I I I I I I R R R R I I I I I I
T06 R R R R R I I I I I R R R R R I I I I I
T07 N N N N N N I I I I N N N N N N I I I I
T08 N N N N N N R I I I N N N N N N R I I I
T09 N N N N N N R R I I N N N N N N R R I I
T10 N N N N N N R R R I N N N N N N R R R I
L01 N N N N N N N N N N I N N N N N N N N N
L02 N N N N N N N N N N N I N N N N N N N N
L03 N N N N N N N N N N N N I N N N N N N N
L04 N N N N N N N N N N N N N I N N N N N N
L05 N N N N N N N N N N N N N N I N N N N N
L06 N N N N N N N N N N N N N N N I N N N N
L07 N N N N N N N N N N N N N N N N I N N N
L08 N N N N N N N N N N N N N N N N N I N N
L09 N N N N N N N N N N N N N N N N N N I N
L10 N N N N N N N N N N N N N N N N N N N I
PARAMETROS CONFIABILIDAD
TRAMOS
λEi (fallas/año) rT (horas) UiTOTAL (horas/año)
T01 1,02 0,92 0,931 Tabla 24.Indices de confiabilidad del alimentador con un
T02 1,02 1,33 1,354 reconectador en tramo 7.
T03 1,02 1,75 1,777
INDICES DE CONFIABILIDAD
T04 1,02 2,17 2,200
T05 1,02 2,58 2,623 Denominación Unidades Valor
T06 1,02 3,00 3,046 FMIK Fallas/KVA/año 3,101
T07 1,69 2,25 3,807 TTIK Horas/KVA/año 4,291
T08 1,69 2,50 4,230 ENS KWH/año 13.653
T09 1,69 2,75 4,653
T10 1,69 3,000 5,076
L01 2,95 0,971 2,867 Se muestra en la Tabla 23 y Tabla 24 los
L02 2,95 1,115 3,290 parámetros de confiabilidad del alimentador y los
L03 2,95 1,258 3,713 índices de confiabilidad respectivamente del
L04 2,95 1,401 4,136 séptimo tramo, obteniendo un índice de pérdida de
L05 2,95 1,545 4,559
energía no suministrada ENS= 13.653 kWh/año,
L06 2,95 1,688 4,982
L07 3,63 1,583 5,744
siendo este el parámetro a considerar para la
L08 3,63 1,699 6,167 comparación con los demás tramos.
L09 3,63 1,816 6,590
L10 3,63 1,933 7,013
Análisis para un reconectador en la posición 8
MATRIZ DE ESTADO
T01 T02 T03 T04 T05 T06 T07 T08 T09 T10 L01 L02 L03 L04 L05 L06 L07 L08 L09 L10
T01 I I I I I I I I I I I I I I I I I I I I
T02 R I I I I I I I I I R I I I I I I I I I
T03 R R I I I I I I I I R R I I I I I I I I
T04 R R R I I I I I I I R R R I I I I I I I
T05 R R R R I I I I I I R R R R I I I I I I
T06 R R R R R I I I I I R R R R R I I I I I
T07 R R R R R R I I I I R R R R R R I I I I
T08 N N N N N N N I I I N N N N N N N I I I
T09 N N N N N N N R I I N N N N N N N R I I
T10 N N N N N N N R R I N N N N N N N R R I
L01 N N N N N N N N N N I N N N N N N N N N
L02 N N N N N N N N N N N I N N N N N N N N
L03 N N N N N N N N N N N N I N N N N N N N
L04 N N N N N N N N N N N N N I N N N N N N
L05 N N N N N N N N N N N N N N I N N N N N
L06 N N N N N N N N N N N N N N N I N N N N
L07 N N N N N N N N N N N N N N N N I N N N
L08 N N N N N N N N N N N N N N N N N I N N
L09 N N N N N N N N N N N N N N N N N N I N
L10 N N N N N N N N N N N N N N N N N N N I
Tabla 26. Parámetros de confiabilidad con un reconectador en tramo 8.
PARAMETROS CONFIABILIDAD
TRAMOS
λEi (fallas/año) rT (horas) UiTOTAL (horas/año) Tabla 27. Indices de confiabilidad del alimentador con un
T01 1,18 0,86 1,015 reconectador en tramo 8.
T02 1,18 1,21 1,438
INDICES DE CONFIABILIDAD
T03 1,18 1,57 1,861
Denominación Unidades Valor
T04 1,18 1,93 2,284
FMIK Fallas/KVA/año 3,182
T05 1,18 2,29 2,707
TTIK Horas/KVA/año 4,332
T06 1,18 2,64 3,130 ENS KWH/año 13.788
T07 1,18 3,00 3,553
T08 1,69 2,50 4,230
T09 1,69 2,75 4,653 Se muestra en la Tabla 26 y Tabla 27 los
T10 1,69 3,000 5,076 parámetros de confiabilidad del alimentador y los
L01 3,12 0,946 2,952 índices de confiabilidad respectivamente del
L02 3,12 1,081 3,375 octavo tramo, obteniendo un índice de pérdida de
L03 3,12 1,217 3,798
energía no suministrada ENS= 13.788 kWh/año,
L04 3,12 1,352 4,221
L05 3,12 1,488 4,644
siendo este el parámetro a considerar para la
L06 3,12 1,623 5,067 comparación con los demás tramos.
L07 3,12 1,759 5,490
L08 3,63 1,699 6,167
L09 3,63 1,816 6,590
L10 3,63 1,933 7,013
Análisis para un reconectador en la posición 9
MATRIZ DE ESTADO
T01 T02 T03 T04 T05 T06 T07 T08 T09 T10 L01 L02 L03 L04 L05 L06 L07 L08 L09 L10
T01 I I I I I I I I I I I I I I I I I I I I
T02 R I I I I I I I I I R I I I I I I I I I
T03 R R I I I I I I I I R R I I I I I I I I
T04 R R R I I I I I I I R R R I I I I I I I
T05 R R R R I I I I I I R R R R I I I I I I
T06 R R R R R I I I I I R R R R R I I I I I
T07 R R R R R R I I I I R R R R R R I I I I
T08 R R R R R R R I I I R R R R R R R I I I
T09 N N N N N N N N I I N N N N N N N N I I
T10 N N N N N N N N R I N N N N N N N N R I
L01 N N N N N N N N N N I N N N N N N N N N
L02 N N N N N N N N N N N I N N N N N N N N
L03 N N N N N N N N N N N N I N N N N N N N
L04 N N N N N N N N N N N N N I N N N N N N
L05 N N N N N N N N N N N N N N I N N N N N
L06 N N N N N N N N N N N N N N N I N N N N
L07 N N N N N N N N N N N N N N N N I N N N
L08 N N N N N N N N N N N N N N N N N I N N
L09 N N N N N N N N N N N N N N N N N N I N
L10 N N N N N N N N N N N N N N N N N N N I
PARAMETROS CONFIABILIDAD
TRAMOS
λEi (fallas/año) rT (horas) UiTOTAL (horas/año)
T01 1,52 0,78 1,184
T02 1,52 1,06 1,607 Tabla 33. Indices de confiabilidad del alimentador con un
T03 1,52 1,33 2,030 reconectador en tramo 10.
T04 1,52 1,61 2,453
INDICES DE CONFIABILIDAD
T05 1,52 1,89 2,876
T06 1,52 2,17 3,299 Denominación Unidades Valor
T07 1,52 2,44 3,722 FMIK Fallas/KVA/año 3,461
T08 1,52 2,72 4,145 TTIK Horas/KVA/año 4,473
T09 1,52 3,00 4,568 ENS KWH/año 14.241
T10 1,69 3,000 5,076
L01 3,46 0,902 3,121 Se muestra en la Tabla 32 y Tabla 33 los parámetros
L02 3,46 1,024 3,544 de confiabilidad del alimentador y los índices de
L03 3,46 1,147 3,967
confiabilidad respectivamente del décimo tramo,
L04 3,46 1,269 4,390
L05 3,46 1,391 4,813
obteniendo un índice de pérdida de energía no
L06 3,46 1,514 5,236 suministrada ENS= 14.241 kWh/año, siendo este el
L07 3,46 1,636 5,659 parámetro a considerar para la comparación con los
L08 3,46 1,758 6,082 demás tramos.
L09 3,46 1,880 6,505
L10 3,63 1,933 7,013
Análisis de resultados
Tabla 34. Resultados de Índices para cada uno de los tramos.
INDICES DE CONFIABILIDAD
Conectador Conectador Conectador Conectador Conectador Conectador Conectador Conectador Conectador Conectador
Denominación Unidades
tramos 1 tramos 2 tramos 3 tramos 4 tramos 5 tramos 6 tramos 7 tramos8 tramo 9 tramo 10
FMIK Fallas/KVA/año 3,6285 3,3591229 3,16091645 3,0787359 3,0432594 3,0533994 3,100783 3,1819849 3,3108694 3,4605101
TTIK Horas/KVA/año 4,5548319 4,4201434 4,32104017 4,2799499 4,2622116 4,2672817 4,2909735 4,3315744 4,3960166 4,4728281
ENS KWH/año 14.504 14.021 13.723 13.605 13.542 13.564 13.653 13.788 13.994 14.241
Se tiene la Tabla 4 donde se muestran los índices de confiabilidad para las diez particiones o tramos, es decir las
diez diferentes posiciones del reconectador. Se observa que el mayor índice es en el Tramo 1 con un ENS de
14.504 Kwh/año lo que implica que no es favorable colocar el reconectador en la posición 1 ya que existieran
mayores pérdidas que en otros tramos. El índice más pequeño de ENS es de 13.542 kw/año se da en el tramo 5,
lo que implica que colocar el reconectador en la posición 5 es la solución más óptima.
Tabla 35. Capacidad de los alimentadores próximos al alimentador VIA A BUENA FE.
09DN25 S/E DAULE NORTE (CNEL-Guayas Los Ríos / Daule Norte) 09DN250T11 (Banife) R (Rural) 8480,0 0,00 0,5 0,1 1,00 0,17
09DN25 S/E DAULE NORTE (CNEL-Guayas Los Ríos / Daule Norte) 09DN250T12 (Limonal) R (Rural) 6530,0 0,00 0,8 0,1 1,00 0,17
Para este caso se tiene que realizar la interconexión con el alimentador BANIFE ya que posee mayor cantidad de
potencia instalada. La interconexión con otro alimentador tiene un costo de $30.000.
CONCLUSIONES:
• Para el análisis de la confiabilidad del alimentador EL LIMONAL nos apoyamos de la herramienta CYME
para obtener la curva del perfil de carga en kvar para cada fase. También con la hoja de cálculo dada por
CNEL obtuvimos los parámetros como ENS mediante el método de matrices de estado para diez
particiones, es decir para diez diferentes posiciones del reconectador.
• Se observa que el mayor índice es en el Tramo 1 con un ENS de 14.504 Kwh/año lo que implica que no es
favorable colocar el reconectador en la posición 1 ya que existieran mayores pérdidas que en otros
tramos.
• El índice más pequeño de ENS es de 13.542 kw/año se da en el tramo 5, lo que implica que colocar el
reconectador en la posición 5 es la solución más óptima.
• Para este caso conviene realizar la interconexión con el alimentador BANIFE ya que posee mayor
cantidad de potencia instalada y esto equivale a un gasto de $30000.