TRAMO long. Eq. caudal m3/h Diam. Tub p1 (man) bar p1(abs) bar p1^2-p2^2 p2 abs bar p2 (man) bar P.prom bar Velosidda caida de P relación Q/D
(mm) bar^2 m/seg (mbar)
1 , 2 12 38.1 32 0.300 1.31300 0.015159 1.307214607 0.294 1.310 10.05359563 5.78539 1.190625
2 , 6 4.8 5.1 15 0.294 1.30721 0.006016 1.304911612 0.292 1.306 6.143654118 2.30299 0.34
2 , 3 18 33 25 0.294 1.30721 0.057534 1.285019833 0.272 1.296 14.42091789 22.19477 1.32
3 , 4 7.2 31 25 0.272 1.28502 0.020538 1.277003332 0.264 1.281 13.70666764 8.01650 1.24
3 , 5 6 2 15 0.272 1.28502 0.001369 1.28448718 0.271 1.285 2.449237655 0.53265 0.13
0.100616
DETERMINACIÓN DEL DIÁMETRO DE TUBERIAS EN INSTALACIÓN INTERNA MULTIFAMILIAR
METODO DEL TANTEO
PRACTICA Nº 1
TRAMO long. Eq. caudal m3/h Diam. Tub p1 (man) bar p1(abs) p1^2-p2^2 p2 abs bar p2 (man) bar P.prom bar Velosidda caida de P relación Q/D
(mm) bar bar^2 m/seg (mbar)
1 , 2 6 133.32 80 0.300 1.31300 0.000895 1.31265931 0.29966 1.3128 5.61707 0.34069 1.667
2 , 6 60 4.9 15 0.300 1.31266 0.069916 1.28575213 0.273 1.299 5.93388193 26.90719 0.327
2 , 3 24 128.43 80 0.300 1.31266 0.003343 1.31138538 0.298 1.312 5.41437759 1.27393 1.605
3 , 4 12 25.54 20 0.298 1.31139 0.070532 1.28421164 0.271 1.298 17.4163399 27.17374 1.277
3 , 5 60 102.88 80 0.298 1.31139 0.005581 1.30925567 0.296 1.310 4.34286871 2.12971 1.286
0.150267
DETERMINACIÓN DEL DIÁMETRO DE TUBERIAS A UNA PRESIÓN DE 140 MBAR
TRAMO long. Eq. caudal m3/h Diam. Tub p1 (man) bar p1(abs) p1^2-p2^2 p2 abs bar p2 (man) bar P.prom bar Velosidda caida de P relación Q/D
(mm) bar bar^2 m/seg (mbar)
1 , 2 0.96 4.48 20 0.140 1.153 0.00024 1.15290 0.13990 1.153 3.43884 0.10300 0.224
2 , 3 8.00 3.89 20 0.140 1.153 0.00153 1.15223 0.13923 1.153 2.98695 0.66433 0.195
3 , 4 3.90 2.76 20 0.140 1.153 0.00040 1.15272 0.13972 1.153 2.11882 0.17330 0.138
4 , 5 8.82 0.60 20 0.140 1.152 0.00006 1.15221 0.13970 1.152 0.46085 0.02439 0.030
1 , 6 15.20 2.16 15 0.140 1.153 0.00399 1.15099 0.13799 1.152 2.95036 1.73182 0.144
1 , 7 13.88 1.13 15 0.140 1.152 0.00112 1.15172 0.13951 1.152 1.54333 0.48631 0.075
1 , 8 2.04 0.60 15 0.140 1.151 0.00005 1.15097 0.13998 1.151 0.82017 0.02260 0.040
0.007387
MEMORIA DE CALCULO
CÁLCULO DE INSTALACIÓN INTERIOR CON CONDUCTOS EN CRUJIA
Tramo Long n. med. Q prom. L. Equiv. D diam Long-real p1-p2 Tramo p1-p2
tramo (m3/h) (m) (mm) (m) (mbar) (mbar)
O-A 19.10 1 1.94 22.92 20.00 17.20 0.531 O-A 0.53
i - i1 52.75 4 8.63 63.3 29.48 5.00 0.360 i - i1 0.89
i1 - i2 52.75 3 6.91 63.3 27.10 5.00 0.360 i1 - i2 1.25
i2 - i3 52.75 2 5.13 63.3 24.22 5.00 0.360 i2 - i3 1.61
i3 - i4 52.75 1 3.25 63.3 20.38 5.00 0.360 i3 - i4 1.97
Tramo Long n. med. Q prom. L. Equiv. D diam Long-real p1-p2 Tramo p1-p2
tramo (m3/h) (m) (mm) (m) (mbar) (mbar)
a-i 1.27 2 3.51 1.044 26.90 0.87 0.019 a - i 0.02
i - i1 1.27 1 2.44 0.480 26.90 0.40 0.005 a - i1 0.02
local técnico
Tramo Long n. med. Q prom. L. Equiv. D diam Long-real p1-p2 Tramo p1-p2
tramo (m3/h) (m) (mm) (m) (mbar) (mbar)
a-i 1.27 2 3.56 1.524 9.74 0.87 2.603 a - i 2.60
i - i1 1.27 1 2.44 1.524 8.45 0.40 1.197 i - i1 3.80
FIRMA PROYECTISTA