Está en la página 1de 286

ESTUDIO COORDINACIÓN Y AJUSTE DE PROTECCIONES

INFORME EAP Nº 98/2016


Gerencia Transelec Zona Sur

S/E CIRUELOS
AMPLIACIÓN SUBESTACIÓN CIRUELOS 220KV
SECCIONAMIENTO LÍNEA 220KV CAUTÍN – VALDIVIA C2

Enero 2016

Documento INFORME EAP N° 98/2016

Preparó

Documento: STA3534-C252-01E-IN-C043_REV 0

Max Missene M.
Revisó
Analistas Estudios de Protecciones Eléctricas

Felipe Pacheco V.
Autorizó
Jefe Estudios de Protecciones Eléctricas

Nº DOCUMENTO VERSIÓN
EAP 98/2016 3
SERVICIOS DE INGENIERÍA DE DISEÑO

PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”

INFORME TÉCNICO
ESTUDIO COORDINACIÓN Y AJUSTE DE PROTECCIONES

DESSAU INGENIERÍA S.p.A.


GERENCIA DE ENERGÍA

0 23/12/16 Para Observaciones y Comentarios FAU CBM DHR


F 13/12/16 Para Observaciones y Comentarios FAU CBM DHR
E 14/11/16 Para Observaciones y Comentarios FAU CBM MSG
D 14/10/16 Para Observaciones y Comentarios FAU CBM MSG
C 07/10/16 Para Observaciones y Comentarios FAU CBM MSG
B 01/08/16 Para Observaciones y Comentarios FAU CBM MSG
A 01/08/16 Para Observaciones y Comentarios FAU CBM MSG
POR REV. APR.
REV FECHA EMITIDO PARA
DESSAU
N° de Documento DESSAU N° de Documento CLIENTE

DT2234-DIE004 STA3534-C252-01E-IN-C-043

DISTRIBUCIÓN
Cant Área Cliente: Mandante:
. 1 ENERGÍA
2-285

TABLA DE CONTENIDOS

1. IDENTIFICACIÓN DEL PROYECTO ............................................................................................ 6


2. OBJETIVO .................................................................................................................................... 6
3. ANTECEDENTES ......................................................................................................................... 6
4. DESCRIPCION DEL SISTEMA ELÉCTRICO ............................................................................... 7
4.1 Estimación de la Demanda .......................................................................................... 9
4.2 Escenarios de Operación ............................................................................................. 9
4.2.1 Hidrología Húmeda ................................................................................................. 9
4.2.2 Hidrología Seca..................................................................................................... 10
4.3 Parámetros Eléctricos de los Elementos del Sistema ................................................ 10
4.4 Análisis del Acoplamiento Mutuo de Secuencia Cero ................................................ 11
5. CRITERIOS Y AJUSTES DE PROTECCIONES ......................................................................... 15
5.1 S/E Ciruelos paño Cautín C2 ..................................................................................... 15
5.1.1 Función de Distancia (21/21N) .............................................................................. 15
5.1.2 Lógica de Teleprotección ...................................................................................... 20
5.1.3 Función direccional de corriente residual (67N) .................................................... 21
5.1.4 Función de Sobrecorriente de Emergencia (51B/51NB) ....................................... 21
5.1.5 Función de Bloqueo por Oscilación de Potencia ................................................... 22
5.1.5.1 Protección 7SA612 ........................................................................................... 22
5.1.5.2 Protección REL670........................................................................................... 23
5.1.6 Función de Cierre contra fallas (50HS) ................................................................. 24
5.1.6.1 Protección 7SA612 ........................................................................................... 24
5.1.6.2 Protección REL670........................................................................................... 25
5.1.7 Reconexión (79) .................................................................................................... 25
5.1.8 Función de Verificación de Sincronismo (25) ........................................................ 26
5.1.9 Función de Falla Fusible ....................................................................................... 26
5.1.9.1 Protección 7SA612 ........................................................................................... 27
5.1.9.2 Protección REL670........................................................................................... 27
5.1.10 Función de Falla de Interruptor (50BF) ................................................................. 29
5.2 S/E Cautín paño Ciruelos C2 ..................................................................................... 30
5.2.1 Función de Distancia (21/21N) .............................................................................. 31
5.2.2 Lógica de Teleprotección ...................................................................................... 35
5.2.3 Función direccional de corriente residual (67N) .................................................... 35
5.2.4 Función de Sobrecorriente de Fases (51/50) protección GE D60 ......................... 36
5.2.5 Función de Bloqueo por Oscilación de Potencia ................................................... 36
5.2.5.1 Protección 7SA612 ........................................................................................... 36
5.2.5.2 Protección GE D60 ........................................................................................... 36
5.2.6 Reconexión (79) .................................................................................................... 38
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
3-285

5.2.7 Función de Verificación de Sincronismo (25) ........................................................ 38


5.2.8 Función de Falla de Interruptor (50BF) ................................................................. 38
5.3 S/E Ciruelos paño Valdivia C2 ................................................................................... 38
5.3.1 Función de Distancia (21/21N) .............................................................................. 39
5.3.2 Lógica de Teleprotección ...................................................................................... 44
5.3.3 Función direccional de corriente residual (67N) .................................................... 44
5.3.4 Función de Sobrecorriente de Emergencia (51B/51NB) ....................................... 45
5.3.5 Función de Bloqueo por Oscilación de Potencia ................................................... 46
5.3.5.1 Protección 7SA612 ........................................................................................... 46
5.3.5.2 Protección REL670........................................................................................... 46
5.3.6 Función de Cierre contra fallas (50HS) ................................................................. 48
5.3.6.1 Protección 7SA612 ........................................................................................... 48
5.3.6.2 Protección REL670........................................................................................... 48
5.3.7 Reconexión (79) .................................................................................................... 49
5.3.8 Función de Verificación de Sincronismo (25) ........................................................ 49
5.3.9 Función de Falla Fusible ....................................................................................... 50
5.3.9.1 Protección 7SA612 ........................................................................................... 50
5.3.9.2 Protección REL670........................................................................................... 51
5.3.10 Función de Falla de Interruptor (50BF) ................................................................. 52
5.4 S/E Valdivia paño Ciruelos C2 ................................................................................... 54
5.4.1 Función de Distancia (21/21N) .............................................................................. 54
5.4.2 Lógica de Teleprotección ...................................................................................... 59
5.4.3 Función direccional de corriente residual (67N) .................................................... 59
5.4.4 Función de Sobrecorriente de Emergencia (51B/51NB) ....................................... 60
5.4.5 Función de Bloqueo por Oscilación de Potencia ................................................... 61
5.4.5.1 Protección 7SA612 ........................................................................................... 61
5.4.5.2 Protección GE D60 ........................................................................................... 61
5.4.6 Reconexión (79) .................................................................................................... 63
5.4.7 Función de Verificación de Sincronismo (25) ........................................................ 63
5.4.8 Función de Falla de Interruptor (50BF) ................................................................. 63
5.5 Protección de falla de interruptor 7SJ80 .................................................................... 64
5.5.1 Paño Seccionador de Barra JS ............................................................................. 64
5.5.2 Paño Acoplador de Barra JR................................................................................. 65
5.6 Línea 220 kV Cautín – Tap Off Rio Tolten - Ciruelos ................................................. 66
5.6.1 S/E Cautín paño Ciruelos C1 ................................................................................ 67
5.6.2 S/E Ciruelos paño Cautín C1 ................................................................................ 68
5.7 Línea 220 kV Ciruelos – Valdivia C1 .......................................................................... 69
5.7.1 S/E Ciruelos paño Valdivia C1 .............................................................................. 70
5.7.2 S/E Valdivia paño Ciruelos C1 .............................................................................. 72
5.8 Linea 2x220 kV Mulchen – Cautin ............................................................................. 75
6. AJUSTES PROPUESTOS .......................................................................................................... 76
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
4-285

6.1 Línea 220kV Cautín – Ciruelos C2 ............................................................................. 76


6.1.1 S/E Ciruelos paño Cautín C2 ................................................................................ 76
6.1.1.1 Protección 7SA612 ........................................................................................... 76
6.1.1.2 Protección REL670........................................................................................... 78
6.1.2 S/E Cautín paño Ciruelos C2 ................................................................................ 83
6.1.2.1 Protección 7SA612 ........................................................................................... 83
6.1.2.2 Protección D60 ................................................................................................. 85
6.2 Línea 220 kV Ciruelos – Valdivia C2 .......................................................................... 89
6.2.1 S/E Ciruelos paño Valdivia C2 .............................................................................. 89
6.2.1.1 Protección 7SA612 ........................................................................................... 89
6.2.1.2 Protección REL670........................................................................................... 91
6.2.2 S/E Valdivia paño Ciruelos C2 .............................................................................. 96
6.2.2.1 Protección 7SA612 ........................................................................................... 96
6.2.2.2 Protección D60 ................................................................................................. 98
6.3 Barra N°2 S/E Ciruelos ............................................................................................ 102
6.3.1.1 Protección 7SJ80 ........................................................................................... 102
6.4 Línea 220 kV Cautín – Tap Off Rio Toltén – Ciruelos C1......................................... 102
6.4.1 S/E Cautín paño Ciruelos C1 .............................................................................. 102
6.4.2 S/E Ciruelos paño Cautín C1 .............................................................................. 103
6.5 Línea 220 kV Ciruelos – Valdivia C1 ........................................................................ 104
6.5.1 S/E Ciruelos paño Valdivia C1 ............................................................................ 104
6.5.2 S/E Valdivia paño Ciruelos C1 ............................................................................ 106
6.6 Línea 2x220kV Mulchen – Cautín C1 y C2 .............................................................. 108
7. COMENTARIOS Y CONCLUSIONES ....................................................................................... 110
ANEXO I. DESPEJE SECUENCIAL DE FALLAS .............................................................. 112
I.1. Línea 2x220 kV Cautín – Ciruelos. ......................................................................... 113
I.2. Línea 2x220 kV Ciruelos – Valdivia. ....................................................................... 119
ANEXO II. TIEMPOS DE OPERACIÓN CON AJUSTES PROPUESTOS ........................... 125
II.1. Escenario 1. Hidrología Húmeda y Demanda Alta (HH-DA)................................... 126
II.2. Escenario 2. Hidrología Húmeda y Demanda Baja (HH-DB).................................. 138
II.3. Escenario 3. Hidrología Seca y Demanda Alta (HS-DA) ........................................ 150
II.4. Escenario 4. Hidrología Seca y Demanda Baja (HS-DB) ....................................... 162
II.5. Escenario 5. Hidrología Humeda y Demanda Alta, considerando interruptor en Tap
Off Rio Tolten F/S (HH-DA-2) ................................................................................. 174
ANEXO III. ESQUEMAS DE DISTANCIA Y CURVAS DE SOBRECORRIENTE ................. 186
III.1. Paño Cautín C2 S/E Ciruelos ................................................................................. 187
III.2. Paño Ciruelos C2 S/E Cautín ................................................................................. 190
III.3. Paño Valdivia C2 S/E Ciruelos ............................................................................... 193
III.4. Paño Ciruelos C2 S/E Valdivia ............................................................................... 196

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
5-285

ANEXO IV. ESTUDIO DE CORTOCIRCUITOS ..................................................................... 199


IV.1. Escenario 1. Hidrología Húmeda y Demanda Alta ................................................. 200
IV.2. Escenario 2. Hidrología Húmeda y Demanda Baja ................................................ 200
IV.3. Escenario 3. Hidrología Seca y Demanda Alta ...................................................... 201
IV.4. Escenario 4. Hidrología Seca y Demanda Baja ..................................................... 201
IV.5. Escenario 5. Hidrología Humeda y Demanda Alta considerando interruptor Tap Off
Rio Tolten abierto ................................................................................................... 202
ANEXO V. DESPACHO DE GENERACIÓN......................................................................... 203
V.1. Despacho de Centrales Convencionales ............................................................... 204
V.2. Despacho de Centrales de ERNC .......................................................................... 208
ANEXO VI. PRINT OUT NUEVAS PROTECCIONES SE CIRUELOS .................................. 209
VI.1 S/E Ciruelos paño Cautín C2 ................................................................................. 210
VI.2 S/E Ciruelos paño Valdivia C2 ............................................................................... 236
VI.3 S/E Ciruelos ........................................................................................................... 262
ANEXO VII. BARRIDOS DE CORTOCIRCUITO Y TABLAS DE COORDINACIÓN
INSTALACIONES MT ........................................................................................................... 269
VI.4 Barridos de cortocircuito......................................................................................... 270
VI.5 Veificaciones de coordinación con MT ................................................................... 278

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
6-285

PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”


ESTUDIO DE COORDINACIÓN Y AJUSTE DE PROTECCIONES

1. IDENTIFICACIÓN DEL PROYECTO

El Proyecto Ampliación de la S/E Ciruelos consiste en el seccionamiento de la línea 1x220 kV Cautín


– Valdivia, junto con la ampliación del patio de 220 kV de la subestación para albergar 7 nuevas
posiciones, de las cuales se visten el paño seccionador, paño acoplador y paños para la línea Cautín
2 y Valdivia 2, y extensiones de barra necesarios para la conexión de la Central San Pedro (2020) y
los paños para las líneas Pichirropulli – Ciruelos 2x220 kV

2. OBJETIVO

El presente informe tiene el objetivo proponer ajustes para los nuevos sistemas de protección
instalados en la Subestación Ciruelos 220kV y para las protecciones existentes en el circuito N°2 de
la línea 220 kV Cautín – Valdivia.

Además, se verifica la coordinación de los ajustes propuestos con los demás sistemas de protección
de las líneas adyacentes a las subestaciones Cautín y Valdivia.

3. ANTECEDENTES

[1] Base de datos en formato DIgSILENT del Sistema Interconectado Central SIC correspondiente a
Abril del 2016.
[2] Fijación de Precio de Nudo de Corto Plazo de Abril 2016, Sistema Interconectado Central (SIC).
Informe Tecnico Definitivo, Abril 2016.
[3] Norma Técnica de Seguridad y Calidad de Servicio. Comisión Nacional de Energía, Enero 2016.
[4] Carta DO N°0678/2016, CDEC-SIC.
[5] C-2234-OFT-3534-1. "Alcances de los Servicios".
[6] Estructura 15 AD linea Cautin-Valdivia, Lamina Clave D107.
[7] Carta O-94, Transelec.
[8] C252-54E-001-L01. "Diagrama Unilineal Ampliación Patio 220 kV".

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
7-285

4. DESCRIPCION DEL SISTEMA ELÉCTRICO

Para la realización del estudio se utilizó el software Power Factory DIgSILENT junto a la última base
de datos disponible en el sitio web del CDEC – SIC al momento de comenzar los estudios,
correspondiente a Abril de 2016 [1]. Sobre esta base se incorporan las instalaciones nuevas que son
parte del proyecto de la Ampliación de S/E Ciruelos.

Las nuevas instalaciones del proyecto son las que se mencionan a continuación

 Seccionamiento de la línea Cautín – Valdivia (lado cordillera) entre las estructuras N° 362-A
y N° 363, aproximadamente a 135 metros al sur de la estructura N° 362-A.

 Montaje en el eje de la línea de una nueva estructura (22A.4C) con disposición para 3 (tres)
circuitos (dos (2) en anclaje y uno (1) en suspensión), en reemplazo de la actual torre de
suspensión N° 363. Esta estructura debe permitir el cruzamiento de la línea a seccionar con
el circuito N°1 correspondiente a la actual línea 220 kV Ciruelos – Valdivia.

 Tendido de conductor ACSR 636 MCM - Grosbeak entre la nueva estructura y los marcos de
líneas de la subestación. La distancia aproximada entre la nueva estructura para el
seccionamiento y los marcos de línea de la nueva subestación Ciruelos es
aproximadamente de 160 metros.

 Construcción de la barra principal N°1 y de la barra principal N°2, la cual se desarrollará en


el patio nuevo de la subestación

 Incorporación de cuatro paños de conexión: paño acoplador, paño seccionador, paño línea
Cautín 2 y paño línea Valdivia 2.

En el siguiente esquema se muestra la nueva configuración de la subestación

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
8-285

Figura 4.1: Esquema sistema resultante con ampliación S/E Ciruelos

Para proyectar la base de datos a la fecha de puesta en servicio de la ampliación de Subestación


Ciruelos, correspondiente a Enero 2017, se incorporan las nuevas obras en construcción, las que
son obtenidas del plan de obras en construcción de la Comisión Nacional de energía, publicado en el
informe “Fijación de Precios de Nudo de Corto Plazo, Abril 2016, Informe Técnico Definitivo”[2]. A
continuación se indica cada uno de ellos:

Tabla N° 4.1 – Obras de Generación en Construcción


Fecha Puesta en Potencia
Obras de Generación en Construcción Tecnología
Servicio [MW]
Los Buenos Aires Abr-16 24,0 Fotovoltaico
Conejo I Abr-16 104,5 Fotovoltaico
Renaico Abr-16 88,0 Eólico
Ancoa Jun-16 27,0 Hidro-Pasada
San Juan Jul-16 184,8 Eólico
Quilapilún Ago-16 103,2 Fotovoltaico
La Mina Sep-16 34,0 Hidro-Pasada
PFV Olmué Ene-17 144,0 Fotovoltaico

Tabla N° 4.2 – Obras de Transmisión en Construcción


Fecha
Proyecto Descripción estimada
PES
Nueva Línea Cardones-Diego de Almagro 2 x 220
Línea Cardones - Diego de Almagro Jun-16
kV: tendido del Segundo circuito
Seccionamiento línea Valdivia – Puerto Montt
Seccionamiento S/E Rahue Feb-17
220kV C2

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
9-285

4.1 Estimación de la Demanda

Para la realización del presente estudio se consideró escenarios de demanda máxima y mínima del
SIC. Para la estimación de la demanda máxima a la fecha de puesta en servicio de la Ampliación de
S/E Ciruelos, se utilizaron las tasas de variación de demanda de los clientes libres y regulados
publicados en el informe “Fijación de Precios de Nudo de Corto Plazo de Abril 2016” [2]. Las tasas
de variación se indican en las siguientes tablas.

Tabla N° 4.3 – Tasas de variación de Demanda de Clientes Regulados previstos por zona del SIC
SIC
Año SIC Norte SIC Centro SIC Itahue SIC Sur SIC Austral
Concepción
2016 4,55% 3,61% 3,89% 3,87% 4,58% 4,05%

Tabla N° 4.4 – Tasas de variación de Demanda de Clientes Libres previstos por zona del SIC
SIC
Año SIC Norte SIC Centro SIC Itahue SIC Sur SIC Austral
Concepción
2016 8,03% 2,51% 2,16% 1,84% 1,34% 1,96%

Para la estimación de la demanda mínima se consideró la misma relación porcentual entre los
escenarios de demanda alta y baja que vienen por defecto en la base de datos en formato
DIgSILENT utilizada [1].

4.2 Escenarios de Operación

Para verificar el cumplimiento de los márgenes de seguridad establecidos en la NTSyCS ante


distintas condiciones de operación en la zona de estudio, se establecen escenarios de generación
bajo eventuales condiciones de hidrología húmeda y seca para cada uno de los escenarios de
demanda mencionados en el punto 4.1. A continuación se detallan cada uno de los escenarios de
operación considerados para el estudio.

4.2.1 Hidrología Húmeda

En particular la hidrología húmeda considera el despacho a plena carga de las 2 unidades de Central
Canutillar, de Central Rucatayo, Carilafquen, Malalcahuello, Valdivia y de las unidades de Angostura.
Ambas unidades de central Antilhue F/S. Los porcentajes de despacho de cada tipo para demanda
alta y baja se muestran a continuación

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
10-285

Tabla N° 4.5 – Porcentajes por tipo de generación, Hidrología Húmeda


Centrales Centrales
Escenarios ERNC Designación
Hidroeléctricas Térmicas
Demanda Alta 54,80% 38,24% 6,95% HH-DA
Demanda Baja 55,02% 36,38% 8,16% HH-DB

A los 2 escenarios de operación mencionados se agrega un tercer escenario adicional, el cual


considera hidrología humeda, demanda alta y el interruptor del Tap Off Rio Tolten F/S (HH-DA-2)

4.2.2 Hidrología Seca

Los escenarios de operación de Hidrología Seca consideran los siguientes despachos

 Central Rucatayo en 15 MW
 Unidad 1 Canutillar en 50 MW, unidad 2 F/S
 Central Angostura: Unidad 1 y 2 F/S y unidad 3 en 40 MW
 Despacho a plena capacidad de ambas unidades de la Central Antilhue
 Despacho Planta Valdivia a plena carga

Los porcentajes de despacho de cada tipo para demanda alta y baja se muestran a continuación

Tabla N° 4.6 – Porcentajes por tipo de generación, Hidrología Seca


Centrales Centrales
Escenarios ERNC Designación
Hidroeléctricas Térmicas
Demanda Alta 37,91% 55,13% 6,97% HS-DA
Demanda Baja 35,96% 55,83% 8,21% HS-DB

4.3 Parámetros Eléctricos de los Elementos del Sistema

Tabla N° 4.7 – Parámetros Eléctricos Líneas de Transmisión


Largo R1 X1 B1 R0 X0 B0
Línea [Km] [ohm/km] [ohm/km] [uS/km] [ohm/km] [ohm/km] [uS/km]

Cautín - Rio Toltén 220 kV 30,8 0,09 0,39 2,93 0,23 1,37 1,71
Rio Toltén - Ciruelos 220 kV 79,1 0,09 0,39 2,93 0,23 1,37 1,71
Cautín - Ciruelos C2 220 kV 109,9 0,14 0,41 2,82 0,28 1,39 1,68
Ciruelos - Valdivia C1 220kV 39,3 0,09 0,39 2,93 0,23 1,37 1,71
Ciruelos - Valdivia C2 220kV 39,3 0,14 0,41 2,82 0,29 1,39 1,68
Ciruelos - Mariquina 220 kV 0,15 0,09 0,41 0,00 0,23 1,36 0,00
Ciruelos - Planta Valdivia 220 kV 1,80 0,11 0,45 2,84 0,25 1,42 1,51
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
11-285

Largo R1 X1 B1 R0 X0 B0
Línea [Km] [ohm/km] [ohm/km] [uS/km] [ohm/km] [ohm/km] [uS/km]

Mulchen - Cautín 220 kV C1 136,22 0,05 0,29 3,93 0,19 1,29 1,59
Mulchen - Cautín 220 kV C2 136,22 0,05 0,29 3,93 0,19 1,29 1,59
Temuco - Cautín 220 kV C1 2,00 0,10 0,40 2,91 0,24 1,37 1,79
Temuco - Cautín 220 kV C2 2,00 0,10 0,40 2,91 0,24 1,37 1,79
Valdivia - Tap Pichirrahue 220 kV 110,10 0,15 0,42 2,78 0,30 1,39 1,74
Tap Pichirrahue - Rahue 220 kV 0,15 0,16 0,42 2,74 0,30 1,38 1,64
Rahue - Pto Montt 220 kV 96,69 0,16 0,42 2,74 0,30 1,38 1,64
Valdivia - Rahue 220 kV C1 110,33 0,10 0,40 2,91 0,24 1,37 1,79
Rahue - Barro Blanco 220 kV 15,98 0,10 0,40 2,91 0,24 1,37 1,79

4.4 Análisis del Acoplamiento Mutuo de Secuencia Cero

Dado que las líneas 2x220 kV Cautín – Ciruelos y 2x220 kV Ciruelos - Valdivia comparten estructura,
se estudia el efecto del acoplamiento mutuo de secuencia cero en las protecciones de distancia.
Para determinar la influencia de este fenómeno en la impedancia medida por las protecciones, se
simulan fallas monofásicas a tierra a lo largo de la línea y se determina los valores de impedancia
medidos por las protecciones de distancia.

Estas simulaciones se realizan para 3 condiciones de operación del circuito paralelo.

 Condición 1: Circuito paralelo en operación


 Condición 2: Circuito paralelo fuera de servicio
 Condición 3: Circuito paralelo fuera de servicio y puesto a tierra en sus extremos

En las siguientes figuras se muestra la impedancia vista desde cada subestación (Cautín, Ciruelos y
Valdivia) hacia el extremo remoto.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
12-285

 Línea 2x220 kV Cautín – Ciruelos C2

Impedancia Vista por Extremo Cautín


70

60
57,81
Impedancia [Ω-pri]

50
46,17
40
35,81
30

20
Cto paralelo en servicio
10
Cto paralelo fuera de servicio
Cto paralelo a tierra
0
0 20 40 60 80 100 120
Longitud [km]

Figura 4.2: Impedancia vista desde extremo Cautín, línea 2x220 kV Cautín – Ciruelos C2

Impedancia Vista por Extremo Ciruelos


70

60 61,61

50 Cto paralelo en servicio


Impedancia [Ω-pri]

46,58
Cto paralelo fuera de servicio
40
34,57 Cto paralelo a tierra
30

20

10

0
0 20 40 60 80 100 120
Longitud [km]

Figura 4.3: Impedancia vista desde extremo Ciruelos, línea 2x220 kV Cautín – Ciruelos C2

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
13-285

 Línea 2x220 kV Ciruelos – Valdivia C2

Impedancia Vista por Extremo Ciruelos


25

21,1
20
Impedancia [Ω-pri]

16,8
15
13,92

10

Cto paralelo en servicio


5 Cto paralelo fuera de servicio
Cto paralelo a tierra
0
0 5 10 15 20 25 30 35 40 45
Longitud [km]
Figura 4.4: Impedancia vista desde extremo Ciruelos, línea 2x220 kV Ciruelos – Valdivia C2

Impedancia Vista por Extremo Valdivia


30

25 25,67
Impedancia [Ω-pri]

20
17,05
15 Cto paralelo en servicio
11,57 Cto paralelo fuera de servicio
10 Cto paralelo a tierra

0
0 5 10 15 20 25 30 35 40 45
Longitud [km]

Figura 4.5: Impedancia vista desde extremo Valdivia, línea 2x220 kV Ciruelos – Valdivia C2

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
14-285

Por lo tanto, para asegurar que la primera zona de las protecciones de distancia actúe dentro de la
línea, esta debe ser ajustada como porcentaje del menor valor impedancia vista. Ahora para
asegurar que la protección actúe en segunda zona a lo largo de toda la línea, esta debe ser ajustada
con una magnitud superior al mayor valor de impedancia vista por el respectivo extremo.

El escenario considerado para realizar el análisis de acoplamiento mutuo fue el que mayor
impedancia veía cada extremo por efecto de acoplamiento mutuo, esto es HH-DA para extremos
Ciruelos respecto a Cautín y Valdivia respecto a Ciruelos, y escenario HS-DA para extremos Cautín
respecto a Ciruelos y Ciruelos respecto a Valdivia.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
15-285

5. CRITERIOS Y AJUSTES DE PROTECCIONES

5.1 S/E Ciruelos paño Cautín C2

El paño de 220kV Cautín C2 de la SE Ciruelos dispone de los siguientes equipos de protección

 Protección de distancia 7SA612 Sistema 1


 Protección de distancia REL670 Sistema 2

Las funciones que se habilitaran para las protecciones mencionadas son las siguientes

 Distancia de Fases y Tierra (21/21N)


 Direccional de sobrecorriente residual (67N)
 Función de Sobrecorriente de Emergencia (51B/51NB)
 Bloqueo por Oscilación de Potencia (68)
 Cierre contra Fallas (50HS)
 Reconexión (79)
 Verificación de Sincronismo (25)
 Falla Fusible
 Falla de Interruptor (50BF)

5.1.1 Función de Distancia (21/21N)

Se habilita cuatro zonas de operación con característica cuadrilátera tanto para fallas entre fases
como fase a tierra.

La primera zona (Z1) considera ajustes en dirección hacia adelante con operación instantánea y un
alcance del 85% de la menor reactancia de línea 2x220kV Cautín – Ciruelos C2, considerando
acoplamiento mutuo de secuencia cero.

La Segunda zona (Z2) considera ajustes en dirección hacia adelante y un alcance del 120% de la
mayor reactancia de la línea 2x220kV Cautín – Ciruelos C2, considerando acoplamiento mutuo de
secuencia cero. El tiempo de operación se ajusta en 0,6 segundos para darle respaldo a las
protecciones que se encuentran en S/E Cautín paño Temuco C1 y C2 dado que el tiempo de
operación de la zona 2 es 0,4 segundos, además de darle respaldo a la línea paralela en caso de
perder la comunicación.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
16-285

Para la protección 7SA612 se ajusta una zona (Z1b) para la correcta operación de la lógica de
subalcance permisivo (PUTT) de la función de teleprotección. Esta zona se ajusta con los mismos
valores de la segunda zona (Z2) y con operación instantánea.

La tercera zona (Z3) relé 7SA612 y cuarta zona (Z4) relé REL670 considera ajustes en dirección
reversa y un alcance del 120% del sobrealcance máximo de zona 2 de la protección ubicada en el
extremo Cautín. Esta zona se ajusta con un tiempo infinito de operación para la protección 7SA612 y
60 segundos para protección REL 670 (máximo ajuste). La finalidad de ajustar esta zona es para el
funcionamiento de la teleprotección de la línea.

La Cuarta zona (Z4) relé 7SA612 y tercera zona (Z3) relé REL670 considera ajustes en dirección
hacia adelante y un alcance del 100% de la reactancia de la línea 2x220kV Cautín – Ciruelos C2,
considerando acoplamiento mutuo de secuencia cero mas el 200% de la reactancia de la línea
2x220kV Mulchen – Cautín C1. El tiempo de operación se ajusta en 1,2 segundos

Se ajusta una Quinta Zona (Z5) con ajustes no direccionales para la protección 7SA612, zona
utilizada para la función de oscilación de potencia. Esta zona considera un alcance del 120% de los
ajustes de tercera zona en dirección adelante. Se ajusta con tiempo infinito de operación

Transformadores de medida Razón


TTCC 800 A-pri 5 A-sec 160
TTPP 230000/√3 V-pri 115/√3 V-sec 2000
Razón TC/TP 0,080

A continuación se determina el valor de resistencia para la zona de carga, de modo de activar el load
encroachment en caso de ser necesario para que se bloquee la operación de la función de distancia.
Para el cálculo se utiliza la tensión de emergencia para 220 [kV] ( 10%), la corriente nominal del
transformador de corriente asociado al paño y un margen de seguridad de 10%. El valor obtenido se
indica a continuación

[ ]
[ ] [ ]
√ [ ]

Zona 1 – Forward

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
17-285

Donde Zmin Cautín – Ciruelos C2: impedancia mínima vista por extremo Ciruelos por efecto de impedancia
mutua de secuencia cero.

7SA612 (21/21N)
Xf= 85% • 31,99 = 27,19 (Ω-pri) = 2,18 (Ω-sec)
Rff= Xf = 27,19 (Ω-pri) = 2,18 (Ω-sec)
Rft= 3 • Xf = 81,57 (Ω-pri) = 6,53 (Ω-sec)
Retardo = 0,00 segundos

REL670 (21/21N)
X1 = 85% • 31,99 = 27,19 (Ω/pri)
R1 = 85% • 13,11 = 11,14 (Ω/pri)
X0 = 85% • 109,12 = 92,75 (Ω/pri)
R0 = 85% • 26,42 = 22,46 (Ω/pri)
RFPP = 2 • X1PP = 54,38 (Ω/l)
RFPG = 3 • X1PP = 81,57 (Ω/l)
Retardo = 0,00 segundos

Zona 1b – Forward (protección 7SA612)

Donde Zmax Cautín – Ciruelos C2: Impedancia máxima vista por extremo Ciruelos por efecto de impedancia
mutua de secuencia cero.

7SA612 (21/21N)
Xf= 120% • 59,22 = 71,06 (Ω-pri) = 5,69 (Ω-sec)
Rff= Xf = 71,06 (Ω-pri) = 5,69 (Ω-sec)
Rft= 3 • Xf = 213,19 (Ω-pri) = 17,06 (Ω-sec)
Retardo = 0,00 segundos

Zona 2 – Forward

Donde Zmax Cautín – Ciruelos C2: Impedancia máxima vista por extremo Ciruelos por efecto de impedancia
mutua de secuencia cero.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
18-285

7SA612 (21/21N)
Xf= 120% • 59,22 = 71,06 (Ω-pri) = 5,69 (Ω-sec)
Rff= Xf = 71,06 (Ω-pri) = 5,69 (Ω-sec)
Rft= 3 • Xf = 213,19 (Ω-pri) = 17,06 (Ω-sec)
Retardo = 0,60 segundos

REL670 (21/21N)
X1 = 120% • 59,22 = 71,06 (Ω/pri)
R1 = 120% • 16,99 = 20,39 (Ω/pri)
X0 = 120% • 202,01 = 242,42 (Ω/pri)
R0 = 120% • 34,26 = 41,11 (Ω/pri)
RFPP = 2 • X1PP = 142,13 (Ω/l)
RFPG = 3 • X1PP = 213,19 (Ω/l)
Retardo = 0,60 segundos

Zona 3 (7SA612) y 4 (REL670) – Reverse

7SA612 (21/21N)
Xff= 120% • (65,88-43,70)= 26,62 (Ω-pri) = 2,13 (Ω-sec)
Rff= 120% • (65,88-15,07)= 60,98 (Ω-pri) = 4,88 (Ω-sec)
Rft= 120% • (131,77-15,07)= 140,04 (Ω-pri) = 11,20 (Ω-sec)
Retardo = ∞ segundos

REL670 (21/21N)
X1 = 120% • (65,88-43,70)= 26,62 (Ω/pri)
R1 = 120% • (21,72-15,07)= 7,99 ((Ω/pri)
X0 = 120% • (178,88-149,07)= 35,78 (Ω/pri)
R0 = 120% • (36,45-30,37)= 7,29 (Ω/pri)
RFPP = 2 • 120%• (65,88-15,07) = 121,96 (Ω/l)
RFPG = 120%• (131,77-15,07) = 140,04 (Ω/l)
Retardo = 60,00 segundos

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
19-285

Zona 4 (7SA612) y 3 (REL670) – Forward

7SA612 (21/21N)
Xf= 100% • 59,22 + 200% • 39,50 = 138,23 (Ω-pri) = 11,06 (Ω-sec)
Rff= Xf = 138,23 (Ω-pri) = 11,06 (Ω-sec)
Rft= 1,85 • Xf = 255,72 (Ω-pri) = 20,46 (Ω-sec)
Retardo = 1,20 segundos

REL670 (21/21N)
X1 = 100% • 59,22 + 200% • 39,50 = 138,23 (Ω-pri)
R1 = 100% • 16,99 + 200% • 6,13 = 29,25 (Ω-pri)
X0 = 100% • 202,01 + 200% • 175,99 = 554,00 (Ω-pri)
R0 = 100% • 34,26 + 200% • 25,47 = 85,20 (Ω-pri)
RFPP = 2 • X1PP = 276,45 (Ω-pri)
RFPG = 1,85 • X1PP = 255,72 (Ω-pri)
Retardo = 1,20 segundos

Zona 5 (7SA612) – Non Directional

7SA612 (21/21N)
Xf= 120% • 138,23 = 165,87 (Ω-pri) = 13,27 (Ω-sec)
Rff= 120% • 138,23 = 165,87 (Ω-pri) = 13,27 (Ω-sec)
Rft= 120% • 255,72 = 306,86 (Ω-pri) = 24,55 (Ω-sec)
Xr= 120% • 138,23 = 165,87 (Ω-pri) = 13,27 (Ω-sec)
Delay = oo segundos

Para la detección de las fallas, la protección REL 670 utiliza la función de selección de fase con
delimitación de carga (FDPSPDIS). Los parámetros de ajuste de esta zona son los siguientes

RLdFwd : Corresponde al limite de carga hacia adelante


RldRev : Corresponde al limite de carga hacia atrás
Corresponde al ángulo de carga, el cual debe ser ajustado como el máximo
LdAngle : ángulo posible de carga para una condición de carga activa máxima, se ajusta
en 30°

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
20-285

Corresponden al alcance reactivo hacia adelante, los cuales deben cubrir la


zona de mayor alcance hacia adelante ajustado en la protección distancia. Por
X1 y X0 :
lo tanto, se tomará el valor de X1PP y X0PE de la zona 3 y se les aplicará un
factor de seguridad de 1,44 según lo recomendado por el fabricante
Corresponde al alcance resistivo de falla fase-fase hacia adelante, el cual debe
RFltFwdPP : cubrir la zona de mayor alcance. En este caso se considerará el 120% del
ajuste de RFPP de la zona 3
Corresponde al alcance resistivo de falla fase-fase hacia atras, el cual debe
RFltRevPP : cubrir la zona reversa más amplia. En este caso se considerará el 120% del
ajuste de RFPP de la zona 4
Corresponde al alcance resistivo de falla fase-tierra hacia adelante, el cual debe
RFltFwdPG : cubrir la zona con el mayor alcance ajustado. En este caso se considerará el
120% del ajuste de RFPE de la zona 3.
Corresponde al alcance resistivo de falla fase-tierra hacia atrás, el cual debe ser
RFltRevPG : mayor que la zona reversa más amplia. En este caso se considerará el 120%
del ajuste de RFPE de la zona 4
Según estos criterios, los ajustes para la función de selección de fase son los que se muestran a
continuación

RLdFwd : 128,75
RldRev : 128,75
LdAngle : 30°
X1 : 199,05
X0 : 797,76
RFltFwdPP : 331,74
RFltRevPP : 146,35
RFltFwdPG : 306,86
RFltRevPG : 168,05

5.1.2 Lógica de Teleprotección

Se habilitará la lógica de Subalcance permisivo (PUTT y Permissive UR para relés 7SA612 y


REL670 respectivamente) esperando la señal de aceleración desde el paño J6 de la S/E Cautín

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
21-285

5.1.3 Función direccional de corriente residual (67N)

Esta función se habilita de forma permanente para detectar y despejar fallas a tierra de alta
resistencia. Se habilita con lógica de comparación direccional.

Se recomienda que tenga una etapa de operación de tiempo inverso y una de tiempo definido, cuyos
ajustes son los que se muestran a continuación.

7SA612
3110 Operating mode : Forward
3111 Pickup : 8,15 A
3112 Time Delay : 0,3 seg
3140 Operating Mode : Forward
3141 Pickup : 0,75 A-sec
3143 Time Dial : 0,6
3151 IEC Curve : Very Inverse

REL670
DirMode1 : Forward
Characteristic1 : IEC Def. Time
IN1> : 163 (%IB)
t1 : 0,30
TD1 : 0,00
DirMode2 : Forward
Characteristic2 : IEC Very Inverse
IN2> : 15 (%IB)
t2 : 0,00
TD2 : 0,60

5.1.4 Función de Sobrecorriente de Emergencia (51B/51NB)

La función de sobrecorriente de emergencia se utiliza como protección de respaldo, en caso que la


protección detecte pérdida de la medida de tensión en una o más fases del transformador de
potencial.

Para la función de sobrecorriente de fases (51) se recomienda que tenga una etapa de tiempo
inverso, cuyo umbral de operación se ajusta igual al 120% la corriente nominal del transformador de
corriente asociado.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
22-285

Ahora, para la función de sobrecorriente residual (51N), se propone los mismos valores de ajuste de
la función 67N para la etapa de tiempo inverso, con la diferencia que esta será no direccional

Los ajustes propuestos son los siguientes

7SA612
2601 Operating Mode : ON: Only Active with Loss of VT
2640 51-B Pickup : 6,00A-sec
2642 51-B Time Dial : 0,05
2646 51-B Add. Time Delay 0,00
2650 51N-B Pickup : 0,75 A-sec
2652 51N-B Time Dial : 0,6
2656 51N-B Add. Time Delay 0,00
2660 IEC Curve : Normal Inverse.

REL670 (51)
DirModeSel1 : Non Directional
Characterist1 : IEC Norm. Inv.
Pickup1 : 120 (%IB)
t1 : 0,00
TD1 : 0,05

REL670 (51N)
DirModeSel3 : Non Directional
Characterist3 : IEC Very Inverse
Pickup3 : 15 (%IB)
t3 : 0,00
TD3 : 0,60

5.1.5 Función de Bloqueo por Oscilación de Potencia

5.1.5.1 Protección 7SA612

Se habilita la opción de bloqueo por oscilación de potencia, con bloqueo de la operación de todas las
zonas de protección y así evitar una operación indeseada de la función de distancia en presencia de
oscilaciones de potencia

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
23-285

5.1.5.2 Protección REL670

La función detección de oscilación de potencia (ZMRPSB) se utiliza para detectar oscilaciones de


potencia y bloquear la operación de las zonas de la protección de distancia. La aparición de
corrientes de falla a tierra durante una oscilación de potencia, impide la operación de la función
ZMRPSB para permitir el despeje de la falla.

Según el principio de operación, la función de detección de oscilación de potencia (ZMRPSB) incluye


una característica de medición cuadrilateral interna y externa con delimitación de carga, como se
muestra a continuación

Figura 5.1: Característica de Operación para función ZMRPSB

A continuación se presentan los criterios de ajustes para la función de detección de oscilación de


potencia en el Relé REL670

 X1lnFw: Define el límite reactivo interior, hacia adelante. Su ajuste se tomará como el 115%
del alcance reactivo ajustado en la zona 3 de la función de distancia (X1)

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
24-285

 R1LIn: Línea resistiva para la característica del ángulo interno. Su ajuste será calculado
como el 115% del alcance resistivo de la zona 3 (R1)
 R1FInFw: Línea de la resistencia de falla para la frontera resistiva interna, hacia adelante.
Su ajuste se tomará como el 115% del alcance resistivo ajustado en la zona 3 de la función
de distancia (RFPP)
 X1InRv: Define el límite reactivo interior, en dirección reversa. Su ajuste se tomará como el
115% del alcance reactivo ajustado en la zona 3 de la característica cuadrilateral de la
función de protección de distancia (X1).
 R1FInRv: Define la línea de la resistencia de falla para la frontera resistiva interna, en
dirección reversa. Su ajuste se tomará como el 115% del alcance resistivo ajustado en la
zona 3 de la función de distancia (RFPP).
 RLdOutFw, RLdOutRv: Corresponde a los límites exteriores de la característica de detección
de oscilación de potencia en dirección adelante y reversa respectivamente, los cuales
tendrán un margen de seguridad determinado por el factor kLdFw de la siguiente forma:

R1FInFw = kLdFw x RLdOutFw

El factor kLdFw toma un valor entre 0.70 y 0.90 dependiendo del rango de detección de oscilación
de potencia deseado. Un valor recomendado es de 0.75 para este factor.

Bajo estos Criterios, los ajustes propuestos son los siguientes

X1InFw : 158,96
R1LIn : 33,64
R1FInFw : 158,96
X1InRv : 158,96
R1FInRv : 158,96
RLdOutFw : 423,89
LdAngle : 30°
RLdOutRv : 423,89
kLdRFw : 0,75
kLdRRv : 0,75

5.1.6 Función de Cierre contra fallas (50HS)

5.1.6.1 Protección 7SA612

Para evitar operaciones indeseadas de esta función ante fallas que tengan lugar fuera de la línea
protegida, el umbral de operación se ajusta en 2,5 veces la corriente nominal.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
25-285

Pickup = 2,5 (pu) = 12,5 (A-sec)

5.1.6.2 Protección REL670

La función de cierre en falla tiene como objetivo la desconexión de forma inmediata y sin retardos de
las líneas de transmisión que cierren bajo condición de falla.

El criterio de ajuste de la corriente de arranque de esta función es considerar el 50% de la corriente


de falla trifásica franca al 1% de la línea desde la subestación Ciruelos 220 kV.

La lógica de cierre en falla se encuentra implementada en la función ZCVPSOF, cuyo disparo


generalmente es no direccional con el fin de asegurar el despeje de las fallas cuando la señal del
transformador de tensión no se encuentre disponible.

De los escenarios analizados, la menor corriente trifásica al 1% desde subestación Ciruelos es de 3466 [A],
por lo tanto esta función se ajusta de la siguiente manera

IphPickup = 1,733 kA

Dado que el valor de corriente supera al valor nominal del transformador de corriente (800 A) y que el ajuste
máximo para esta función es de 100%, el umbral de operación de ajusta al 100% de la corriente nominal del
transformador de corriente

IphPickup = 100% IB

5.1.7 Reconexión (79)

Se habilita reconexión Tripolar con un sólo intento de cierre.

La reconexión se realiza si la operación de la protección se realiza en forma instantánea, por fallas al


interior de la línea. Esto es actuación de las funciones de distancia o de comparación direccional de
corriente residual, ambas apoyadas por sus respectivas lógicas de teleprotección. La apertura de
interruptor con algún retardo de tiempo, no activa la reconexión.

El tiempo de retardo para la orden de cierre será de 0,5 segundos, tiempo adecuado para asegurar
la extinción del arco.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
26-285

5.1.8 Función de Verificación de Sincronismo (25)

Para permitir que la línea pueda ser energizada por ambos extremos, la función se configura para
permitir el cierre del interruptor en las condiciones barra viva – línea viva, barra viva – línea muerta,
barra muerta – línea viva y barra muerta – línea muerta.

Las diferencias máximas de voltaje se ajustan igual a un 10% la tensión nominal de la barra.

=6,4 [V]

Las diferencias máximas de ángulos se ajustan igual a 30°.

Finalmente, para el ajuste de la diferencia de frecuencia se recomienda un valor de 0,2 Hz. Valor
referenciado a la variación tolerable de frecuencia en torno al valor nominal para una condición en
régimen permanente, establecido en la Norma Técnica de Seguridad y Calidad de Servicio.

5.1.9 Función de Falla Fusible

Esta función se encarga de monitorear y señalizar la pérdida de la señal de voltaje desde los
transformadores de tensión hacia los diferentes equipos de protección y control que operan con esta
señal, tales como la función distancia, la función de sobrecorriente residual direccional, entre otras.

La operación de esta función se basa en el monitoreo de la corriente y tension de secuencia


negativa para la protección 7SA612 y en el monitoreo de de la corriente y tension de secuencia
negativa y/o cero para la protección REL670

Entonces, para asegurar la correcta operación de esta función, el ajuste de las corrientes de
arranque de secuencia negativa y/o secuencia cero debe ser aproximadamente un 20% por debajo
del más bajo valor de contribución de corriente de secuencia negativa y secuencia cero para una
condición de falla en el extremo remoto. Para esto se simulan fallas bifásicas aisladas, bifásicas a
tierra y monofásicas al 99% de la línea para determinar las mínimas corrientes de falla de secuencia
negativa y secuencia cero.

Los resultados obtenidos se muestran a continuación

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
27-285

Tabla N° 5.1 – Corrientes de Cortocircuitos línea 220 kV Ciruelos – Cautín C2


Falla 99% línea 220 kV Ciruelos – Cautín C2
Bifasica Aislada Bifasica a tierra Monofasica Mínima
I0 [kA] 0 0,13 0,15 0,13
I2 [kA] 0,36 0,26 0,22 0,22
V0 [pu] 0 0,09 0,1 0,09
V2 [pu] 0,39 0,28 0,24 0,24

5.1.9.1 Protección 7SA612

Los ajustes de corrientes y tension de secuencia negativa serán los siguientes

Además posee ajustes para una detección de falla de tension tripolar con los ajustes de tension y
corriente 2913A y 2914A los cuales se recomienda que se ajusten por defecto.

Con esto los ajustes propuestos para esta función son los siguientes.

2910 Fuse Failure Monitor ON


2911A Minimun Voltage Threshold V> 22 V
2912A Maximum Current Threshold I< 1,1 A
2913A Maximum Voltage Threshold V< 5V
2914A Differential Current Threshold 0,5 A

5.1.9.2 Protección REL670

Los ajustes de corrientes y tension de secuencia negativa serán los siguientes

Sin embargo, se recomienda que estos parámetros tengan los siguientes ajustes

3V0PU 60
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
28-285

3I0PU 20
3V2PU 60
3I2PU 20

Además de los parametros mencionados, se debe ajustar lo siguiente

VSealInPU: Identifica la condición de bajo voltaje en el sistema, por lo que debe ajustarse a un valor
inferior al mínimo voltaje de operación durante condiciones de emergencia. Este parámetro se
recomienda ajustarlo en 70% de la tensión base.

IDLDPU: Umbral de corriente para detección de la condición de línea muerta, el cual se ajusta con
un valor inferior a la corriente de carga en estado estable y superior a la corriente de carga cuando
una fase se encuentra desconectada. Este parámetro se ajustará en 20% de la corriente base

VDLDPU: Umbral de tensión para detección de la condición de línea muerta, el cual se ajusta con el
mínimo voltaje de operación esperado en el sistema. Este parámetro se ajustará en 70% de la
tensión base.

OpDVDI: Con modo de operación se considera la medida delta de la corriente y de la tensión para el
registro de pérdidas trifásicas (falla fusible) de las tensiones, con lo cual se previenen operaciones
indeseadas de la protección distancia cuando. Este parámetro se ajusta en Enabled y los demás
parámetros asociados con este modo de operación (DU>, DI<) se ajustan en el valor por defecto.

Con esto, los ajustes propuestos para esta función son los que se muestran a continuacion

OpModeSel V0I0 OR V2I2


3V0PU 60
3I0PU 20
3V2PU 60
3I2PU 20
OpDVDI Enabled
DVPU 70
DIPU 15
VPPU 70
IPPU 10
SealIn Enabled
VSealInPU 70
IDLDPU 20
VDLDPU 70

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
29-285

5.1.10 Función de Falla de Interruptor (50BF)

La protección de falla de interruptor se activa por la operación (disparo) de todas las protecciones de
línea y por la recepción de transferencia directa de desenganche (TDD).

Para determinar los ajustes para esta función se calculan las corrientes de cortocircuitos minimas
que ve esta protección, esto es fallas al 99% de la línea. Los resultados obtenidos son los que se
muestran a continuación

Tabla N° 5.2 – Corrientes de Cortocircuitos línea 220 kV Ciruelos – Cautín C2


Falla 99% línea 220 kV Ciruelos – Cautín C2
Trifasica [kA] Bifasica Aislada [kA] Bifasica a tierra [kA] Monofasica [kA]
IkssA 0,725 0,12 0,15 0,6
IkssB 0,725 0,57 0,63 0,19
IkssC 0,725 0,68 0,72 0,06
3I0 0 0 0,4 0,44

La corriente mínima de operación para fallas entre fases se ajustará al 80% de la corriente mínima
mostrada en la Tabla N° 5.2.

Pickup 50BF = 0,8 * 570 (A-pri) = 456 (A - pri) = 2,85 (A - sec) ó 0,57 pu

La corriente mínima de operación para fallas a tierra tendrá un valor igual al 30% de la corriente
nominal de los trasformadores de corriente asociados al interruptor, valor que es menor al 80% de la
corriente mínima de corcircuito.

Pickup 50BF = = 240 (A - pri) = 1,5 (A - sec)

Esta función de protección tiene dos etapas de operación, la primera etapa de repetición del disparo
(retrip) y la segunda de orden de apertura de los interruptores vecinos.

La etapa de orden de apertura dará orden de disparo al sistema de protección diferencial de barra,
para que a través de ella se emita la orden de apertura a los interruptores correspondientes a la
zona de la barra a la cual está conectada la línea, y envíe una orden de transferencia directa de
desenganche al interruptor 52J6 de la S/E Cautín.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
30-285

Para ésta etapa se recomienda un tiempo de retardo de la operación igual a 0,20 segundos, tiempo
suficiente para la extinción del arco en el interruptor. A continuación se muestran los ajustes para
esta función.

Para la función de retrip, se recomienda temporizar en 10 ms

7SA612
3901 50BF Breaker Failure Protection ON
3902 I>BF 2,85 A-sec
3904 T1-1pole 0,01 seg
3905 T1-3pole 0,01 seg
3906 T2 0,2 seg
3912 3Io>BF 1,5 A-sec

REL670
Pickup_PH 57% IB
Pickup_N 30% IB
t1 0,01 seg
T2 0,2 seg

5.2 S/E Cautín paño Ciruelos C2

El paño de 220kV Ciruelos C2 de la S/E Cautín dispone de los siguientes equipos de protección.

 Protección de distancia 7SA612 Sistema 1


 Protección de distancia GE D60 Sistema 2

Los Ajustes de estas protecciones se verificarán y en caso de ser necesario se modificaran las
siguientes funciones.

 Distancia de fases y tierra (21/21N)


 Función de sobrecorriente direccional residual (67N)
 Función de Sobrecorriente de Fases (51/50) Protección D60
 Bloqueo por Oscilacion de Potencia (68)
 Reconexión (79)
 Verificación de Sincronismo (25)
 Falla de Interruptor (50BF)

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
31-285

5.2.1 Función de Distancia (21/21N)

Se habilita cuatro zonas de operación con característica cuadrilátera tanto para fallas entre fases
como fase a tierra.

La primera zona (Z1) considera ajustes en dirección hacia adelante con operación instantánea y un
alcance del 85% de la menor reactancia de línea 2x220kV Cautín – Ciruelos C2, considerando
acoplamiento mutuo de secuencia cero.

La Segunda zona (Z2) considera ajustes en dirección hacia adelante y un alcance del 120% de la
mayor reactancia de la línea 2x220kV Cautín – Ciruelos C2, considerando acoplamiento mutuo de
secuencia cero. El tiempo de operación se ajusta en 0,6 segundos para darle respaldo a la línea
paralela en caso de perder la comunicación.

Para la protección 7SA612 se ajusta una zona (Z1b) para la correcta operación de la lógica de
subalcance permisivo (PUTT) de la función de teleprotección. Esta zona se ajusta con los mismos
valores de la segunda zona (Z2) y con operación instantánea.

La tercera zona (Z3) relé 7SA612 y cuarta zona (Z4) relé D60 considera ajustes en dirección reversa
y un alcance del 120% del sobrealcance máximo de zona 2 de la protección ubicada en el extremo
Ciruelos. Esta zona se ajusta con un tiempo infinito de operación para la protección 7SA612 y
65,535 segundos para protección D60 (máximo ajuste). La finalidad de ajustar esta zona es para el
funcionamiento de la teleprotección de la línea.

La Cuarta zona (Z4) relé 7SA612 y tercera zona (Z3) relé D60 considera ajustes en dirección hacia
adelante y un alcance del 100% de la reactancia de la línea 2x220kV Cautín – Ciruelos C2,
considerando acoplamiento mutuo de secuencia cero mas el 110% de la reactancia de la línea
2x220kV Ciruelos – Valdivia C2. El tiempo de operación se ajusta en 1,2 segundos

Se ajusta una Quinta Zona (Z5) con ajustes no direccionales para la protección 7SA612, zona
utilizada para la función de oscilación de potencia. Esta zona considera un alcance del 120% de los
ajustes de tercera zona hacia adelante. Se ajusta con tiempo infinito de operación

Transformadores de medida Razón


TTCC 1200 A-pri 1 A-sec 1200
TTPP 230000/√3 V-pri 115/√3 V-sec 2000
Razón TC/TP 0,600

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
32-285

A continuación se determina el valor de resistencia para la zona de carga, de modo de activar el load
encroachment en caso de ser necesario para que se bloquee la operación de la función de distancia.
Para el cálculo se utiliza la tensión de emergencia para 220 [kV] ( 10%), la corriente nominal del
transformador de corriente asociado al paño y un margen de seguridad de 10%. El valor obtenido se
indica a continuación

[ ]
[ ] [ ]
√ [ ]

Zona 1 – Forward

Donde Zmin Cautín – Ciruelos C2: impedancia mínima vista por extremo Cautín por efecto de impedancia
mutua de secuencia cero.

7SA612 (21/21N)
Xf= 85% • 34,05 = 28,94 (Ω-pri) = 17,36 (Ω-sec)
Rff= Xf = 28,94 (Ω-pri) = 17,36 (Ω-sec)
Rft= 3 • Xf = 86,82 (Ω-pri) = 52,09 (Ω-sec)
Retardo = 0,00 segundos

D60 (21)
REACH= 85% • 34,05 = 28,94 (Ω-pri) = 17,36 (Ω-sec)
RGT BLD = REACH= 28,94 (Ω-pri) = 17,36 (Ω-sec)
LFT BLD = REACH= 28,94 (Ω-pri) = 17,36 (Ω-sec)
Retardo = 0,00 segundos

D60 (21N)
REACH= 85% • 34,05 = 28,94 (Ω-pri) = 17,36 (Ω-sec)
RGT BLD = 3 • REACH= 86,82 (Ω-pri) = 52,09 (Ω-sec)
LFT BLD = 3 • REACH= 86,82 (Ω-pri) = 52,09 (Ω-sec)
Retardo = 0,00 segundos

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
33-285

Zona 1b – Forward (protección 7SA612)

Donde Zmax Cautín – Ciruelos C2: Impedancia máxima vista por extremo Cautín por efecto de impedancia
mutua de secuencia cero.

7SA612 (21/21N)
Xff= 120% • 54,90 = 65,88 (Ω-pri) = 39,53 (Ω-sec)
Rff= Xf = 65,88 (Ω-pri) = 39,53 (Ω-sec)
Rft= 2 • Xf = 131,77 (Ω-pri) = 79,06 (Ω-sec)
Retardo = 0,00 segundos

Zona 2 – Forward

Donde Zmax Cautín – Ciruelos C2: Impedancia máxima vista por extremo Cautín por efecto de impedancia
mutua de secuencia cero.

7SA612 (21/21N)
Xff= 120% • 54,90 = 65,88 (Ω-pri) = 39,53 (Ω-sec)
Rff= Xf = 65,88 (Ω-pri) = 39,53 (Ω-sec)
Rft= 2 • Xf = 131,77 (Ω-pri) = 79,06 (Ω-sec)
Retardo = 0,60 segundos

D60 (21)
REACH= 120% • 54,90 = 65,88 (Ω-pri) = 39,53 (Ω-sec)
RGT BLD = REACH= 65,88 (Ω-pri) = 39,53 (Ω-sec)
LFT BLD = REACH= 65,88 (Ω-pri) = 39,53 (Ω-sec)
Retardo = 0,60 segundos

D60 (21N)
REACH= 120% • 54,90 = 65,88 (Ω-pri) = 39,53 (Ω-sec)
RGT BLD = 2 • REACH= 131,77 (Ω-pri) = 79,06 (Ω-sec)
LFT BLD = 2 • REACH= 131,77 (Ω-pri) = 79,06 (Ω-sec)
Retardo = 0,60 segundos

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
34-285

Zona 3 (7SA612) y 4 (D60) – Reverse

7SA612 (21/21N)
Xff= 120% • (71,06-43,70)= 32,84 (Ω-pri) = 19,70 (Ω-sec)
Rff= 120% • (71,06-15,07)= 67,20 (Ω-pri) = 40,32 (Ω-sec)
Rft= 120% • (213,19-15,07)= 237,75 (Ω-pri) = 142,65 (Ω-sec)
Retardo = ∞ segundos

D60 (21)
REACH= 120% • (71,06-43,70)= 32,84 (Ω-pri) = 19,70 (Ω-sec)
RGT BLD = 120% • (71,06-15,07)= 67,20 (Ω-pri) = 40,32 (Ω-sec)
LFT BLD = 120% • (71,06-15,07)= 67,20 (Ω-pri) = 40,32 (Ω-sec)
Retardo = 65,535 segundos

D60 (21N)
REACH= 120% • (71,06-43,70)= 32,84 (Ω-pri) = 19,70 (Ω-sec)
RGT BLD = 120% • (213,19-15,07)= 237,75 (Ω-pri) = 142,65 (Ω-sec)
LFT BLD = 120% • (213,19-15,07)= 237,75 (Ω-pri) = 142,65 (Ω-sec)
Retardo = 65,535 segundos

Zona 4 (7SA612) y 3 (D60) – Forward

7SA612 (21/21N)
Xf= 100% • 54,90 + 110% • 16,01 = 72,51 (Ω-pri) = 43,51 (Ω-sec)
Rff= Xf = 72,51 (Ω-pri) = 43,51 (Ω-sec)
Rft= 2 • Xf = 145,02 (Ω-pri) = 87,01 (Ω-sec)
Retardo = 1,20 segundos

D60 (21)
REACH= 100% • 54,90 + 110% • 16,01 = 72,51 (Ω-pri) = 43,51 (Ω-sec)
RGT BLD = REACH= 72,51 (Ω-pri) = 43,51 (Ω-sec)
LFT BLD = REACH= 72,51 (Ω-pri) = 43,51 (Ω-sec)
Retardo = 1,20 segundos

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
35-285

D60 (21N)
REACH= 100% • 54,90 + 110% • 16,01 = 72,51 (Ω-pri) = 43,51 (Ω-sec)
RGT BLD = 2 • REACH= 145,02 (Ω-pri) = 87,01 (Ω-sec)
LFT BLD = 2 • REACH= 145,02 (Ω-pri) = 87,01 (Ω-sec)
Retardo = 1,20 segundos

Zona 5 (7SA612) – Non Directional

7SA612 (21/21N)
Xf= 120% • 72,51 = 87,01 (Ω-pri) = 52,21 (Ω-sec)
Rff= 120% • 72,51 = 87,01 (Ω-pri) = 52,21 (Ω-sec)
Rft= 120% • 237,75 = 285,30 (Ω-pri) = 171,18 (Ω-sec)
Xr= 120% • 72,51 = 87,01 (Ω-pri) = 52,21 (Ω-sec)
Delay = oo segundos

5.2.2 Lógica de Teleprotección

Se habilitará la lógica de Subalcance permisivo (PUTT) esperando la señal de aceleración desde el


paño J6 de la S/E Ciruelos

5.2.3 Función direccional de corriente residual (67N)

Esta función se habilita de forma permanente para detectar y despejar fallas a tierra de alta
resistencia. Se habilita con lógica de comparación direccional.

Se recomienda que tenga una etapa de operación de tiempo inverso y una de tiempo definido, cuyos
ajustes se muestran a continuación.

7SA612
3110 Operating mode : Forward
3111 Pickup : 1,17 A
3112 Time Delay : 0,3 seg
3140 Operating Mode : Forward
3141 Pickup : 0,1 A-sec
3143 Time Dial : 0,28
3151 IEC Curve : Normal Inverse

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
36-285

D60
NEUTRAL TOC1 Function : Enabled
NEUTRAL TOC1 Pickup : 0,1 pu
NEUTRAL TOC1 Curve : IEC Curve A
NEUTRAL TOC1 TD Multiplier : 0,28
NEUTRAL IOC1 Function : Enabled
NEUTRAL IOC1 Pickup : 1,17 pu
NEUTRAL IOC1 Delay : 0,30

5.2.4 Función de Sobrecorriente de Fases (51/50) protección GE D60

Debido a que la protección no tiene activada una función de sobrecorriente de emergencia para
fallas entre fases, se mantiene activada esta función. Sin embargo, para darle prioridad de operación
a la función de distancia, se modifica el time dial. Los ajustes propuestos son los siguientes

D60
PHASE TOC1 Function : Enabled
PHASE TOC1 Pickup : 0,6 pu
PHASE TOC1 Curve : IEC Curve A
PHASE TOC1 TD Multiplier : 0,11

5.2.5 Función de Bloqueo por Oscilación de Potencia

5.2.5.1 Protección 7SA612

No se modifican ajustes actuales

5.2.5.2 Protección GE D60

Esta función se habilita para evitar que la función de distancia opere de forma indeseada ante
oscilaciones de este tipo.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
37-285

Figura 5.2: Característica de detección de oscilación de potencia protección D60

En la Figura 5.2 se muestra la característica de detección de la función de bloqueo por oscilación de


potencia de la protección D60.

A continuación se presenta los ajustes para la función de oscilación de potencia

Donde, Zcarga: Impedancia de Carga

[ ] [ ]

Entonces,

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
38-285

5.2.6 Reconexión (79)

No se modifican ajustes actuales

5.2.7 Función de Verificación de Sincronismo (25)

No se modifican ajustes actuales

5.2.8 Función de Falla de Interruptor (50BF)

No se modifican ajustes actuales

5.3 S/E Ciruelos paño Valdivia C2

El paño de 220kV Valdivia C2 de la SE Ciruelos dispone de los siguientes equipos de protección

 Protección de distancia 7SA612 Sistema 1


 Protección de distancia REL670 Sistema 2

Las funciones que se habilitaran para las protecciones mencionadas son las siguientes

 Distancia de Fases y Tierra (21/21N)


 Direccional de sobrecorriente residual (67N)
 Sobrecorriente de Emergencia (51B/51NB)
 Bloqueo por Oscilación de Potencia (68)
 Cierre contra Fallas (50HS)
 Reconexión (79)
 Verificación de Sincronismo (25)
 Falla Fusible

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
39-285

 Falla de Interruptor (50BF)

5.3.1 Función de Distancia (21/21N)

Se habilita cuatro zonas de operación con característica cuadrilátera tanto para fallas entre fases
como fase a tierra.

La primera zona (Z1) considera ajustes en dirección hacia adelante con operación instantánea y un
alcance del 85% de la menor reactancia de línea 2x220kV Ciruelos - Valdivia C2, considerando
acoplamiento mutuo de secuencia cero.

La Segunda zona (Z2) considera ajustes en dirección hacia adelante y un alcance del 120% de la
mayor reactancia de la línea 2x220kV Ciruelos - Valdivia C2, considerando acoplamiento mutuo de
secuencia cero. El tiempo de operación se ajusta en 0,3 segundos para darle respaldo a la línea
paralela en caso de perder la comunicación.

Para la protección 7SA612 se ajusta una zona (Z1b) para la correcta operación de la lógica de
Subalcance permisivo (PUTT) de la función de teleprotección. Esta zona se ajusta con los mismos
valores de la segunda zona (Z2) y con operación instantánea.

La tercera zona (Z3) relé 7SA612 y cuarta zona (Z4) relé REL670 considera ajustes en dirección
reversa y un alcance del 120% del sobrealcance máximo de zona 2 de la protección ubicada en el
extremo Valdivia. Esta zona se ajusta con un tiempo infinito de operación para la protección 7SA612
y 60 segundos para protección REL 670 (máximo ajuste). La finalidad de ajustar esta zona es para el
funcionamiento de la teleprotección de la línea.

La Cuarta zona (Z4) relé 7SA612 y tercera zona (Z3) relé REL670 considera ajustes en dirección
hacia adelante y un alcance del 100% de la reactancia de la línea 2x220kV Ciruelos - Valdivia C2,
considerando acoplamiento mutuo de secuencia cero mas el 110% de la reactancia de la línea
220kV Valdivia - Rahue. El tiempo de operación se ajusta en 1,20 segundos

Se ajusta una Quinta Zona (Z5) con ajustes no direccionales para la protección 7SA612, zona
utilizada para la función de oscilación de potencia. Esta zona considera un alcance del 120% de los
ajustes de tercera zona hacia adelante. Se ajusta con tiempo infinito de operación

Transformadores de medida Razón


TTCC 800 A-pri 5 A-sec 160

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
40-285

TTPP 230000/√3 V-pri 115/√3 V-sec 2000


Razón TC/TP 0,080

A continuación se determina el valor de resistencia para la zona de carga, de modo de activar el load
encroachment en caso de ser necesario para que se bloquee la operación de la función de distancia.
Para el cálculo se utiliza la tensión de emergencia para 220 [kV] ( 10%), la corriente nominal del
transformador de corriente asociado al paño y un margen de seguridad de 10%. El valor obtenido se
indica a continuación

[ ]
[ ] [ ]
√ [ ]

Zona 1 – Forward

Donde Zmin Ciruelos – Valdivia C2: impedancia mínima vista por extremo Ciruelos por efecto de impedancia
mutua de secuencia cero.

7SA612 (21/21N)
Xf= 85% • 13,15 = 11,18 (Ω-pri) = 0,89 (Ω-sec)
Rff= Xf = 11,18 (Ω-pri) = 0,89 (Ω-sec)
Rft= 4 • Xf = 44,73 (Ω-pri) = 3,58 (Ω-sec)
Retardo = 0,00 segundos

REL670 (21/21N)
X1 = 85% • 13,15 = 11,18 (Ω/pri)
R1 = 85% • 4,55 = 3,87 (Ω/pri)
X0 = 85% • 44,84 = 38,11 (Ω/pri)
R0 = 85% • 9,25 = 7,86 (Ω/pri)
RFPP = 2 • X1PP = 22,36 (Ω/l)
RFPG = 4 • X1PP = 44,73 (Ω/l)
Retardo = 0,00 segundos

Zona 1b – Forward (protección 7SA612)

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
41-285

Donde Zmax Ciruelos - Valdivia C2: Impedancia máxima vista por extremo Ciruelos por efecto de impedancia
mutua de secuencia cero.

7SA612 (21/21N)
Xf= 120% • 19,97 = 23,97 (Ω-pri) = 1,92 (Ω-sec)
Rff= Xf = 23,97 (Ω-pri) = 1,92 (Ω-sec)
Rft= 5 • Xf = 119,85 (Ω-pri) = 9,59 (Ω-sec)
Retardo = 0,00 segundos

Zona 2 – Forward

Donde Zmax Ciruelos - Valdivia C2: Impedancia máxima vista por extremo Ciruelos por efecto de impedancia
mutua de secuencia cero.

7SA612 (21/21N)
Xf= 120% • 19,97 = 23,97 (Ω-pri) = 1,92 (Ω-sec)
Rff= Xf = 23,97 (Ω-pri) = 1,92 (Ω-sec)
Rft= 5 • Xf = 119,85 (Ω-pri) = 9,59 (Ω-sec)
Retardo = 0,30 segundos

REL670 (21/21N)
X1 = 120% • 19,97 = 23,97 (Ω/pri)
R1 = 120% • 6,80 = 8,16 (Ω/pri)
X0 = 120% • 68,08 = 81,70 (Ω/pri)
R0 = 120% • 13,82 = 16,58 (Ω/pri)
RFPP = 2 • X1PP = 47,94 (Ω/l)
RFPG = 5 • X1PP = 119,85 (Ω/l)
Retardo = 0,30 segundos

Zona 3 (7SA612) y 4 (REL670) – Reverse

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
42-285

7SA612 (21/21N)
Xff= 120% • (29,64-16,01)= 16,37 (Ω-pri) = 1,31 (Ω-sec)
Rff= 120% • (29,64-5,52)= 28,95 (Ω-pri) = 2,32 (Ω-sec)
Rft= 120% • (118,58-5,52)= 135,67 (Ω-pri) = 10,85 (Ω-sec)
Retardo = ∞ segundos

REL670 (21/21N)
X1 = 120% • (29,64-16,01)= 16,37 (Ω/pri)
R1 = 120% • (8,37-5,52)= 3,42 (Ω/pri)
X0 = 120% • (65,47-54,56)= 13,09 (Ω/pri)
R0 = 120% • (13,46-11,21)= 2,69 (Ω/pri)
RFPP = 2 • 120%• (29,64-5,52) = 57,90 (Ω/li)
RFPG = 120%• (118,58-5,52) = 135,67 (Ω/l)
Retardo = 60,00 segundos

Zona 4 (7SA612) y 3 (REL670) – Forward

7SA612 (21/21N)
Xf= 100% • 19,97 + 110% • 43,89 = 68,25 (Ω-pri) = 5,46 (Ω-sec)
Rff= Xf = 68,25 (Ω-pri) = 5,46 (Ω-sec)
Rft= 3 • Xf = 204,76 (Ω-pri) = 16,38 (Ω-sec)
Retardo = 1,20 segundos

REL670 (21/21N)
X1 = 100% • 19,97 + 110% • 43,89 = 68,25 (Ω/pri)
R1 = 100% • 6,80 + 110% • 11,09 = 19,00 (Ω/pri)
X0 = 100% • 68,08 + 110% • 151,19 = 234,39 (Ω/pri)
R0 = 100% • 13,82 + 110% • 26,88 = 43,38 (Ω/pri)
RFPP = 2 • X1PP = 136,51 (Ω/l)
RFPG = 3 • X1PP = 204,76 (Ω/l)
Retardo = 1,20 segundos

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
43-285

Zona 5 (7SA612) – Non Directional

7SA612 (21/21N)
Xf= 120% • 68,25 = 81,90 (Ω-pri) = 6,55 (Ω-sec)
Rff= 120% • 68,25 = 81,90 (Ω-pri) = 6,55 (Ω-sec)
Rft= 120% • 204,76 = 245,71 (Ω-pri) = 19,66 (Ω-sec)
Xr= 120% • 68,25 = 81,90 (Ω-pri) = 6,55 (Ω-sec)
Delay = oo segundos

Para la detección de las fallas, la protección REL 670 utiliza la función de selección de fase con
delimitación de carga (FDPSPDIS). Los parámetros de ajuste de esta zona son los siguientes

RLdFwd : Corresponde al limite de carga hacia adelante


RldRev : Corresponde al limite de carga hacia atrás
Corresponde al ángulo de carga, el cual debe ser ajustado como el máximo
LdAngle : ángulo posible de carga para una condición de carga activa máxima, se ajusta
en 30°
Corresponden al alcance reactivo hacia adelante, los cuales deben cubrir la
zona de mayor alcance hacia adelante ajustado en la protección distancia. Por
X1 y X0 :
lo tanto, se tomará el valor de X1PP y X0PE de la zona 3 y se les aplicará un
factor de seguridad de 1,44 según lo recomendado por el fabricante
Corresponde al alcance resistivo de falla fase-fase hacia adelante, el cual debe
RFltFwdPP : cubrir la zona de mayor alcance. En este caso se considerará el 120% del
ajuste de RFPP de la zona 3
Corresponde al alcance resistivo de falla fase-fase hacia atras, el cual debe
RFltRevPP : cubrir la zona reversa más amplia. En este caso se considerará el 120% del
ajuste de RFPP de la zona 4
Corresponde al alcance resistivo de falla fase-tierra hacia adelante, el cual debe
RFltFwdPG : cubrir la zona con el mayor alcance ajustado. En este caso se considerará el
120% del ajuste de RFPE de la zona 3.
Corresponde al alcance resistivo de falla fase-tierra hacia atrás, el cual debe ser
RFltRevPG : mayor que la zona reversa más amplia. En este caso se considerará el 120%
del ajuste de RFPE de la zona 4
Según estos criterios, los ajustes para la función de selección de fase son los que se muestran a
continuación

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
44-285

RLdFwd : 128,75
RldRev : 128,75
LdAngle : 30°
X1 : 98,29
X0 : 337,52
RFltFwdPP : 163,81
RFltRevPP : 69,35
RFltFwdPG : 245,71
RFltRevPG : 162,81

5.3.2 Lógica de Teleprotección

Se habilitará la lógica de Subalcance permisivo (PUTT y Permissive UR para relés 7SA612 y


REL670 respectivamente) esperando la señal de aceleración desde el paño J4 de la S/E Valdivia

5.3.3 Función direccional de corriente residual (67N)

Esta función se habilita de forma permanente para detectar y despejar fallas a tierra de alta
resistencia. Se habilita con lógica de comparación direccional.

Se recomienda que tenga una etapa de operación de tiempo inverso y una de tiempo definido, cuyos
ajustes se muestran a continuación.

7SA612
3110 Operating mode : Forward
3111 Pickup : 13,15 A
3112 Time Delay : 0,3 seg
3140 Operating Mode : Forward
3141 Pickup : 1,0 A-sec
3143 Time Dial : 0,27
3151 IEC Curve : Normal Inverse

REL670
DirMode1 : Forward
Characteristic1 : IEC Def. Time
IN1> : 263 (%IB)
t1 : 0,30
TD1 : 0,00

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
45-285

DirMode2 : Forward
Characteristic2 : IEC Normal Inverse
IN2> : 20 (%IB)
t2 : 0,00
TD2 : 0,27

5.3.4 Función de Sobrecorriente de Emergencia (51B/51NB)

La función de sobrecorriente de emergencia se utiliza como protección de respaldo, en caso que la


protección detecte pérdida de la medida de tensión en una o más fases del transformador de
potencial.

Para la función de sobrecorriente de fases (51) se recomienda que tenga una etapa de tiempo
inverso, cuyo umbral de operación se ajusta igual al 120% la corriente nominal del transformador de
corriente asociado al paño.

Ahora, para la función de sobrecorriente residual (51N), se propone los mismos valores de ajuste de
la función 67N para la etapa de tiempo inverso, con la diferencia que esta será no direccional.

7SA612
2601 Operating Mode : ON: Only Active with Loss of VT
2640 51-B Pickup : 6,0 A-sec
2642 51-B Time Dial : 0,07
2646 51-B Add. Time Delay 0,00
2650 51N-B Pickup : 1,0 A-sec
2652 51N-B Time Dial : 0,27
2656 51N-B Add. Time Delay 0,00
2660 IEC Curve : Normal Inverse.

REL670 (51)
DirModeSel1 : Non directional
Characterist1 : IEC Norm. Inv.
Pickup1 : 120 (%IB)
t1 : 0,00
TD1 : 0,07

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
46-285

REL670 (51N)
DirModeSel3 : Non Directional
Characterist3 : IEC Normal Inverse
Pickup3 : 20 (%IB)
t3 : 0,00
TD3 : 0,27

5.3.5 Función de Bloqueo por Oscilación de Potencia

5.3.5.1 Protección 7SA612

Se habilita la opción de bloqueo por oscilación de potencia, con bloqueo de la operación de todas las
zonas de protección y así evitar una operación indeseada de la función de distancia en presencia de
oscilaciones de potencia

5.3.5.2 Protección REL670

La función detección de oscilación de potencia (ZMRPSB) se utiliza para detectar oscilaciones de


potencia y bloquear la operación de las zonas de la protección de distancia. La aparición de
corrientes de falla a tierra durante una oscilación de potencia, impide la operación de la función
ZMRPSB para permitir el despeje de la falla.

Según el principio de operación, la función de detección de oscilación de potencia (ZMRPSB) incluye


una característica de medición cuadrilateral interna y externa con delimitación de carga, como se
muestra a continuación.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
47-285

Figura 5.3: Característica de Operación para función ZMRPSB

A continuación se presentan los criterios de ajustes para la función de detección de oscilación de


potencia en el Relé REL670

 X1lnFw: Define el límite reactivo interior, hacia adelante. Su ajuste se tomará como el 115%
del alcance reactivo ajustado en la zona 3 de la función de distancia (X1)
 R1LIn: Línea resistiva para la característica del ángulo interno. Su ajuste será calculado
como el 115% del alcance resistivo de la zona 3 (R1)
 R1FInFw: Línea de la resistencia de falla para la frontera resistiva interna, hacia adelante.
Su ajuste se tomará como el 115% del alcance resistivo ajustado en la zona 3 de la función
de distancia (RFPP)
 X1InRv: Define el límite reactivo interior, en dirección reversa. Su ajuste se tomará como el
115% del alcance reactivo ajustado en la zona 3 de la característica cuadrilateral de la
función de protección de distancia (X1).
 R1FInRv: Define la línea de la resistencia de falla para la frontera resistiva interna, en
dirección reversa. Su ajuste se tomará como el 115% del alcance resistivo ajustado en la
zona 3 de la función de distancia (RFPP).
 RLdOutFw, RLdOutRv: Corresponde a los límites exteriores de la característica de detección
de oscilación de potencia en dirección adelante y reversa respectivamente, los cuales
tendrán un margen de seguridad determinado por el factor kLdFw de la siguiente forma:
R1FInFw = kLdFw x RLdOutFw
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
48-285

El factor kLdFw toma un valor entre 0.70 y 0.90 dependiendo del rango de detección de oscilación
de potencia deseado. Un valor recomendado es de 0.75 para este factor.

Bajo estos Criterios, los ajustes propuestos son los siguientes

X1InFw : 78,49
R1LIn : 21,85
R1FInFw : 78,49
X1InRv : 78,49
R1FInRv : 78,49
RLdOutFw : 209,31
LdAngle : 30°
RLdOutRv : 209,31
kLdRFw : 0,75
kLdRRv : 0,75

5.3.6 Función de Cierre contra fallas (50HS)

5.3.6.1 Protección 7SA612

Para evitar operaciones indeseadas de esta función ante fallas que tengan lugar fuera de la línea
protegida, el umbral de operación se ajusta en 2,5 veces la corriente nominal.

Pickup = 2,5 (pu) = 12,5 (A-sec)

5.3.6.2 Protección REL670

La función de cierre en falla tiene como objetivo la desconexión de forma inmediata y sin retardos de
las líneas de transmisión que cierren bajo condición de falla.

El criterio de ajuste de la corriente de arranque de esta función es considerar el 50% de la corriente


de falla trifásica franca al 1% de la línea desde la subestación Ciruelos 220 kV.

La lógica de cierre en falla se encuentra implementada en la función ZCVPSOF, cuyo disparo


generalmente es no direccional con el fin de asegurar el despeje de las fallas cuando la señal del
transformador de tensión no se encuentre disponible.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
49-285

De los escenarios analizados, la menor corriente trifásica al 1% desde subestación Ciruelos es de 4232 [A],
por lo tanto esta función se ajusta de la siguiente manera

IphPickup = 2,116 kA

Dado que el valor de corriente supera al valor nominal del transformador de corriente (800 A) y que el ajuste
máximo para esta función es de 100%, el umbral de operación de ajusta al 100% de la corriente nominal del
transformador de corriente

IphPickup = 100% IB

5.3.7 Reconexión (79)

Se habilita reconexión Tripolar con un sólo intento de cierre.

La reconexión se realiza si la operación de la protección se realiza en forma instantánea, por fallas al


interior de la línea. Esto es actuación de las funciones de distancia o de comparación direccional de
corriente residual, ambas apoyadas por sus respectivas lógicas de teleprotección. La apertura de
interruptor con algún retardo de tiempo, no activa la reconexión.

El tiempo de retardo para la orden de cierre será de 0,4 segundos, tiempo adecuado para asegurar
la extinción del arco.

5.3.8 Función de Verificación de Sincronismo (25)

Para permitir que la línea pueda ser energizada por ambos extremos, la función se configura para
permitir el cierre del interruptor en las condiciones barra viva – línea viva, barra viva – línea muerta,
barra muerta – línea viva y barra muerta – línea muerta.

Las diferencias máximas de voltaje se ajustan igual a un 10% la tensión nominal de la barra.

=6,4 [V]

Las diferencias máximas de ángulos se ajustan igual a 30°.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
50-285

Finalmente, para el ajuste de la diferencia de frecuencia se recomienda un valor de 0,2 Hz. Valor
referenciado a la variación tolerable de frecuencia en torno al valor nominal para una condición en
régimen permanente, establecido en la Norma Técnica de Seguridad y Calidad de Servicio.

5.3.9 Función de Falla Fusible

Esta función se encarga de monitorear y señalizar la pérdida de la señal de voltaje desde los
transformadores de tensión hacia los diferentes equipos de protección y control que operan con esta
señal, tales como la función distancia, la función de sobrecorriente residual direccional, entre otras.

La operación de esta función se basa en el monitoreo de la corriente y tension de secuencia


negativa para la protección 7SA612 y en el monitoreo de de la corriente y tension de secuencia
negativa y/o cero para la protección REL670

Entonces, para asegurar la correcta operación de esta función, el ajuste de las corrientes de
arranque de secuencia negativa y/o secuencia cero debe ser aproximadamente un 20% por debajo
del más bajo valor de contribución de corriente de secuencia negativa y secuencia cero para una
condición de falla en el extremo remoto. Para esto se simulan fallas bifásicas aisladas, bifásicas a
tierra y monofásicas al 99% de la línea para determinar las mínimas corrientes de falla de secuencia
negativa y secuencia cero.

Los resultados obtenidos se muestran a continuación

Tabla N° 5.3 – Corrientes de Cortocircuitos línea 220 kV Ciruelos – Valdivia C2


Falla 99% línea 220 kV Ciruelos – Valdivia C2
Bifasica Aislada Bifasica a tierra Monofasica Mínima
I0 [kA] 0 0,17 0,15 0,15
I2 [kA] 0,7 0,4 0,52 0,4
V0 [pu] 0 0,17 0,14 0,14
V2 [pu] 0,42 0,24 0,32 0,24

5.3.9.1 Protección 7SA612

Los ajustes de corrientes y tension de secuencia negativa serán los siguientes

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
51-285

Además posee ajustes para una detección de falla de tension tripolar con los ajustes de tension y
corriente 2913A y 2914A los cuales se recomienda que se ajusten por defecto.

Con esto los ajustes propuestos para esta función son los siguientes.

2910 Fuse Failure Monitor ON


2911A Minimun Voltage Threshold V> 22 V
2912A Maximum Current Threshold I< 2A
2913A Maximum Voltage Threshold V< 5V
2914A Differential Current Threshold 0,5 A

5.3.9.2 Protección REL670

Los ajustes de corrientes y tension de secuencia negativa serán los siguientes

Sin embargo, se recomienda que estos parámetros tengan los siguientes ajustes

3V0PU 60
3I0PU 20
3V2PU 60
3I2PU 20

Además de los parametros mencionados, se debe ajustar lo siguiente

VSealInPU: Identifica la condición de bajo voltaje en el sistema, por lo que debe ajustarse a un valor
inferior al mínimo voltaje de operación durante condiciones de emergencia. Este parámetro se
recomienda ajustarlo en 70% de la tensión base.

IDLDPU: Umbral de corriente para detección de la condición de línea muerta, el cual se ajusta con
un valor inferior a la corriente de carga en estado estable y superior a la corriente de carga cuando
una fase se encuentra desconectada. Este parámetro se ajustará en 20% de la corriente base

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
52-285

VDLDPU: Umbral de tensión para detección de la condición de línea muerta, el cual se ajusta con el
mínimo voltaje de operación esperado en el sistema. Este parámetro se ajustará en 70% de la
tensión base.

OpDVDI: Con modo de operación se considera la medida delta de la corriente y de la tensión para el
registro de pérdidas trifásicas (falla fusible) de las tensiones, con lo cual se previenen operaciones
indeseadas de la protección distancia. Este parámetro se ajusta en Enabled y los demás parámetros
asociados con este modo de operación (DU>, DI<) se ajustan en el valor por defecto.

Con esto, los ajustes propuestos para esta función son los que se muestran a continuacion

OpModeSel V0I0 OR V2I2


3V0PU 60
3I0PU 20
3V2PU 60
3I2PU 20
OpDVDI Enabled
DVPU 70
DIPU 15
VPPU 70
IPPU 10
SealIn Enabled
VSealInPU 70
IDLDPU 20
VDLDPU 70

5.3.10 Función de Falla de Interruptor (50BF)

La protección de falla de interruptor se activa por la operación (disparo) de todas las protecciones de
línea y por la recepción de transferencia directa de desenganche (TDD).

Para determinar los ajustes para esta función se calculan las corrientes de cortocircuitos minimas
que ve esta protección, esto es fallas al 99% de la línea. Los resultados obtenidos son los que se
muestran a continuación

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
53-285

Tabla N° 5.4 – Corrientes de Cortocircuitos línea 220 kV Ciruelos – Valdivia C2


Falla 99% línea 220 kV Ciruelos – Valdivia C2
Trifasica [kA] Bifasica Aislada [kA] Bifasica a tierra [kA] Monofasica [kA]
IkssA 1,4 0,2 0,44 1,2
IkssB 1,4 1,31 1,3 0,23
IkssC 1,4 1,13 1,32 0,54
3I0 0 0 0,52 0,44

La corriente mínima de operación para fallas entre fases se ajustará al 80% de la corriente mínima
mostrada en la Tabla N° 5.4

Pickup 50BF = 0,8 * 1.130 (A-pri) = 904 (A - pri) = 5,65 (A - sec) ó 1,13 pu

La corriente mínima de operación para fallas a tierra tendrá un valor igual al 30% de la corriente
nominal de los trasformadores de corriente asociados al interruptor. Ajuste que es menor al 80% de
corriente mínima de cortocircuito

Pickup 50BF = = 240 (A - pri) = 1,5 (A - sec)

Esta función de protección tiene dos etapas de operación, la primera etapa de repetición del disparo
(retrip) y la segunda de orden de apertura de los interruptores vecinos.

La etapa de orden de apertura dará orden de disparo al sistema de protección diferencial de barra,
para que a través de ella se emita la orden de apertura a los interruptores correspondientes a la
zona de la barra a la cual está conectada la línea, y envíe una orden de transferencia directa de
desenganche al interruptor 52J4 de la S/E Valdivia.

Para ésta etapa se recomienda un tiempo de retardo de la operación igual a 0,20 segundos, tiempo
suficiente para la extinción del arco en el interruptor. A continuación se muestran los ajustes para
esta función

Para la función de retrip, se recomienda temporizar en 10 ms

7SA612
3901 50BF Breaker Failure Protection ON
3902 I>BF 5,65 A-sec
3904 T1-1pole 0,01 seg

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
54-285

3905 T1-3pole 0,01 seg


3906 T2 0,2 seg
3912 3Io>BF 1,5 A-sec

REL670
Pickup_PH 113% IB
Pickup_N 30% IB
t1 0,01 seg
T2 0,2 seg

5.4 S/E Valdivia paño Ciruelos C2

El paño de 220kV Ciruelos C2 de la S/E Valdivia dispone de los siguientes equipos de protección.

 Protección de distancia 7SA612 Sistema 1


 Protección de distancia GE D60 Sistema 2

Los Ajustes de estas protecciones se verificarán y en caso de ser necesario se modificaran las
siguientes funciones.

 Distancia de fases y tierra (21/21N)


 Función de sobrecorriente direccional residual (67N)
 Función de Sobrecorriente de Emergencia (51B/51NB)
 Bloqueo por oscilación de potencia (68)
 Reconexión (79)
 Verificación de Sincronismo (25)
 Falla de Interruptor (50BF)

5.4.1 Función de Distancia (21/21N)

Se habilita cuatro zonas de operación con característica cuadrilátera tanto para fallas entre fases
como fase a tierra.

La primera zona (Z1) considera ajustes en dirección hacia adelante con operación instantánea y un
alcance del 85% de la menor reactancia de línea 2x220kV Ciruelos - Valdivia C2, considerando
acoplamiento mutuo de secuencia cero.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
55-285

La Segunda zona (Z2) considera ajustes en dirección hacia adelante y un alcance del 120% de la
mayor reactancia de la línea 2x220kV Ciruelos - Valdivia C2, considerando acoplamiento mutuo de
secuencia cero. El tiempo de operación se ajusta en 0,3 segundos, con el fin de darle respaldo a la
línea paralela en caso de perder la comunicación.

Para la protección 7SA612 se ajusta una zona (Z1b) para el la correcta operación de la lógica de
Subalcance permisivo (PUTT) de la función de teleprotección. Esta zona se ajusta con los mismos
valores de la segunda zona (Z2) y con operación instantánea.

La tercera zona (Z3) relé 7SA612 y cuarta zona (Z4) relé D60 considera ajustes en dirección reversa
y un alcance del 120% del sobrealcance máximo de zona 2 de la protección ubicada en el extremo
Ciruelos. Esta zona se ajusta con un tiempo infinito de operación para la protección 7SA612 y
65,535 segundos para protección D60 (máximo ajuste). La finalidad de ajustar esta zona es para el
funcionamiento de la teleprotección de la línea.

La Cuarta zona (Z4) relé 7SA612 y tercera zona (Z3) relé D60 considera ajustes en dirección hacia
adelante y un alcance del 100% de la reactancia de la línea 2x220kV Ciruelos - Valdivia C2,
considerando acoplamiento mutuo de secuencia cero mas el 110% de la reactancia de la línea
2x220kV Cautín - Ciruelos C2. El tiempo de operación se ajusta en 1,20 segundos

Se ajusta una Quinta Zona (Z5) con ajustes no direccionales para la protección 7SA612, zona
utilizada para la función de oscilación de potencia. Esta zona considera un alcance del 120% de los
ajustes de tercera zona en dirección adelante. Se ajusta con tiempo infinito de operación

Transformadores de medida Razón


TTCC 800 A-pri 1 A-sec 800
TTPP 230000/√3 V-pri 115/√3 V-sec 2000,0
Razón TC/TP 0,400

A continuación se determina el valor de resistencia para la zona de carga, de modo de activar el load
encroachment en caso de ser necesario para que se bloquee la operación de la función de distancia.
Para el cálculo se utiliza la tensión de emergencia para 220 [kV] ( 10%), la corriente nominal del
transformador de corriente asociado al paño y un margen de seguridad de 10%. El valor obtenido se
indica a continuación

[ ]
[ ] [ ]
√ [ ]
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
56-285

Zona 1 – Forward

Donde Zmin Ciruelos - Valdivia C2: impedancia mínima vista por extremo Valdivia por efecto de impedancia
mutua de secuencia cero.

7SA612 (21/21N)
Xf= 85% • 10,76 = 9,15 (Ω-pri) = 3,66 (Ω-sec)
Rff= Xf = 9,15 (Ω-pri) = 3,66 (Ω-sec)
Rft= 4,5 • Xf = 41,16 (Ω-pri) = 16,46 (Ω-sec)
Retardo = 0,00 segundos

D60 (21)
REACH= 85% • 10,76 = 9,15 (Ω-pri) = 3,66 (Ω-sec)
RGT BLD = REACH= 9,15 (Ω-pri) = 3,66 (Ω-sec)
LFT BLD = REACH= 9,15 (Ω-pri) = 3,66 (Ω-sec)
Retardo = 0,00 segundos

D60 (21N)
REACH= 85% • 10,76 = 9,15 (Ω-pri) = 3,66 (Ω-sec)
RGT BLD = 4,5 • REACH= 41,16 (Ω-pri) = 16,46 (Ω-sec)
LFT BLD = 4,5 • REACH= 41,16 (Ω-pri) = 16,46 (Ω-sec)
Retardo = 0,00 segundos

Zona 1b – Forward (protección 7SA612)

Donde Zmax Ciruelos - Valdivia C2: Impedancia máxima vista por extremo Valdivia por efecto de impedancia
mutua de secuencia cero.

7SA612 (21/21N)
Xf= 120% • 24,70 = 29,64 (Ω-pri) = 11,86 (Ω-sec)
Rff= Xf = 29,64 (Ω-pri) = 11,86 (Ω-sec)

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
57-285

Rft= 4 • Xf = 118,58 (Ω-pri) = 47,43 (Ω-sec)


Retardo = 0,00 segundos

Zona 2 – Forward

Donde Zmax Ciruelos - Valdivia C2: Impedancia máxima vista por extremo Valdivia por efecto de impedancia
mutua de secuencia cero.

7SA612 (21/21N)
Xf= 120% • 24,70 = 29,64 (Ω-pri) = 11,86 (Ω-sec)
Rff= Xf = 29,64 (Ω-pri) = 11,86 (Ω-sec)
Rft= 4 • Xf = 118,58 (Ω-pri) = 47,43 (Ω-sec)
Retardo = 0,30 segundos

D60 (21)
REACH= 120% • 24,70 = 29,64 (Ω-pri) = 11,86 (Ω-sec)
RGT BLD = REACH= 29,64 (Ω-pri) = 11,86 (Ω-sec)
LFT BLD = REACH= 29,64 (Ω-pri) = 11,86 (Ω-sec)
Retardo = 0,30 segundos

D60 (21N)
REACH= 120% • 24,70 = 29,64 (Ω-pri) = 11,86 (Ω-sec)
RGT BLD = 4 • REACH= 118,58 (Ω-pri) = 47,43 (Ω-sec)
LFT BLD = 4 • REACH= 118,58 (Ω-pri) = 47,43 (Ω-sec)
Retardo = 0,30 segundos

Zona 3 (7SA612) y 4 (D60) – Reverse

7SA612 (21/21N)
Xf= 120% • (23,97-16,01)= 9,55 (Ω-pri) = 3,82 (Ω-sec)
Rff= 120% • (23,97-5,52)= 22,14 (Ω-pri) = 8,86 (Ω-sec)
Rft= 120% • (119,85-5,52)= 137,19 (Ω-pri) = 54,88 (Ω-sec)
Retardo = ∞ segundos

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
58-285

D60 (21)
REACH= 120% • (23,97-16,01)= 9,55 (Ω-pri) = 3,82 (Ω-sec)
RGT BLD = 120% • (23,97-5,52)= 22,14 (Ω-pri) = 8,86 (Ω-sec)
LFT BLD = 120% • (23,97-5,52)= 22,14 (Ω-pri) = 8,86 (Ω-sec)
Retardo = 65,535 segundos

D60 (21N)
REACH= 120% • (23,97-16,01)= 9,55 (Ω-pri) = 3,82 (Ω-sec)
RGT BLD = 120% • (119,85-5,52)= 137,19 (Ω-pri) = 54,88 (Ω-sec)
LFT BLD = 120% • (119,85-5,52)= 137,19 (Ω-pri) = 54,88 (Ω-sec)
Retardo = 65,535 segundos

Zona 4 (7SA612) y 3 (D60) – Forward

7SA612 (21/21N)
Xf= 100% • 24,70 + 110% • 43,70 = 72,77 (Ω-pri) = 29,11 (Ω-sec)
Rff= Xf = 72,77 (Ω-pri) = 29,11 (Ω-sec)
Rft= 3 • Xf = 218,32 (Ω-pri) = 87,33 (Ω-sec)
Retardo = 1,20 segundos

D60 (21)
REACH= 100% • 24,70 + 110% • 43,70 = 72,77 (Ω-pri) = 29,11 (Ω-sec)
RGT BLD = REACH= 72,77 (Ω-pri) = 29,11 (Ω-sec)
LFT BLD = REACH= 72,77 (Ω-pri) = 29,11 (Ω-sec)
Retardo = 1,20 segundos

D60 (21N)
REACH= 100% • 24,70 + 110% • 43,70 = 72,77 (Ω-pri) = 29,11 (Ω-sec)
RGT BLD = 3 • REACH= 218,32 (Ω-pri) = 87,33 (Ω-sec)
LFT BLD = 3 • REACH= 218,32 (Ω-pri) = 87,33 (Ω-sec)
Retardo = 1,20 segundos

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
59-285

Zona 5 (7SA612) – Non Directional

7SA612 (21/21N)
Xf= 120% • 72,77 = 87,33 (Ω-pri) = 34,93 (Ω-sec)
Rff= 120% • 72,77 = 87,33 (Ω-pri) = 34,93 (Ω-sec)
Rft= 120% • 218,32 = 261,98 (Ω-pri) = 104,79 (Ω-sec)
Xr= 120% • 72,77 = 87,33 (Ω-pri) = 34,93 (Ω-sec)
Delay = oo segundos

5.4.2 Lógica de Teleprotección

Se habilitará la lógica de Subalcance permisivo (PUTT) esperando la señal de aceleración desde el


paño J7 de la S/E Ciruelos

5.4.3 Función direccional de corriente residual (67N)

Esta función se habilita de forma permanente para detectar y despejar fallas a tierra de alta
resistencia. Se habilita con lógica de comparación direccional.

Se recomienda que tenga una etapa de operación de tiempo inverso, cuyo umbral de operación se
ajusta igual al 20% la corriente nominal del transformador de corriente asociado al paño Ciruelos C2
de la S/E Valdivia.

7SA612
3110 Operating mode : Forward
3111 Pickup : 2,63 A
3112 Time Delay : 0,3 seg
3140 Operating Mode : Forward
3141 Pickup : 0,2 A-sec
3143 Time Dial : 0,60
3151 IEC Curve : Very Inverse

D60
NEUTRAL TOC1 Function : Enabled
NEUTRAL TOC1 Pickup : 0,2 pu

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
60-285

NEUTRAL TOC1 Curve : IEC Curve B


NEUTRAL TOC1 TD Multiplier : 0,60
NEUTRAL IOC1 Function : Enabled
NEUTRAL IOC1 Pickup : 2,63 pu
NEUTRAL IOC1 Delay : 0,30

5.4.4 Función de Sobrecorriente de Emergencia (51B/51NB)

Para la función de sobrecorriente de fases (51B) se mantienen ajustes actuales

Ahora, para la función de sobrecorriente residual (51NB), se mantienen ajustes para protección
7SA612 y para protección D60 se modifican debido al cambio de ajustes propuestos para la función
de sobrecorriente residual direccional (67N)

Bajo esto los ajustes son los que se muestran a continuación

7SA612
2601 Operating Mode : ON: Only Active with Loss of VT
2610 50-B1 Pickup : 0,48 A-sec
2611 50-B1 Delay : 0,60
2612 50N-B1 Pickup : 0,45 A-sec
2613 50N-B1 Delay : 0,6
2640 51-B Pickup : 1,00 A-sec
2642 51-B Time Dial : 0,05
2646 51-B Add. Time Delay 0,00
2650 51N-B Pickup : 0,60 A-sec
2652 51N-B Time Dial : 0,05
2656 51N-B Add. Time Delay 0,00
2660 IEC Curve : Normal Inverse.

D60
PHASE TOC1 Function : Enabled
PHASE TOC1 Pickup : 1,00 pu
PHASE TOC1 Curve : IEC Curve A
PHASE TOC1 TD Multiplier : 0,05
PHASE TOC1 Block A : Potencial-Ok On
PHASE TOC1 Block B : Potencial-Ok On
PHASE TOC1 Block C : Potencial-Ok On

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
61-285

NEUTRAL TOC1 Function : Enabled


NEUTRAL TOC1 Pickup : 0,2 pu
NEUTRAL TOC1 Curve : IEC Curve B
NEUTRAL TOC1 TD Multiplier : 0,60
NEUTRAL IOC1 Function : Enabled
NEUTRAL IOC1 Pickup : 2,63 pu
NEUTRAL IOC1 Delay : 0,30

5.4.5 Función de Bloqueo por Oscilación de Potencia

5.4.5.1 Protección 7SA612

No se modifican ajustes actuales

5.4.5.2 Protección GE D60

Esta función se habilita para evitar que la función de distancia opere de forma indeseada ante
oscilaciones de este tipo.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
62-285

Figura 5.4: Característica de detección de oscilación de potencia protección D60

En la Figura 5.4 se muestra la característica de detección de la función de bloqueo por oscilación de


potencia de la protección D60.

A continuación se presenta los ajustes para la función de oscilación de potencia

Donde, Zcarga: Impedancia de Carga

[ ] [ ]

Entonces,

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
63-285

5.4.6 Reconexión (79)

No se modifican ajustes actuales

5.4.7 Función de Verificación de Sincronismo (25)

No se modifican ajustes actuales

5.4.8 Función de Falla de Interruptor (50BF)

No se modifican ajustes actuales

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
64-285

5.5 Protección de falla de interruptor 7SJ80

5.5.1 Paño Seccionador de Barra JS

Para determinar los ajustes para esta función se calculan las corrientes de cortocircuitos minimas
que ve esta protección, al existir fallas en una de las 2 barras de la S/E Ciruelos Los resultados
obtenidos son los que se muestran a continuación

Tabla N° 5.5 – Corrientes de Cortocircuitos Barra 1 S/E Ciruelos


Falla Barra 2 Ciruelos
Trifasica [kA] Bifasica Aislada [kA] Bifasica a tierra [kA] Monofasica [kA]
IkssA 2,105 0,08 0,16 1,83
IkssB 2,105 1,79 1,89 0,22
IkssC 2,105 1,87 2,09 0,08
3I0 0 0 1,43 1,54

Tabla N° 5.6 – Corrientes de Cortocircuitos línea 220 Barra 2 S/E Ciruelos


Falla Barra 2 Ciruelos
Trifasica [kA] Bifasica Aislada [kA] Bifasica a tierra [kA] Monofasica [kA]
IkssA 2,843 0,08 0,16 2,8
IkssB 2,843 2,52 2,69 0,22
IkssC 2,843 2,44 2,96 0,08
3I0 0 0 2,89 3,1

La corriente mínima de operación para fallas entre fases se ajustará al 80% de la corriente mínima
mostrada entre la Tabla N° 5.5 y la Tabla N° 5.6

Pickup 50BF = 0,8 * 1.790 (A-pri) = 1.432 (A - pri) = 4,77 (A - sec)

La corriente mínima de operación para fallas a tierra tendrá un valor igual al 30% de la corriente
nominal de los trasformadores de corriente asociados al interruptor. Ajuste que es menor al 80% de
corriente mínima de cortocircuito

Pickup 50BF = = 450 (A - pri) = 1,50 (A - sec)

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
65-285

La etapa de orden de apertura dará orden de disparo al sistema de protección diferencial de barra,
para que a través de ella se emita la orden de apertura a los interruptores correspondientes a la
barra.

Para ésta etapa se recomienda un tiempo de retardo de la operación igual a 0,20 segundos, tiempo
suficiente para la extinción del arco en el interruptor. A continuación se muestran los ajustes para
esta función

7001 50BF Breaker Failure Protection ON


7005 TRIP-Timer 0,2 seg
7006 50BF Pickup Current Threshold 4,77 A-sec
7007 50BF Pickup Earth Current Threshold 1,5 A-sec

5.5.2 Paño Acoplador de Barra JR

La corriente mínima de operación para fallas entre fases (50BF Pickup), tendra igual ajuste que para
las protecciones de las líneas, puesto que este paño reemplaza al de alguna línea por lo que su
ajuste debe ser el mismo. Bajo esto tendrá el minimo ajuste propuesto para esta función entre los
paños J6 y J7 de la S/E Ciruelos

Pickup 50BF = 0,8 * 570 (A-pri) = 456 (A - pri) = 2,85 (A - sec)

La corriente mínima de operación para fallas a tierra (50BF Pickup IE>) tendrá un valor igual al 30%
de la corriente nominal del trasformador de corriente.

Pickup 50BF = = 240 (A - pri) = 1,50 (A - sec)

La etapa de orden de apertura dará orden de disparo al sistema de protección diferencial de barra,
para que a través de ella se emita la orden de apertura a los interruptores correspondientes a la
barra.

Para ésta etapa se recomienda un tiempo de retardo de la operación igual a 0,20 segundos, tiempo
suficiente para la extinción del arco en el interruptor. A continuación se muestran los ajustes para
esta función

7001 50BF Breaker Failure Protection ON


7005 TRIP-Timer 0,2 seg
7006 50BF Pickup Current Threshold 2,85 A-sec
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
66-285

7007 50BF Pickup Earth Current Threshold 1,5 A-sec

5.6 Línea 220 kV Cautín – Tap Off Rio Tolten - Ciruelos

Debido al seccionamiento de la línea 220 kV Cautín – Valdivia, se produce que los alcances de la
actual línea 220 kV Cautín – Tap Off Rio Tolten – Ciruelos se puedan ver alterados por el efecto del
acoplamiento mutuo de secuencia cero. Bajo esto se realizo un análisis que entregó como resultado
las siguientes impedancias vistas desde cada extremo de la línea.

Impedancia Vista por Extremo Cautín


80

70
67,59
60 Cto paralelo en servicio
Cto paralelo fuera de servicio
Impedancia [Ω-pri]

50 Cto paralelo a tierra 50,06

40 38,35
30

20

10

0
0 20 40 60 80 100 120
Longitud [km]

Figura 5.5: Impedancia vista desde extremo Cautín, línea 2x220 kV Cautín – Tap Off Rio Tolten – Ciruelos

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
67-285

Impedancia Vista por Extremo Ciruelos


80
72,67
70

60
Impedancia [Ω-pri]

51,76 Cto paralelo en servicio


50
Cto paralelo fuera de servicio
40 Cto paralelo a tierra
37,7
30

20

10

0
0 20 40 60 80 100 120
Longitud [km]

Figura 5.6: Impedancia vista desde extremo Ciruelos, línea 2x220 kV Cautín – Tap Off Rio Tolten – Ciruelos

Con el fin que se cumpla la teleprotección de la línea, la segunda zona debe estar ajustada al 120%
de la impedancia máxima vista por el extremo remoto. Según este criterio, se recomienda lo
siguiente:

5.6.1 S/E Cautín paño Ciruelos C1

El ajuste actual de zona 2 de las protecciones ubicadas en el extremo Cautín (7SA612 y D60) se
encuentra ajustado en 38,5 Ω-sec (64,16 Ω-pri), ajuste inferior a la impedancia máxima vista por
este extremo (67,13 Ω-pri), por lo que se recomienda modificar el alcance de esta zona al 120% de
la impedancia máxima vista por este extremo. Además se modifica el tiempo de operación para darle
respaldo a la línea paralela en caso de perder la comunicación. Según esto el alcance nuevo seria el
siguiente

7SA612
N° Parámetro Ajustes Actuales Ajustes Propuestos
1311 Operating mode Z2 Forward Forward
1312 R(Z2), Resistance for ph-ph-faults 38,5 Ohm 38,5 Ohm
1313 X(Z2), Reactance 38,5 Ohm 48,3 Ohm

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
68-285

7SA612
N° Parámetro Ajustes Actuales Ajustes Propuestos
1314 RG(Z2), Resistance for ph-gnd faults 77 Ohm 77 Ohm
1315 T2-1phase, delay for single phase faults 0,4 seg 0,6 seg
1316 T2multi-ph, delay for multi phase faults 0,4 seg 0,6 seg

D60
21 (Z2) 21N (Z2)
Parámetro
Actuales Propuestos Actuales Propuestos
Direction Forward Forward Forward Forqard
Shape Quad Quad Quad Quad
Reach 38,5 48,3 38,5 48,3
RCA 90 90 90 90
Delay 0,40 0,60 0,40 0,60
Quad Right Blinder 38,5 38,5 77,00 77,00
Quad Left Blinder 38,5 38,5 77,00 77,00

5.6.2 S/E Ciruelos paño Cautín C1

Se propone modificar el ajuste de tiempo de operación de la segunda zona. El ajuste propuesto es


0,6 segundos para darle respaldo a las protecciones de la línea paralela en caso de perder la
comunicación y para darle respaldo a las protecciones que se encuentran en S/E Cautín paño
Temuco C1 y C2. Los nuevos ajustes son los que se mencionan a continuación

7SA612
N° Parámetro Ajustes Actuales Ajustes Propuestos
1311 Operating mode Z2 Forward Forward
1312 R(Z2), Resistance for ph-ph-faults 5,300 Ohm 5,300 Ohm
1313 X(Z2), Reactance 5,300 Ohm 5,300 Ohm
1314 RG(Z2), Resistance for ph-gnd faults 15,000 Ohm 15,000 Ohm
1315 T2-1phase, delay for single phase faults 0,40 seg 0,60 seg
1316 T2multi-ph, delay for multi phase faults 0,40 seg 0,60 seg

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
69-285

D60
21 (Z2) 21N (Z2)
Parámetro
Actuales Propuestos Actuales Propuestos
Direction Forward Forward Forward Forward
Shape Mho Mho Mho Mho
Reach 5,30 5,30 5,30 5,30
RCA 76 76 76 76
Delay 0,40 0,60 0,40 0,60
Quad Right Blinder 0,02 0,02 15,00 15,00
Quad Left Blinder 0,02 0,02 15,00 15,00

5.7 Línea 220 kV Ciruelos – Valdivia C1

Se analiza el efecto de acoplamiento mutuo de secuencia cero, de modo de determinar posibles


modificaciones en los ajustes actuales de la línea. Realizado el análisis se obtuvo lo siguiente

25
Impedancia Vista por Extremo Ciruelos

20 19,45
Impedancia [Ω-pri]

Cto paralelo en servicio


15 15,64
Cto paralelo fuera de servicio
Cto paralelo a tierra 12,82

10

0
0 5 10 15 20 25 30 35 40 45
Longitud [km]

Figura 5.7: Impedancia vista desde extremo Ciruelos, línea 2x220 Ciruelos – Valdivia C1

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
70-285

Impedancia Vista por Extremo Valdivia


25
22,74

20
Impedancia [Ω-pri]

15,96
15

11,12
10 Cto paralelo en servicio
Cto paralelo fuera de servicio
Cto paralelo a tierra
5

0
0 5 10 15 20 25 30 35 40 45
Longitud [km]

Figura 5.8: Impedancia vista desde extremo Valdivia, línea 2x220 Ciruelos – Valdivia C1

Con estos resultados se proponen las siguientes modificaciones

5.7.1 S/E Ciruelos paño Valdivia C1

Se propone modificar los alcances de zona 1 y de zona 2, debido a que con los ajustes actuales la
zona 1 tiene un alcance muy cercano al extremo remoto y la zona 2 tiene un sobrealcance muy
elevado. Los criterios para modificar los alcances son los siguientes

La primera zona (Z1) considera un alcance del 85% de la menor reactancia de línea 2x220kV
Ciruelos – Valdivia C1 considerando acoplamiento mutuo de secuencia cero. Tiempo de operación
instantaneo

La Segunda zona (Z2) considera un alcance del 120% de la mayor reactancia de la línea 2x220kV
Ciruelos – Valdivia C2 considerando acoplamiento mutuo de secuencia cero. El tiempo de operación
se ajusta en 0,3 segundos para darle respaldo a las protecciones de la línea paralela en caso de
perder la comunicación.

Con esto los nuevos ajustes son los que se muestran a continuación

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
71-285

7SA612
N° Parámetro Ajustes Actuales Ajustes Propuestos
1301 Operating mode Z1 Forward Forward
1302 R(Z1), Resistance for ph-ph-faults 0,74 Ohm 0,74 Ohm
1303 X(Z1), Reactance 0,74 Ohm 0,64 Ohm
1304 RG(Z1), Resistance for ph-gnd faults 2,96 Ohm 2,96 Ohm
1305 T1-1phase, delay for single phase faults 0,0 seg 0,0 seg
1306 T1multi-ph, delay for multi phase faults 0,0 seg 0,0 seg
1311 Operating mode Z2 Forward Forward
1312 R(Z2), Resistance for ph-ph-faults 2,05 Ohm 2,05 Ohm
1313 X(Z2), Reactance 2,05 Ohm 1,38 Ohm
1314 RG(Z2), Resistance for ph-gnd faults 4,10 Ohm 4,10 Ohm
1315 T2-1phase, delay for single phase faults 0,4 seg 0,3 seg
1316 T2multi-ph, delay for multi phase faults 0,4 seg 0,3 seg

D60
21 21N
Parámetro
Actuales Propuestos Actuales Propuestos
Z1: Direction Forward Forward Forward Forward
Z1: Shape Mho Mho Quad Quad
Z1: Reach 0,78 0,64 0,78 0,64
Z1: RCA 76 76 76 76
Z1: Delay 0,0 0,0 0,0 0,0
Z1: Quad Right Blinder 0,02 0,02 2,96 2,96
Z1: Quad Left Blinder 0,02 0,02 2,96 2,96
Z2: Direction Forward Forward Forward Forward
Z2: Shape Mho Mho Quad Quad
Z2: Reach 2,12 1,38 2,49 1,38
Z2: RCA 76 76 76 76
Z2: Delay 0,40 0,30 0,40 0,30
Z2: Quad Right Blinder 0,02 0,02 4,10 4,10
Z2: Quad Left Blinder 0,02 0,02 4,10 4,10

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
72-285

Además, para la situación que se pierda la comunicación entre los extremos de la línea y con el fin
de tener un correcto orden de operación de las protecciones se recomienda habilitar para la función
de sobrecorriente direccional residual (67N) una etapa de tiempo definido con tiempo de operación
de 0,3 segundos. Con esto los ajustes propuestos serian los siguientes para cada protección

7SA612
N° Parámetro Ajustes Actuales Ajustes Propuestos
3110 Operating mode Inactive Forward
3111 Pickup 20,00 A 18,35 A
3112 Time Delay 0,3 seg 0,3 seg
3140 Operating Mode Forward Forward
3141 Pickup 0,7 A-sec 0,7 A-sec
3143 Time Dial 0,8 0,8
3151 IEC Curve Very Inverse Very Inverse

D60
Parámetro Ajustes Actuales Ajustes Propuestos
NEUTRAL TOC1 Function Enabled Enabled
NEUTRAL TOC1 Pickup 0,14 pu 0,14 pu
NEUTRAL TOC1 Curve IEC Curve B IEC Curve B
NEUTRAL TOC1 TD Multiplier 0,80 0,80
NEUTRAL IOC1 Function Disabled Enabled
NEUTRAL IOC1 Pickup -- 3,67 pu
NEUTRAL IOC1 Delay -- 0,30

Se habilita con lógica de comparación direccional.

5.7.2 S/E Valdivia paño Ciruelos C1

Se propone modificar los alcances de zona 1 y de zona 2, debido a que con los ajustes actuales la
zona 1 tiene un alcance muy cercano al extremo remoto y la zona 2 tiene un sobrealcance muy
elevado. Los criterios para modificar los alcances son los siguientes

La primera zona (Z1) considera un alcance del 85% de la menor reactancia de línea 2x220kV
Ciruelos – Valdivia C1 considerando acoplamiento mutuo de secuencia cero. Tiempo de operación
instantaneo

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
73-285

La Segunda zona (Z2) considera un alcance del 120% de la mayor reactancia de la línea 2x220kV
Ciruelos – Valdivia C2 considerando acoplamiento mutuo de secuencia cero. El tiempo de operación
se ajusta en 0,3 segundos para darle respaldo a las protecciones de la línea paralela al perder la
comunicación.

Con esto los nuevos ajustes son los que se muestran a continuación

7SA612
N° Parámetro Ajustes Actuales Ajustes Propuestos
1301 Operating mode Z1 Forward Forward
1302 R(Z1), Resistance for ph-ph-faults 5,04 Ohm 5,04 Ohm
1303 X(Z1), Reactance 5,04 Ohm 3,67 Ohm
1304 RG(Z1), Resistance for ph-gnd faults 12,60 Ohm 12,60 Ohm
1305 T1-1phase, delay for single phase faults 0,0 seg 0,0 seg
1306 T1multi-ph, delay for multi phase faults 0,0 seg 0,0 seg
1311 Operating mode Z2 Forward Forward
1312 R(Z2), Resistance for ph-ph-faults 16,74 Ohm 16,74 Ohm
1313 X(Z2), Reactance 16,74 Ohm 10,8 Ohm
1314 RG(Z2), Resistance for ph-gnd faults 16,74 Ohm 16,74 Ohm
1315 T2-1phase, delay for single phase faults 0,4 seg 0,3 seg
1316 T2multi-ph, delay for multi phase faults 0,4 seg 0,3 seg

P443
Parámetro Ajustes Actuales Ajustes Propuestos
Z1 Ph. Reach 12,95 9,19
Z1 Ph. Angle 76.00 76.00
R1 Ph. Resistive 25,20 25,20
Z2 Ph. Reach 43,10 27,01
Z2 Ph. Angle 76.00 76.00
R2 Ph. Resistive 83,70 83,70
Z1 Gnd. Reach 12,95 9,19
Z1 Gnd. Angle 76.00 76.00
R1 Gnd. Resistive 56,70 56,70
Z1 Gnd. Reach 43,10 27,01
Z1 Gnd. Angle 76.00 76.00
R1 Gnd. Resistive 75,3 75,3

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
74-285

P443
Parámetro Ajustes Actuales Ajustes Propuestos
tZ2 Ph. Delay 400.0 ms 300.0 ms
tZ2 Gnd. Delay 400.0 ms 300.0 ms

Además, para la situación que se pierda la comunicación entre los extremos de la línea y con el fin
de tener un correcto orden de operación de las protecciones se recomienda habilitar para la función
de sobrecorriente direccional residual (67N) una etapa de tiempo definido con tiempo de operación
de 0,3 segundos. Con esto los ajustes propuestos serian los siguientes para cada protección

7SA612
N° Parámetro Ajustes Actuales Ajustes Propuestos
3110 Operating mode Inactive Active
3111 Pickup 4,00 A 2,63 A
3112 Time Delay 0,3 seg 0,3 seg
3140 Operating Mode Forward Forward
3141 Pickup 0,58 A-sec 0,58 A-sec
3143 Time Dial 0,15 0,15
3151 IEC Curve Normal Inverse Normal Inverse

P443
Parámetro Ajustes Actuales Ajustes Propuestos
IN>2 Status Enabled Enabled
IN>2 Function IEC S Inverse IEC S Inverse
IN>2 Directional Directional Fwd Directional Fwd
IN>2 Current Set 460 A 460 A
IN>2 TMS 150e-3 150e-3
IN>3 Status Disabled Enabled
IN>3 Function -- Def Time
IN>3 Directional -- Directional Fwd
IN>3 Current Set -- 2100
IN>3 TMS -- 300e-3

Se habilita con lógica de comparación direccional.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
75-285

5.8 Linea 2x220 kV Mulchen – Cautin

Dado el seccionamiento se recomienda modificar el alcance de zona 3 en direccion hacia adelante,


de modo que solo tenga alcance hasta la subestación Ciruelos. De acuerdo a esto, el criterio de
ajuste es el siguiente.

La tercera zona (Z3) considera un alcance del 100% de la reactancia de la línea 2x220kV Mulchen –
Cautín mas el 110% de la reactancia de la línea 220kV Cautín – Ciruelos C2. El tiempo de operación
se mantiene en 1,2 segundos

Con esto los nuevos ajustes son los que se muestran a continuación

7SA612
N° Parámetro Ajustes Actuales Ajustes Propuestos
1321 Operating mode Z3 Forward Forward
1322 R(Z3), Resistance for ph-ph-faults 83,12 Ohm 83,12 Ohm
1323 X(Z3), Reactance 147,24 Ohm 87,57 Ohm
1324 RG(Z3), Resistance for ph-gnd faults 125 Ohm 125 Ohm
1325 T3 Delay 1,20 seg 1,20 seg

D60
21 21N
Parámetro
Actuales Propuestos Actuales Propuestos
Direction Forward Forward Forward Forqard
Shape Quad Quad Quad Quad
Reach 147,24 87,57 147,24 87,57
RCA 90 90 90 90
Delay 1,20 1,20 1,20 1,20
Quad Right Blinder 83,12 83,12 125 125
Quad Left Blinder 249,36 249,36 271,01 271,01

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
76-285

6. AJUSTES PROPUESTOS

En esta sección se presentan de forma resumida los principales ajustes recomendados para los
nuevos sistemas de protecciones a instalar en la S/E Ciruelos, como también para las protecciones
existentes en las S/E Cautín y Valdivia.

6.1 Línea 220kV Cautín – Ciruelos C2

6.1.1 S/E Ciruelos paño Cautín C2

6.1.1.1 Protección 7SA612

Equipos de Medida

Transformadores de medida Razón


TTCC: 800 A-pri 5 A-sec 160
TTPP: 230000/√3 V-pri 115/√3 V-sec 2000
Razón TC/TP 0,080

Función de Distancia (21/21N)

Parámetro Z1 Z1b Z2 Z3 Z4 Z5
Non
Operating Mode Forward Forward Forward Reverse Forward
Directional
Resistance for ph-ph faults
2,18 5,69 5,69 4,88 11,06 13,27
(Ω-sec)
Reactance (Ω-sec) 2,18 5,69 5,69 2,13 11,06 13,27
Resistance for ph-gnd faults
6,53 17,06 17,06 11,20 20,46 24,55
(Ω-sec)
Delay for single phase faults 0,00 0,00 0,60 oo 1,20 oo
Delay for multi phase faults 0,00 0,00 0,60 oo 1,20 oo

Función de Teleprotección

2101 85-21 Pilot Prot. for Distance prot. ON


3201 85-67N Pilot Prot. for Dir.Ground O/C ON
2103A Time for send signal prolongation 0,08

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
77-285

2109A Transient Block: Duration external flt. 0,03


2110A Transient Block: Blk.T. after ext. flt. 0,15

Función de Sobrecorriente Direccional Residual (67N)

3110 Operating Mode Forward


3111 Pickup 8,15 A
3112 Time Delay 0,3 seg
3113 Instantaneous Trip Via Pilot Prot./Bl Yes
3140 Operating Mode Forward
3141 Pickup 0,75 A-sec
3143 Time Dial 0,6
3148 Instantaneous Trip Via Pilot Prot./Bl Yes
3151 IEC Curve Very Inverse

Función de Sobrecorriente de Emergencia

2601 Operating Mode ON: Only Active with Loss of VT


2640 51-B Pickup 6,00 A-sec
2642 51-B Time Dial 0,05
2646 51-B Add. Time Delay 0,00
2650 51N-B Pickup 0,75 A-sec
2652 51N-B Time Dial 0,6
2656 51N-B Add. Time Delay 0,00
2660 IEC Curve Normal Inverse.

Función de Reconexión

3450 Start of AR allowed in this cycle Yes


3451 Action time 0,5 seg
3457 Dead time after 3pole trip 0,5 seg
3458 Dead time after evolving fault 1,2 seg

Función de Verificación de Sincronismo

3510 Operating mode with AR without consideration of 52 closing time

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
78-285

3511 Maximum voltage difference 6,4 V


3512 Maximum frequency difference 0,2 Hz
3513 Maximum angle difference 30

Función de Falla Fusible

2910 Fuse Failure Monitor ON


2911A Minimun Voltage Threshold V> 22 V
2912A Maximum Current Threshold I< 1,1 A
2913A Maximum Voltage Threshold V< 5V
2914A Differential Current Threshold 0,5 A

Función de Falla de Interruptor

3901 50BF Breaker Failure Protection ON


3902 I>BF 2,85 A-sec
3904 T1-1pole 0,01 seg
3905 T1-3pole 0,01 seg
3906 T2 0,2 seg
3912 3Io>BF 1,5 A-sec

6.1.1.2 Protección REL670

Equipos de Medida

Transformadores de medida Razón


TTCC: 800 A-pri 5 A-sec 160
TTPP: 230000/√3 V-pri 115/√3 V-sec 2000
Razón TC/TP 0,080

Función de Distancia (21/21N)

Parámetro Z1 Z2 Z3 Z4
OperationDir Forward Forward Forward Reverse
X1 (Ω/pri) 27,19 71,06 138,23 26,62
R1 (Ω/pri) 11,14 20,39 29,25 7,99
X0 (Ω/pri) 92,75 242,42 554,00 35,78
R0 (Ω/pri) 22,46 41,11 85,20 7,29

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
79-285

Parámetro Z1 Z2 Z3 Z4
RFPP (Ω/l) 54,38 142,13 276,45 121,96
RFPG (Ω/l) 81,57 213,19 255,72 140,04
tPP 0,00 0,60 1,20 60,00
tPG 0,00 0,60 1,20 60,00

Phase Selection (FDPSPDIS)

RLdFwd 128,75
RldRev 128,75
LdAngle 30°
X1 199,05
X0 797,76
RFltFwdPP 331,74
RFltRevPP 146,35
RFltFwdPG 306,86
RFltRevPG 168,05

Directional Impedance (ZDRDIR)

ArgNegRes 115
ArgDir 15

Función de Teleprotección

Función Distancia
Operation Enabled
SchemeType Permissive UR
tCoord 0,00
tSendMin 0,1
Unblock Disabled
tSecurity 0,035
CurrRev Enabled
tPickUpRev 0,15
tDelayRev 0,03
WEI Off
tPickUpWEI 0,01

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
80-285

Upp< 70
Upn< 35

Sobrecorriente Residual
Operation Enabled
SchemeType Permissive UR
tCoord 0,00
tSendMin 0,1
Unblock Disabled
tSecurity 0,035
CurrRev Enabled
tPickUpRev 0,15
tDelayRev 0,03
WEI Off
tPickUpWEI 0,01
3VOPU 25

Función de Sobrecorriente Direccional Residual (67N)

DirMode1 Forward
Characteristic1 IEC Def. Time
IN1> 163 (%IB)
t1 0,30
TD1 0,00
DirMode2 Forward
Characteristic2 IEC Very Inverse
IN2> 15 (%IB)
t2 0,00
TD2 0,60

Función de Sobrecorriente de Emergencia

Fase
DirModeSel1 Non Directional
Characterist1 IEC Norm. Inv.
Pickup1 120 (%IB)
t1 0,00
TD1 0,05
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
81-285

Residual
DirModeSel3 Non Directional
Characterist3 IEC Very Inverse
Pickup3 15 (%IB)
t3 0,00
TD3 0,60

Función de Bloqueo de Oscilacion de Potencia

X1InFw 158,96
R1LIn 33,64
R1FInFw 158,96
X1InRv 158,96
R1FInRv 158,96
RLdOutFw 423,89
LdAngle 30°
RLdOutRv 423,89
kLdRFw 0,75
kLdRRv 0,75

Función de Reconexión

Operation Enabled
AR Mode 3 phase
t1 1Ph 0,5 s
t1 3Ph 0,5 s
t1 3PhHS 0,5 s
tReclaim 15,0 s
tSync 1,0 s
tTrip 0,2 s
tPulse 0,2 s
NoOfShots 1
CBReady Type CO

Función de Verificación de Sincronismo

Operation Enabled
VHigh Bus Synch 80 %UB
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
82-285

VHigh Bus Synch 80 %UB


VDiff Synch 10 %UB
Freq Diff Min 0,01 Hz
Freq Diff Max 0,2 Hz
tBreaker 0,08 s
tClose Pulse 0,2
Operation SC Enabled
UHigh Bus SC 80 %UB
UHigh Bus SC 80 %UB
UDiffSC 15 %UB
Freq Diff A 0,2 Hz
Freq Diff M 0,2 Hz
Phase Diff A 30°
Phase Diff A 30°
tSCA 0,1 s
tSCM 0,1 s

Función de Falla Fusible

OpModeSel V0I0 OR V2I2


3V0PU 60
3I0PU 20
3V2PU 60
3I2PU 20
OpDVDI Enabled
DVPU 70
DIPU 15
VPPU 70
IPPU 10
SealIn Enabled
VSealInPU 70
IDLDPU 20
VDLDPU 70

Función de Falla de Interruptor

Pickup_PH 57% IB
Pickup_N 30% IB
t1 0,01 seg
T2 0,2 seg

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
83-285

6.1.2 S/E Cautín paño Ciruelos C2

6.1.2.1 Protección 7SA612

Equipos de Medida

Transformadores de medida Razón


TTCC 1200 A-pri 1 A-sec 1200
TTPP 230000/√3 V-pri 115/√3 V-sec 2000
Razón TC/TP 0,600

Función de Distancia (21/21N)

Z1 Z1b Z2
Parámetro
Actuales Propuestos Actuales Propuestos Actuales Propuestos
Operating Mode Forward Forward Forward Forward Forward Forward
Resistance for ph-ph faults (Ω-sec) 29,16 17,36 54,00 39,53 54,00 39,53
Reactance (Ω-sec) 29,16 17,36 54,00 39,53 54,00 39,53
Resistance for ph-gnd faults (Ω-sec) 29,16 52,09 54,00 79,06 54,00 79,06
Delay for single phase faults 0,00 0,00 0,00 0,00 0,40 0,60
Delay for multi phase faults 0,00 0,00 0,00 0,00 0,40 0,60

Z3 Z4 Z5
Parámetro
Actuales Propuestos Actuales Propuestos Actuales Propuestos
Operating Mode Reverse Reverse Forward Forward Non Non
Resistance for ph-ph faults (Ω-sec) 0,12 40,32 107,8 43,51 108 52,21
Reactance (Ω-sec) 0,12 19,70 107,8 43,51 108 52,21
Resistance for ph-gnd faults (Ω-sec) 0,12 142,65 107,8 87,01 108 171,18
Delay for single phase faults 3,30 oo 3,20 1,20 oo oo
Delay for multi phase faults 3,30 oo 3,20 1,20 oo oo

Teleprotección

No. Parametro Ajuste Actual Ajuste Propuesto


121 85-21 Pilot Protection for distance prot. PUTT PUTT
Directional
132 85-67N Pilot Protection Earth O/C Disabled
Comparison Pickup

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
84-285

2101 85-21 Pilot Prot. for Distance prot. ON ON


2102 Type of Line Two Terminal Two Terminal
2103A Time for send signal prolongation 0,10 Seg 0,10 Seg
3201 85-67N Pilot Prot. for Dir.Ground O/C OFF ON
3202 Line Configuration -- Two Terminal
3203A Time for send signal prolongation -- 0,10 Seg
3209A Transient Block.: Duration external flt. -- 0,03 Seg
3210A Transient Block.: Blk.T. after ext. flt. -- 0,15 Seg
3212A EF transient block by DIS -- YES

Función de Sobrecorriente Direccional Residual

N° Parámetro Ajustes Actuales Ajustes Propuestos


3110 Operating Mode Forward Forward
3111 Pickup 0,89 A 1,17 A
3112 Time Delay oo 0,3 seg
3113 Instantaneous Trip Via Pilot Prot./Bl No Yes
3120 Operating Mode Forward Inactive
3121 Pickup 0,1 A 0,1 A
3122 Time Delay 4,00 4,00
3123 Instantaneous Trip Via Pilot Prot./Bl No No
3140 Operating Mode Forward Forward
3141 Pickup 0,2 A 0,1 A-sec
3143 Time Dial 0,18 0,28
3148 Instantaneous Trip Via Pilot Prot./Bl No Yes
3151 IEC Curve Normal Inverse Normal Inverse

Load Encroachment

No. Parametro Ajuste Actual Ajuste Propuesto


1241 R load, minimum Load Impedance (ph-g) oo 51,44
1242 PHI load, maximum Load Angle (ph-g) 30° 30°
1243 R load, minimum Load Impedance (ph-ph) oo 51,44
1244 PHI load, maximum Load Angle (ph-ph) 30° 30°

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
85-285

6.1.2.2 Protección D60

Equipos de Medida

Transformadores de medida Razón


TTCC 1200 A-pri 1 A-sec 1200
TTPP 230000/√3 V-pri 115/√3 V-sec 2000
Razón TC/TP 0,600

Función de Distancia (21)

Z1 Z2
Parámetro
Actuales Propuestos Actuales Propuestos
Direction Forward Forward Forward Forward
Shape Quad Quad Quad Quad
Reach 29,16 17,36 54,00 39,53
RCA 90 90 90 90
Delay 0,00 0,00 0,40 0,60
Quad Right Blinder 29,16 17,36 54,00 39,53
Quad Left Blinder 29,16 17,36 54,00 39,53

Z3 Z4
Parámetro
Actuales Propuestos Actuales Propuestos
Direction Forward Forward Reverse Reverse
Shape Quad Quad Quad Quad
Reach 107,80 43,51 0,12 19,70
RCA 90 90 90 90
Delay 3,20 1,20 3,30 65,535
Quad Right Blinder 107,80 43,51 0,12 40,32
Quad Left Blinder 107,80 43,51 0,12 40,32

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
86-285

Función de Distancia (21N)

Z1 Z2
Parámetro
Actuales Propuestos Actuales Propuestos
Direction Forward Forward Forward Forward
Shape Quad Quad Quad Quad
Reach 29,16 17,36 54,00 39,53
RCA 90 90 90 90
Delay 0,00 0,00 0,40 0,60
Quad Right Blinder 29,16 52,09 54,00 79,06
Quad Left Blinder 29,16 52,09 54,00 79,06

Z3 Z4
Parámetro
Actuales Propuestos Actuales Propuestos
Direction Forward Forward Reverse Reverse
Shape Quad Quad Quad Quad
Reach 107,80 43,51 0,12 19,70
RCA 90 90 90 90
Delay 3,20 1,20 3,30 65,535
Quad Right Blinder 107,80 87,01 0,12 142,65
Quad Left Blinder 107,80 87,01 0,12 142,65

Teleprotección

PUTT:
Se mantienen ajustes actuales.

85C:
Se debe impelmentar lógica de comparación direccional (en el caso de la protección GE D60 se
debe impelmentar en FlexLogic).

Función de Sobrecorriente de Fase

Parámetro Ajuste Actual Ajuste Propuesto


PHASE TOC1 Function Enabled Enabled

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
87-285

PHASE TOC1 Pickup 0,6 pu 0,6 pu


PHASE TOC1 Curve IEC Curve A IEC Curve A
PHASE TOC1 TD Multiplier 0,05 0,11

Función de Sobrecorriente Residual

Parámetro Ajuste Actual Ajuste Propuesto


NEUTRAL TOC1 Function Enabled Enabled
NEUTRAL TOC1 Pickup 0,2 pu 0,1 pu
NEUTRAL TOC1 Curve IEC Curve A IEC Curve A
NEUTRAL TOC1 TD Multiplier 0,17 0,28
NEUTRAL IOC1 Function Enabled Enabled
NEUTRAL IOC1 Pickup 0,1 pu 1,17 pu
NEUTRAL IOC1 Delay 4,00 0,30
NEUTRAL DIR OC1 Forward Pickup 0,2 pu 0,1 pu
NEUTRAL DIR OC1 Reverse Pickup 0,2 pu 0,1 pu

Función de Bloqueo por Oscilacion de Potencia

Parámetro Ajuste Actual Ajuste Propuesto


Function Enabled Enabled
Shape Quad Shape Quad Shape
Mode Two Step Two Step
Fwd Reach 148,45 52,21
Quad Fwd Out 150,45 145,82
Fwd RCA 73° 73°
Rev Reach 40,2 52,21
Quad Rev Out 42,2 145,82
Rev RCA 90° 90°
Outer Limit Angle 120° 120°
Inner Limit Angle 73° 73°
Outer Rgt Bld 119,89 145,82
Outer Lft Bld 99,36 145,82
Inner Rgt Bld 117,89 52,21
Inner Lft Bld 97,36 52,21

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
88-285

Función Load Encroachment

Parámetro Ajuste Actual Ajuste Propuesto


Function Disabled Enabled
Source -- Linea (SRC 1)
Min Volt -- 0.25 pu
Reach -- 51,44
Angle -- 30°
PKP Delay -- 0.00 s
Rst Delay -- 0.00 s
Block -- BLK 21-PS/TP On (VO9)
Target -- Latched
Events -- Enabled

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
89-285

6.2 Línea 220 kV Ciruelos – Valdivia C2

6.2.1 S/E Ciruelos paño Valdivia C2

6.2.1.1 Protección 7SA612

Equipos de Medida

Transformadores de medida Razón


TTCC: 800 A-pri 5 A-sec 160
TTPP: 230000/√3 V-pri 115/√3 V-sec 2000
Razón TC/TP 0,080

Función de Distancia (21/21N)

Parámetro Z1 Z1b Z2 Z3 Z4 Z5
Operating Mode Forward Forward Forward Reverse Forward Non
Resistance for ph-ph faults (Ω-
0,89 1,92 1,92 2,32 5,46 6,55
sec)
Reactance (Ω-sec) 0,89 1,92 1,92 1,31 5,46 6,55
Resistance for ph-gnd faults (Ω-
3,58 9,59 9,59 10,85 16,38 19,66
sec)
Delay for single phase faults 0,00 0,00 0,30 oo 1,20 oo
Delay for multi phase faults 0,00 0,00 0,30 oo 1,20 oo

Función de Teleprotección

2101 85-21 Pilot Prot. for Distance prot. ON


3201 85-67N Pilot Prot. for Dir.Ground O/C ON
2103A Time for send signal prolongation 0,08
2109A Transient Block: Duration external flt. 0,03
2110A Transient Block: Blk.T. after ext. flt. 0,15

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
90-285

Función de Sobrecorriente Direccional Residual (67N)

3110 Operating Mode Forward


3111 Pickup 13,15 A
3112 Time Delay 0,3 seg
3113 Instantaneous Trip Via Pilot Prot./Bl Yes
3140 Operating Mode Forward
3141 Pickup 1,0 A-sec
3143 Time Dial 0,27
3148 Instantaneous Trip Via Pilot Prot./Bl Yes
3151 IEC Curve Normal Inverse

Función de Sobrecorriente de Emergencia

2601 Operating Mode ON: Only Active with Loss of VT


2640 51-B Pickup 6,0 A-sec
2642 51-B Time Dial 0,07
2646 51-B Add. Time Delay 0,00
2650 51N-B Pickup 1,0 A-sec
2652 51N-B Time Dial 0,27
2656 51N-B Add. Time Delay 0,00
2660 IEC Curve Normal Inverse.

Función de Reconexión

3450 Start of AR allowed in this cycle Yes


3451 Action time 0,4 seg
3457 Dead time after 3pole trip 0,4 seg
3458 Dead time after evolving fault 1,2 seg

Función de Verificación de Sincronismo

without consideration of 52 closing


3510 Operating mode with AR
time
3511 Maximum voltage difference 6,4 V
3512 Maximum frequency difference 0,2 Hz
3513 Maximum angle difference 30

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
91-285

Función Falla Fusible

2910 Fuse Failure Monitor ON


2911A Minimun Voltage Threshold V> 22 V
2912A Maximum Current Threshold I< 2A
2913A Maximum Voltage Threshold V< 5V
2914A Differential Current Threshold 0,5 A

Función de Falla de Interruptor

3901 50BF Breaker Failure Protection ON


3902 I>BF 5,65 A-sec
3904 T1-1pole 0,01 seg
3905 T1-3pole 0,01 seg
3906 T2 0,2 seg
3912 3Io>BF 1,5 A-sec

6.2.1.2 Protección REL670

Equipos de Medida

Transformadores de medida Razón


TTCC: 800 A-pri 5 A-sec 160
TTPP: 230000/√3 V-pri 115/√3 V-sec 2000
Razón TC/TP 0,080
Función de Distancia (21/21N)

Parámetro Z1 Z2 Z3 Z4
OperationDir Forward Forward Forward Reverse
X1 (Ω/pri) 11,18 23,97 68,25 16,37
R1 (Ω/pri) 3,87 8,16 19,00 3,42
X0 (Ω/pri) 38,11 81,70 234,39 13,09
R0 (Ω/pri) 7,86 16,58 43,38 2,69
RFPP (Ω/l) 22,36 47,94 136,51 57,90
RFPG (Ω/l) 44,73 119,85 204,76 135,67
tPP 0,00 0,30 1,20 60,00
tPG 0,00 0,30 1,20 60,00

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
92-285

Phase Selection (FDPSPDIS)

RLdFwd 128,75
RldRev 128,75
LdAngle 30°
X1 98,29
X0 337,52
RFltFwdPP 163,81
RFltRevPP 69,35
RFltFwdPG 245,71
RFltRevPG 162,81

Directional Impedance (ZDRDIR)

ArgNegRes 115
ArgDir 15

Función de Teleprotección

Función Distancia
Operation Enabled
SchemeType Permissive UR
tCoord 0,00
tSendMin 0,1
Unblock Disabled
tSecurity 0,035
CurrRev Enabled
tPickUpRev 0,15
tDelayRev 0,03
WEI Off
tPickUpWEI 0,01
Upp< 70
Upn< 35

Sobrecorriente Residual
Operation Enabled
SchemeType Permissive UR

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
93-285

tCoord 0,00
tSendMin 0,1
Unblock Disabled
tSecurity 0,035
CurrRev Enabled
tPickUpRev 0,15
tDelayRev 0,03
WEI Off
tPickUpWEI 0,01
3VOPU 25

Función de Sobrecorriente Direccional Residual (67N)

DirMode1 Forward
Characteristic1 IEC Def. Time
IN1> 263 (%IB)
t1 0,30
TD1 0,00
DirMode2 Forward
Characteristic2 IEC Normal Inverse
IN2> 20 (%IB)
t2 0,00
TD2 0,27

Función de Sobrecorriente de Emergencia

Fase
DirModeSel1 Non directional
Characterist1 IEC Norm. Inv.
Pickup1 120 (%IB)
t1 0,00
TD1 0,07

Residual
DirModeSel3 Non Directional
Characterist3 IEC Normal Inverse
Pickup3 20 (%IB)

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
94-285

t3 0,00
TD3 0,27

Función de Bloqueo de Oscilacion de Potencia

X1InFw 78,49
R1LIn 21,85
R1FInFw 78,49
X1InRv 78,49
R1FInRv 78,49
RLdOutFw 209,31
LdAngle 30°
RLdOutRv 209,31
kLdRFw 0,75
kLdRRv 0,75

Función de Reconexión

Operation Enabled
AR Mode 3 phase
t1 1Ph 0,4 s
t1 3Ph 0,4 s
t1 3PhHS 0,4 s
tReclaim 15,0 s
tSync 1,0 s
tTrip 0,2 s
tPulse 0,2 s
NoOfShots 1
CBReady Type CO

Función de Verificación de Sincronismo

Operation Enabled
VHigh Bus Synch 80 %UB
VHigh Bus Synch 80 %UB
VDiff Synch 10% UB
Freq Diff Min 0,01 Hz
Freq Diff Max 0,2 Hz

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
95-285

tBreaker 0,08 s
tClose Pulse 0,2
Operation SC Enabled
UHigh Bus SC 80 %UB
UHigh Bus SC 80 %UB
UDiffSC 15 %UB
Freq Diff A 0,2 Hz
Freq Diff M 0,2 Hz
Phase Diff A 30°
Phase Diff A 30°
tSCA 0,1 s
tSCM 0,1 s

Función Falla Fusible

OpModeSel V0I0 OR V2I2


3V0PU 60
3I0PU 20
3V2PU 60
3I2PU 20
OpDVDI Enabled
DVPU 70
DIPU 15
VPPU 70
IPPU 10
SealIn Enabled
VSealInPU 70
IDLDPU 20
VDLDPU 70

Función de Falla de Interruptor

Pickup_PH 113% IB
Pickup_N 30% IB
t1 0,01 seg
T2 0,2 seg

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
96-285

6.2.2 S/E Valdivia paño Ciruelos C2

6.2.2.1 Protección 7SA612

Equipos de Medida

Transformadores de medida Razón


TTCC 800 A-pri 1 A-sec 800
TTPP 230000/√3 V-pri 115/√3 V-sec 2000
Razón TC/TP 0,400

Función de Distancia (21/21N)

Z1 Z1b Z2
Parámetro
Actuales Propuestos Actuales Propuestos Actuales Propuestos
Operating Mode Forward Forward Forward Forward Forward Forward
Resistance for ph-ph faults (Ω-
19,70 3,66 36,00 11,86 36,00 11,86
sec)
Reactance (Ω-sec) 19,70 3,66 36,00 11,86 36,00 11,86
Resistance for ph-gnd faults (Ω-
19,70 16,46 36,00 47,43 36,00 47,43
sec)
Delay for single phase faults 0,00 0,00 0,00 0,00 0,40 0,30
Delay for multi phase faults 0,00 0,00 0,00 0,00 0,40 0,30

Z3 Z4 Z5
Parámetro
Actuales Propuestos Actuales Propuestos Actuales Propuestos
Operating Mode Reverse Reverse Forward Forward Non Non
Resistance for ph-ph faults (Ω-
22,00 8,86 49,38 29,11 49,22 34,93
sec)
Reactance (Ω-sec) 22,00 3,82 49,38 29,11 49,22 34,93
Resistance for ph-gnd faults (Ω-
26,00 54,88 49,38 87,33 49,22 104,79
sec)
Delay for single phase faults 3,30 oo 3,40 1,20 oo oo
Delay for multi phase faults 3,30 oo 3,40 1,20 oo oo

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
97-285

Teleprotección

No. Parametro Ajuste Actual Ajuste Propuesto


121 85-21 Pilot Protection for distance prot. PUTT PUTT
Directional
132 85-67N Pilot Protection Earth O/C Disabled
Comparison Pickup
2101 85-21 Pilot Prot. for Distance prot. ON ON
2102 Type of Line Two Terminal Two Terminal
2103A Time for send signal prolongation 0,05 Seg 0,05 Seg
3201 85-67N Pilot Prot. for Dir.Ground O/C OFF ON
3202 Line Configuration -- Two Terminal
3203A Time for send signal prolongation -- 0,05 Seg
3209A Transient Block.: Duration external flt. -- 0,03 Seg
3210A Transient Block.: Blk.T. after ext. flt. -- 0,15 Seg
3212A EF transient block by DIS -- YES

Función de Sobrecorriente de Emergencia

No Parametro Ajuste Actual


2601 Operating Mode ON: Only Active with Loss of VT
2610 50-B1 Pickup 0,48 A-sec
2611 50-B1 Delay 0,60
2612 50N-B1 Pickup 0,45 A-sec
2613 50N-B1 Delay 0,6
2640 51-B Pickup 1,00 A-sec
2642 51-B Time Dial 0,05
2646 51-B Add. Time Delay 0,00
2650 51N-B Pickup 0,60 A-sec
2652 51N-B Time Dial 0,05
2656 51N-B Add. Time Delay 0,00
2660 IEC Curve Normal Inverse.

Función de Sobrecorriente Direccional Residual

No Parametro Ajuste Actual Ajuste Propuesto


3110 Operating Mode Forward Forward
3111 Pickup 0,45 A 2,63 A
3112 Time Delay 0,7 0,3 seg
3113 Instantaneous Trip Via Pilot Prot./Bl No Yes

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
98-285

No Parametro Ajuste Actual Ajuste Propuesto


3120 Operating Mode Forward Inactive
3121 Pickup 1,2 A 1,2 A
3122 Time Delay oo oo
3123 Instantaneous Trip Via Pilot Prot./Bl No No
3140 Operating Mode Forward Forward
3141 Pickup 0,6 A 0,2 A-sec
3143 Time Dial 0,06 0,60
3148 Instantaneous Trip Via Pilot Prot./Bl No Yes
3151 IEC Curve Normal Inverse Very Inverse

Load Encroachment

No. Parametro Ajuste Actual Ajuste Propuesto


1241 R load, minimum Load Impedance (ph-g) oo 34,3
1242 PHI load, maximum Load Angle (ph-g) 30° 30°
1243 R load, minimum Load Impedance (ph-ph) oo 34,3
1244 PHI load, maximum Load Angle (ph-ph) 30° 30°

6.2.2.2 Protección D60

Equipos de Medida

Transformadores de medida Razón


TTCC 800 A-pri 1 A-sec 800
TTPP 230000/√3 V-pri 115/√3 V-sec 2000
Razón TC/TP 0,400

Función de Distancia (21)

Z1 Z2
Parámetro
Actuales Propuestos Actuales Propuestos
Direction Forward Forward Forward Forward
Shape Quad Quad Quad Quad
Reach 19,70 3,66 36,00 11,86

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
99-285

RCA 90 90 90 90
Delay 0,00 0,00 0,40 0,30
Quad Right Blinder 19,70 3,66 36,00 11,86
Quad Left Blinder 19,70 3,66 36,00 11,86

Z3 Z4
Parámetro
Actuales Propuestos Actuales Propuestos
Direction Forward Forward Reverse Reverse
Shape Quad Quad Quad Quad
Reach 49,38 29,11 22,00 3,82
RCA 90 90 90 90
Delay 3,40 1,20 3,30 65,535
Quad Right Blinder 49,38 29,11 22,00 8,86
Quad Left Blinder 49,38 29,11 22,00 8,86

Función de Distancia (21N)

Z1 Z2
Parámetro
Actuales Propuestos Actuales Propuestos
Direction Forward Forward Forward Forward
Shape Quad Quad Quad Quad
Reach 19,70 3,66 36,00 11,86
RCA 90 90 90 90
Delay 0,00 0,00 0,40 0,30
Quad Right Blinder 19,70 16,46 36,00 47,43
Quad Left Blinder 19,70 16,46 36,00 47,43

Z3 Z4
Parámetro
Actuales Propuestos Actuales Propuestos
Direction Forward Forward Reverse Reverse
Shape Quad Quad Quad Quad
Reach 49,38 29,11 22,00 3,82
RCA 90 90 90 90
Delay 3,40 1,20 3,30 65,535
Quad Right Blinder 49,38 87,33 22,00 54,88
Quad Left Blinder 49,38 87,33 22,00 54,88
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
100-
285

Función de Sobrecorriente

Parámetro Ajuste Actual Ajuste Propuesto


PHASE TOC1 Function Enabled Enabled
PHASE TOC1 Pickup 1,00 pu 1,00 pu
PHASE TOC1 Curve IEC Curve A IEC Curve A
PHASE TOC1 TD Multiplier 0,05 0,05
PHASE TOC1 Block A Potencial-Ok On Potencial-Ok On
PHASE TOC1 Block B Potencial-Ok On Potencial-Ok On
PHASE TOC1 Block C Potencial-Ok On Potencial-Ok On
PHASE IOC1 Function Enabled Disabled
PHASE IOC1 Pickup 0,48 pu 0,48 pu
PHASE IOC1 Delay 0,60 0,60

Función de Sobrecorriente Direccional Residual

Parámetro Ajuste Actual Ajuste Propuesto


NEUTRAL TOC1 Function Enabled Enabled
NEUTRAL TOC1 Pickup 0,6 pu 0,2 pu
NEUTRAL TOC1 Curve IEC Curve A IEC Curve B
NEUTRAL TOC1 TD Multiplier 0,06 0,60
NEUTRAL IOC1 Function Enabled Enabled
NEUTRAL IOC1 Pickup 0,45 pu 2,63 pu
NEUTRAL IOC1 Delay 0,7 0,30
NEUTRAL DIR OC1 Forward Pickup 0,45 pu 0,2 pu
NEUTRAL DIR OC1 Reverse Pickup 0,45 pu 0,2 pu

Teleprotección

PUTT:
Se mantienen ajustes actuales.
85C:
Se debe impelmentar lógica de comparación direccional (en el caso de la protección GE D60 se
debe impelmentar en FlexLogic).

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
101-
285

Función de Bloqueo por Oscilacion de Potencia

Parámetro Ajuste Actual Ajuste Propuesto


Function Enabled Enabled
Shape Quad Shape Quad Shape
Mode Two Step Two Step
Fwd Reach 68,00 34,93
Quad Fwd Mid 25,00 25,00
Quad Fwd Out 72,00 97,22
Fwd RCA 73° 73°
Rev Reach 36,00 34,93
Quad Rev Mid 18,00 18,00
Quad Rev Out 40,00 97,22
Rev RCA 90° 90°
Outer Limit Angle 120° 120°
Midle Limit Angle 90° 90°
Inner Limit Angle 73° 73°
Outer Rgt Bld 58,00 97,22
Outer Lft Bld 48,60 97,22
Midle Rgt Bld 28,00 28,00
Midle Lft Bld 28,00 28,00
Inner Rgt Bld 54,00 34,93
Inner Lft Bld 44,60 34,93

Función Load Encroachment

Parámetro Ajuste Actual Ajuste Propuesto


Function Disabled Enabled
Source -- Linea (SRC 1)
Min Volt -- 0.25 pu
Reach -- 34.3
Angle -- 30°
PKP Delay -- 0.00 s
Rst Delay -- 0.00 s
Block -- BLK 21-PS/TP On (VO9)
Target -- Self-Reset
Events -- Enabled

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
102-
285

6.3 Barra N°2 S/E Ciruelos

6.3.1.1 Protección 7SJ80

Paño Acoplador

7001 50BF Breaker Failure Protection ON


7005 TRIP-Timer 0,2 seg
7006 50BF Pickup Current Threshold 2,85 A-sec
7007 50BF Pickup Earth Current Threshold 1,5 A-sec

Paño Seccionador

7001 50BF Breaker Failure Protection ON


7005 TRIP-Timer 0,2 seg
7006 50BF Pickup Current Threshold 4,77 A-sec
7007 50BF Pickup Earth Current Threshold 1,5 A-sec

6.4 Línea 220 kV Cautín – Tap Off Rio Toltén – Ciruelos C1

6.4.1 S/E Cautín paño Ciruelos C1

7SA612
N° Parámetro Ajustes Actuales Ajustes Propuestos
1311 Operating mode Z2 Forward Forward
1312 R(Z2), Resistance for ph-ph-faults 38,5 Ohm 38,5 Ohm
1313 X(Z2), Reactance 38,5 Ohm 48,3 Ohm
1314 RG(Z2), Resistance for ph-gnd faults 77 Ohm 77 Ohm
1315 T2-1phase, delay for single phase faults 0,4 seg 0,6 seg
1316 T2multi-ph, delay for multi phase faults 0,4 seg 0,6 seg

D60
21 (Z2) 21N (Z2)
Parámetro
Actuales Propuestos Actuales Propuestos
Direction Forward Forward Forward Forqard
Shape Quad Quad Quad Quad
Reach 38,5 48,3 38,5 48,3

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
103-
285

D60
21 (Z2) 21N (Z2)
Parámetro
Actuales Propuestos Actuales Propuestos
RCA 90 90 90 90
Delay 0,40 0,60 0,40 0,60
Quad Right Blinder 38,5 38,5 77,00 77,00
Quad Left Blinder 38,5 38,5 77,00 77,00

6.4.2 S/E Ciruelos paño Cautín C1

7SA612
N° Parámetro Ajustes Actuales Ajustes Propuestos
1311 Operating mode Z2 Forward Forward
1312 R(Z2), Resistance for ph-ph-faults 5,300 Ohm 5,300 Ohm
1313 X(Z2), Reactance 5,300 Ohm 5,300 Ohm
1314 RG(Z2), Resistance for ph-gnd faults 15,000 Ohm 15,000 Ohm
1315 T2-1phase, delay for single phase faults 0,40 seg 0,60 seg
1316 T2multi-ph, delay for multi phase faults 0,40 seg 0,60 seg

D60
21 (Z2) 21N (Z2)
Parámetro
Actuales Propuestos Actuales Propuestos
Direction Forward Forward Forward Forward
Shape Mho Mho Mho Mho
Reach 5,30 5,30 5,30 5,30
RCA 76 76 76 76
Delay 0,40 0,60 0,40 0,60
Quad Right Blinder 0,02 0,02 15,00 15,00
Quad Left Blinder 0,02 0,02 15,00 15,00

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
104-
285

6.5 Línea 220 kV Ciruelos – Valdivia C1

6.5.1 S/E Ciruelos paño Valdivia C1

Función de Distancia

7SA612
N° Parámetro Ajustes Actuales Ajustes Propuestos
1301 Operating mode Z1 Forward Forward
1302 R(Z1), Resistance for ph-ph-faults 0,74 Ohm 0,74 Ohm
1303 X(Z1), Reactance 0,74 Ohm 0,64 Ohm
1304 RG(Z1), Resistance for ph-gnd faults 2,96 Ohm 2,96 Ohm
1305 T1-1phase, delay for single phase faults 0,0 seg 0,0 seg
1306 T1multi-ph, delay for multi phase faults 0,0 seg 0,0 seg
1311 Operating mode Z2 Forward Forward
1312 R(Z2), Resistance for ph-ph-faults 2,05 Ohm 2,05 Ohm
1313 X(Z2), Reactance 2,05 Ohm 1,38 Ohm
1314 RG(Z2), Resistance for ph-gnd faults 4,10 Ohm 4,10 Ohm
1315 T2-1phase, delay for single phase faults 0,4 seg 0,3 seg
1316 T2multi-ph, delay for multi phase faults 0,4 seg 0,3 seg

D60
21 21N
Parámetro
Actuales Propuestos Actuales Propuestos
Z1: Direction Forward Forward Forward Forward
Z1: Shape Mho Mho Quad Quad
Z1: Reach 0,78 0,64 0,78 0,64
Z1: RCA 76 76 76 76
Z1: Delay 0,0 0,0 0,0 0,0
Z1: Quad Right Blinder 0,02 0,02 2,96 2,96
Z1: Quad Left Blinder 0,02 0,02 2,96 2,96
Z2: Direction Forward Forward Forward Forward
Z2: Shape Mho Mho Quad Quad
Z2: Reach 2,12 1,38 2,49 1,38

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
105-
285

D60
21 21N
Parámetro
Actuales Propuestos Actuales Propuestos
Z2: RCA 76 76 76 76
Z2: Delay 0,40 0,30 0,40 0,30
Z2: Quad Right Blinder 0,02 0,02 4,10 4,10
Z2: Quad Left Blinder 0,02 0,02 4,10 4,10

Función de Sobrecorriente Residual

7SA612
Ajustes Ajustes
N° Parámetro
Actuales Propuestos
3110 Operating mode Inactive Forward
3111 Pickup 20,00 A 18,35 A
3112 Time Delay 0,3 seg 0,3 seg
3113 Instantaneous Trip Via Pilot Prot./Bl NO YES
3140 Operating Mode Forward Forward
3141 Pickup 0,7 A-sec 0,7 A-sec
3143 Time Dial 0,8 0,8
3148 Instantaneous Trip Via Pilot Prot./Bl NO YES
3151 IEC Curve Very Inverse Very Inverse
3201 85-67N Pilot Prot. For Dir. Ground O/C --- ON
3202 Line Configuration --- Two Terminal
3203A Time for send signal prolongation --- 0,05 s
3209A Transient Block: Duration external Ftl. --- 0,03 s
3210A Transient Block: Blk. T. after ext. flt --- 0,15 s
3212 EF transient block by DIS --- YES

D60
Parámetro Ajustes Actuales Ajustes Propuestos
NEUTRAL TOC1 Function Enabled Enabled
NEUTRAL TOC1 Pickup 0,14 pu 0,14 pu
NEUTRAL TOC1 Curve IEC Curve B IEC Curve B
NEUTRAL TOC1 TD Multiplier 0,80 0,80
NEUTRAL IOC1 Function Disabled Enabled

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
106-
285

D60
Parámetro Ajustes Actuales Ajustes Propuestos
NEUTRAL IOC1 Pickup -- 3,67 pu
NEUTRAL IOC1 Delay -- 0,30

Teleprotección
PUTT:
Se mantienen ajustes actuales.

85C:
Se debe impelmentar lógica de comparación direccional (en el caso de la protección GE D60 se
debe impelmentar en FlexLogic).

6.5.2 S/E Valdivia paño Ciruelos C1

Función de Distancia

7SA612
N° Parámetro Ajustes Actuales Ajustes Propuestos
1301 Operating mode Z1 Forward Forward
1302 R(Z1), Resistance for ph-ph-faults 5,04 Ohm 5,04 Ohm
1303 X(Z1), Reactance 5,04 Ohm 3,67 Ohm
1304 RG(Z1), Resistance for ph-gnd faults 12,6 Ohm 12,6 Ohm
1305 T1-1phase, delay for single phase faults 0,0 seg 0,0 seg
1306 T1multi-ph, delay for multi phase faults 0,0 seg 0,0 seg
1311 Operating mode Z2 Forward Forward
1312 R(Z2), Resistance for ph-ph-faults 16,74 Ohm 16,74 Ohm
1313 X(Z2), Reactance 16,74 Ohm 10,8 Ohm
1314 RG(Z2), Resistance for ph-gnd faults 16,74 Ohm 16,74 Ohm
1315 T2-1phase, delay for single phase faults 0,4 seg 0,3 seg
1316 T2multi-ph, delay for multi phase faults 0,4 seg 0,3 seg

P443
Parámetro Ajustes Actuales Ajustes Propuestos
Z1 Ph. Reach 12,95 9,19
Z1 Ph. Angle 76.00 76.00

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
107-
285

P443
Parámetro Ajustes Actuales Ajustes Propuestos
R1 Ph. Resistive 25,20 25,20
Z2 Ph. Reach 43,10 27,01
Z2 Ph. Angle 76.00 76.00
R2 Ph. Resistive 83,70 83,70
Z1 Gnd. Reach 12,95 9,19
Z1 Gnd. Angle 76.00 76.00
R1 Gnd. Resistive 56,70 56,70
Z2 Gnd. Reach 43,10 27,01
Z2 Gnd. Angle 76.00 76.00
R2 Gnd. Resistive 75,3 75,3

Función de Sobrecorriente Residual

7SA612
Ajustes Ajustes
N° Parámetro
Actuales Propuestos
0132 85-67N Pilot Protection Gnd. Overcurrent Disabled Enabled
3110 Operating mode Inactive Active
3111 Pickup 4,00 A 2,63 A
3112 Time Delay 0,3 seg 0,3 seg
3113 Instantaneous Trip Via Pilot Prot./Bl NO YES
3140 Operating Mode Forward Forward
3141 Pickup 0,58 A-sec 0,58 A-sec
3143 Time Dial 0,15 0,15
3148 Instantaneous Trip Via Pilot Prot./Bl NO YES
3151 IEC Curve Normal Inverse Normal Inverse
3201 85-67N Pilot Prot. For Dir. Ground O/C --- ON
3202 Line Configuration --- Two Terminal
3203A Time for send signal prolongation --- 0,05 s
3209A Transient Block: Duration external Ftl. --- 0,03 s
3210A Transient Block: Blk. T. after ext. flt --- 0,15 s
3212 EF transient block by DIS --- YES

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
108-
285

P443
Parámetro Ajustes Actuales Ajustes Propuestos
IN>2 Status Enabled Enabled
IN>2 Function IEC S Inverse IEC S Inverse
IN>2 Directional Directional Fwd Directional Fwd
IN>2 Current Set 460 A 460 A
IN>2 TMS 150e-3 150e-3
IN>3 Status Disabled Enabled
IN>3 Function -- Def Time
IN>3 Directional -- Directional Fwd
IN>3 Current Set -- 2100 A
IN>3 TMS -- 300e-3
DEF Char. Angle 76.00 deg -60.00 deg

Teleprotección

PUTT:
Se mantienen ajustes actuales.

85C:
Se debe impelmentar lógica de comparación direccional (en el caso de la protección MiCOM P443
se debe impelmentar en PSL).
.

6.6 Línea 2x220kV Mulchen – Cautín C1 y C2

7SA612
N° Parámetro Ajustes Actuales Ajustes Propuestos
1321 Operating mode Z3 Forward Forward
1322 R(Z3), Resistance for ph-ph-faults 83,12 Ohm 83,12 Ohm
1323 X(Z3), Reactance 147,24 Ohm 87,57 Ohm
1324 RG(Z3), Resistance for ph-gnd faults 125 Ohm 125 Ohm
1325 T3 Delay 1,20 seg 1,20 seg

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
109-
285

D60 (Z3)
21 21N
Parámetro
Actuales Propuestos Actuales Propuestos
Direction Forward Forward Forward Forqard
Shape Quad Quad Quad Quad
Reach 147,24 87,57 147,24 87,57
RCA 90 90 90 90
Delay 1,20 1,20 1,20 1,20
Quad Right Blinder 83,12 83,12 125 125
Quad Left Blinder 249,36 249,36 271,01 271,01

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
110-
285

7. COMENTARIOS Y CONCLUSIONES

Respecto a los ajustes propuestos para las protecciones se puede comentar lo siguiente

 La finalidad con que se ajusta la zona 3 en reversa es para tener una correcta teleprotección
entre las protecciones de las líneas. Es por ello que todas las protecciones en estudio se
ajustaron con un tiempo máximo de operación.

 Con los alcances resistivos propuestos para las protecciones ubicadas en las S/E Cautín y S/E
Ciruelos de la línea 220 kV Cautín – Ciruelos C2, despejan las fallas a tierra con resistencia al
otro extremo de la respectiva línea la función de sobrecorriente residual no asi la función de
distancia. Esto se debe a que en esas fallas la función de distancia se encuentra bloqueada por
estar en la zona de carga de la línea. Sin embargo, operaria por comparación direccional o en
caso de perder la comunicación por redistribución de corriente operarían en 0,3 seg (etapa de
tiempo definido función de sobrecorriente residual).

 Ahora, con los alcances resistivos propuestos para las protecciones ubicadas en las S/E
Ciruelos y S/E Valdivia de la línea 220 kV Ciruelos – Valdivia C2 se logra despejar las fallas a
tierra con resistencia al otro extremo de la respectiva línea en tiempo de zona 2, por lo que
actuaría correctamente la teleprotección de las líneas.

Respecto a descoordinaciones que se presentan en el estudio se mencionan las siguientes:

 En las protecciones de la línea paralela 220 kV Cautín – Ciruelos C1 se tienen ajustadas las
zonas 2 en un tiempo de 0,4 seg, con estos tiempos de operación se producen
descoordinaciones al realizar fallas en las líneas en estudio en caso de perder la comunicación.
Es por ello que se recomienda aumentar el tiempo de operación a 0,6 segundos en las
protecciones de esta línea. Además con el fin de garantizar el correcto orden de apertura en
caso de perder realizar fallas en la línea 220 kV Ciruelos – Valdivia C1 y además perder la
comunicación, es que se propone ajustar en ambos extremos de la línea una etapa de tiempo
definido de 0,3 segundos para la función de sobrecorriente residual, cuyo pickup esté ajustado
de tal manera que solo opere en caso de presentar corrientes elevadas.

 Las protecciones de las líneas 220kV Ciruelos – Valdivia C1 y C2 presentan traslape de zonas
2 con las protecciones de los paños J6 y J5 de S/E Cautín. Par amitigar dichas
descoordinaciones se proponen un tiempo de 0,3 seg en los tiempos de las zonas 2 de los
paños J1 y J2 de S/E Ciruelos, así se establece el mismo tiempos en las zonas 2 de los paños
J4 y J5 de S/E Valdivia. En anexo VII se muestran barridos de cortocircutos y se aprecia la
coordinacicón de las zonas 2 desde S/E Rahue hasta S/E Mulché y viceversa.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
111-
285

 En la protección 7SA87 ubicada en Tap Off Rio Toltén se tiene que con el tiempo actual de
zona 2 (0,6 seg), se presenta un sobrealcance en la línea 2x220 kV Cautín – Ciruelos C2,
operando en el mismo tiempo de zona 2 de esta línea. Sin embargo, no se presentarían
problemas debido a que las protecciones ubicadas en ambos extremos de la línea 2x220 kV
Cautín – Ciruelos C2 operan correctamente al realizar fallas dentro de ella, por lo que actuarían
instantáneamente por teleprotección.

 Al realizar fallas cercanas a Temuco en las líneas 2x220 kV Temuco – Cautín C1 y C2, se da
que operan en tiempos de zona 2 (0,4 seg) las protecciones de los paños Cautín C1 y C2 de
S/E Mulchen. Esto se debe a que al ser una línea corta (Temuco – Cautín) las protecciones de
Mulchen tienen un sobre alcance sobre la línea. Sin embargo, las líneas 2x220 kV Temuco –
Cautín C1 y C2 poseen protecciones diferenciales de línea, operando de forma instantánea
para fallas dentro de la línea, no existiendo problemas de coordinación. Aunque si se pierde la
comunicación estas operarán en el mismo tiempo (0,4 seg) puesto que además las
protecciones de distancia que tienen las líneas 2x220 kV Temuco – Cautín tienen inactiva la
primara zona de tiempo instantáneo.

 Al realizar fallas en S/E Mariquina 220 kV no se observa ninguna operación de la protección


ubicada en esta subestación, esto se debe a que esta protección protege al transformador de
220/23 kV con 2 zona en dirección adelante, por lo que no ve fallas hacia atrás. Sin embargo
este paño posee una protección diferencial que operaria de manera instantánea al realizar fallas
en Mariquina 220 kV, no existiendo descordinaciones con las demás protecciones.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
112-
285

ANEXO I. DESPEJE SECUENCIAL DE FALLAS

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
113-
285

I.1. Línea 2x220 kV Cautín – Ciruelos.

En caso de perder la comunicación para la operación de la teleprotección de la línea, se analiza de


modo secuencial la operación de las protecciones al realizar fallas monofásicas, con el fin de mostrar
el correcto orden de apertura de las protecciones.

I.1.1. Falla Monofásica al 1% de línea 220 kV Cautín – Ciruelos C2 desde Extremo Ciruelos

Al realizar la falla en este extremo, el interruptor ubicado en Ciruelos C2 opera instantáneamente.


Posterior a la apertura del interruptor se redistribuyen las corrientes, por lo que operan las
protecciones del extremo Cautín C2 en un tiempo de 0,3 segundos (67N) y luego operarían las
protecciones del extremo Ciruelos C1 del la línea paralela en 0,6 segundos (Z2). A continuación se
muestran graficas con las protecciones.

DIgSILENT
225,
[pri.Ohm]
200,

175,

150,

125,

100,

75,0 Cau-Cir 7SA612 C2


Zone (1): Polarizing Z1
Z A 36,098 pri.Ohm 71,13°
Z B 133,895 pri.Ohm -30,33°
50,0 Z C 154,328 pri.Ohm -171,57°
Zone (> 1): Polarizing Z1b-Z2-Z5
Z A 36,098 pri.Ohm 71,13°
Z B 133,895 pri.Ohm -30,33°
25,0 Z C 154,328 pri.Ohm -171,57°
Fault Type: A (Starting)
Tripping Time: 0,32 s

-325, -300, -275, -250, -225, -200, -175, -150, -125, -100, -75,0 -50,0 -25,0 25,0 50,0 75,0 100, 125, 150, 175, 200, 225, 250, 275, [pri.Ohm]

-25,0

-50,0

-75,0

-100,

-125,

-150,

-175,

-200,

-225,

Cautin\Cub_0.2\Cau-Cir 7SA612 C2

Cau-Cir C2 Date: 10/5/2016


Annex:

Figura. I.1 – Característica de tierra protección 7SA612, extremo Cautín C2

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
114-
285

DIgSILENT
300,
[pri.Ohm]
270,

240,

210,

180,

150,

120,

90,0

60,0

30,0

-390, -360, -330, -300, -270, -240, -210, -180, -150, -120, -90,0 -60,0 -30,0 30,0 60,0 90,0 120, 150, 180, 210, 240, 270, 300, 330, [pri.Ohm]

-30,0 Cir-Tol-Cau 7SA612 C1


Zone (1): Polarizing Z1
Z A 90,557 pri.Ohm 67,47°
Z B 197,689 pri.Ohm -32,19°
-60,0 Z C 232,924 pri.Ohm -169,27°
Zone (> 1): Polarizing Z1b-Z2-Z5
Z A 90,557 pri.Ohm 67,47°
-90,0 Z B 197,689 pri.Ohm -32,19°
Z C 232,924 pri.Ohm -169,27°
Fault Type: A (Starting)
Tripping Time: 0,61 s
-120,

-150,

-180,

-210,

-240,

Ciruelos 220kV\R1\Cir-Tol-Cau 7SA612 C1

R-X Plot(1) Date: 10/12/2016


Annex:

Figura. I.2 – Característica de tierra protección 7SA612, extremo Ciruelos C1

Lo mismo sucede para fallas con resistencia de 25Ω

I.1.2. Falla Monofásica al 1% de línea 220 kV Cautín – Ciruelos C2 desde Extremo Cautín

Al realizar la falla en este extremo, el interruptor ubicado en Cautín C2 opera instantáneamente.


Posterior a la apertura del interruptor se redistribuyen las corrientes, por lo que operan las
protecciones del extremo Ciruelos C2 en un tiempo de 0,3 segundos (67N) y luego operarían las
protecciones del extremo Cautín C1 del la línea paralela en 0,6 segundos (Z2). A continuación se
muestran graficas con las protecciones.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
115-
285

DIgSILENT
450,
[pri.Ohm]
400,

350,

300,

250,

Cir-Cau REL670 C2
Zone (1): ZMQPDIS\ZMQ1 200,
Z A 73,41 pri.Ohm 54,66°
Z B 10859,939 pri.Ohm -0,84°
Z C 16174,864 pri.Ohm -179,7°
Zone (2): ZMQPDIS\ZMQ2 150,
Z A 73,415 pri.Ohm 54,65°
Z B 10247,396 pri.Ohm -0,89°
Z C 16508,332 pri.Ohm -179,7°
Zone (3): ZMQPDIS\ZMQ3 100,
Z A 73,374 pri.Ohm 54,65°
Z B 10406,185 pri.Ohm -0,78°
Z C 16423,876 pri.Ohm -179,74°
Zone (4): ZMQPDIS\ZMQ4 50,0
Z A 73,663 pri.Ohm 54,68°
Z B 7936,124 pri.Ohm -4,9°
Z C 17794,072 pri.Ohm -178,75°
Fault Type: A (Phase Selector)
-650, -600, -550, -500, -450, -400, Tripping
-350, Time: -250,
-300, 0,31 s -200, -150, -100, -50,0 50,0 100, 150, 200, 250, 300, 350, 400, 450, 500, 550, [pri.Ohm]
Zone 2
ZMQ2: 0,621 s
Zone 3 -50,0
ZMQ3: 1,221 s

-100,
Cir-Cau 7SA612 C2
Zone (1): Polarizing Z1
Z A 44,171 pri.Ohm 49,83°
Z B 145,988 pri.Ohm -43,03° -150,
Z C 194,762 pri.Ohm 178,38°
Zone (> 1): Polarizing Z1b-Z2-Z5
Z A 44,058 pri.Ohm 49,82°
Z B 145,022 pri.Ohm -43,07° -200,
Z C 193,358 pri.Ohm 178,37°
Fault Type: A (Starting)
Tripping Time: 0,32 s
Zone 2 -250,
Z2: 0,61 s
Zone 4
Z4: 1,21 s
-300,

-350,

-400,

-450,

Ciruelos 220kV\L4\Cir-Cau 7SA612 C2


Ciruelos 220kV\L4\Cir-Cau REL670 C2

Cir-Cau C2 Date: 10/5/2016


Annex:

Figura. I.3 – Característica de tierra protección 7SA612 y REL670, extremo Ciruelos C2

DIgSILENT
125,
[pri.Ohm]
100,

75,0

50,0

25,0
Cau-Tol-Cir 7SA612 C1
-375, -350, -325, -300, -275, Zone
-250, -225, Z1
(1): Polarizing -200, -175, -150, -125, -100, -75,0 -50,0 -25,0 25,0 50,0 75,0 100, 125, 150, 175, 200, 225, [pri.Ohm]
Z A 85,29 pri.Ohm 57,07°
Z B 168,342 pri.Ohm -47,41°
Z C 248,483 pri.Ohm -174,21°
Zone (> 1): Polarizing Z1b-Z2-Z5
Z A 85,29 pri.Ohm 57,07° -25,0
Z B 168,342 pri.Ohm -47,41°
Z C 248,483 pri.Ohm -174,21°
Fault Type: A (Starting)
Tripping Time: 0,61 s -50,0

-75,0

-100,

-125,

-150,

-175,

-200,

-225,

-250,

-275,

-300,

-325,

Cautin\Cub_0.3\Cau-Tol-Cir 7SA612 C1

Cau-Cir C1 Date: 10/5/2016


Annex:

Figura. I.4 – Característica de tierra protección 7SA612, extremo Cautín C1

Lo mismo sucede para fallas con resistencia de 25Ω

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
116-
285

I.1.3. Falla Monofásica al 1% de línea 220 kV Cautín – Ciruelos C1 desde Extremo Ciruelos

Al realizar la falla en este extremo, el interruptor ubicado en Ciruelos C1 opera instantáneamente.


Posterior a la apertura del interruptor se redistribuyen las corrientes, por lo que operan las
protecciones del extremo Cautín C1 en un tiempo de 0,6 segundos (Z2) y luego operarían las
protecciones del extremo Ciruelos C2 del la línea paralela en 1,2 segundos (Z3). A continuación se
muestran graficas con las protecciones

DIgSILENT
125,
[pri.Ohm]
100,

75,0

50,0

25,0
Cau-Tol-Cir 7SA612 C1
-375, -350, -325, -300, -275, Zone
-250, -225, Z1
(1): Polarizing -200, -175, -150, -125, -100, -75,0 -50,0 -25,0 25,0 50,0 75,0 100, 125, 150, 175, 200, 225, [pri.Ohm]
Z A 37,761 pri.Ohm 78,46°
Z B 131,406 pri.Ohm -42,01°
Z C 116,002 pri.Ohm -169,01°
Zone (> 1): Polarizing Z1b-Z2-Z5
Z A 37,761 pri.Ohm 78,46° -25,0
Z B 131,406 pri.Ohm -42,01°
Z C 116,002 pri.Ohm -169,01°
Fault Type: A (Starting)
Tripping Time: 0,61 s -50,0

-75,0

-100,

-125,

-150,

-175,

-200,

-225,

-250,

-275,

-300,

-325,

Cautin\Cub_0.3\Cau-Tol-Cir 7SA612 C1

Cau-Cir C1 Date: 10/5/2016


Annex:

Figura. I.5 – Característica de tierra protección 7SA612, extremo Cautín C1

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
117-
285

DIgSILENT
450,
[pri.Ohm]
400,

350,

300,

250,

200,
Cir-Cau REL670 C2
Zone (1): ZMQPDIS\ZMQ1
Z A 159,244 pri.Ohm 79,68°
Z B 3018,457 pri.Ohm -21,2° 150,
Z C 297,963 pri.Ohm -179,22°
Zone (2): ZMQPDIS\ZMQ2
Z A 161,925 pri.Ohm 78,78°
Z B 2383,729 pri.Ohm -22,27° 100,
Z C 298,068 pri.Ohm -179,23°
Zone (3): ZMQPDIS\ZMQ3
Z A 157,617 pri.Ohm 77,06°
Z B 2920,142 pri.Ohm -19,15° 50,0
Z C 297,947 pri.Ohm -179,25°
Zone (4): ZMQPDIS\ZMQ4
Z A 197,928 pri.Ohm 90,59°
Z B 760,922 pri.Ohm -97,84°
-650, -600, -550, -500, -450, -400, Z C 298,953
-350, -300, pri.Ohm
-250, -179,°
-200, -150, -100, -50,0 50,0 100, 150, 200, 250, 300, 350, 400, 450, 500, 550, [pri.Ohm]
Fault Type: A (Phase Selector)
Tripping Time: 1,220608 s
Zone 3 -50,0
ZMQ3: 1,221 s

-100,

Cir-Cau 7SA612 C2
Zone (1): Polarizing Z1 -150,
Z A 91,635 pri.Ohm 77,4°
Z B 214,982 pri.Ohm -50,07°
Z C 148,455 pri.Ohm -174,°
Zone (> 1): Polarizing Z1b-Z2-Z5 -200,
Z A 91,32 pri.Ohm 77,35°
Z B 213,742 pri.Ohm -50,02°
Z C 147,905 pri.Ohm -173,98°
Fault Type: A (Starting) -250,
Tripping Time: 1,21 s
Zone 4
Z4: 1,21 s
-300,

-350,

-400,

-450,

Ciruelos 220kV\L4\Cir-Cau 7SA612 C2


Ciruelos 220kV\L4\Cir-Cau REL670 C2

Cir-Cau C2 Date: 10/5/2016


Annex:

Figura. I.6 – Característica de tierra protección 7SA612 y REL670, extremo Ciruelos C2

Lo mismo sucede para fallas con resistencia de 25Ω

I.1.4. Falla Monofásica al 1% de línea 220 kV Cautín – Ciruelos C1 desde Extremo Cautín

Al realizar la falla en este extremo, el interruptor ubicado en Cautín C1 opera instantáneamente.


Posterior a la apertura del interruptor se redistribuyen las corrientes, por lo que operan las
protecciones del extremo Ciruelos C1 en un tiempo de 0,6 segundos (Z2) y luego operarían las
protecciones del extremo Cautín C2 del la línea paralela en 0,99 segundos (67N). A continuación se
muestran graficas con las protecciones.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
118-
285

DIgSILENT
270,
[pri.Ohm]
240,

210,

180,

150,
Cir-Tol-Cau 7SA612 C1
Zone (1): Polarizing Z1
Z A 37,31 pri.Ohm 77,57°
120, Z B 174,299 pri.Ohm -43,45°
Z C 146,95 pri.Ohm -175,22°
Zone (> 1): Polarizing Z1b-Z2-Z5
Z A 37,31 pri.Ohm 77,57°
90,0 Z B 174,299 pri.Ohm -43,45°
Z C 146,95 pri.Ohm -175,22°
Fault Type: A (Starting)
Tripping Time: 0,61 s
60,0 Zone 2
Z2: 0,61 s
Zone 4
Z4: 3,41 s
30,0

-390, -360, -330, -300, -270, -240, -210, -180, -150, -120, -90,0 -60,0 -30,0 30,0 60,0 90,0 120, 150, 180, 210, 240, 270, 300, 330, [pri.Ohm]

-30,0

-60,0

-90,0

-120,

-150,

-180,

-210,

-240,

-270,

Ciruelos 220kV\R1\Cir-Tol-Cau 7SA612 C1

Cir-Cau C1 Date: 10/5/2016


Annex:

Figura. I.7 – Característica de tierra protección 7SA612, extremo Ciruelos C1

DIgSILENT
225,
[pri.Ohm]
200,

175,

150,

125,

100,

75,0 Cau-Cir 7SA612 C2


Zone (1): Polarizing Z1
Z A 81,446 pri.Ohm 67,93°
Z B 205,897 pri.Ohm -28,84°
50,0 Z C 423,029 pri.Ohm -164,9°
Zone (> 1): Polarizing Z1b-Z2-Z5
Z A 81,446 pri.Ohm 67,93°
Z B 205,897 pri.Ohm -28,84°
25,0 Z C 423,029 pri.Ohm -164,9°
Fault Type: A (Starting)
Tripping Time: 0,9983805 s

-325, -300, -275, -250, -225, -200, -175, -150, -125, -100, -75,0 -50,0 -25,0 25,0 50,0 75,0 100, 125, 150, 175, 200, 225, 250, 275, [pri.Ohm]

-25,0

-50,0

-75,0

-100,

-125,

-150,

-175,

-200,

-225,

Cautin\Cub_0.2\Cau-Cir 7SA612 C2

Cau-Cir C2 Date: 10/5/2016


Annex:

Figura. I.8 – Característica de tierra protección 7SA612, extremo Cautín C2

Lo mismo sucede para fallas con resistencia de 25Ω

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
119-
285

I.2. Línea 2x220 kV Ciruelos – Valdivia.

En caso de perder la comunicación para la operación de la teleprotección de la línea, se analiza de


modo secuencial la operación de las protecciones de la línea al realizar fallas monofásicas, con el fin
de mostrar el correcto orden de apertura de las protecciones.

I.2.1. Falla Monofásica al 1% de línea 220 kV Ciruelos – Valdivia C2 desde Extremo Ciruelos

Al realizar la falla en este extremo, el interruptor ubicado en Ciruelos C2 opera instantáneamente.


Posterior a la apertura del interruptor se redistribuyen las corrientes, por lo que operan las
protecciones del extremo Valdivia C2 en un tiempo de 0,3 segundos (67N) y luego operarían las
protecciones del extremo Ciruelos C1 del la línea paralela en 0,87 segundos (67N). A continuación
se muestran graficas con las protecciones.

DIgSILENT
225,
[pri.Ohm]
200,

175,

150,

125,

100,

Val-Cir 7SA612 C2
Zone (1): Polarizing Z1 75,0
Z A 13,983 pri.Ohm 71,53°
Z B 87,066 pri.Ohm -26,09°
Z C 93,783 pri.Ohm -174,16°
Zone (> 1): Polarizing Z1b-Z2-Z5 50,0
Z A 13,983 pri.Ohm 71,53°
Z B 87,066 pri.Ohm -26,09°
Z C 93,783 pri.Ohm -174,16°
Fault Type: A (Starting) 25,0
Tripping Time: 0,32 s

-325, -300, -275, -250, -225, -200, -175, -150, -125, -100, -75,0 -50,0 -25,0 25,0 50,0 75,0 100, 125, 150, 175, 200, 225, 250, 275, [pri.Ohm]

-25,0

-50,0

-75,0

-100,

-125,

-150,

-175,

-200,

-225,

Val\52J4\Val-Cir 7SA612 C2

Val-Cir C2 Date: 10/5/2016


Annex:

Figura. I.9 – Característica de tierra protección 7SA612, extremo Valdivia C2

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
120-
285

DIgSILENT
163,
[pri.Ohm]
150,

138,

125,

113,

100,

87,5
Cir-Val 7SA612 C1
Zone (1): Polarizing Z1
75,0 Z A 29,379 pri.Ohm 66,92°
Z B 167,106 pri.Ohm -20,03°
Z C 1316,659 pri.Ohm -157,23°
Zone (> 1): Polarizing Z1b-Z2-Z5
62,5 Z A 29,379 pri.Ohm 66,92°
Z B 167,106 pri.Ohm -20,03°
Z C 1316,659 pri.Ohm -157,23°
Fault Type: A (Starting)
50,0 Tripping Time: 0,8715633 s

37,5

25,0

12,5

-138, -125, -113, -100, -87,5 -75,0 -62,5 -50,0 -37,5 -25,0 -12,5 12,5 25,0 37,5 50,0 62,5 75,0 87,5 100, 113, 125, 138, 150, 163, [pri.Ohm]

-12,5

-25,0

-37,5

-50,0

-62,5

Ciruelos 220kV\R2\Cir-Val 7SA612 C1

R-X Plot Date: 12/5/2016


Annex:

Figura. I.10 – Característica de tierra protección 7SA612, extremo Ciruelos C1

Lo mismo sucede para fallas con resistencia de 25Ω

I.2.2. Falla Monofásica al 1% de línea 220 kV Ciruelos – Valdivia C2 desde Extremo Valdivia

Al realizar la falla en este extremo, el interruptor ubicado en Valdivia C2 opera instantáneamente.


Posterior a la apertura del interruptor se redistribuyen las corrientes, por lo que operan las
protecciones del extremo Ciruelos C2 en un tiempo de 0,0 segundos (Z1) y luego operarían las
protecciones del extremo Valdivia C1 del la línea paralela en 0,31 segundos (Z2). A continuación se
muestran graficas con las protecciones.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
121-
285

DIgSILENT
270,
[pri.Ohm]
240,

210,

180,

150,
Cir-Val REL670 C2
Zone (1): ZMQPDIS\ZMQ1
Z A 21,376 pri.Ohm 73,43° 120,
Z B 15570,508 pri.Ohm -0,72°
Z C 27356,296 pri.Ohm -179,37°
Zone (2): ZMQPDIS\ZMQ2
Z A 21,376 pri.Ohm 73,43° 90,0
Z B 15534,756 pri.Ohm -0,72°
Z C 27440,52 pri.Ohm -179,37°
Zone (3): ZMQPDIS\ZMQ3
Z A 21,376 pri.Ohm 73,43° 60,0
Z B 15520,593 pri.Ohm -0,72°
Z C 27488,878 pri.Ohm -179,37°
Zone (4): ZMQPDIS\ZMQ4 30,0
Z A 21,417 pri.Ohm 73,43°
Z B 1579,956 pri.Ohm 18,69°
Z C 13824,1 pri.Ohm -3,19°
Fault Type: A (Phase Selector)
Tripping Time: 0,31 s
-390, -360, -330, -300, -270, Zone
-240,
2 -210, -180, -150, -120, -90,0 -60,0 -30,0 30,0 60,0 90,0 120, 150, 180, 210, 240, 270, 300, 330, [pri.Ohm]
ZMQ2: 0,621 s
Zone 3 -30,0
ZMQ3: 1,221 s

Cir-Val 7SA612 C2 -60,0


Zone (1): Polarizing Z1
Z A 12,279 pri.Ohm 69,25°
Z B 91,575 pri.Ohm -23,74°
Z C 103,748 pri.Ohm -172,96° -90,0
Zone (> 1): Polarizing Z1b-Z2-Z5
Z A 12,279 pri.Ohm 69,25°
Z B 91,575 pri.Ohm -23,74° -120,
Z C 103,748 pri.Ohm -172,96°
Fault Type: A (Starting)
Tripping Time: 0,32 s
Zone 2 -150,
Z2: 0,61 s
Zone 4
Z4: 1,21 s
-180,

-210,

-240,

-270,

Ciruelos 220kV\L3\Cir-Val 7SA612 C2


Ciruelos 220kV\L3\Cir-Val REL670 C2

Cir-Val C2 Date: 10/5/2016


Annex:

Figura. I.11 – Característica de tierra protección 7SA612 y REL670, extremo Ciruelos C2

DIgSILENT
113,
[pri.Ohm]
100,

87,5

75,0

Val-Cir 7SA612 C1
62,5 Zone (1): Polarizing Z1
Zl A 144,056 pri.Ohm 139,98°
Zl B 341,85 pri.Ohm 171,54°
Zl C 287,644 pri.Ohm 76,67°
50,0 Z A 25,906 pri.Ohm 71,93°
Z B 100,404 pri.Ohm -37,5°
Z C 72,785 pri.Ohm -175,07°
Zone (> 1): Polarizing Z1b-Z2-Z5
37,5 Z A 26,03 pri.Ohm 71,99°
Z B 101,159 pri.Ohm -37,58°
Z C 73,138 pri.Ohm -175,07°
Fault Type: A (Starting)
25,0 Tripping Time: 0,31 s

12,5

-163, -150, -138, -125, -113, -100, -87,5 -75,0 -62,5 -50,0 -37,5 -25,0 -12,5 12,5 25,0 37,5 50,0 62,5 75,0 87,5 100, 113, 125, 138, [pri.Ohm]

-12,5

-25,0

-37,5

-50,0

-62,5

-75,0

-87,5

-100,

-113,

Val\52J5\Val-Cir 7SA612 C1

J5 Valdivia(1) Date: 1/30/2017


Annex:

Figura. I.12 – Característica de tierra protección 7SA612, extremo Valdivia C1

Lo mismo sucede para fallas con resistencia de 25Ω

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
122-
285

I.2.3. Falla Monofásica al 1% de línea 220 kV Ciruelos – Valdivia C1 desde Extremo Ciruelos

Al realizar la falla en este extremo, el interruptor ubicado en Ciruelos C1 opera instantáneamente.


Posterior a la apertura del interruptor se redistribuyen las corrientes, por lo que operan las
protecciones del extremo Valdivia C1 en un tiempo de 0,32 segundos (Z2) y luego operarían las
protecciones del extremo Ciruelos C2 del la línea paralela en 0,95 segundos (67N). A continuación
se muestran graficas con las protecciones.

DIgSILENT
110,
[pri.Ohm]
100,

90,0

80,0

70,0 Val-Cir 7SA612 C1


Zone (1): Polarizing Z1
Z A 13,016 pri.Ohm 76,03°
Z B 89,124 pri.Ohm -22,85°
60,0 Z C 94,363 pri.Ohm -173,87°
Zone (> 1): Polarizing Z1b-Z2-Z5
Z A 13,066 pri.Ohm 76,04°
50,0 Z B 89,898 pri.Ohm -22,85°
Z C 95,186 pri.Ohm -173,87°
Fault Type: A (Starting)
Tripping Time: 0,32 s
40,0

30,0

20,0

10,0

-130, -120, -110, -100, -90,0 -80,0 -70,0 -60,0 -50,0 -40,0 -30,0 -20,0 -10,0 10,0 20,0 30,0 40,0 50,0 60,0 70,0 80,0 90,0 100, 110, [pri.Ohm]

-10,0

-20,0

-30,0

-40,0

-50,0

-60,0

-70,0

Val\52J5\Val-Cir 7SA612 C1

R-X Plot(1) Date: 12/5/2016


Annex:

Figura. I.13 – Característica de tierra protección 7SA612, extremo Valdivia C1

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
123-
285

DIgSILENT
270,
[pri.Ohm]
240,

210,

180,

150,

Cir-Val REL670 C2 120,


Zone (1): ZMQPDIS\ZMQ1
Z A 52,377 pri.Ohm 72,18°
Z B 557,673 pri.Ohm 0,46°
Z C 265,381 pri.Ohm -124,19° 90,0
Zone (2): ZMQPDIS\ZMQ2
Z A 51,563 pri.Ohm 72,75°
Z B 557,67 pri.Ohm 0,46°
Z C 231,353 pri.Ohm -11,13° 60,0
Zone (3): ZMQPDIS\ZMQ3
Z A 51,595 pri.Ohm 72,78°
Z B 557,688 pri.Ohm 0,46° 30,0
Z C 231,576 pri.Ohm -10,84°
Zone (4): ZMQPDIS\ZMQ4
Z A 47,086 pri.Ohm 65,82°
Z B 548,579 pri.Ohm 1,05°
Z C 251,445 pri.Ohm 2,77°
-390, -360, -330, -300, -270, Fault
-240,
Type:-210, -180, Selector)
CA-E (Phase -150, -120, -90,0 -60,0 -30,0 30,0 60,0 90,0 120, 150, 180, 210, 240, 270, 300, 330, [pri.Ohm]
Tripping Time: 0,9474338 s
Zone 3 -30,0
ZMQ3: 1,221 s

-60,0

Cir-Val 7SA612 C2
Zone (1): Polarizing Z1
Z A 29,85 pri.Ohm 68,05° -90,0
Z B 183,402 pri.Ohm -17,69°
Z C 4157,42 pri.Ohm -157,66°
Zone (> 1): Polarizing Z1b-Z2-Z5 -120,
Z A 29,85 pri.Ohm 68,05°
Z B 183,402 pri.Ohm -17,69°
Z C 4157,42 pri.Ohm -157,66°
Fault Type: A (Starting) -150,
Tripping Time: 0,9524338 s
Zone 4
Z4: 1,21 s
-180,

-210,

-240,

-270,

Ciruelos 220kV\L3\Cir-Val 7SA612 C2


Ciruelos 220kV\L3\Cir-Val REL670 C2

Cir-Val C2 Date: 10/5/2016


Annex:

Figura. I.14 – Característica de tierra protección 7SA612 y REL670, extremo Ciruelos C2

Lo mismo sucede para fallas con resistencia de 25Ω

I.2.4. Falla Monofásica al 1% de línea 220 kV Ciruelos – Valdivia C1 desde Extremo Valdivia

Al realizar la falla en este extremo, el interruptor ubicado en Valdivia C1 opera instantáneamente.


Posterior a la apertura del interruptor se redistribuyen las corrientes, por lo que operan las
protecciones del extremo Ciruelos C1 en un tiempo de 0,3 segundos (67N) y luego operarían las
protecciones del extremo Valdivia C2 del la línea paralela en 0,76 segundos (67N). A continuación
se muestran graficas con las protecciones.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
124-
285

DIgSILENT
163,
[pri.Ohm]
150,

138,

125,

113,

100,

87,5
Cir-Val 7SA612 C1
Zone (1): Polarizing Z1
75,0 Z A 11,317 pri.Ohm 75,42°
Z B 79,623 pri.Ohm -24,76°
Z C 86,781 pri.Ohm -171,05°
Zone (> 1): Polarizing Z1b-Z2-Z5
62,5 Z A 11,317 pri.Ohm 75,42°
Z B 79,623 pri.Ohm -24,76°
Z C 86,781 pri.Ohm -171,05°
Fault Type: A (Starting)
50,0 Tripping Time: 0,32 s

37,5

25,0

12,5

-138, -125, -113, -100, -87,5 -75,0 -62,5 -50,0 -37,5 -25,0 -12,5 12,5 25,0 37,5 50,0 62,5 75,0 87,5 100, 113, 125, 138, 150, 163, [pri.Ohm]

-12,5

-25,0

-37,5

-50,0

-62,5

Ciruelos 220kV\R2\Cir-Val 7SA612 C1

R-X Plot Date: 12/5/2016


Annex:

Figura. I.15 – Característica de tierra protección 7SA612, extremo Ciruelos C1

DIgSILENT
225,
[pri.Ohm]
200,

175,
Val-Cir 7SA612 C2
Zone (1): Polarizing Z1
150, Z A 30,554 pri.Ohm 79,03°
Z B 113,663 pri.Ohm -38,3°
Z C 76,287 pri.Ohm -173,54°
Zone (> 1): Polarizing Z1b-Z2-Z5
125, Z A 30,554 pri.Ohm 79,03°
Z B 113,663 pri.Ohm -38,3°
Z C 76,287 pri.Ohm -173,54°
Fault Type: A (Starting)
100, Tripping Time: 0,768165 s

75,0

50,0

25,0

-325, -300, -275, -250, -225, -200, -175, -150, -125, -100, -75,0 -50,0 -25,0 25,0 50,0 75,0 100, 125, 150, 175, 200, 225, 250, 275, [pri.Ohm]

-25,0

-50,0

-75,0

-100,

-125,

-150,

-175,

-200,

-225,

Val\52J4\Val-Cir 7SA612 C2

J4 Valdivia(1) Date: 1/30/2017


Annex:

Figura. I.16 – Característica de tierra protección 7SA612, extremo Valdivia C2

Lo mismo sucede para fallas con resistencia de 25Ω

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
125-
285

ANEXO II. TIEMPOS DE OPERACIÓN CON AJUSTES PROPUESTOS

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
126-
285

II.1. Escenario 1. Hidrología Húmeda y Demanda Alta (HH-DA)

II.1.1. Falla Trifásica

Tabla II.1 – Tiempos de Operación, falla Trifásica


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 --- --- --- --- --- 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 0,63 0,63 0,63 0,63 0,63 0,63 --- --- --- --- --- 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 0,61 0,61 0,02 0,02 --- --- --- --- --- 0,61 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C2 REL670 0,62 0,62 0,02 0,02 --- --- --- --- --- 0,62 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,62 0,62 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 0,61 0,61 0,61 0,61 0,61 0,61 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- --- 0,52 0,49 0,52 0,63 0,63 0,63 0,03 0,03 0,21 0,21 0,31 0,47 0,52 0,63 0,63 0,49 --- 0,51 --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,61 0,61 2,51 0,61 0,61 2,51 2,51 2,51 2,51 0,61 0,61 0,02 0,02 0,61 0,61 2,51 2,51 2,51 0,61 --- 2,51 2,51 2,51 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,61 0,61 --- --- --- --- --- --- --- 0,61 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C1 D60 0,63 0,63 --- --- --- --- --- --- --- 0,63 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 0,63 0,63 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- 1,21 0,31 --- --- --- --- --- --- --- 1,21 1,21

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,02 0,32 0,32 --- --- --- --- --- --- --- 1,22 0,32 --- --- --- --- --- --- --- 1,22 1,22

Valdivia Ciruelos C2 7SA612 --- --- --- 0,31 0,31 0,31 0,02 0,02 --- --- --- --- --- --- 0,31 0,31 --- --- 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- --- 0,33 0,33 0,33 0,03 0,03 --- --- --- --- --- --- 0,33 0,33 --- --- 0,33 --- 0,33 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- 3,21 0,31 0,31 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- 3,23 0,33 0,33 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 3,21 3,21 3,21 0,31 0,31 0,3 1 3,31 3,31 3,31 3,21 3,21 3,21 3,21 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Valdivia Ciruelos C1 P443 3,21 3,21 --- 0,31 0,31 0,31 3,31 3,31 3,31 3,21 --- --- --- --- 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Trafo 230/24 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 2,03 --- --- --- --- --- --- ---
Mariquina D30
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- 0,02 --- 3,01 3,01 --- ---

Cautín Mulchen C1 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- 0,03 --- 3,03 3,03 --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- --- 0,02 3,01 3,01 --- ---

Cautín Mulchen C2 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- --- 0,03 3,03 3,03 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
127-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 3,41 3,41 --- --- --- --- --- --- --- --- --- --- --- 0,41 3,31 --- ---

Cautín Temuco C1 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

Temuco Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 3,41 3,41 --- --- --- --- --- --- --- --- --- --- --- 3,31 0,41 --- ---

Cautín Temuco C2 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

Valdivia Rahue C2 7SA612 3,31 3,31 --- 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 --- --- 3,31 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- 3,31 3,31 0,02 ---

Valdivia Rahue C2 D60 3,33 3,33 --- 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 --- --- 3,33 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- 3,33 3,33 0,03 ---

Rahue Valdivia C2 7SA612 3,21 --- --- 3,21 3,21 3,21 3,21 3,21 3,21 --- --- --- --- --- 3,21 3,21 3,21 3,21 3,21 --- 3,21 --- --- --- --- 0,61 ---

Rahue Valdivia C2 7SA87 3,21 --- --- 3,21 3,21 3,21 3,21 3,21 3,21 --- --- --- --- --- 3,21 3,21 3,21 3,21 3,21 --- 3,21 --- --- --- --- 0,61 ---

Valdivia Rahue C1 7SA612 --- --- --- --- 1,51 --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- 0,02

Valdivia Rahue C1 P443 --- --- --- --- 1,51 --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 1,01 0,61 1,01 1,01 0,61 0,61 --- --- --- --- --- 1,01 1,01 1,01 0,61 0,61 --- 1,01 --- --- --- --- --- 0,02

Rahue Valdivia C1 D60 --- --- --- 1,03 0,63 1,03 1,03 0,63 0,63 --- --- --- --- --- 1,03 1,03 1,03 0,63 0,63 --- 1,03 --- --- --- --- --- 0,03

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
128-
285

II.1.2. Falla Bifásica Aislada

Tabla II.2 – Tiempos de Operación, falla Bifásica Aislada


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 --- --- --- --- --- 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 0,63 0,63 0,63 0,63 0,63 0,63 --- --- --- --- --- 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 0,61 0,61 0,02 0,02 --- --- --- --- --- 0,61 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C2 REL670 0,62 0,62 0,02 0,02 --- --- --- --- --- 0,62 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,62 0,62 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 0,61 0,61 0,61 0,61 0,61 0,61 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- --- 0,63 0,58 0,62 0,63 0,63 0,63 0,03 0,03 0,22 0,23 0,35 0,55 0,62 0,63 0,63 0,58 --- 0,6 --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,61 0,61 2,51 0,61 0,61 0,61 2,51 2,51 2,51 0,61 0,61 0,02 0,02 0,61 0,61 0,61 2,51 2,51 0,61 --- 0,61 2,51 2,51 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,61 0,61 --- --- --- --- --- --- --- 0,61 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C1 D60 0,63 0,63 --- --- --- --- --- --- --- 0,63 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 0,63 0,63 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- 1,21 0,31 --- --- --- --- --- --- --- 1,21 1,21

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,02 0,32 0,32 --- --- --- --- --- --- --- 1,22 0,32 --- --- --- --- --- --- --- 1,22 1,22

Valdivia Ciruelos C2 7SA612 --- --- --- 0,31 0,31 0,31 0,02 0,02 --- --- --- --- --- --- 0,31 --- --- --- 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- --- 0,33 0,33 0,33 0,03 0,03 --- --- --- --- --- --- 0,33 0,33 --- --- 0,33 --- 0,33 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- 3,21 0,31 0,31 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- 3,23 0,33 0,33 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 --- --- --- 0,31 0,31 0,31 --- 3,31 3,31 --- --- --- --- --- 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- --- --- 3,31 3,31

Valdivia Ciruelos C1 P443 3,21 3,21 --- 0,31 0,31 0,31 3,31 3,31 3,31 3,21 --- --- --- --- 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 2,38 --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- 0,02 --- 3,01 3,01 --- ---

Cautín Mulchen C1 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- 0,03 --- 3,03 3,03 --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- --- 0,02 3,01 3,01 --- ---

Cautín Mulchen C2 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- --- 0,03 --- --- --- ---

Temuco Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 3,41 3,41 3,41 --- --- --- --- --- --- --- --- --- --- 0,41 3,31 --- ---

Cautín Temuco C1 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
129-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 3,41 3,41 3,41 --- --- --- --- --- --- --- --- --- --- 3,31 0,41 --- ---

Cautín Temuco C2 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

Valdivia Rahue C2 7SA612 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- 3,31 3,31 0,02 ---

Valdivia Rahue C2 D60 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- 3,33 3,33 0,03 ---

Rahue Valdivia C2 7SA612 3,21 --- --- 3,21 3,21 3,21 3,21 3,21 3,21 --- --- --- --- --- 3,21 3,21 3,21 3,21 3,21 --- 3,21 --- --- --- --- 0,61 ---

Rahue Valdivia C2 7SA87 3,21 --- --- 3,21 3,21 3,21 3,21 3,21 3,21 --- --- --- --- --- 3,21 3,21 3,21 3,21 3,21 --- 3,21 --- --- --- --- 0,61 ---

Valdivia Rahue C1 7SA612 --- --- --- --- 1,51 --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- 0,02

Valdivia Rahue C1 P443 --- --- --- --- 1,51 --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 1,01 0,61 1,01 1,01 0,61 0,61 --- --- --- --- --- 1,01 1,01 1,01 0,61 0,61 --- 1,01 --- --- --- --- --- 0,02

Rahue Valdivia C1 D60 --- --- --- 1,03 0,63 1,03 1,03 0,63 0,63 --- --- --- --- --- 1,03 1,03 1,03 0,63 0,63 --- 1,03 --- --- --- --- --- 0,03

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
130-
285

II.1.3. Falla Bifásica a tierra

Tabla II.3 – Tiempos de Operación, falla Bifásica a tierra


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 --- --- --- --- --- 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 0,63 0,63 0,63 0,63 0,63 0,63 --- --- --- --- --- 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 0,61 0,61 0,02 0,02 --- --- --- --- --- 0,61 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C2 REL670 0,62 0,62 0,02 0,02 --- --- --- --- --- 0,62 18,74 --- --- --- --- --- --- --- --- --- --- --- --- 0,62 0,62 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 0,61 0,61 0,61 0,61 0,61 0,61 0,02 0,02 0,58 0,61 0,61 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- 11,86 0,62 0,57 0,61 0,63 0,63 0,63 0,03 0,03 0,21 0,22 0,34 0,54 0,61 0,63 0,63 0,57 --- 0,59 --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,6 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 --- 0,61 0,61 0,61 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio 1,00 1,00 1,00 --- --- --- --- --- --- 1,00 1,00 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- 1,00 1,00 --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 1,00 1,00 1,00 --- --- --- --- --- --- 1,00 1,00 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- 1,00 1,00 --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,61 0,61 --- --- --- --- --- --- --- 0,61 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C1 D60 0,63 0,63 --- --- --- --- --- --- --- 0,63 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 0,63 0,63 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- 0,31 0,31 --- --- --- --- --- --- --- 1,21 1,21

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,02 0,32 0,32 --- --- --- --- --- --- --- 0,32 0,32 --- --- --- --- --- --- --- 1,22 1,22

Valdivia Ciruelos C2 7SA612 --- --- 6,92 0,31 0,31 0,31 0,02 0,02 --- --- --- 10,99 10,22 4,04 0,31 0,31 9,2 --- 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- 6,93 0,33 0,33 0,33 0,32 0,03 --- --- --- 11 10,23 4,05 0,33 1,23 9,21 --- 0,33 --- 0,33 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- 0,31 0,31 0,31 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- 0,33 0,33 0,33 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 3,21 3,21 3,21 0,31 0,31 0,31 3,31 3,31 3,31 3,21 --- 3,21 3,21 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Valdivia Ciruelos C1 P443 3,21 3,21 3,21 0,31 0,31 0,31 3,31 3,31 3,31 3,21 --- --- --- 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 2,03 --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- 0,02 --- 3,01 3,01 --- ---

Cautín Mulchen C1 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- 0,03 --- 3,03 3,03 --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- --- 0,02 3,01 3,01 --- ---

Cautín Mulchen C2 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- --- 0,03 3,03 3,03 --- ---

Temuco Cautín C1 7SA612 0,41 0,41 1,02 --- --- --- --- --- --- 0,41 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 0,28 3,31 --- ---

Cautín Temuco C1 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 3,31 --- --- --- --- --- --- --- --- --- --- --- --- 0,37 0,41 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
131-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 0,41 0,41 1,02 --- --- --- --- --- --- 0,41 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 3,31 0,28 --- ---

Cautín Temuco C2 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 3,31 --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,37 --- ---

Valdivia Rahue C2 7SA612 3,31 --- --- 3,31 3,31 3,31 3,31 3,31 3,31 3,31 --- --- --- 3,31 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- 3,31 3,31 0,02 ---

Valdivia Rahue C2 D60 3,34 --- --- 3,34 3,34 3,34 3,34 3,34 3,34 3,34 --- --- --- 3,34 3,34 3,34 3,34 3,34 3,34 --- 3,34 --- --- 3,34 3,34 0,03 ---

Rahue Valdivia C2 7SA612 3,21 --- --- 3,21 3,21 3,21 3,21 2,11 1,96 --- --- --- --- --- 3,21 3,21 3,21 2,11 3,21 --- 3,21 --- --- --- --- 0,42 ---

Rahue Valdivia C2 7SA87 3,21 --- --- 3,21 3,21 3,21 3,21 2,11 1,96 --- --- --- --- --- 3,21 3,21 3,21 2,11 3,21 --- 3,21 --- --- --- --- 0,42 ---

Valdivia Rahue C1 7SA612 --- --- --- --- 1,51 --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- 0,02

Valdivia Rahue C1 P443 --- --- --- --- 1,51 --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 1,01 0,61 1,01 1,01 0,61 0,61 --- --- --- --- --- 1,01 1,01 1,01 0,61 0,61 --- 1,01 --- --- --- --- --- 0,02

Rahue Valdivia C1 D60 --- --- --- 1,03 1,03 1,03 1,03 0,63 0,63 --- --- --- --- --- 1,03 1,03 1,03 0,63 1,03 --- 1,03 --- --- --- --- --- 0,03

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
132-
285

II.1.4. Falla Monofásica

Tabla II.4 – Tiempos de Operación, falla Monofásica


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 0,61 0,61 0,61 2,08 4,23 4,74 --- --- --- --- 4,18 0,61 0,61 2,06 4,22 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 0,63 0,63 1,23 2,09 4,24 4,75 --- --- --- --- 4,19 1,23 1,23 2,07 4,23 0,63 --- 0,63 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 0,61 0,61 0,02 0,02 --- --- --- --- --- 0,61 14,25 --- --- --- --- --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C2 REL670 0,62 0,62 0,02 0,02 --- --- --- --- --- 0,62 14,25 --- --- --- --- --- --- --- --- --- --- 30,37 30,37 0,62 0,62 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 0,61 0,61 0,61 --- 3,31 --- 0,02 0,02 0,51 0,54 0,61 0,61 0,61 3,31 3,31 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- 8,26 0,63 0,63 0,63 --- 3,24 --- 0,03 0,03 0,24 0,25 0,46 0,63 0,63 3,24 3,24 0,63 --- 0,63 --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,61 0,61 0,61 0,61 0,61 0,61 0,61 2,51 2,51 0,61 0,52 0,02 0,02 0,61 0,61 0,61 0,61 2,51 0,61 --- 0,61 2,51 2,51 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio 1,00 1,00 1,00 --- --- --- --- --- --- 1,00 1,00 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- 1,00 1,00 --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 1,00 1,00 1,00 --- --- --- --- --- --- 1,00 1,00 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- 1,00 1,00 --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,61 3,41 --- --- --- --- --- --- --- 0,61 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C1 D60 0,63 3,43 --- --- --- --- --- --- --- 0,63 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 0,63 0,63 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- 1,21 0,31 --- --- --- --- --- --- --- --- ---

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,02 0,32 0,32 --- --- --- --- --- --- --- --- 0,32 --- --- --- --- --- --- --- 26,51 20,75

Valdivia Ciruelos C2 7SA612 --- --- 4,99 0,31 0,31 0,31 0,02 0,02 --- --- 11,93 8,18 7,66 3,16 0,31 1,21 8,75 --- 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- 5,00 0,33 0,33 0,33 0,03 0,03 --- --- 11,94 8,19 7,67 3,17 0,33 1,23 8,76 --- 0,33 --- 0,33 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- --- 0,31 0,31 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- --- 0,33 0,33 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 --- --- 3,21 0,31 0,31 1,44 --- 3,31 3,31 --- --- --- --- 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C1 P443 --- --- --- 3,21 0,31 1,45 --- 3,31 3,31 --- --- --- --- --- 3,21 0,31 0,02 0,02 0,31 --- 0,31 --- --- --- --- --- ---

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 6,84 --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,07 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 4,77 5,14 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 5,13 5,54 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 --- --- --- --- --- --- --- --- --- --- 0,02 --- 3,01 3,01 --- ---

Cautín Mulchen C1 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 --- --- --- --- --- --- --- --- --- --- 0,03 --- 3,03 3,03 --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 4,77 5,14 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 5,13 5,54 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 --- --- --- --- --- --- --- --- --- --- --- 0,02 3,01 3,01 --- ---

Cautín Mulchen C2 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 --- --- --- --- --- --- --- --- --- --- --- 0,03 3,03 3,03 --- ---

Temuco Cautín C1 7SA612 0,41 0,41 1,02 --- --- --- --- --- --- 0,41 0,9 1,02 1,02 1,02 --- --- --- --- --- --- --- 1,02 1,02 0,28 3,31 --- ---

Cautín Temuco C1 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 3,31 --- --- --- --- --- --- --- --- --- --- --- --- 0,35 0,41 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
133-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 0,41 0,41 1,02 --- --- --- --- --- --- 0,41 0,9 1,02 1,02 1,02 --- --- --- --- --- --- --- 1,02 1,02 3,31 0,28 --- ---

Cautín Temuco C2 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 3,31 --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,35 --- ---

Valdivia Rahue C2 7SA612 --- --- --- 3,31 3,31 3,31 3,31 3,31 3,31 --- --- --- --- --- 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- --- --- 0,02 ---

Valdivia Rahue C2 D60 --- --- --- 3,33 3,33 3,33 3,33 3,33 3,33 --- --- --- --- --- 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- --- --- 0,03 ---

Rahue Valdivia C2 7SA612 --- --- --- 3,21 3,21 3,21 3,21 2,48 2,33 --- --- --- --- --- 3,21 3,21 3,21 2,47 3,21 --- 3,21 --- --- --- --- 0,42 ---

Rahue Valdivia C2 7SA87 --- --- --- 3,21 3,21 3,21 3,21 2,48 2,33 --- --- --- --- --- 3,21 3,21 3,21 2,47 3,21 --- 3,21 --- --- --- --- 0,42 ---

Valdivia Rahue C1 7SA612 --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Valdivia Rahue C1 P443 --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 2,28 1,01 1,01 1,01 0,61 0,61 --- --- --- --- --- 2,27 1,01 1,01 0,61 1,01 --- 2,28 --- --- --- --- --- 0,02

Rahue Valdivia C1 D60 --- --- --- 2,29 1,03 1,03 1,03 0,63 0,63 --- --- --- --- --- 2,28 1,03 1,03 0,63 1,03 --- 2,29 --- --- --- --- --- 0,03

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
134-
285

II.1.5. Falla Bifásica a tierra R=25 Ω

Tabla II.5 – Tiempos de Operación, falla Bifásica R=25 Ω


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 1,72 1,92 2,07 3,38 --- --- --- --- --- --- --- 2,04 2,07 3,38 --- 1,93 --- 2,01 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 1,73 1,93 2,08 3,39 --- --- --- --- --- --- --- 2,05 2,08 3,39 --- 1,94 --- 2,02 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 8,13 5,18 0,02 0,02 --- --- --- --- --- 9,22 --- --- --- --- --- --- --- --- --- --- --- --- --- 8,79 8,79 --- ---

Ciruelos Cautín C2 REL670 8,12 5,18 0,62 0,02 --- --- --- --- --- 9,21 --- --- --- --- --- --- --- --- --- --- --- --- --- 8,79 8,79 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 0,61 0,61 0,61 3,31 3,31 3,31 0,02 0,59 0,61 0,61 0,61 0,61 0,61 3,31 3,31 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- --- 0,63 0,63 0,63 0,63 3,23 3,23 0,03 0,25 0,28 0,29 0,49 0,63 0,63 0,63 3,23 0,63 --- 0,63 --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,61 0,61 0,61 0,61 0,61 0,61 0,61 2,51 2,51 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 2,51 0,61 --- 0,61 0,61 0,61 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- --- --- --- --- --- --- --- --- --- 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 9,15 14,8 --- --- --- --- --- --- --- 3,41 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- --- --- 9,82 9,82 --- ---

Ciruelos Cautín C1 D60 9,15 14,8 --- --- --- --- --- --- --- 3,43 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 9,82 9,82 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- --- 0,31 --- --- --- --- --- --- --- --- ---

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,31 0,32 0,32 0,32 --- --- --- --- --- --- --- --- 0,32 --- --- --- --- --- --- --- --- ---

Valdivia Ciruelos C2 7SA612 --- --- 10,88 2,5 2,35 0,31 0,02 0,02 --- --- --- --- --- 5,68 2,49 2,79 --- --- 2,36 --- 2,47 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- 10,89 2,5 2,36 0,33 0,03 0,03 --- --- --- --- --- 5,69 2,5 2,8 --- --- 2,37 --- 2,48 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- --- 3,21 3,21 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- --- 3,23 3,23 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 --- --- --- 2,41 2,17 3,01 --- --- --- --- --- --- --- --- 2,4 1,58 0,31 0,02 2,19 --- 2,37 --- --- --- --- --- ---

Valdivia Ciruelos C1 P443 --- --- --- 2,42 2,18 3,02 --- --- --- --- --- --- --- --- 2,41 1,59 0,31 0,02 2,2 --- 2,38 --- --- --- --- --- ---

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,19 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 1,21 --- --- --- --- --- --- --- 0,41 1,21 --- --- --- --- --- --- --- --- --- --- 0,02 --- 1,21 1,21 --- ---

Mulchen Cautín C1 D60 0,43 1,23 --- --- --- --- --- --- --- 0,43 1,23 --- --- --- --- --- --- --- --- --- --- 0,03 --- 1,23 1,23 --- ---

Cautín Mulchen C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02 --- --- --- --- ---

Cautín Mulchen C1 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,03 --- --- --- --- ---

Mulchen Cautín C2 7SA612 0,41 1,21 --- --- --- --- --- --- --- 0,41 1,21 --- --- --- --- --- --- --- --- --- --- --- 0,02 1,21 1,21 --- ---

Mulchen Cautín C2 D60 0,43 1,23 --- --- --- --- --- --- --- 0,43 1,23 --- --- --- --- --- --- --- --- --- --- --- 0,03 1,23 1,23 --- ---

Cautín Cautín C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02 --- --- --- ---

Cautín Mulchen C2 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,03 --- --- --- ---

Temuco Cautín C1 7SA612 1,02 1,02 --- --- --- --- --- --- --- 1,02 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 0,39 3,31 --- ---

Cautín Temuco C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,58 0,82 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
135-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 1,02 1,02 --- --- --- --- --- --- --- 1,02 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 3,31 0,39 --- ---

Cautín Temuco C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,82 0,58 --- ---

Valdivia Rahue C2 7SA612 --- --- --- 3,31 3,31 3,31 3,31 3,31 3,31 --- --- --- --- --- 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- --- --- 0,61 ---

Valdivia Rahue C2 D60 --- --- --- 3,33 3,33 3,33 3,33 3,33 3,33 --- --- --- --- --- 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- --- --- 0,63 ---

Rahue Valdivia C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,82 ---

Rahue Valdivia C2 7SA87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,82 ---

Valdivia Rahue C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,17

Valdivia Rahue C1 P443 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61

Rahue Valdivia C1 7SA612 --- --- --- --- 4,14 3,8 2,45 0,61 0,61 --- --- --- --- --- --- 3,77 2,42 0,61 4,17 --- --- --- --- --- --- --- 0,61

Rahue Valdivia C1 D60 --- --- --- --- 1,03 3,81 2,46 0,63 0,63 --- --- --- --- --- --- 3,78 2,43 0,63 1,03 --- --- --- --- --- --- --- 0,63

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
136-
285

II.1.6. Falla Monofásica R=25 Ω

Tabla II.6 – Tiempos de Operación, falla Monofásica R=25 Ω


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 1,66 1,87 2,01 3,4 --- --- --- --- --- --- --- 1,97 2,01 3,4 --- 1,88 --- 1,95 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 1,67 1,88 2,02 3,41 --- --- --- --- --- --- --- 1,98 2,02 3,41 --- 1,89 --- 1,96 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 7,91 4,98 0,02 0,02 --- --- --- --- --- 8,83 --- --- --- --- --- --- --- --- --- --- --- --- --- 8,6 8,6 --- ---

Ciruelos Cautín C2 REL670 7,9 4,97 0,02 0,02 --- --- --- --- --- 8,83 --- --- --- --- --- --- --- --- --- --- --- --- --- 8,6 8,6 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 0,61 0,61 0,61 --- --- --- 0,02 0,02 0,61 0,61 0,61 0,61 0,61 --- --- 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- --- 0,63 0,63 0,63 --- --- --- 0,03 0,27 0,32 0,33 0,63 0,63 0,63 --- --- 0,63 --- 0,63 --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,61 0,61 0,61 0,61 0,61 0,61 0,61 2,51 2,51 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 2,51 0,61 --- 0,61 0,61 0,61 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- --- 1,00 --- --- --- --- --- --- --- 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- --- 1,00 --- --- --- --- --- --- --- 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 9,07 14,19 --- --- --- --- --- --- --- 3,41 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- --- --- 9,8 9,8 --- ---

Ciruelos Cautín C1 D60 9,07 14,19 --- --- --- --- --- --- --- 6,75 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 9,8 9,8 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- --- 0,31 --- --- --- --- --- --- --- --- ---

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,32 0,32 0,32 --- --- --- --- --- --- --- --- 0,32 --- --- --- --- --- --- --- --- ---

Valdivia Ciruelos C2 7SA612 --- --- 8,41 2,44 2,32 0,31 0,31 0,02 --- --- --- --- --- 4,79 2,43 2,75 --- --- 2,33 --- 2,47 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- 8,42 2,45 2,33 0,33 0,33 0,03 --- --- --- --- --- 4,8 2,44 2,76 --- --- 2,34 --- 2,48 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- --- 3,21 3,21 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 15,76 14,85

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- --- 3,23 3,23 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 15,76 14,85

Valdivia Ciruelos C1 7SA612 --- --- --- 2,34 2,16 2,98 --- --- --- --- --- --- --- --- 2,33 1,57 0,31 0,02 2,17 --- 2,35 --- --- --- --- --- ---

Valdivia Ciruelos C1 P443 --- --- --- 2,35 2,17 2,99 --- --- --- --- --- --- --- --- 2,34 1,58 0,02 0,02 2,18 --- 2,36 --- --- --- --- --- ---

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,19 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 --- --- --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 --- --- --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02 --- --- --- --- ---

Cautín Mulchen C1 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,03 --- --- --- --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 --- --- --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 --- --- --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02 --- --- --- ---

Cautín Mulchen C2 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,03 --- --- --- ---

Temuco Cautín C1 7SA612 1,02 1,02 1,02 --- --- --- --- --- --- 1,02 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 0,39 3,31 --- ---

Cautín Temuco C1 7SA612 3,21 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,58 0,82 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
137-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 1,02 1,02 1,02 --- --- --- --- --- --- 1,02 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 3,31 0,39 --- ---

Cautín Temuco C2 7SA612 3,21 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,82 0,58 --- ---

Valdivia Rahue C2 7SA612 --- --- --- 3,31 3,31 3,31 3,31 3,31 3,31 --- --- --- --- --- 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- --- --- 0,61 ---

Valdivia Rahue C2 D60 --- --- --- 3,33 3,33 3,33 3,33 3,33 3,33 --- --- --- --- --- 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- --- --- 0,63 ---

Rahue Valdivia C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61 ---

Rahue Valdivia C2 7SA87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61 ---

Valdivia Rahue C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,17

Valdivia Rahue C1 P443 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- --- 4,09 3,74 2,5 1,01 0,61 --- --- --- --- --- --- 3,72 2,46 1,01 4,11 --- --- --- --- --- --- --- 0,61

Rahue Valdivia C1 D60 --- --- --- --- 4,1 3,75 2,51 1,03 0,63 --- --- --- --- --- --- 3,73 2,47 1,03 4,12 --- --- --- --- --- --- --- 0,03

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
138-
285

II.2. Escenario 2. Hidrología Húmeda y Demanda Baja (HH-DB)

II.2.1. Falla Trifásica

Tabla II.7 – Tiempos de Operación, falla Trifásica


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 --- --- --- --- --- 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 0,63 0,63 0,63 0,63 0,63 0,63 --- --- --- --- --- 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 0,61 0,61 0,02 0,02 --- --- --- --- --- 0,61 1,21 --- --- --- --- --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C2 REL670 0,62 0,62 0,02 0,02 --- --- --- --- --- 0,62 1,22 --- --- --- --- --- --- --- --- --- --- --- --- 0,62 0,62 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 0,61 0,61 0,61 0,61 0,61 0,61 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- --- 0,63 0,63 0,63 0,63 0,63 0,63 0,03 0,03 0,63 0,63 0,63 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,61 0,61 2,51 0,61 0,61 0,61 2,51 2,51 2,51 0,61 0,61 0,02 0,02 0,61 0,61 0,61 2,51 2,51 0,61 --- 0,61 2,51 2,51 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,61 0,61 --- --- --- --- --- --- --- 0,61 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C1 D60 0,63 0,63 --- --- --- --- --- --- --- 0,63 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 0,63 0,63 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- 1,21 0,31 --- --- --- --- --- --- --- 1,21 1,21

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,02 0,32 0,32 --- --- --- --- --- --- --- 1,22 0,32 --- --- --- --- --- --- --- 1,22 1,22

Valdivia Ciruelos C2 7SA612 --- --- --- 0,31 0,31 0,31 0,02 0,02 --- --- --- --- --- --- 0,31 0,31 --- --- 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- --- 0,33 0,33 0,33 0,03 0,03 --- --- --- --- --- --- 0,33 0,33 --- --- 0,33 --- 0,33 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- 3,21 0,31 0,31 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- 3,23 0,33 0,33 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 3,21 3,21 3,21 0,31 0,31 0,31 --- 3,31 3,31 3,21 3,21 3,21 3,21 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Valdivia Ciruelos C1 P443 3,21 3,21 3,21 0,31 0,31 0,31 3,31 3,31 3,31 3,21 3,21 3,21 3,21 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Trafo 230/24 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 2,03 --- --- --- --- --- --- ---
Mariquina D30
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- 0,02 --- 3,01 3,01 --- ---

Cautín Mulchen C1 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- 0,03 --- 3,03 3,03 --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- --- 0,02 3,01 3,01 --- ---

Cautín Mulchen C2 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- --- 0,03 3,03 3,03 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
139-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 3,41 3,41 3,41 --- --- --- --- --- --- --- --- --- --- 0,41 3,31 --- ---

Cautín Temuco C1 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

Temuco Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 3,41 3,41 3,41 --- --- --- --- --- --- --- --- --- --- 3,31 0,41 --- ---

Cautín Temuco C2 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

Valdivia Rahue C2 7SA612 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- 3,31 3,31 0,02 ---

Valdivia Rahue C2 D60 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- 3,33 3,33 0,03 ---

Rahue Valdivia C2 7SA612 3,21 3,21 --- 3,21 3,21 3,21 3,21 3,21 3,21 3,21 --- --- --- 3,21 3,21 3,21 3,21 3,21 3,21 --- 3,21 --- --- 3,21 3,21 0,61 ---

Rahue Valdivia C2 7SA87 3,21 3,21 --- 3,21 3,21 3,21 3,21 3,21 3,21 3,21 --- --- --- 3,21 3,21 3,21 3,21 3,21 3,21 --- 3,21 --- --- 3,21 3,21 0,61 ---

Valdivia Rahue C1 7SA612 --- --- --- --- 1,51 --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- 0,02

Valdivia Rahue C1 P443 --- --- --- --- 1,51 --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 1,01 0,61 1,01 1,01 0,61 0,61 --- --- --- --- --- 1,01 1,01 1,01 0,61 0,61 --- 1,01 --- --- --- --- --- 0,02

Rahue Valdivia C1 D60 --- --- --- 1,03 0,63 1,03 1,03 0,63 0,63 --- --- --- --- --- 1,03 1,03 1,03 0,63 0,63 --- 1,03 --- --- --- --- --- 0,03

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
140-
285

II.2.2. Falla Bifásica Aislada

Tabla II.8 – Tiempos de Operación, falla Bifásica Aislada


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 --- --- --- --- --- 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 0,63 0,63 0,63 0,63 0,63 0,63 --- --- --- --- --- 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 0,61 0,61 0,02 0,02 --- --- --- --- --- 0,61 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C2 REL670 0,62 0,62 0,02 0,02 --- --- --- --- --- 0,62 1,22 --- --- --- --- --- --- --- --- --- --- --- --- 0,62 0,62 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 0,61 0,61 0,61 0,61 0,61 0,61 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- --- 0,63 0,63 0,63 0,63 0,63 0,63 0,03 0,03 0,63 0,63 0,63 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,61 0,61 2,51 0,61 0,61 0,61 2,51 2,51 2,51 0,61 0,61 0,02 0,02 0,61 0,61 0,61 2,51 2,51 0,61 --- 0,61 2,51 2,51 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,61 0,61 --- --- --- --- --- --- --- 0,61 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C1 D60 0,63 0,63 --- --- --- --- --- --- --- 0,63 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 0,63 0,63 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- 1,21 0,31 --- --- --- --- --- --- --- 1,21 1,21

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,02 0,32 0,32 --- --- --- --- --- --- --- 1,22 0,32 --- --- --- --- --- --- --- 1,22 1,22

Valdivia Ciruelos C2 7SA612 --- --- --- 0,31 0,31 0,31 0,02 0,02 --- --- --- --- --- --- 0,31 0,31 --- --- 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- --- 0,33 0,33 0,33 0,03 0,03 --- --- --- --- --- --- 0,33 0,33 --- --- 0,33 --- 0,33 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- 3,21 0,31 0,31 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- 3,23 0,33 0,33 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 3,21 3,21 3,21 0,31 0,31 0,31 --- 3,31 3,31 3,21 3,21 --- --- 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Valdivia Ciruelos C1 P443 3,21 3,21 3,21 0,31 0,31 0,31 3,31 3,31 3,31 3,21 3,21 3,21 3,21 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 2,37 --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- 0,02 --- 3,01 3,01 --- ---

Cautín Mulchen C1 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- 0,03 --- 3,03 3,03 --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- --- 0,02 3,01 3,01 --- ---

Cautín Mulchen C2 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- --- 0,03 --- --- --- ---

Temuco Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 3,41 3,41 3,41 --- --- --- --- --- --- --- --- --- --- 0,41 3,31 --- ---

Cautín Temuco C1 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
141-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 3,41 3,41 3,41 --- --- --- --- --- --- --- --- --- --- 3,31 0,41 --- ---

Cautín Temuco C2 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

Valdivia Rahue C2 7SA612 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- 3,31 3,31 0,02 ---

Valdivia Rahue C2 D60 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- 3,33 3,33 0,03 ---

Rahue Valdivia C2 7SA612 3,21 3,21 --- 3,21 3,21 3,21 3,21 3,21 3,21 3,21 --- --- --- 3,21 3,21 3,21 3,21 3,21 3,21 --- 3,21 --- --- 3,21 3,21 0,61 ---

Rahue Valdivia C2 7SA87 3,21 3,21 --- 3,21 3,21 3,21 3,21 3,21 3,21 3,21 --- --- --- 3,21 3,21 3,21 3,21 3,21 3,21 --- 3,21 --- --- 3,21 3,21 0,61 ---

Valdivia Rahue C1 7SA612 --- --- --- --- 1,51 --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- 0,02

Valdivia Rahue C1 P443 --- --- --- --- 1,51 --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 1,01 0,61 1,01 1,01 0,61 0,61 --- --- --- --- --- 1,01 1,01 1,01 0,61 0,61 --- 1,01 --- --- --- --- --- 0,02

Rahue Valdivia C1 D60 --- --- --- 1,03 0,63 1,03 1,03 0,63 0,63 --- --- --- --- --- 1,03 1,03 1,03 0,63 0,63 --- 1,03 --- --- --- --- --- 0,03

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
142-
285

II.2.3. Falla Bifásica a tierra

Tabla II.9 – Tiempos de Operación, falla Bifásica a tierra


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 --- --- --- --- --- 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 0,63 0,63 0,63 0,63 1,23 1,23 --- --- --- --- --- 0,63 0,63 0,63 1,23 0,63 --- 0,63 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 0,61 0,61 0,02 0,02 --- --- --- --- --- 0,61 1,21 --- --- --- --- --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C2 REL670 0,62 0,62 0,02 0,02 --- --- --- --- --- 0,62 1,22 --- --- --- --- --- --- --- --- --- --- 1,22 1,22 0,62 0,62 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 0,61 0,61 0,61 0,61 0,61 0,61 0,02 0,02 0,59 0,61 0,61 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- 3,23 0,63 0,63 0,63 0,63 0,63 0,63 0,03 0,03 0,6 0,63 0,63 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---
Trafo 220/110 TO Rio
7SA87 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 --- 0,61 0,61 0,61 0,61 0,61 --- ---
kV Rio Tolten Tolten
Trafo 220/110 TO Rio 1,00 1,00 1,00 --- --- --- --- --- --- 1,00 1,00 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- 1,00 1,00 --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio 1,00 1,00 1,00 --- --- --- --- --- --- 1,00 1,00 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- 1,00 1,00 --- ---
7UT87
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,61 0,61 --- --- --- --- --- --- --- 0,61 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C1 D60 0,63 0,63 --- --- --- --- --- --- --- 0,63 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 0,63 0,63 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- 1,21 0,31 --- --- --- --- --- --- --- 1,21 1,21

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,02 0,32 0,32 --- --- --- --- --- --- --- 1,22 0,32 --- --- --- --- --- --- --- 1,22 1,22

Valdivia Ciruelos C2 7SA612 --- --- 7,11 0,31 0,31 0,31 0,02 0,02 --- --- --- 11,38 10,56 4,13 0,31 0,31 10,03 --- 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- 7,12 0,33 0,33 0,33 0,03 0,03 --- --- --- 11,39 10,57 4,14 0,33 0,33 10,04 --- 0,33 --- 0,33 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- 3,21 0,31 0,31 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- 3,23 0,33 0,33 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 3,21 3,21 3,21 0,31 0,31 0,31 --- 3,31 3,31 3,21 3,21 3,21 3,21 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Valdivia Ciruelos C1 P443 3,21 3,21 3,21 0,31 0,31 0,31 3,31 3,31 3,31 3,21 3,21 3,21 3,21 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 2,03 --- --- --- --- --- --- ---
kV Mariquina
Planta
Ciruelos 7SJ64 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 --- --- --- --- --- ---
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- 0,02 --- 3,01 3,01 --- ---

Cautín Mulchen C1 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- 0,03 --- 3,03 3,03 --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- --- 0,02 3,01 3,01 --- ---

Cautín Mulchen C2 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- --- 0,03 3,03 3,03 --- ---

Temuco Cautín C1 7SA612 0,41 0,41 1,02 --- --- --- --- --- --- 0,41 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 0,29 3,31 --- ---

Cautín Temuco C1 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 3,31 --- --- --- --- --- --- --- --- --- --- --- --- 0,37 0,41 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
143-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 0,41 0,41 1,02 --- --- --- --- --- --- 0,41 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 3,31 0,29 --- ---

Cautín Temuco C2 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 3,31 --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,37 --- ---

Valdivia Rahue C2 7SA612 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- 3,31 3,31 0,02 ---

Valdivia Rahue C2 D60 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- 3,33 3,33 0,03 ---

Rahue Valdivia C2 7SA612 3,21 3,21 --- 3,21 3,21 3,21 3,21 2,13 1,97 3,21 --- --- --- 3,21 3,21 3,21 3,21 2,12 3,21 --- 3,21 --- --- 3,21 3,21 0,42 ---

Rahue Valdivia C2 7SA87 3,21 3,21 --- 3,21 3,21 3,21 3,21 2,13 1,97 3,21 --- --- --- 3,21 3,21 3,21 3,21 2,12 3,21 --- 3,21 --- --- 3,21 3,21 0,42 ---

Valdivia Rahue C1 7SA612 --- --- --- --- 1,51 --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- 0,02

Valdivia Rahue C1 P443 --- --- --- --- 1,51 --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 1,01 0,61 1,01 1,01 0,61 0,61 --- --- --- --- --- 1,01 1,01 1,01 0,61 0,61 --- 1,01 --- --- --- --- --- 0,02

Rahue Valdivia C1 D60 --- --- --- 1,03 1,03 1,03 1,03 0,63 0,63 --- --- --- --- --- 1,03 1,03 1,03 0,63 1,03 --- 1,03 --- --- --- --- --- 0,03

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
144-
285

II.2.4. Falla Monofásica

Tabla II.10 – Tiempos de Operación, falla Monofásica


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 0,61 0,61 0,61 2,13 4,53 --- --- --- --- --- 4,57 0,61 0,61 2,12 4,51 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 0,63 0,63 0,63 2,14 4,54 --- --- --- --- --- 4,58 0,63 0,63 2,13 4,52 0,63 --- 0,63 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 0,61 0,61 0,02 0,02 --- --- --- --- --- 0,61 13,01 --- --- --- --- --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C2 REL670 0,62 0,62 0,02 0,28 --- --- --- --- --- 0,62 13,01 --- --- --- --- --- --- --- --- --- --- 27,42 27,42 0,62 0,62 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 0,61 0,61 0,61 3,31 --- --- 0,02 0,02 0,51 0,54 0,61 0,61 0,61 3,31 --- 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- 7,95 0,63 0,63 0,63 3,23 --- --- 0,03 0,03 0,52 0,55 0,63 0,63 0,63 3,23 --- 0,63 --- 0,63 --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,52 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 --- 0,61 2,51 2,51 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio 1,00 1,00 1,00 --- --- --- --- --- --- 1,00 1,00 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- 1,00 1,00 --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 1,00 1,00 1,00 --- --- --- --- --- --- 1,00 1,00 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- 1,00 1,00 --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,61 3,41 --- --- --- --- --- --- --- 0,61 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C1 D60 0,63 3,43 --- --- --- --- --- --- --- 0,63 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 0,63 0,63 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- --- 0,31 --- --- --- --- --- --- --- --- ---

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,02 0,32 0,32 --- --- --- --- --- --- --- --- 0,32 --- --- --- --- --- --- --- 18,71 15,78

Valdivia Ciruelos C2 7SA612 --- --- 5,19 0,31 0,31 0,31 0,02 0,02 --- --- 12,78 8,62 8,06 3,26 0,31 1,21 9,84 --- 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- 5,2 0,33 0,33 0,33 0,03 0,03 --- --- 12,79 8,63 8,07 3,27 0,33 1,23 9,85 --- 0,33 --- 0,33 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- --- 0,31 0,31 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- --- 0,33 0,33 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 --- --- --- 0,31 0,31 1,47 --- 3,31 3,31 --- --- --- --- 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C1 P443 --- --- --- 3,21 0,31 1,48 --- 3,31 3,31 --- --- --- --- --- 3,21 0,31 0,02 0,02 0,31 --- 0,31 --- --- --- --- --- ---

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 6,94 --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 4,7 5,05 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 5,05 5,44 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 --- --- --- --- --- --- --- --- --- --- 0,02 --- 3,01 3,01 --- ---

Cautín Mulchen C1 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 --- --- --- --- --- --- --- --- --- --- 0,03 --- 3,03 3,03 --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 4,7 5,05 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 5,05 5,44 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 --- --- --- --- --- --- --- --- --- --- --- 0,02 3,01 3,01 --- ---

Cautín Mulchen C2 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 --- --- --- --- --- --- --- --- --- --- --- 0,03 3,03 3,03 --- ---

Temuco Cautín C1 7SA612 0,41 0,41 1,02 --- --- --- --- --- --- 0,41 0,92 1,02 1,02 1,02 --- --- --- --- --- --- --- 1,02 1,02 0,28 3,31 --- ---

Cautín Temuco C1 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 3,31 --- --- --- --- --- --- --- --- --- --- --- --- 0,35 0,41 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
145-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 0,41 0,41 1,02 --- --- --- --- --- --- 0,41 0,92 1,02 1,02 1,02 --- --- --- --- --- --- --- 1,02 1,02 3,31 0,28 --- ---

Cautín Temuco C2 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 3,31 --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,35 --- ---

Valdivia Rahue C2 7SA612 --- --- --- 3,31 3,31 3,31 3,31 3,31 3,31 --- --- --- --- --- 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- --- --- 0,02 ---

Valdivia Rahue C2 D60 --- --- --- 3,33 3,33 3,33 3,33 3,33 3,33 --- --- --- --- --- 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- --- --- 0,03 ---

Rahue Valdivia C2 7SA612 --- --- --- 3,21 3,21 3,21 3,21 2,51 2,36 --- --- --- --- --- 3,21 3,21 3,21 2,51 3,21 --- 3,21 --- --- --- --- 0,42 ---

Rahue Valdivia C2 7SA87 --- --- --- 3,21 3,21 3,21 3,21 2,51 2,36 --- --- --- --- --- 3,21 3,21 3,21 2,51 3,21 --- 3,21 --- --- --- --- 0,42 ---

Valdivia Rahue C1 7SA612 --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Valdivia Rahue C1 P443 --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 2,33 1,01 1,01 1,01 0,61 0,61 --- --- --- --- --- 2,33 1,01 1,01 0,61 1,01 --- 2,34 --- --- --- --- --- 0,02

Rahue Valdivia C1 D60 --- --- --- 2,34 1,03 1,03 1,03 0,63 0,63 --- --- --- --- --- 2,34 1,03 1,03 0,63 1,03 --- 2,35 --- --- --- --- --- 0,03

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
146-
285

II.2.5. Falla Bifásica a tierra R=25 Ω

Tabla II.11 – Tiempos de Operación, falla Bifásica R=25 Ω


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 1,73 1,94 2,09 3,45 --- --- --- --- --- --- --- 2,06 2,09 3,45 --- 1,95 --- 2,03 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 1,74 1,95 2,1 3,46 --- --- --- --- --- --- --- 2,07 2,1 3,46 --- 1,96 --- 2,04 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 7,8 5,05 0,02 0,02 --- --- --- --- --- 7,85 --- --- --- --- --- --- --- --- --- --- --- --- --- 8,41 8,41 --- ---

Ciruelos Cautín C2 REL670 7,8 5,04 0,62 0,02 --- --- --- --- --- 7,84 --- --- --- --- --- --- --- --- --- --- --- --- --- 8,4 8,4 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 3,31 3,31 3,31 3,31 --- --- 0,02 0,59 0,61 0,61 0,61 0,61 3,31 3,31 --- 3,31 --- 3,31 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- --- 0,63 0,63 0,63 3,23 --- --- 0,03 0,6 0,63 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- 0,63 --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,61 0,61 0,61 0,61 0,61 0,61 0,61 2,51 2,51 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 2,51 0,61 --- 0,61 0,61 0,61 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- 1 1 1 --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- --- --- --- --- --- --- --- --- --- 1 1 1 --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,61 0,61 --- --- --- --- --- --- --- 0,61 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C1 D60 3,43 3,43 --- --- --- --- --- --- --- 0,63 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 0,63 0,63 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- --- 0,31 --- --- --- --- --- --- --- --- ---

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,31 0,32 0,32 0,32 --- --- --- --- --- --- --- --- 0,32 --- --- --- --- --- --- --- --- ---

Valdivia Ciruelos C2 7SA612 --- --- 11,18 2,52 2,37 0,31 0,02 0,02 --- --- --- --- --- 5,79 2,51 2,82 --- --- 2,38 --- 2,5 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- 11,19 2,53 2,38 0,33 0,03 0,03 --- --- --- --- --- 5,8 2,52 2,83 --- --- 2,39 --- 2,51 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- --- 3,21 3,21 --- --- --- --- --- --- 0,02 0,02 2,55 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- --- 3,23 3,23 --- --- --- --- --- --- 0,03 0,03 2,55 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 --- --- --- 2,47 2,22 3,11 --- --- --- --- --- --- --- --- 2,46 1,59 0,31 0,02 2,23 --- 2,43 --- --- --- --- --- ---

Valdivia Ciruelos C1 P443 --- --- --- 2,48 2,23 3,12 --- --- --- --- --- --- --- --- 2,47 1,6 0,31 0,02 2,24 --- 2,44 --- --- --- --- --- ---

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,19 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 1,21 1,21 --- --- --- --- --- --- --- 1,21 1,21 --- --- --- --- --- --- --- --- --- --- 0,02 --- 1,21 1,21 --- ---

Mulchen Cautín C1 D60 1,23 1,23 --- --- --- --- --- --- --- 1,23 1,23 --- --- --- --- --- --- --- --- --- --- 0,03 --- 1,23 1,23 --- ---

Cautín Mulchen C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02 --- --- --- --- ---

Cautín Mulchen C1 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,03 --- --- --- --- ---

Mulchen Cautín C2 7SA612 1,21 1,21 --- --- --- --- --- --- --- 1,21 1,21 --- --- --- --- --- --- --- --- --- --- --- 0,02 1,21 1,21 --- ---

Mulchen Cautín C2 D60 1,23 1,23 --- --- --- --- --- --- --- 1,23 1,23 --- --- --- --- --- --- --- --- --- --- --- 0,03 1,23 1,23 --- ---

Cautín Cautín C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02 --- --- --- ---

Cautín Mulchen C2 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,03 --- --- --- ---

Temuco Cautín C1 7SA612 1,02 1,02 --- --- --- --- --- --- --- 1,02 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 0,39 3,31 --- ---

Cautín Temuco C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,57 0,8 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
147-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 1,02 1,02 --- --- --- --- --- --- --- 1,02 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 3,31 0,39 --- ---

Cautín Temuco C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,8 0,57 --- ---

Valdivia Rahue C2 7SA612 --- --- --- 3,31 3,31 3,31 3,31 3,31 3,31 --- --- --- --- 3,31 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- --- --- 0,61 ---

Valdivia Rahue C2 D60 --- --- --- 3,33 3,33 3,33 3,33 3,33 3,33 --- --- --- --- 3,33 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- --- --- 0,63 ---

Rahue Valdivia C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,82 ---

Rahue Valdivia C2 7SA87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,82 ---

Valdivia Rahue C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,17

Valdivia Rahue C1 P443 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61

Rahue Valdivia C1 7SA612 --- --- --- 1,01 1,01 1,01 1,01 0,61 0,61 --- --- --- --- --- 1,01 1,01 1,01 0,61 1,01 --- 1,01 --- --- --- --- --- 0,61

Rahue Valdivia C1 D60 --- --- --- 1,03 1,03 1,03 1,03 0,63 0,63 --- --- --- --- --- 1,03 1,03 1,03 0,63 1,03 --- 1,03 --- --- --- --- --- 0,63

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
148-
285

II.2.6. Falla Monofásica R=25 Ω

Tabla II.12 – Tiempos de Operación, falla Monofásica R=25 Ω


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 1,68 1,9 2,05 3,51 --- --- --- --- --- --- --- 2,01 2,05 3,44 --- 1,91 --- 1,98 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 1,68 1,91 2,06 3,52 --- --- --- --- --- --- --- 2,02 2,06 3,45 --- 1,92 --- 1,99 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 7,48 4,8 0,02 0,02 --- --- --- --- --- 8,3 --- --- --- --- --- --- --- --- --- --- --- --- --- 8,09 8,09 --- ---

Ciruelos Cautín C2 REL670 7,47 4,79 0,02 0,02 --- --- --- --- --- 8,31 --- --- --- --- --- --- --- --- --- --- --- --- --- 8,1 8,1 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- --- --- --- --- --- --- 0,02 0,02 0,61 0,61 0,61 0,61 --- --- --- 3,31 --- --- --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- --- --- --- --- --- --- --- 0,03 0,56 0,63 0,63 0,63 0,63 --- --- --- 3,23 --- --- --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,61 0,61 0,61 0,61 0,61 0,61 0,61 2,51 2,51 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 2,51 0,61 --- 0,61 0,61 0,61 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- --- 1,00 --- --- --- --- --- --- --- 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- --- 1,00 --- --- --- --- --- --- --- 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,61 13,15 --- --- --- --- --- --- --- 0,61 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C1 D60 3,43 13,15 --- --- --- --- --- --- --- 3,43 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 3,43 3,43 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- --- 0,31 --- --- --- --- --- --- --- --- ---

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,32 0,32 0,32 --- --- --- --- --- --- --- --- 0,32 --- --- --- --- --- --- --- --- ---

Valdivia Ciruelos C2 7SA612 --- --- 8,75 2,48 2,37 0,31 0,02 0,02 --- --- --- --- --- 4,93 2,48 2,81 --- --- 2,38 --- 2,49 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- 8,76 2,49 2,38 0,33 0,03 0,03 --- --- --- --- --- 4,94 2,49 2,82 --- --- 2,39 --- 2,5 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- --- 5,06 3,21 --- --- --- --- --- --- 0,02 0,02 2,93 --- --- --- --- --- --- --- 15,00 14,16

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- --- 5,06 3,23 --- --- --- --- --- --- 0,03 0,03 2,93 --- --- --- --- --- --- --- 15,00 14,16

Valdivia Ciruelos C1 7SA612 --- --- --- 2,4 2,2 3,08 --- --- --- --- --- --- --- --- 2,38 1,58 0,31 0,02 2,21 --- 2,41 --- --- --- --- --- ---

Valdivia Ciruelos C1 P443 --- --- --- 2,41 2,21 3,09 --- --- --- --- --- --- --- --- 2,39 1,59 0,02 0,02 2,22 --- 2,42 --- --- --- --- --- ---

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,19 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 1,21 --- --- --- --- --- --- --- 1,21 1,21 1,21 --- --- --- --- --- --- --- --- --- 0,02 --- 1,21 1,21 --- ---

Mulchen Cautín C1 D60 0,43 1,23 --- --- --- --- --- --- --- 1,23 1,23 --- --- --- --- --- --- --- --- --- --- 0,03 --- 1,23 1,23 --- ---

Cautín Mulchen C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02 --- --- --- --- ---

Cautín Mulchen C1 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,03 --- --- --- --- ---

Mulchen Cautín C2 7SA612 0,41 1,21 --- --- --- --- --- --- --- 1,21 1,21 1,21 --- --- --- --- --- --- --- --- --- --- 0,02 1,21 1,21 --- ---

Mulchen Cautín C2 D60 0,43 1,23 --- --- --- --- --- --- --- 1,23 1,23 --- --- --- --- --- --- --- --- --- --- --- 0,03 1,23 1,23 --- ---

Cautín Cautín C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02 --- --- --- ---

Cautín Mulchen C2 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,03 --- --- --- ---

Temuco Cautín C1 7SA612 1,02 1,02 1,02 --- --- --- --- --- --- 1,02 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 0,39 3,31 --- ---

Cautín Temuco C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,56 0,79 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
149-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 1,02 1,02 1,02 --- --- --- --- --- --- 1,02 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 3,31 0,39 --- ---

Cautín Temuco C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,79 0,56 --- ---

Valdivia Rahue C2 7SA612 --- --- --- 3,31 3,31 3,31 3,31 3,31 3,31 --- --- --- --- --- 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- --- --- 0,61 ---

Valdivia Rahue C2 D60 --- --- --- 3,33 3,33 3,33 3,33 3,33 3,33 --- --- --- --- --- 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- --- --- 0,63 ---

Rahue Valdivia C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61 ---

Rahue Valdivia C2 7SA87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61 ---

Valdivia Rahue C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,17

Valdivia Rahue C1 P443 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 1,01 1,01 1,01 1,01 0,61 0,61 --- --- --- --- --- 1,01 1,01 1,01 0,61 1,01 --- 1,01 --- --- --- --- --- 0,61

Rahue Valdivia C1 D60 --- --- --- 1,03 1,03 1,03 1,03 0,63 0,63 --- --- --- --- --- 1,03 1,03 1,03 0,63 1,03 --- 1,03 --- --- --- --- --- 0,63

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
150-
285

II.3. Escenario 3. Hidrología Seca y Demanda Alta (HS-DA)

II.3.1. Falla Trifásica

Tabla II.13 – Tiempos de Operación, falla Trifásica


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 --- --- --- --- --- 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 0,63 0,63 0,63 0,63 0,63 0,63 --- --- --- --- --- 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 0,61 0,61 0,02 0,02 --- --- --- --- --- 0,61 1,21 --- --- --- --- --- --- --- --- --- --- 1,21 1,21 0,61 0,61 --- ---

Ciruelos Cautín C2 REL670 0,62 0,62 0,02 0,02 --- --- --- --- --- 0,62 1,22 --- --- --- --- --- --- --- --- --- --- 1,22 1,22 0,62 0,62 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 0,61 0,61 0,61 0,61 0,61 0,61 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- --- 0,63 0,63 0,63 0,63 0,63 0,63 0,03 0,03 0,63 0,63 0,63 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,61 0,61 2,51 0,61 0,61 2,51 2,51 2,51 2,51 0,61 0,61 0,02 0,02 0,61 0,61 2,51 2,51 2,51 0,61 --- 2,51 2,51 2,51 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,61 0,61 --- --- --- --- --- --- --- 0,61 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C1 D60 0,63 0,63 --- --- --- --- --- --- --- 0,63 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 0,63 0,63 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- 1,21 0,31 --- --- --- --- --- --- --- 1,21 1,21

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,02 0,32 0,32 --- --- --- --- --- --- --- 1,22 0,32 --- --- --- --- --- --- --- 1,22 1,22

Valdivia Ciruelos C2 7SA612 --- --- --- 0,31 0,31 0,31 0,02 0,02 --- --- --- --- --- 1,21 0,31 0,31 --- --- 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- --- 0,33 0,33 0,33 0,03 0,03 --- --- --- --- --- 1,23 0,33 0,33 --- --- 0,33 --- 0,33 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- 3,21 0,31 0,31 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- 3,23 0,33 0,33 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 3,21 3,21 3,21 0,31 0,31 0,31 --- 3,31 3,31 3,21 3,21 3,21 3,21 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Valdivia Ciruelos C1 P443 3,21 3,21 3,21 0,31 0,31 0,31 3,31 3,31 3,31 3,21 --- --- --- 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Trafo 230/24 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 2,03 --- --- --- --- --- --- ---
Mariquina D30
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,05 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- 0,02 --- 3,01 3,01 --- ---

Cautín Mulchen C1 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- 0,03 --- 3,03 3,03 --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- --- 0,02 3,01 3,01 --- ---

Cautín Mulchen C2 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- --- 0,03 3,03 3,03 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
151-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 3,41 3,41 3,41 --- --- --- --- --- --- --- --- --- --- 0,41 3,31 --- ---

Cautín Temuco C1 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

Temuco Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 3,41 3,41 3,41 --- --- --- --- --- --- --- --- --- --- 3,31 0,41 --- ---

Cautín Temuco C2 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

Valdivia Rahue C2 7SA612 --- --- --- 3,31 3,31 3,31 3,31 3,31 3,31 --- --- --- --- --- 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- --- --- 0,02 3,21

Valdivia Rahue C2 D60 --- --- --- 3,33 3,33 3,33 3,33 3,33 3,33 --- --- --- --- --- 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- --- --- 0,03 3,23

Rahue Valdivia C2 7SA612 --- --- --- 3,21 3,21 3,21 3,21 3,21 3,21 --- --- --- --- --- 3,21 3,21 3,21 3,21 3,21 --- 3,21 --- --- --- --- 0,61 2,01

Rahue Valdivia C2 7SA87 --- --- --- 3,21 3,21 3,21 3,21 3,21 3,21 --- --- --- --- --- 3,21 3,21 3,21 3,21 3,21 --- 3,21 --- --- --- --- 0,61 2,01

Valdivia Rahue C1 7SA612 --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Valdivia Rahue C1 P443 --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 1,01 1,01 1,01 1,01 0,61 0,61 --- --- --- --- --- 1,01 1,01 1,01 0,61 1,01 --- 1,01 --- --- --- --- --- 0,02

Rahue Valdivia C1 D60 --- --- --- 1,03 1,03 1,03 1,03 0,63 0,63 --- --- --- --- --- 1,03 1,03 1,03 0,63 1,03 --- 1,03 --- --- --- --- --- 0,03

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
152-
285

II.3.2. Falla Bifásica Aislada

Tabla II.14 – Tiempos de Operación, falla Bifásica Aislada


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 --- --- --- --- --- 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 0,63 0,63 0,63 0,63 0,63 0,63 --- --- --- --- --- 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 0,61 0,61 0,02 0,02 --- --- --- --- --- 0,61 1,21 --- --- --- --- --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C2 REL670 0,62 0,62 0,02 0,02 --- --- --- --- --- 0,62 1,22 --- --- --- --- --- --- --- --- --- --- --- --- 0,62 0,62 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 0,61 0,61 0,61 0,61 0,61 0,61 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- --- 0,63 0,63 0,63 0,63 0,63 0,63 0,03 0,03 0,63 0,63 0,63 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,61 0,61 2,51 0,61 0,61 0,61 2,51 2,51 2,51 0,61 0,61 0,02 0,02 0,61 0,61 0,61 2,51 2,51 0,61 --- 0,61 2,51 2,51 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,61 0,61 --- --- --- --- --- --- --- 0,61 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- 3,41 3,41 0,61 0,61 --- ---

Ciruelos Cautín C1 D60 0,63 0,63 --- --- --- --- --- --- --- 0,63 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 0,63 0,63 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- 1,21 0,31 --- --- --- --- --- --- --- 1,21 1,21

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,02 0,32 0,32 --- --- --- --- --- --- --- --- 0,32 --- --- --- --- --- --- --- 1,22 1,22

Valdivia Ciruelos C2 7SA612 --- --- --- 0,31 0,31 0,31 0,02 0,02 --- --- --- --- --- 1,21 0,31 0,31 --- --- 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- --- 0,33 0,33 0,33 0,03 0,03 --- --- --- --- --- 1,23 0,33 0,33 --- --- 0,33 --- 0,33 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- 3,21 0,31 0,31 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- 3,23 0,33 0,33 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 3,21 3,21 3,21 0,31 0,31 0,31 --- 3,31 3,31 3,21 3,21 3,21 3,21 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Valdivia Ciruelos C1 P443 3,21 3,21 3,21 0,31 0,31 0,31 3,31 3,31 3,31 3,21 --- --- --- 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 2,35 --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- 0,02 --- 3,01 3,01 --- ---

Cautín Mulchen C1 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- 0,03 --- 3,03 3,03 --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- --- 0,02 3,01 3,01 --- ---

Cautín Mulchen C2 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- --- 0,03 3,03 3,03 --- ---

Temuco Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 3,41 3,41 3,41 --- --- --- --- --- --- --- --- --- --- 0,41 3,31 --- ---

Cautín Temuco C1 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
153-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 3,41 3,41 3,41 --- --- --- --- --- --- --- --- --- --- 3,31 0,41 --- ---

Cautín Temuco C2 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

Valdivia Rahue C2 7SA612 --- --- --- 3,31 3,31 3,31 3,31 3,31 3,31 --- --- --- --- --- 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- --- --- 0,02 3,21

Valdivia Rahue C2 D60 --- --- --- 3,33 3,33 3,33 3,33 3,33 3,33 --- --- --- --- --- 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- --- --- 0,03 3,23

Rahue Valdivia C2 7SA612 --- --- --- 3,21 3,21 3,21 3,21 3,21 3,21 --- --- --- --- --- 3,21 3,21 3,21 3,21 3,21 --- 3,21 --- --- --- --- 0,61 2,01

Rahue Valdivia C2 7SA87 --- --- --- 3,21 3,21 3,21 3,21 3,21 3,21 --- --- --- --- --- 3,21 3,21 3,21 3,21 3,21 --- 3,21 --- --- --- --- 0,61 2,01

Valdivia Rahue C1 7SA612 --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Valdivia Rahue C1 P443 --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 1,01 1,01 1,01 1,01 0,61 0,61 --- --- --- --- --- 1,01 1,01 1,01 0,61 1,01 --- 1,01 --- --- --- --- --- 0,02

Rahue Valdivia C1 D60 --- --- --- 1,03 1,03 1,03 1,03 0,63 0,63 --- --- --- --- --- 1,03 1,03 1,03 0,63 1,03 --- 1,03 --- --- --- --- --- 0,03

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
154-
285

II.3.3. Falla Bifásica a tierra

Tabla II.15 – Tiempos de Operación, falla Bifásica a tierra


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 --- --- --- --- --- 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 0,63 0,63 0,63 0,63 0,63 0,63 --- --- --- --- --- 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 0,61 0,61 0,02 0,02 --- --- --- --- --- 0,61 1,21 --- --- --- --- --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C2 REL670 0,62 0,62 0,02 0,02 --- --- --- --- --- 0,62 1,22 --- --- --- --- --- --- --- --- --- --- --- --- 0,62 0,62 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 0,61 0,61 0,61 0,61 0,61 0,61 0,02 0,02 0,58 0,61 0,61 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- 11,49 0,63 0,63 0,63 0,63 0,63 0,63 0,03 0,03 0,59 0,63 0,63 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,6 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 --- 0,61 0,61 0,61 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio 1,00 1,00 1,00 --- --- --- --- --- --- 1,00 1,00 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- 1,00 1,00 --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 1,00 1,00 1,00 --- --- --- --- --- --- 1,00 1,00 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- 1,00 1,00 --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,61 0,61 --- --- --- --- --- --- --- 0,61 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- 3,41 3,41 0,61 0,61 --- ---

Ciruelos Cautín C1 D60 0,63 0,63 --- --- --- --- --- --- --- 0,63 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- 3,43 3,43 0,63 0,63 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- 0,31 0,31 --- --- --- --- --- --- --- 1,21 1,21

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,02 0,32 0,32 --- --- --- --- --- --- --- 0,32 0,32 --- --- --- --- --- --- --- 1,22 1,22

Valdivia Ciruelos C2 7SA612 --- --- 6,79 0,31 0,31 0,31 0,02 0,02 --- --- --- 10,79 10,03 1,21 0,31 0,31 8,57 --- 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- 6,8 0,33 0,33 0,33 0,03 0,03 --- --- --- 10,8 10,04 1,23 0,33 0,33 8,58 --- 0,33 --- 0,33 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- 0,31 0,31 0,31 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- 0,33 0,33 0,33 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 3,21 3,21 3,21 0,31 0,31 0,31 --- 3,31 3,31 3,21 3,21 3,21 3,21 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Valdivia Ciruelos C1 P443 3,21 3,21 3,21 0,31 0,31 0,31 3,31 3,31 3,31 3,21 3,21 3,21 3,21 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 2,03 --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- 0,02 --- 3,01 3,01 --- ---

Cautín Mulchen C1 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- 0,03 --- 3,03 3,03 --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- --- 0,02 3,01 3,01 --- ---

Cautín Mulchen C2 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- --- 0,03 3,03 3,03 --- ---

Temuco Cautín C1 7SA612 0,41 0,41 1,02 --- --- --- --- --- --- 0,41 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 0,28 3,31 --- ---

Cautín Temuco C1 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 3,31 --- --- --- --- --- --- --- --- --- --- --- --- 0,37 0,41 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
155-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 0,41 0,41 1,02 --- --- --- --- --- --- 0,41 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 3,31 0,28 --- ---

Cautín Temuco C2 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 3,31 --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,37 --- ---

Valdivia Rahue C2 7SA612 --- --- --- 3,31 3,31 3,31 3,31 3,31 0,02 --- --- --- --- --- 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- --- --- 0,02 3,21

Valdivia Rahue C2 D60 --- --- --- 3,33 3,33 3,33 3,33 3,33 3,33 --- --- --- --- --- 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- --- --- 0,03 3,23

Rahue Valdivia C2 7SA612 --- --- --- 3,21 3,21 3,21 3,21 1,98 1,84 --- --- --- --- --- 3,21 3,21 3,21 1,98 3,21 --- 3,21 --- --- --- --- 0,42 2,01

Rahue Valdivia C2 7SA87 --- --- --- 3,21 3,21 3,21 3,21 1,98 1,84 --- --- --- --- --- 3,21 3,21 3,21 1,98 3,21 --- 3,21 --- --- --- --- 0,42 2,01

Valdivia Rahue C1 7SA612 --- --- --- --- --- --- --- 1,51 0,02 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Valdivia Rahue C1 P443 --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 1,01 1,01 1,01 1,01 0,61 0,61 --- --- --- --- --- 1,01 1,01 1,01 0,61 1,01 --- 1,01 --- --- --- --- --- 0,02

Rahue Valdivia C1 D60 --- --- --- 1,03 1,03 1,03 1,03 0,63 0,63 --- --- --- --- --- 1,03 1,03 1,03 0,63 1,03 --- 1,03 --- --- --- --- --- 0,03

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
156-
285

II.3.4. Falla Monofásica

Tabla II.16 – Tiempos de Operación, falla Monofásica


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 0,61 0,61 0,61 1,93 3,44 3,73 --- --- --- --- 3,95 0,61 0,61 1,91 3,43 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 0,63 0,63 0,63 1,94 3,45 3,74 --- --- --- --- 3,96 0,63 0,63 1,92 3,44 0,63 --- 0,63 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 0,61 0,61 0,02 0,02 --- --- --- --- --- 0,61 14,12 --- --- --- --- --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C2 REL670 0,62 0,62 0,02 0,02 --- --- --- --- --- 0,62 14,12 --- --- --- --- --- --- --- --- --- --- 33,85 33,85 0,62 0,62 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 0,61 0,61 0,61 --- --- 3,31 0,02 0,02 0,5 0,54 0,61 0,61 0,61 --- --- 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- 7,93 0,63 0,63 0,63 --- --- 3,23 0,03 0,03 0,51 0,55 0,63 0,63 0,63 --- --- 0,63 --- 0,63 --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,61 0,61 0,61 0,61 0,61 0,61 0,61 2,51 2,51 0,61 0,52 0,02 0,02 0,61 0,61 0,61 0,61 2,51 0,61 --- 0,61 2,51 2,51 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio 1,00 1,00 1,00 --- --- --- --- --- --- 1,00 1,00 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- 1,00 1,00 --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 1,00 1,00 1,00 --- --- --- --- --- --- 1,00 1,00 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- 1,00 1,00 --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,61 0,61 --- --- --- --- --- --- --- 0,61 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C1 D60 0,63 3,43 --- --- --- --- --- --- --- 0,63 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 0,63 0,63 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- --- 0,31 --- --- --- --- --- --- --- --- ---

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,02 0,32 0,32 --- --- --- --- --- --- --- 1,22 0,32 --- --- --- --- --- --- --- 18,77 15,62

Valdivia Ciruelos C2 7SA612 --- --- 4,86 0,31 0,31 0,31 0,02 0,02 --- --- 11,85 8,03 7,52 3,04 0,31 0,31 7,59 --- 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- 4,87 0,33 0,33 0,33 0,03 0,03 --- --- 11,86 8,04 7,53 3,05 0,33 0,33 7,6 --- 0,33 --- 0,33 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- --- 0,31 0,31 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- --- 0,33 0,33 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 3,21 --- 3,21 0,31 0,31 1,33 --- 3,31 3,31 --- --- --- --- 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C1 P443 3,21 --- 3,21 0,31 0,31 1,34 --- 3,31 3,31 --- --- --- --- 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- --- --- --- ---

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 6,77 --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 4,71 5,06 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 5,07 5,45 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 --- --- --- --- --- --- --- --- --- --- 0,02 --- 3,01 3,01 --- ---

Cautín Mulchen C1 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 --- --- --- --- --- --- --- --- --- --- 0,03 --- 3,03 3,03 --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 4,71 5,06 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 5,07 5,45 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 --- --- --- --- --- --- --- --- --- --- --- 0,02 3,01 3,01 --- ---

Cautín Mulchen C2 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 --- --- --- --- --- --- --- --- --- --- --- 0,03 3,03 3,03 --- ---

Temuco Cautín C1 7SA612 0,41 0,41 1,02 --- --- --- --- --- --- 0,41 0,9 1,02 1,02 1,02 --- --- --- --- --- --- --- 1,02 1,02 0,28 3,31 --- ---

Cautín Temuco C1 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 3,31 --- --- --- --- --- --- --- --- --- --- --- --- 0,36 0,41 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
157-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 0,41 0,41 1,02 --- --- --- --- --- --- 0,41 0,9 1,02 1,02 1,02 --- --- --- --- --- --- --- 1,02 1,02 3,31 0,28 --- ---

Cautín Temuco C2 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 3,31 --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,36 --- ---

Valdivia Rahue C2 7SA612 --- --- --- 3,31 3,31 3,31 3,31 3,31 3,31 --- --- --- --- --- 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- --- --- 0,02 3,21

Valdivia Rahue C2 D60 --- --- --- 3,33 3,33 3,33 3,33 3,33 3,33 --- --- --- --- --- 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- --- --- 0,03 3,23

Rahue Valdivia C2 7SA612 --- --- --- --- 3,21 3,21 3,21 2,15 2,03 --- --- --- --- --- --- 3,21 3,21 2,15 3,21 --- --- --- --- --- --- 0,42 ---

Rahue Valdivia C2 7SA87 --- --- --- --- 3,21 3,21 3,21 2,15 2,03 --- --- --- --- --- --- 3,21 3,21 2,15 3,21 --- --- --- --- --- --- 0,42 ---

Valdivia Rahue C1 7SA612 --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Valdivia Rahue C1 P443 --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 2,12 1,99 1,93 1,01 0,61 0,61 --- --- --- --- --- 2,12 1,92 1,01 0,61 2,00 --- 2,12 --- --- --- --- --- 0,02

Rahue Valdivia C1 D60 --- --- --- 2,13 2,00 1,94 1,03 0,63 0,63 --- --- --- --- --- 2,13 1,93 1,03 0,63 2,01 --- 2,13 --- --- --- --- --- 0,03

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
158-
285

II.3.5. Falla Bifásica a tierra R=25 Ω

Tabla II.17 – Tiempos de Operación, falla Bifásica R=25 Ω


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 1,7 1,89 2,03 3,25 --- --- --- --- --- --- --- 2 2,03 3,25 --- 1,89 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 1,71 1,9 2,04 3,26 --- --- --- --- --- --- --- 2,01 2,04 3,26 --- 1,9 --- 0,63 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 8,07 5,16 0,02 0,02 --- --- --- --- --- 9,14 --- --- --- --- --- --- --- --- --- --- --- --- --- 8,73 8,73 --- ---

Ciruelos Cautín C2 REL670 8,08 5,17 0,62 0,02 --- --- --- --- --- 9,15 --- --- --- --- --- --- --- --- --- --- --- --- --- 8,74 8,74 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 0,61 0,61 0,61 --- --- --- 0,02 0,58 0,61 0,61 0,61 0,61 0,61 --- --- 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- --- 0,63 0,63 0,63 0,63 --- --- 0,03 0,59 0,63 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- 0,63 --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,61 0,61 0,61 0,61 0,61 0,61 0,61 2,51 2,51 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 2,51 0,61 --- 0,61 0,61 0,61 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- --- --- --- --- --- --- --- --- --- 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 9,11 14,69 --- --- --- --- --- --- --- 3,41 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- --- --- 9,77 9,77 --- ---

Ciruelos Cautín C1 D60 9,11 14,69 --- --- --- --- --- --- --- 6,88 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 9,77 9,77 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- --- 0,31 --- --- --- --- --- --- --- --- ---

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,31 0,32 0,32 0,32 --- --- --- --- --- --- --- --- 0,32 --- --- --- --- --- --- --- --- ---

Valdivia Ciruelos C2 7SA612 --- --- 10,66 2,43 2,29 0,31 0,02 0,02 --- --- --- --- --- --- 2,43 2,71 --- --- 2,29 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- 10,67 2,44 2,3 0,33 0,03 0,03 --- --- --- --- --- --- 2,44 2,72 --- --- 2,3 --- 0,33 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- --- 4,33 3,21 --- --- --- --- --- --- 0,02 0,02 2,55 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- --- 4,33 3,23 --- --- --- --- --- --- 0,03 0,03 2,55 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 --- --- --- 2,31 2,09 2,84 --- --- --- --- --- --- --- --- 2,3 1,53 0,31 0,02 2,1 --- 2,27 --- --- --- --- --- ---

Valdivia Ciruelos C1 P443 --- --- --- 2,32 2,1 2,85 --- --- --- --- --- --- --- --- 2,31 1,54 0,31 0,02 2,11 --- 2,28 --- --- --- --- --- ---

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,19 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 1,21 1,21 --- --- --- --- --- --- --- 1,21 1,21 --- --- --- --- --- --- --- --- --- --- 0,02 --- 1,21 1,21 --- ---

Mulchen Cautín C1 D60 1,23 1,23 --- --- --- --- --- --- --- 1,23 1,23 --- --- --- --- --- --- --- --- --- --- 0,03 --- 1,23 1,23 --- ---

Cautín Mulchen C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02 --- --- --- --- ---

Cautín Mulchen C1 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,03 --- --- --- --- ---

Mulchen Cautín C2 7SA612 1,21 1,21 --- --- --- --- --- --- --- 1,21 1,21 --- --- --- --- --- --- --- --- --- --- --- 0,02 1,21 1,21 --- ---

Mulchen Cautín C2 D60 1,23 1,23 --- --- --- --- --- --- --- 1,23 1,23 --- --- --- --- --- --- --- --- --- --- --- 0,03 1,23 1,23 --- ---

Cautín Cautín C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02 --- --- --- ---

Cautín Mulchen C2 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,03 --- --- --- ---

Temuco Cautín C1 7SA612 1,02 1,02 --- --- --- --- --- --- --- 1,02 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 0,39 3,31 --- ---

Cautín Temuco C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,58 0,82 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
159-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 1,02 1,02 --- --- --- --- --- --- --- 1,02 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 3,31 0,39 --- ---

Cautín Temuco C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,82 0,58 --- ---

Valdivia Rahue C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61 3,21

Valdivia Rahue C2 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,63 3,23

Rahue Valdivia C2 7SA612 --- --- --- --- --- --- --- --- 4,06 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,82 ---

Rahue Valdivia C2 7SA87 --- --- --- --- --- --- --- --- 4,06 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,82 ---

Valdivia Rahue C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,17

Valdivia Rahue C1 P443 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- --- 3,94 3,63 2,37 1,53 1,48 --- --- --- --- --- --- 3,6 2,34 1,53 3,97 --- --- --- --- --- --- --- 0,61

Rahue Valdivia C1 D60 --- --- --- --- 3,95 3,64 2,38 1,54 1,49 --- --- --- --- --- --- 3,61 2,35 1,54 3,98 --- --- --- --- --- --- --- 0,63

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
160-
285

II.3.6. Falla Monofásica R=25 Ω

Tabla II.18 – Tiempos de Operación, falla Monofásica R=25 Ω


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 1,6 1,8 1,93 3,13 --- --- --- --- --- --- --- 1,9 1,93 3,13 --- 1,8 --- 1,87 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 1,61 1,81 1,94 3,14 --- --- --- --- --- --- --- 1,91 1,94 3,14 --- 1,81 --- 1,88 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 7,91 4,98 0,02 0,02 --- --- --- --- --- 8,83 --- --- --- --- --- --- --- --- --- --- --- --- --- 8,62 8,62 --- ---

Ciruelos Cautín C2 REL670 7,91 4,97 0,02 0,02 --- --- --- --- --- 8,84 --- --- --- --- --- --- --- --- --- --- --- --- --- 8,63 8,63 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 0,61 0,61 0,61 --- --- --- 0,02 0,02 0,61 0,61 0,61 0,61 0,61 --- --- 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- --- 0,63 0,63 0,63 --- --- --- 0,03 0,56 0,63 0,63 0,63 0,63 0,63 --- --- 0,63 --- 0,63 --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,61 0,61 0,61 0,61 0,61 0,61 0,61 2,51 2,51 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 2,51 0,61 --- 0,61 0,61 0,61 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- --- 1,00 --- --- --- --- --- --- --- 1,00 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- --- 1,00 --- --- --- --- --- --- --- 1,00 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 9,08 14,19 --- --- --- --- --- --- --- 3,41 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- --- --- 9,81 9,81 --- ---

Ciruelos Cautín C1 D60 9,08 14,19 --- --- --- --- --- --- --- 6,76 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 9,81 9,81 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- --- 0,31 --- --- --- --- --- --- --- --- ---

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,32 0,32 0,32 --- --- --- --- --- --- --- --- 0,32 --- --- --- --- --- --- --- --- ---

Valdivia Ciruelos C2 7SA612 --- --- 8,19 2,32 2,21 0,31 0,31 0,02 --- --- --- --- --- 4,63 2,31 2,61 --- --- 2,21 --- 2,32 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- 8,2 2,33 2,22 0,33 0,03 0,03 --- --- --- --- --- 4,64 2,32 2,62 --- --- 2,22 --- 2,33 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- --- 4,81 3,21 --- --- --- --- --- --- 0,02 0,02 2,78 --- --- --- --- --- --- --- 14,86 14

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- --- 4,81 3,23 --- --- --- --- --- --- 0,03 0,03 2,78 --- --- --- --- --- --- --- 14,86 14

Valdivia Ciruelos C1 7SA612 --- --- --- 2,16 2,00 2,67 --- --- --- --- --- --- --- --- 2,15 1,48 0,31 0,02 2,00 --- 2,16 --- --- --- --- --- ---

Valdivia Ciruelos C1 P443 --- --- --- 2,17 2,01 2,68 --- --- --- --- --- --- --- --- 2,16 1,49 0,02 0,02 2,01 --- 2,17 --- --- --- --- --- ---

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,19 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 --- --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 --- --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02 --- --- --- --- ---

Cautín Mulchen C1 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,03 --- --- --- --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 --- --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 --- --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02 --- --- --- ---

Cautín Mulchen C2 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,03 --- --- --- ---

Temuco Cautín C1 7SA612 1,02 1,02 1,02 --- --- --- --- --- --- 1,02 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 0,39 3,31 --- ---

Cautín Temuco C1 7SA612 3,21 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,58 0,82 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
161-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 1,02 1,02 1,02 --- --- --- --- --- --- 1,02 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 3,31 0,39 --- ---

Cautín Temuco C2 7SA612 3,21 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,82 0,58 --- ---

Valdivia Rahue C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61 3,21

Valdivia Rahue C2 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,03 3,23

Rahue Valdivia C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61 ---

Rahue Valdivia C2 7SA87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61 ---

Valdivia Rahue C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,17

Valdivia Rahue C1 P443 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 4,08 3,73 3,44 2,33 1,61 1,01 --- --- --- --- --- 4,05 3,42 2,3 1,6 3,75 --- 4,08 --- --- --- --- --- 0,61

Rahue Valdivia C1 D60 --- --- --- 4,09 3,74 3,45 2,34 1,62 1,03 --- --- --- --- --- 4,06 3,43 2,31 1,61 3,76 --- 4,09 --- --- --- --- --- 0,63

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
162-
285

II.4. Escenario 4. Hidrología Seca y Demanda Baja (HS-DB)

II.4.1. Falla Trifásica

Tabla II.19 – Tiempos de Operación, falla Trifásica


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 --- --- --- --- --- 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 0,63 0,63 0,63 0,63 0,63 0,63 --- --- --- --- --- 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- ---

Ciruelos Cautín C2 7SA612 0,61 0,61 0,02 0,02 --- --- --- --- --- 0,61 1,21 --- --- --- --- --- --- --- --- --- --- 1,21 1,21 0,61 0,61 --- ---

Ciruelos Cautín C2 REL670 0,62 0,62 0,02 0,02 --- --- --- --- --- 0,62 1,22 --- --- --- --- --- --- --- --- --- --- 1,22 1,22 0,62 0,62 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 0,61 0,61 0,61 0,61 0,61 0,61 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- --- 0,63 0,63 0,63 0,63 0,63 0,63 0,03 0,03 0,63 0,63 0,63 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,61 0,61 2,51 2,51 2,51 2,51 --- --- --- 0,61 0,61 0,02 0,02 0,61 2,51 2,51 --- --- 2,51 --- 2,51 --- --- 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,61 0,61 --- --- --- --- --- --- --- 0,61 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C1 D60 0,63 0,63 --- --- --- --- --- --- --- 0,63 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 0,63 0,63 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- --- 0,31 --- --- --- --- --- --- --- --- ---

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,02 0,32 0,32 --- --- --- --- --- --- --- --- 0,32 --- --- --- --- --- --- --- --- ---

Valdivia Ciruelos C2 7SA612 --- --- --- 0,31 0,31 0,31 0,02 0,02 --- --- --- --- --- 1,21 0,31 0,31 --- --- 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- --- 0,33 0,33 0,33 0,03 0,03 --- --- --- --- --- 1,23 0,33 0,33 --- --- 0,33 --- 0,33 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- 3,21 0,31 0,31 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- 3,21 0,33 0,33 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 3,21 3,21 3,21 0,31 0,31 0,31 --- 3,31 3,31 3,21 3,21 3,21 3,21 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Valdivia Ciruelos C1 P443 3,21 3,21 3,21 0,31 0,31 0,31 --- 3,31 3,31 3,21 3,21 3,21 3,21 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Trafo 230/24 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 2,03 --- --- --- --- --- --- ---
Mariquina D30
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,05 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- 0,02 --- 3,01 3,01 --- ---

Cautín Mulchen C1 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- 0,03 --- 3,03 3,03 --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- --- 0,02 3,01 3,01 --- ---

Cautín Mulchen C2 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- --- 0,03 3,03 3,03 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
163-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 3,41 3,41 3,41 --- --- --- --- --- --- --- --- --- --- 0,41 3,31 --- ---

Cautín Temuco C1 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

Temuco Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 3,41 3,41 3,41 --- --- --- --- --- --- --- --- --- --- 3,31 0,41 --- ---

Cautín Temuco C2 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

Valdivia Rahue C2 7SA612 --- --- --- 3,31 3,31 3,31 3,31 3,31 3,31 --- --- --- --- --- 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- --- --- 0,02 3,21

Valdivia Rahue C2 D60 --- --- --- 3,33 3,33 3,33 3,33 3,33 3,33 --- --- --- --- --- 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- --- --- 0,03 3,23

Rahue Valdivia C2 7SA612 --- --- --- 3,21 3,21 3,21 3,21 3,21 3,21 --- --- --- --- --- 3,21 3,21 3,21 3,21 3,21 --- 3,21 --- --- --- --- 0,61 2,01

Rahue Valdivia C2 7SA87 --- --- --- 3,21 3,21 3,21 3,21 3,21 3,21 --- --- --- --- --- 3,21 3,21 3,21 3,21 3,21 --- 3,21 --- --- --- --- 0,61 2,01

Valdivia Rahue C1 7SA612 --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Valdivia Rahue C1 P443 --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 1,01 1,01 1,01 1,01 0,61 0,61 --- --- --- --- --- 1,01 1,01 1,01 0,61 1,01 --- 1,01 --- --- --- --- --- 0,02

Rahue Valdivia C1 D60 --- --- --- 1,03 1,03 1,03 1,03 0,63 0,63 --- --- --- --- --- 1,03 1,03 1,03 0,63 1,03 --- 1,03 --- --- --- --- --- 0,03

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
164-
285

II.4.2. Falla Bifásica Aislada

Tabla II.20 – Tiempos de Operación, falla Bifásica Aislada


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 --- --- --- --- --- 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 0,63 0,63 0,63 0,63 0,63 0,63 --- --- --- --- --- 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 0,61 0,61 0,02 0,02 --- --- --- --- --- 0,61 1,21 --- --- --- --- --- --- --- --- --- --- 1,21 1,21 0,61 0,61 --- ---

Ciruelos Cautín C2 REL670 0,62 0,62 0,02 0,02 --- --- --- --- --- 0,62 1,22 --- --- --- --- --- --- --- --- --- --- 1,22 1,22 0,62 0,62 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 0,61 0,61 0,61 0,61 0,61 0,61 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- --- 0,63 0,63 0,63 0,63 0,63 0,63 0,03 0,03 0,63 0,63 0,63 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,61 0,61 2,51 2,51 2,51 2,51 2,51 2,51 2,51 0,61 0,61 0,02 0,02 0,61 2,51 2,51 2,51 2,51 2,51 --- 2,51 2,51 2,51 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,61 0,61 --- --- --- --- --- --- --- 0,61 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- 3,41 3,41 0,61 0,61 --- ---

Ciruelos Cautín C1 D60 0,63 0,63 --- --- --- --- --- --- --- 0,63 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 0,63 0,63 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- --- 0,31 --- --- --- --- --- --- --- --- ---

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,02 0,32 0,32 --- --- --- --- --- --- --- --- 0,32 --- --- --- --- --- --- --- --- ---

Valdivia Ciruelos C2 7SA612 --- --- --- 0,31 0,31 0,31 0,02 0,02 --- --- --- --- --- 1,21 0,31 0,31 --- --- 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- --- 0,33 0,33 0,33 0,03 0,03 --- --- --- --- --- 1,23 0,33 0,33 --- --- 0,33 --- 0,33 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- 3,21 0,31 0,31 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- 3,21 0,33 0,33 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 3,21 3,21 3,21 0,31 0,31 0,31 --- 3,31 3,31 3,21 3,21 3,21 3,21 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Valdivia Ciruelos C1 P443 3,21 3,21 3,21 0,31 0,31 0,31 --- 3,31 3,31 3,21 3,21 3,21 3,21 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 2,35 --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- 0,02 --- 3,01 3,01 --- ---

Cautín Mulchen C1 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- 0,03 --- 3,03 3,03 --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- --- 0,02 3,01 3,01 --- ---

Cautín Mulchen C2 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- --- 0,03 3,03 3,03 --- ---

Temuco Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 3,41 3,41 3,41 --- --- --- --- --- --- --- --- --- --- 0,41 3,31 --- ---

Cautín Temuco C1 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
165-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 3,41 3,41 3,41 --- --- --- --- --- --- --- --- --- --- 3,31 0,41 --- ---

Cautín Temuco C2 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

Valdivia Rahue C2 7SA612 --- --- --- 3,31 3,31 3,31 3,31 3,31 3,31 --- --- --- --- --- 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- --- --- 0,02 3,21

Valdivia Rahue C2 D60 --- --- --- 3,33 3,33 3,33 3,33 3,33 3,33 --- --- --- --- --- 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- --- --- 0,03 3,23

Rahue Valdivia C2 7SA612 --- --- --- 3,21 3,21 3,21 3,21 3,21 3,21 --- --- --- --- --- 3,21 3,21 3,21 3,21 3,21 --- 3,21 --- --- --- --- 0,61 2,01

Rahue Valdivia C2 7SA87 --- --- --- 3,21 3,21 3,21 3,21 3,21 3,21 --- --- --- --- --- 3,21 3,21 3,21 3,21 3,21 --- 3,21 --- --- --- --- 0,61 2,01

Valdivia Rahue C1 7SA612 --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Valdivia Rahue C1 P443 --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 1,01 1,01 1,01 1,01 0,61 0,61 --- --- --- --- --- 1,01 1,01 1,01 0,61 1,01 --- 1,01 --- --- --- --- --- 0,02

Rahue Valdivia C1 D60 --- --- --- 1,03 1,03 1,03 1,03 0,63 0,63 --- --- --- --- --- 1,03 1,03 1,03 0,63 1,03 --- 1,03 --- --- --- --- --- 0,03

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
166-
285

II.4.3. Falla Bifásica a tierra

Tabla II.21 – Tiempos de Operación, falla Bifásica a tierra


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 --- --- --- --- --- 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 0,63 0,63 0,63 0,63 1,23 0,63 --- --- --- --- --- 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 0,61 0,61 0,02 0,02 --- --- --- --- --- 0,61 1,21 --- --- --- --- --- --- --- --- --- --- 1,21 1,21 0,61 0,61 --- ---

Ciruelos Cautín C2 REL670 0,62 0,62 0,02 0,02 --- --- --- --- --- 0,62 1,22 --- --- --- --- --- --- --- --- --- --- 1,22 1,22 0,62 0,62 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 0,61 0,61 0,61 0,61 0,61 0,61 0,02 0,02 0,6 0,61 0,61 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- 6,25 0,63 0,63 0,63 0,63 0,63 0,63 0,03 0,03 0,61 0,63 0,63 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,6 0,46 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 --- 0,61 0,61 0,61 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio 1,00 1,00 1,00 --- --- --- --- --- --- 1,00 1,00 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- 1,00 1,00 --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 1,00 1,00 1,00 --- --- --- --- --- --- 1,00 1,00 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- 1,00 1,00 --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,61 0,61 --- --- --- --- --- --- --- 0,61 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- 3,41 3,41 0,61 0,61 --- ---

Ciruelos Cautín C1 D60 0,63 0,63 --- --- --- --- --- --- --- 0,63 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 0,63 0,63 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- 0,31 0,31 --- --- --- --- --- --- --- 1,21 1,21

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,02 0,32 0,32 --- --- --- --- --- --- --- 0,32 0,32 --- --- --- --- --- --- --- 1,22 1,22

Valdivia Ciruelos C2 7SA612 --- --- 7,17 0,31 0,31 0,31 0,02 0,02 --- --- --- 11,96 10,98 1,21 0,31 0,31 9,59 --- 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- 7,18 0,33 0,33 0,33 0,03 0,03 --- --- --- 11,97 10,99 1,23 0,33 0,33 9,6 --- 0,33 --- 0,33 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- 3,21 0,31 0,31 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- 3,23 0,33 0,33 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 3,21 3,21 3,21 0,31 0,31 0,31 --- 3,31 3,31 3,21 3,21 3,21 3,21 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Valdivia Ciruelos C1 P443 3,21 3,21 3,21 0,31 0,31 0,31 --- 3,31 3,31 3,21 3,21 3,21 3,21 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 2,03 --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- 0,02 --- 3,01 3,01 --- ---

Cautín Mulchen C1 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- 0,03 --- 3,03 3,03 --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- --- 0,02 3,01 3,01 --- ---

Cautín Mulchen C2 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- --- 0,03 3,03 3,03 --- ---

Temuco Cautín C1 7SA612 0,41 0,41 1,02 --- --- --- --- --- --- 0,41 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 0,28 3,31 --- ---

Cautín Temuco C1 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 3,31 --- --- --- --- --- --- --- --- --- --- --- --- 0,36 0,41 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
167-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 0,41 0,41 1,02 --- --- --- --- --- --- 0,41 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 3,31 0,28 --- ---

Cautín Temuco C2 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 3,31 --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,36 --- ---

Valdivia Rahue C2 7SA612 --- --- --- 3,31 3,31 3,31 3,31 3,31 0,02 --- --- --- --- --- 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- --- --- 0,02 3,21

Valdivia Rahue C2 D60 --- --- --- 3,33 3,33 3,33 3,33 3,33 3,33 --- --- --- --- --- 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- --- --- 0,03 3,23

Rahue Valdivia C2 7SA612 --- --- --- 3,21 3,21 3,21 3,21 1,99 1,85 --- --- --- --- --- 3,21 3,21 3,21 1,99 3,21 --- 3,21 --- --- --- --- 0,42 2,01

Rahue Valdivia C2 7SA87 --- --- --- 3,21 3,21 3,21 3,21 1,99 1,85 --- --- --- --- --- 3,21 3,21 3,21 1,99 3,21 --- 3,21 --- --- --- --- 0,42 2,01

Valdivia Rahue C1 7SA612 --- --- --- --- --- --- --- 1,51 0,02 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Valdivia Rahue C1 P443 --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 1,01 1,01 1,01 1,01 0,61 0,61 --- --- --- --- --- 1,01 1,01 1,01 0,61 1,01 --- 1,01 --- --- --- --- --- 0,02

Rahue Valdivia C1 D60 --- --- --- 1,03 1,03 1,03 1,03 0,63 0,63 --- --- --- --- --- 1,03 1,03 1,03 0,63 1,03 --- 1,03 --- --- --- --- --- 0,03

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
168-
285

II.4.4. Falla Monofásica

Tabla II.22 – Tiempos de Operación, falla Monofásica


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 0,61 0,61 0,61 1,97 3,61 3,94 --- --- --- --- 4,11 0,61 0,61 1,95 3,6 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 0,63 0,63 0,63 1,98 3,62 3,95 --- --- --- --- 4,12 0,63 0,63 1,96 3,61 0,63 --- 0,63 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 0,61 0,61 0,02 0,02 --- --- --- --- --- 0,61 13,07 --- --- --- --- --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C2 REL670 0,62 0,62 0,02 0,02 --- --- --- --- --- 0,62 13,07 --- --- --- --- --- --- --- --- --- --- 31,1 31,1 0,62 0,62 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 0,61 0,61 0,61 --- --- --- 0,02 0,02 0,53 0,57 0,61 0,61 0,61 --- --- 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- 4,72 0,63 0,63 0,63 --- --- --- 0,03 0,03 0,54 0,58 0,63 0,63 0,63 --- --- 0,63 --- 0,63 --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,59 0,57 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,56 0,41 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 --- 0,61 2,07 2,07 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio 1,00 1,00 1,00 --- --- --- --- --- --- 1,00 1,00 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- 1,00 1,00 --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 1,00 1,00 1,00 --- --- --- --- --- --- 1,00 1,00 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- 1,00 1,00 --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,61 3,41 --- --- --- --- --- --- --- 0,61 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C1 D60 0,63 3,43 --- --- --- --- --- --- --- 0,63 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 0,63 0,63 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- --- 0,31 --- --- --- --- --- --- --- --- ---

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,02 0,32 0,32 --- --- --- --- --- --- --- --- 0,32 --- --- --- --- --- --- --- 13,97 12,22

Valdivia Ciruelos C2 7SA612 --- --- 5,21 0,31 0,31 0,31 0,02 0,02 --- --- 14,79 9,36 8,66 3,2 0,31 0,31 8,7 --- 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- 5,22 0,33 0,33 0,33 0,03 0,03 --- --- 14,79 9,37 8,66 3,21 0,33 0,33 8,69 --- 0,33 --- 0,33 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- --- 0,31 0,31 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- --- 0,33 0,33 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 --- --- 3,21 0,31 0,31 1,37 --- 3,31 3,31 --- --- --- --- 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C1 P443 --- --- 3,21 0,31 0,31 1,38 --- 3,31 3,31 --- --- --- --- 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- --- --- --- ---

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 6,9 --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 4,92 5,33 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 5,3 5,76 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 --- --- --- --- --- --- --- --- --- --- 0,02 --- 3,01 3,01 --- ---

Cautín Mulchen C1 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 --- --- --- --- --- --- --- --- --- --- 0,03 --- 3,03 3,03 --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 4,92 5,33 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 5,3 5,76 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 --- --- --- --- --- --- --- --- --- --- --- 0,02 3,01 3,01 --- ---

Cautín Mulchen C2 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 --- --- --- --- --- --- --- --- --- --- --- 0,03 3,03 3,03 --- ---

Temuco Cautín C1 7SA612 0,41 0,41 1,02 --- --- --- --- --- --- 0,41 0,96 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 0,28 3,31 --- ---

Cautín Temuco C1 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 3,31 --- --- --- --- --- --- --- --- --- --- --- --- 0,35 0,41 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
169-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 0,41 0,41 1,02 --- --- --- --- --- --- 0,41 0,96 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 3,31 0,28 --- ---

Cautín Temuco C2 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 3,31 --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,35 --- ---

Valdivia Rahue C2 7SA612 --- --- --- 3,31 3,31 3,31 3,31 3,31 3,31 --- --- --- --- --- 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- --- --- 0,02 ---

Valdivia Rahue C2 D60 --- --- --- 3,33 3,33 3,33 3,33 3,33 3,33 --- --- --- --- --- 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- --- --- 0,03 ---

Rahue Valdivia C2 7SA612 --- --- --- --- 3,21 3,21 3,21 2,18 2,06 --- --- --- --- --- --- 3,21 3,21 2,18 3,21 --- --- --- --- --- --- 0,42 ---

Rahue Valdivia C2 7SA87 --- --- --- --- 3,21 3,21 3,21 2,18 2,06 --- --- --- --- --- --- 3,21 3,21 2,18 3,21 --- --- --- --- --- --- 0,42 ---

Valdivia Rahue C1 7SA612 --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Valdivia Rahue C1 P443 --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 2,18 2,04 1,97 1,01 0,61 0,61 --- --- --- --- --- 2,17 1,96 1,01 0,61 2,05 --- 2,18 --- --- --- --- --- 0,02

Rahue Valdivia C1 D60 --- --- --- 2,19 2,05 1,98 1,03 0,63 0,63 --- --- --- --- --- 2,18 1,97 1,03 0,63 2,06 --- 2,19 --- --- --- --- --- 0,03

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
170-
285

II.4.5. Falla Bifásica a tierra R=25 Ω

Tabla II.23 – Tiempos de Operación, falla Bifásica R=25 Ω


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 1,7 1,9 2,04 3,3 --- --- --- --- --- --- --- 2,01 2,04 3,3 --- 1,91 --- 1,98 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 1,71 1,91 2,05 3,31 --- --- --- --- --- --- --- 2,02 2,05 3,31 --- 1,92 --- 1,99 --- --- --- --- ---

Ciruelos Cautín C2 7SA612 7,83 5,04 0,02 0,02 --- --- --- --- --- 7,88 --- --- --- --- --- --- --- --- --- --- --- --- --- 8,45 8,45 --- ---

Ciruelos Cautín C2 REL670 7,83 5,03 0,62 0,02 --- --- --- --- --- 7,87 --- --- --- --- --- --- --- --- --- --- --- --- --- 8,45 8,45 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 3,31 0,61 3,31 --- --- --- 0,02 0,6 0,61 0,61 0,61 0,61 3,31 3,31 --- 0,61 --- 3,31 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- 10,06 3,23 0,63 0,63 --- --- --- 0,03 0,61 0,63 0,63 0,63 0,63 0,63 3,23 --- 0,63 --- 0,63 --- --- --- --- --- ---
Trafo 220/110 TO Rio 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,61 0,5 0,5 0,61 0,61 0,61 0,61 0,61 0,61 --- 0,61 0,61 0,61 0,61 0,61 --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- --- 1,00 --- --- --- --- --- --- --- 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- --- 1,00 --- --- --- --- --- --- --- 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,61 3,41 --- --- --- --- --- --- --- 0,61 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- --- --- 3,41 3,41 --- ---

Ciruelos Cautín C1 D60 3,43 3,43 --- --- --- --- --- --- --- 3,43 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 3,43 3,43 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- --- 0,31 --- --- --- --- --- --- --- --- ---

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,31 0,32 0,32 0,32 --- --- --- --- --- --- --- --- 0,32 --- --- --- --- --- --- --- --- ---

Valdivia Ciruelos C2 7SA612 --- --- 11,49 2,47 2,32 0,31 0,02 0,02 --- --- --- --- --- 5,81 2,47 2,76 --- --- 2,33 --- 2,45 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- 11,5 2,48 2,33 0,33 0,03 0,03 --- --- --- --- --- 5,82 2,48 2,77 --- --- 2,34 --- 2,46 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- --- 4,08 3,24 --- --- --- --- --- --- 0,02 0,02 2,45 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- --- 4,08 3,24 --- --- --- --- --- --- 0,03 0,03 2,45 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 --- --- --- 2,39 2,15 2,98 --- --- --- --- --- --- --- --- 2,38 1,55 0,31 0,02 2,16 --- 2,35 --- --- --- --- --- ---

Valdivia Ciruelos C1 P443 --- --- --- 2,4 2,16 2,99 --- --- --- --- --- --- --- --- 2,39 1,56 0,31 0,02 2,17 --- 2,36 --- --- --- --- --- ---

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,19 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 1,21 1,21 --- --- --- --- --- --- --- 1,21 1,21 --- --- --- --- --- --- --- --- --- --- 0,02 --- 1,21 1,21 --- ---

Mulchen Cautín C1 D60 1,23 1,23 --- --- --- --- --- --- --- 1,23 1,23 --- --- --- --- --- --- --- --- --- --- 0,03 --- 1,23 1,23 --- ---

Cautín Mulchen C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02 --- --- --- --- ---

Cautín Mulchen C1 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,03 --- --- --- --- ---

Mulchen Cautín C2 7SA612 1,21 1,21 --- --- --- --- --- --- --- 1,21 1,21 --- --- --- --- --- --- --- --- --- --- --- 0,02 1,21 1,21 --- ---

Mulchen Cautín C2 D60 1,23 1,23 --- --- --- --- --- --- --- 1,23 1,23 --- --- --- --- --- --- --- --- --- --- --- 0,03 1,23 1,23 --- ---

Cautín Cautín C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02 --- --- --- ---

Cautín Mulchen C2 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,03 --- --- --- ---

Temuco Cautín C1 7SA612 1,02 1,02 --- --- --- --- --- --- --- 1,02 1,02 1,02 1,02 --- --- --- --- --- --- --- --- --- --- 0,39 3,31 --- ---

Cautín Temuco C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,55 0,75 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
171-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 1,02 1,02 --- --- --- --- --- --- --- 1,02 1,02 1,02 1,02 --- --- --- --- --- --- --- --- --- --- 3,31 0,39 --- ---

Cautín Temuco C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,75 0,55 --- ---

Valdivia Rahue C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61 3,21

Valdivia Rahue C2 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,63 3,23

Rahue Valdivia C2 7SA612 --- --- --- --- --- --- --- --- 4,06 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,81 ---

Rahue Valdivia C2 7SA87 --- --- --- --- --- --- --- --- 4,06 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,81 ---

Valdivia Rahue C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,17

Valdivia Rahue C1 P443 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- --- 4,07 3,72 2,39 0,61 0,61 --- --- --- --- --- --- 3,7 2,35 0,61 4,1 --- --- --- --- --- --- --- 0,61

Rahue Valdivia C1 D60 --- --- --- --- 4,08 3,73 2,4 0,63 0,63 --- --- --- --- --- --- 3,71 2,36 0,63 4,11 --- --- --- --- --- --- --- 0,63

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
172-
285

II.4.6. Falla Monofásica R=25 Ω

Tabla II.24 – Tiempos de Operación, falla Monofásica R=25 Ω


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 1,62 1,82 1,96 3,22 --- --- --- --- --- --- --- 1,93 1,96 3,22 --- 1,83 --- 1,9 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 1,63 1,83 1,97 3,23 --- --- --- --- --- --- --- 1,94 1,97 3,23 --- 1,84 --- 1,91 --- --- --- --- ---

Ciruelos Cautín C2 7SA612 7,56 4,83 0,02 0,02 --- --- --- --- --- 8,4 --- --- --- --- --- --- --- --- --- --- --- --- --- 8,2 8,2 --- ---

Ciruelos Cautín C2 REL670 7,56 4,82 0,02 0,02 --- --- --- --- --- 8,39 --- --- --- --- --- --- --- --- --- --- --- --- --- 8,2 8,2 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- --- --- --- --- --- --- 0,02 0,02 0,61 0,61 0,61 3,31 --- --- --- --- --- --- --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- 8,35 --- --- --- --- --- --- 0,03 0,03 0,63 0,63 0,63 3,23 --- --- --- --- --- --- --- --- --- --- --- ---
Trafo 220/110 TO Rio
7SA87 0,61 0,61 0,61 0,61 0,61 0,61 0,61 2,51 2,51 0,61 0,61 0,48 0,47 0,61 0,61 0,61 0,61 2,51 0,61 --- 0,61 2,51 2,51 0,61 0,61 --- ---
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- 1,00 1,00 --- --- --- --- --- --- --- 1,00 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- 1,00 1,00 --- --- --- --- --- --- --- 1,00 1,00 1,00 1,00 --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,61 3,41 --- --- --- --- --- --- --- 0,61 0,61 0,61 0,61 0,02 0,02 --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C1 D60 3,43 3,43 --- --- --- --- --- --- --- 3,43 0,63 0,63 0,63 0,03 0,03 --- --- --- --- --- --- --- --- 3,43 3,43 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- --- 0,31 --- --- --- --- --- --- --- --- ---

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,32 0,32 0,32 --- --- --- --- --- --- --- --- 0,32 --- --- --- --- --- --- --- --- ---

Valdivia Ciruelos C2 7SA612 --- --- 8,96 2,38 2,26 0,31 0,02 0,02 --- --- --- --- --- 4,9 2,38 2,69 --- --- 2,27 --- 2,39 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- 8,97 2,39 2,27 0,33 0,03 0,03 --- --- --- --- --- 4,91 2,39 2,7 --- --- 2,28 --- 2,4 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- --- 4,54 3,63 --- --- --- --- --- --- 0,02 0,02 2,68 --- --- --- --- --- --- --- 13,9 13,13

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- --- 4,54 3,63 --- --- --- --- --- --- 0,03 0,03 2,68 --- --- --- --- --- --- --- 13,9 13,13

Valdivia Ciruelos C1 7SA612 --- --- --- 2,24 2,06 2,81 --- --- --- --- --- --- --- --- 2,23 1,50 0,31 0,02 2,07 --- 2,25 --- --- --- --- --- ---

Valdivia Ciruelos C1 P443 --- --- --- 2,25 2,07 2,82 --- --- --- --- --- --- --- --- 2,24 1,51 0,02 0,02 2,08 --- 2,26 --- --- --- --- --- ---

Trafo 230/24 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
Mariquina D30
kV Mariquina
Planta
Ciruelos 7SJ64 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,19 --- --- --- --- --- ---
Valdivia
Mulchen Cautín C1 7SA612 1,21 1,21 --- --- --- --- --- --- --- 1,21 1,21 --- --- --- --- --- --- --- --- --- --- 0,02 --- 1,21 1,21 --- ---

Mulchen Cautín C1 D60 1,23 1,23 --- --- --- --- --- --- --- 1,23 1,23 --- --- --- --- --- --- --- --- --- --- 0,03 --- 1,23 1,23 --- ---

Cautín Mulchen C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02 --- --- --- --- ---

Cautín Mulchen C1 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,03 --- --- --- --- ---

Mulchen Cautín C2 7SA612 1,21 1,21 --- --- --- --- --- --- --- 1,21 1,21 --- --- --- --- --- --- --- --- --- --- --- 0,02 1,21 1,21 --- ---

Mulchen Cautín C2 D60 1,23 1,23 --- --- --- --- --- --- --- 1,23 1,23 --- --- --- --- --- --- --- --- --- --- --- 0,03 1,23 1,23 --- ---

Cautín Cautín C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02 --- --- --- ---

Cautín Mulchen C2 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,03 --- --- --- ---

Temuco Cautín C1 7SA612 1,02 1,02 1,02 --- --- --- --- --- --- 1,02 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 0,39 3,31 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
173-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Temuco C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,55 0,76 --- ---

Temuco Cautín C2 7SA612 1,02 1,02 1,02 --- --- --- --- --- --- 1,02 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 3,31 0,39 --- ---

Cautín Temuco C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,76 0,55 --- ---

Valdivia Rahue C2 7SA612 --- --- --- --- --- --- --- 3,31 3,31 --- --- --- --- --- --- --- --- 3,31 --- --- --- --- --- --- --- 0,61 ---

Valdivia Rahue C2 D60 --- --- --- --- --- --- --- 3,33 3,33 --- --- --- --- --- --- --- --- 3,33 --- --- --- --- --- --- --- 0,03 ---

Rahue Valdivia C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61 ---

Rahue Valdivia C2 7SA87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61 ---

Valdivia Rahue C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,17

Valdivia Rahue C1 P443 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 4,27 3,89 3,55 2,35 1,01 0,61 --- --- --- --- --- 4,25 3,53 2,31 1,01 3,91 --- 4,28 --- --- --- --- --- 0,61

Rahue Valdivia C1 D60 --- --- --- 4,28 3,9 3,56 2,36 1,03 0,63 --- --- --- --- --- 4,26 3,54 2,32 1,03 3,92 --- 4,29 --- --- --- --- --- 0,63

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
174-
285

II.5. Escenario 5. Hidrología Humeda y Demanda Alta, considerando interruptor en Tap Off Rio Tolten F/S (HH-DA-2)

II.5.1. Falla Trifásica

Tabla II.25 – Tiempos de Operación, falla Trifásica


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 --- --- --- --- --- 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 0,63 0,63 0,63 0,63 0,63 0,63 --- --- --- --- --- 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 0,61 0,61 0,02 0,02 --- --- --- --- --- 0,61 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C2 REL670 0,62 0,62 0,02 0,02 --- --- --- --- --- 0,62 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,62 0,62 --- ---

Cautín Ciruelos C1 7SA612 3,31 --- --- 0,41 0,41 0,41 --- --- --- 0,02 0,02 0,02 0,02 0,02 0,41 0,41 --- --- 0,41 --- 0,41 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 3,33 --- --- 0,43 0,43 0,43 0,62 0,65 0,64 0,03 0,03 0,03 0,03 0,03 0,43 0,43 0,61 0,64 0,43 --- 0,43 --- --- --- --- --- ---
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,41 3,41 --- --- --- --- --- --- --- 0,41 0,41 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

Ciruelos Cautín C1 D60 0,43 3,43 --- --- --- --- --- --- --- 0,43 0,43 0,03 0,03 0,03 0,03 --- --- --- --- --- --- --- --- 0,43 0,43 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- 1,21 0,31 --- --- --- --- --- --- --- 1,21 1,21

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,02 0,32 0,32 --- --- --- --- --- --- --- 1,22 0,32 --- --- --- --- --- --- --- 1,22 1,22

Valdivia Ciruelos C2 7SA612 --- --- --- 0,31 0,31 0,31 0,02 0,02 --- --- --- --- --- --- 0,31 0,31 --- --- 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- --- 0,33 0,33 0,33 0,03 0,03 --- --- --- --- --- --- 0,33 0,33 --- --- 0,33 --- 0,33 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- 3,21 0,31 0,31 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- 3,23 0,33 0,33 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 3,21 3,21 3,21 0,31 0,31 0,31 --- 3,31 3,31 3,21 3,21 3,21 3,21 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Valdivia Ciruelos C1 P443 3,21 3,21 --- 0,31 0,31 0,31 3,31 3,31 3,31 3,21 --- --- --- --- 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Trafo 230/24 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 2,03 --- --- --- --- --- --- ---
Mariquina D30
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- 0,02 --- 3,01 3,01 --- ---

Cautín Mulchen C1 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- 0,03 --- 3,03 3,03 --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- --- 0,02 3,01 3,01 --- ---

Cautín Mulchen C2 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- --- 0,03 3,03 3,03 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
175-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 3,41 3,41 --- --- --- --- --- --- --- --- --- --- --- 0,41 3,31 --- ---

Cautín Temuco C1 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

Temuco Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 3,41 3,41 --- --- --- --- --- --- --- --- --- --- --- 3,31 0,41 --- ---

Cautín Temuco C2 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

Valdivia Rahue C2 7SA612 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 --- --- 3,31 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- 3,31 3,31 0,02 ---

Valdivia Rahue C2 D60 3,33 3,33 --- 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 --- --- 3,33 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- 3,33 3,33 0,03 ---

Rahue Valdivia C2 7SA612 3,21 --- --- 3,21 3,21 3,21 3,21 3,21 3,21 --- --- --- --- --- 3,21 3,21 3,21 3,21 3,21 --- 3,21 --- --- --- --- 0,61 ---

Rahue Valdivia C2 7SA87 3,21 --- --- 3,21 3,21 3,21 3,21 3,21 3,21 --- --- --- --- --- 3,21 3,21 3,21 3,21 3,21 --- 3,21 --- --- --- --- 0,61 ---

Valdivia Rahue C1 7SA612 --- --- --- --- 1,51 --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- 0,02

Valdivia Rahue C1 P443 --- --- --- --- 1,51 --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 1,01 0,61 1,01 1,01 0,61 0,61 --- --- --- --- --- 1,01 1,01 1,01 0,61 0,61 --- 1,01 --- --- --- --- --- 0,02

Rahue Valdivia C1 D60 --- --- --- 1,03 0,63 1,03 1,03 0,63 0,63 --- --- --- --- --- 1,03 1,03 1,03 0,63 0,63 --- 1,03 --- --- --- --- --- 0,03

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
176-
285

II.5.2. Falla Bifásica Aislada

Tabla II.26 – Tiempos de Operación, falla Bifásica Aislada


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 --- --- --- --- --- 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 0,63 0,63 0,63 0,63 0,63 0,63 --- --- --- --- --- 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 0,61 0,61 0,02 0,02 --- --- --- --- --- 0,61 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C2 REL670 0,62 0,62 0,02 0,02 --- --- --- --- --- 0,62 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,62 0,62 --- ---

Cautín Ciruelos C1 7SA612 3,31 --- --- 0,41 0,41 0,41 --- --- --- 0,02 0,02 0,02 0,02 0,02 0,41 0,41 --- --- 0,41 --- 0,41 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 3,33 --- --- 0,43 0,43 0,43 0,73 0,76 0,75 0,03 0,03 0,03 0,03 0,03 0,43 0,43 0,72 0,76 0,43 --- 0,43 --- --- --- --- --- ---
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,41 3,41 --- --- --- --- --- --- --- 0,41 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

Ciruelos Cautín C1 D60 0,43 3,43 --- --- --- --- --- --- --- 0,43 0,03 0,03 0,03 0,03 0,03 --- --- --- --- --- --- --- --- 0,43 0,43 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- 1,21 0,31 --- --- --- --- --- --- --- 1,21 1,21

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,02 0,32 0,32 --- --- --- --- --- --- --- 1,22 0,32 --- --- --- --- --- --- --- 1,22 1,22

Valdivia Ciruelos C2 7SA612 --- --- --- 0,31 0,31 0,31 0,02 0,02 --- --- --- --- --- --- 0,31 0,31 --- --- 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- --- 0,33 0,33 0,33 0,03 0,03 --- --- --- --- --- --- 0,33 0,33 --- --- 0,33 --- 0,33 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- 3,21 0,31 0,31 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- 3,23 0,33 0,33 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 --- --- --- 0,31 0,31 0,31 --- 3,31 3,31 --- --- --- --- --- 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- --- --- 3,31 3,31

Valdivia Ciruelos C1 P443 3,21 3,21 3,21 0,31 0,31 0,31 3,31 3,31 3,31 3,21 --- --- --- --- 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 2,39 --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- 0,02 --- 3,01 3,01 --- ---

Cautín Mulchen C1 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- 0,03 --- 3,03 3,03 --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- --- 0,02 3,01 3,01 --- ---

Cautín Mulchen C2 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- --- 0,03 3,03 3,03 --- ---

Temuco Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 3,41 3,41 3,41 --- --- --- --- --- --- --- --- --- --- 0,41 3,31 --- ---

Cautín Temuco C1 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
177-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 3,41 3,41 3,41 --- --- --- --- --- --- --- --- --- --- 3,31 0,41 --- ---

Cautín Temuco C2 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

Valdivia Rahue C2 7SA612 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- 3,31 3,31 0,02 ---

Valdivia Rahue C2 D60 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- 3,33 3,33 0,03 ---

Rahue Valdivia C2 7SA612 3,21 --- --- 3,21 3,21 3,21 3,21 3,21 3,21 3,21 --- --- --- --- 3,21 3,21 3,21 3,21 3,21 --- 3,21 --- --- --- --- 0,61 ---

Rahue Valdivia C2 7SA87 3,21 --- --- 3,21 3,21 3,21 3,21 3,21 3,21 3,21 --- --- --- --- 3,21 3,21 3,21 3,21 3,21 --- 3,21 --- --- --- --- 0,61 ---

Valdivia Rahue C1 7SA612 --- --- --- --- 1,51 --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- 0,02

Valdivia Rahue C1 P443 --- --- --- --- 1,51 --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 1,01 0,61 1,01 1,01 0,61 0,61 --- --- --- --- --- 1,01 1,01 1,01 0,61 0,61 --- 1,01 --- --- --- --- --- 0,02

Rahue Valdivia C1 D60 --- --- --- 1,03 0,63 1,03 1,03 0,63 0,63 --- --- --- --- --- 1,03 1,03 1,03 0,63 0,63 --- 1,03 --- --- --- --- --- 0,03

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
178-
285

II.5.3. Falla Bifásica a tierra

Tabla II.27 – Tiempos de Operación, falla Bifásica a tierra


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 0,61 0,61 0,61 0,61 0,61 0,61 --- --- --- --- --- 0,61 0,61 0,61 0,61 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 0,63 0,63 0,63 0,63 0,63 0,63 --- --- --- --- --- 0,63 0,63 0,63 0,63 0,63 --- 0,63 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 0,61 0,61 0,02 0,02 --- --- --- --- --- 0,61 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C2 REL670 0,62 0,62 0,02 0,02 --- --- --- --- --- 0,62 21,63 --- --- --- --- --- --- --- --- --- --- --- --- 0,62 0,62 --- ---

Cautín Ciruelos C1 7SA612 3,31 --- --- 0,41 0,41 0,41 1,79 --- --- 0,02 0,02 0,02 0,02 0,02 0,41 0,41 1,77 --- 0,41 --- 0,41 --- --- 1,21 1,21 --- ---

Cautín Ciruelos C1 D60 3,33 --- --- 0,58 0,43 0,58 0,75 0,78 0,77 0,03 0,03 0,03 0,03 0,03 0,43 0,58 0,74 0,78 0,43 --- 0,56 --- --- --- --- --- ---
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 0,41 2,94 --- --- --- --- --- --- --- 0,41 0,02 0,02 0,02 0,02 0,02 --- --- --- --- --- --- 18,28 18,28 0,41 0,41 --- ---

Ciruelos Cautín C1 D60 2,35 2,94 --- --- --- --- --- --- --- 2,11 0,43 0,03 0,03 0,03 0,03 --- --- --- --- --- --- --- --- 2,44 2,44 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- 0,31 0,31 --- --- --- --- --- --- --- 1,21 1,21

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,02 0,32 0,32 --- --- --- --- --- --- --- 0,32 0,32 --- --- --- --- --- --- --- 1,22 1,22

Valdivia Ciruelos C2 7SA612 15,95 15,4 6,39 0,31 0,31 0,31 0,02 0,02 --- 15,63 12,1 9,48 9,07 3,95 0,31 0,31 8,40 --- 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 15,96 15,41 6,4 0,33 0,33 0,33 0,03 0,03 --- 15,64 12,11 9,49 9,08 3,96 0,33 1,23 8,41 --- 0,33 --- 0,33 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- 0,31 0,31 0,31 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- 0,33 0,33 0,33 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 3,21 3,21 3,21 0,31 0,31 0,31 3,31 3,31 3,31 3,21 3,21 3,21 3,21 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Valdivia Ciruelos C1 P443 3,21 3,21 3,21 0,31 0,31 0,31 3,31 3,31 3,31 3,21 --- --- --- 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- 3,21 3,21 3,31 3,31

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 2,03 --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,06 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- 0,02 --- 3,01 3,01 --- ---

Cautín Mulchen C1 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- 0,03 --- 3,03 3,03 --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 3,01 3,01 --- --- --- --- --- --- --- --- --- 0,02 3,01 3,01 --- ---

Cautín Mulchen C2 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 3,03 3,03 --- --- --- --- --- --- --- --- --- 0,03 3,03 3,03 --- ---

Temuco Cautín C1 7SA612 0,41 0,41 1,02 --- --- --- --- --- --- 0,41 1,02 1,02 1,02 1,02 --- --- --- --- --- --- --- 1,02 1,02 0,29 3,31 --- ---

Cautín Temuco C1 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 3,31 --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
179-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 0,41 0,41 1,02 --- --- --- --- --- --- 0,41 1,02 1,02 1,02 1,02 --- --- --- --- --- --- --- 1,02 1,02 3,31 0,29 --- ---

Cautín Temuco C2 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 3,31 --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,41 --- ---

Valdivia Rahue C2 7SA612 3,31 --- --- 3,31 3,31 3,31 3,31 3,31 3,31 3,31 --- --- --- 3,31 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- 3,31 3,31 0,02 ---

Valdivia Rahue C2 D60 3,33 --- --- 3,33 3,33 3,33 3,33 3,33 3,33 3,33 --- --- --- 3,33 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- 3,33 3,33 0,03 ---

Rahue Valdivia C2 7SA612 3,21 --- --- 3,21 3,21 3,21 3,21 2,11 1,96 3,21 --- --- --- --- 3,21 3,21 3,21 2,11 3,21 --- 3,21 --- --- --- --- 0,42 ---

Rahue Valdivia C2 7SA87 3,21 --- --- 3,21 3,21 3,21 3,21 2,11 1,96 3,21 --- --- --- --- 3,21 3,21 3,21 2,11 3,21 --- 3,21 --- --- --- --- 0,42 ---

Valdivia Rahue C1 7SA612 --- --- --- --- 1,51 --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- 0,02

Valdivia Rahue C1 P443 --- --- --- --- 1,51 --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 1,01 0,61 1,01 1,01 0,61 0,61 --- --- --- --- --- 1,01 1,01 1,01 0,61 0,61 --- 1,01 --- --- --- --- --- 0,02

Rahue Valdivia C1 D60 --- --- --- 1,03 1,03 1,03 1,03 0,63 0,63 --- --- --- --- --- 1,03 1,03 1,03 0,63 1,03 --- 1,03 --- --- --- --- --- 0,03

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
180-
285

II.5.4. Falla Monofásica

Tabla II.28 – Tiempos de Operación, falla Monofásica


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 0,61 0,61 0,61 2,12 4,35 --- --- --- --- --- --- 0,61 0,61 2,1 4,34 0,61 --- 0,61 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 0,63 0,63 0,63 2,13 4,36 --- --- --- --- --- --- 0,63 0,63 2,11 4,35 0,63 --- 0,63 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 0,61 0,61 0,02 0,02 --- --- --- --- --- 0,61 14,49 --- --- --- --- --- --- --- --- --- --- --- --- 0,61 0,61 --- ---

Ciruelos Cautín C2 REL670 0,62 0,62 0,02 0,02 --- --- --- --- --- 0,62 14,48 --- --- --- --- --- --- --- --- --- --- 28,71 28,71 0,62 0,62 --- ---

Cautín Ciruelos C1 7SA612 3,31 --- --- 0,99 0,92 1,00 1,71 --- --- 0,02 0,02 0,02 0,02 0,02 0,83 1,00 1,69 --- 0,93 --- 0,97 --- --- 1,11 1,11 --- ---

Cautín Ciruelos C1 D60 3,33 --- --- 1,00 0,8 1,01 1,72 --- --- 0,03 0,03 0,03 0,03 0,03 0,76 1,01 1,7 --- 0,81 --- 0,98 --- --- --- --- --- ---
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 2,13 2,57 --- --- --- --- --- --- --- 1,88 0,41 0,02 0,02 0,02 0,02 --- --- --- --- --- --- 9,04 9,04 2,24 2,24 --- ---

Ciruelos Cautín C1 D60 2,13 2,57 --- --- --- --- --- --- --- 1,88 0,43 0,03 0,03 0,03 0,03 --- --- --- --- --- --- 9,04 9,04 2,24 2,24 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- --- 0,31 --- --- --- --- --- --- --- --- ---

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,02 0,32 0,32 --- --- --- --- --- --- --- --- 0,32 --- --- --- --- --- --- --- --- 29

Valdivia Ciruelos C2 7SA612 12,59 11,45 4,48 0,31 0,31 0,31 0,02 0,02 --- 11,95 8,09 6,31 6,06 3 0,31 1,21 7,98 --- 0,31 --- 0,31 --- --- 14,03 14,03 --- ---

Valdivia Ciruelos C2 D60 12,6 11,46 4,49 0,33 0,33 0,33 0,03 0,03 --- 11,96 8,1 6,32 6,07 3,01 0,33 1,23 7,99 --- 0,33 --- 0,33 --- --- 14,04 14,04 --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- --- 0,31 0,31 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- --- 0,33 0,33 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 --- --- 3,21 0,31 0,31 1,41 --- 3,31 3,31 --- --- --- --- 3,21 0,31 0,31 0,02 0,02 0,31 --- 0,31 --- --- --- --- --- ---

Valdivia Ciruelos C1 P443 --- --- --- 3,21 0,31 1,42 --- 3,31 3,31 --- --- --- --- --- 3,21 0,31 0,02 0,02 0,31 --- 0,31 --- --- --- --- --- ---

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 6,84 --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,07 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 7,16 --- --- --- --- --- --- 0,41 1,21 4,08 4,3 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 7,78 --- --- --- --- --- --- 0,43 1,23 4,37 4,61 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 --- --- --- --- --- --- --- --- --- --- 0,02 --- 3,01 3,01 --- ---

Cautín Mulchen C1 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 --- --- --- --- --- --- --- --- --- --- 0,03 --- 3,03 3,03 --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 7,16 --- --- --- --- --- --- 0,41 1,21 4,08 4,3 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 7,78 --- --- --- --- --- --- 0,43 1,23 4,37 4,61 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 3,01 3,01 --- --- --- --- --- --- --- 3,01 3,01 --- --- --- --- --- --- --- --- --- --- --- 0,02 3,01 3,01 --- ---

Cautín Mulchen C2 D60 3,03 3,03 --- --- --- --- --- --- --- 3,03 3,03 --- --- --- --- --- --- --- --- --- --- --- 0,03 3,03 3,03 --- ---

Temuco Cautín C1 7SA612 0,41 0,41 1,02 --- --- --- --- --- --- 0,41 0,81 1,02 1,02 1,02 --- --- --- --- --- --- --- 1,02 1,02 0,28 3,31 --- ---

Cautín Temuco C1 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 3,31 --- --- --- --- --- --- --- --- --- --- --- --- 0,39 0,41 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
181-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 0,41 0,41 1,02 --- --- --- --- --- --- 0,41 0,81 1,02 1,02 1,02 --- --- --- --- --- --- --- 1,02 1,02 3,31 0,28 --- ---

Cautín Temuco C2 7SA612 3,31 3,31 --- --- --- --- --- --- --- 3,31 3,31 --- --- --- --- --- --- --- --- --- --- --- --- 0,41 0,39 --- ---

Valdivia Rahue C2 7SA612 --- --- --- 3,31 3,31 3,31 3,31 3,31 3,31 --- --- --- --- --- 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- --- --- 0,02 ---

Valdivia Rahue C2 D60 --- --- --- 3,33 3,33 3,33 3,33 3,33 3,33 --- --- --- --- --- 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- --- --- 0,03 ---

Rahue Valdivia C2 7SA612 --- --- --- 3,21 3,21 3,21 3,21 2,48 2,34 --- --- --- --- --- 3,21 3,21 3,21 2,47 3,21 --- 3,21 --- --- --- --- 0,42 ---

Rahue Valdivia C2 7SA87 --- --- --- 3,21 3,21 3,21 3,21 2,48 2,34 --- --- --- --- --- 3,21 3,21 3,21 2,47 3,21 --- 3,21 --- --- --- --- 0,42 ---

Valdivia Rahue C1 7SA612 --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Valdivia Rahue C1 P443 --- --- --- --- --- --- --- 1,51 1,51 --- --- --- --- --- --- --- --- 1,51 --- --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 2,24 1,01 1,01 1,01 0,61 0,61 --- --- --- --- --- 2,24 1,01 1,01 0,61 1,01 --- 2,25 --- --- --- --- --- 0,02

Rahue Valdivia C1 D60 --- --- --- 2,25 1,03 1,03 1,03 0,63 0,63 --- --- --- --- --- 2,25 1,03 1,03 0,63 1,03 --- 2,26 --- --- --- --- --- 0,03

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
182-
285

II.5.5. Falla Bifásica a tierra R=25 Ω

Tabla II.29 – Tiempos de Operación, falla Bifásica R=25 Ω


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 1,76 1,97 2,12 3,49 --- --- --- --- --- --- --- 2,1 2,12 3,42 --- 1,98 --- 2,05 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 1,77 1,98 2,13 3,5 --- --- --- --- --- --- --- 2,11 2,13 3,43 --- 1,99 --- 2,06 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 8,04 5,22 0,02 0,02 --- --- --- --- --- 9,13 --- --- --- --- --- --- --- --- --- --- --- --- --- 8,67 8,67 --- ---

Ciruelos Cautín C2 REL670 8,04 5,21 0,62 0,02 --- --- --- --- --- 9,12 --- --- --- --- --- --- --- --- --- --- --- --- --- 8,66 8,66 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 1,67 1,51 1,7 --- --- --- 0,02 0,02 0,02 0,02 0,41 1,29 1,69 --- --- 1,52 --- 1,61 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- --- 1,68 1,52 1,71 --- --- --- 0,03 0,03 0,03 0,03 0,43 1,3 1,7 --- --- 1,53 --- 1,62 --- --- --- --- --- ---
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 4,53 5,41 --- --- --- --- --- --- --- 3,84 1,72 0,41 0,41 0,01 0,02 --- --- --- --- --- --- --- --- 4,77 4,77 --- ---

Ciruelos Cautín C1 D60 4,53 5,41 --- --- --- --- --- --- --- 3,84 1,72 0,43 0,43 0,03 0,03 --- --- --- --- --- --- --- --- 4,77 4,77 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- --- 0,31 --- --- --- --- --- --- --- --- ---

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,31 0,32 0,32 0,32 --- --- --- --- --- --- --- --- 0,32 --- --- --- --- --- --- --- --- ---

Valdivia Ciruelos C2 7SA612 --- --- 9,44 2,45 2,31 0,31 0,02 0,02 --- --- --- --- 15,98 5,37 2,44 2,72 --- --- 2,32 --- 2,43 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- 9,45 2,46 2,32 0,33 0,03 0,03 --- --- --- --- 15,99 5,38 2,45 2,73 --- --- 2,33 --- 2,44 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- --- 3,21 3,21 --- --- --- --- --- --- 0,02 0,02 0,31 --- --- --- --- --- --- --- 3,21 3,21

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- --- 3,23 3,23 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 3,23 3,23

Valdivia Ciruelos C1 7SA612 --- --- --- 2,33 2,11 2,87 --- --- --- --- --- --- --- --- 2,32 1,56 0,31 0,02 2,13 --- 2,3 --- --- --- --- --- ---

Valdivia Ciruelos C1 P443 --- --- --- 2,34 2,12 2,88 --- --- --- --- --- --- --- --- 2,33 1,57 0,31 0,02 2,14 --- 2,31 --- --- --- --- --- ---

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,19 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 0,41 1,21 1,21 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 0,43 1,23 1,23 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02 --- --- --- --- ---

Cautín Mulchen C1 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,03 --- --- --- --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 0,41 1,21 1,21 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 0,43 1,23 1,23 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02 --- --- --- ---

Cautín Mulchen C2 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,03 --- --- --- ---

Temuco Cautín C1 7SA612 0,96 1,02 1,02 --- --- --- --- --- --- 1,02 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 0,38 3,31 --- ---

Cautín Temuco C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,67 1,11 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
183-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 0,96 1,02 1,02 --- --- --- --- --- --- 1,02 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 3,31 0,38 --- ---

Cautín Temuco C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 1,11 0,67 --- ---

Valdivia Rahue C2 7SA612 --- --- --- 3,31 3,31 3,31 3,31 3,31 3,31 --- --- --- --- --- 3,31 3,31 3,31 3,31 3,31 --- 3,31 --- --- --- --- 0,61 ---

Valdivia Rahue C2 D60 --- --- --- 3,33 3,33 3,33 3,33 3,33 3,33 --- --- --- --- --- 3,33 3,33 3,33 3,33 3,33 --- 3,33 --- --- --- --- 0,63 ---

Rahue Valdivia C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,82 ---

Rahue Valdivia C2 7SA87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,82 ---

Valdivia Rahue C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,17

Valdivia Rahue C1 P443 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61

Rahue Valdivia C1 7SA612 --- --- --- --- 4,00 3,7 2,43 0,61 0,61 --- --- --- --- --- --- 3,67 2,39 0,61 4,03 --- --- --- --- --- --- --- 0,61

Rahue Valdivia C1 D60 --- --- --- --- 4,01 3,71 2,44 0,63 0,63 --- --- --- --- --- --- 3,68 2,4 0,63 4,01 --- --- --- --- --- --- --- 0,63

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
184-
285

II.5.6. Falla Monofásica R=25 Ω

Tabla II.30 – Tiempos de Operación, falla Monofásica R=25 Ω


2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV
220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Cautín Ciruelos C2 7SA612 --- 0,02 0,02 1,68 1,9 2,05 3,47 --- --- --- --- --- --- --- 2,01 2,05 3,4 --- 1,91 --- 1,98 --- --- --- --- --- ---

Cautín Ciruelos C2 D60 --- 0,03 0,03 1,69 1,91 2,06 3,48 --- --- --- --- --- --- --- 2,02 2,06 3,41 --- 1,92 --- 1,99 --- --- --- --- --- ---

Ciruelos Cautín C2 7SA612 7,76 4,96 0,02 0,02 --- --- --- --- --- 8,66 --- --- --- --- --- --- --- --- --- --- --- --- --- 8,45 8,45 --- ---

Ciruelos Cautín C2 REL670 7,76 4,95 0,02 0,02 --- --- --- --- --- 8,66 --- --- --- --- --- --- --- --- --- --- --- --- --- 8,44 8,44 --- ---

Cautín Ciruelos C1 7SA612 --- --- --- 1,59 1,45 1,63 --- --- --- 0,02 0,02 0,02 0,02 0,41 1,22 1,62 --- --- 1,46 --- 1,54 --- --- --- --- --- ---

Cautín Ciruelos C1 D60 --- --- --- 1,6 1,46 1,64 --- --- --- 0,03 0,03 0,03 0,03 0,43 1,23 1,63 --- --- 1,47 --- 1,55 --- --- --- --- --- ---
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7SA87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
7UT87
kV Rio Tolten Tolten
Trafo 220/110 TO Rio
7UT87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Rio Tolten Tolten
Ciruelos Cautín C1 7SA612 4,4 5,13 --- --- --- --- --- --- --- 3,69 1,53 0,41 0,41 0,02 0,02 --- --- --- --- --- --- 16,79 16,79 4,66 4,66 --- ---

Ciruelos Cautín C1 D60 4,4 5,13 --- --- --- --- --- --- --- 3,69 1,53 0,43 0,43 0,03 0,03 --- --- --- --- --- --- 16,79 16,79 4,66 4,66 --- ---

Ciruelos Valdivia C2 7SA612 --- --- --- --- --- 0,02 0,02 0,31 0,31 --- --- --- --- --- --- --- --- 0,31 --- --- --- --- --- --- --- --- ---

Ciruelos Valdivia C2 REL670 --- --- --- --- --- 0,02 0,32 0,32 0,32 --- --- --- --- --- --- --- --- 0,32 --- --- --- --- --- --- --- --- ---

Valdivia Ciruelos C2 7SA612 --- --- 7,13 2,38 2,27 0,31 0,31 0,02 --- --- --- 12,14 11,23 4,42 2,37 2,68 --- --- 2,28 --- 2,38 --- --- --- --- --- ---

Valdivia Ciruelos C2 D60 --- --- 7,14 2,39 2,28 0,33 0,03 0,03 --- --- --- 12,15 11,24 4,43 2,38 2,69 --- --- 2,29 --- 2,39 --- --- --- --- --- ---

Ciruelos Valdivia C1 7SA612 --- --- --- --- --- --- --- 3,21 3,21 --- --- --- --- --- --- 0,02 0,02 0,32 --- --- --- --- --- --- --- 16,78 15,78

Ciruelos Valdivia C1 D60 --- --- --- --- --- --- --- 3,23 3,23 --- --- --- --- --- --- 0,03 0,03 0,33 --- --- --- --- --- --- --- 16,78 15,78

Valdivia Ciruelos C1 7SA612 --- --- --- 2,24 2,08 2,83 --- --- --- --- --- --- --- --- 2,23 1,54 0,31 0,02 2,09 --- 2,26 --- --- --- --- --- ---

Valdivia Ciruelos C1 P443 --- --- --- 2,25 2,09 2,83 --- --- --- --- --- --- --- --- 2,24 1,55 0,02 0,02 2,1 --- 2,27 --- --- --- --- --- ---

Trafo 230/24
Mariquina D30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
kV Mariquina
Planta --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,19 --- --- --- --- --- ---
Ciruelos 7SJ64
Valdivia
Mulchen Cautín C1 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- 0,02 --- 0,41 0,41 --- ---

Mulchen Cautín C1 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- 0,03 --- 0,43 0,43 --- ---

Cautín Mulchen C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02 --- --- --- --- ---

Cautín Mulchen C1 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,03 --- --- --- --- ---

Mulchen Cautín C2 7SA612 0,41 0,41 --- --- --- --- --- --- --- 0,41 1,21 1,21 1,21 --- --- --- --- --- --- --- --- --- 0,02 0,41 0,41 --- ---

Mulchen Cautín C2 D60 0,43 0,43 --- --- --- --- --- --- --- 0,43 1,23 1,23 1,23 --- --- --- --- --- --- --- --- --- 0,03 0,43 0,43 --- ---

Cautín Cautín C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02 --- --- --- ---

Cautín Mulchen C2 D60 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,03 --- --- --- ---

Temuco Cautín C1 7SA612 0,95 1,02 1,02 --- --- --- --- --- --- 0,99 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 0,38 3,31 --- ---

Cautín Temuco C1 7SA612 3,21 3,21 --- --- --- --- --- --- --- 3,21 --- --- --- --- --- --- --- --- --- --- --- --- --- 0,66 1,09 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
185-
285

2x220 kV 2x220 kV 2x220 kV 2x220 kV 220 kV


220 kV
2x220kV Cautín - Ciruelos 2x220kV Ciruelos - 220kV Cautín - TO Rio 220kV TO Rio Toltén - 2x220kV Ciruelos - Cautín - Cautín - Cautín - Cautín - Valdivia -
Planta Valdivia -
Cautín C2 Ciruelos Valdivia C2 Valdivia Toltén Ciruelos Valdivia C1 Mariquina Mariquin Mulchen Mulchen Temuco Temuco Tap
Subestación Paño Relé Valdivia Rahue
220 kV 220 kV 220 kV 220 kV a 23 kV C1 C2 C1 C2 Pichirrahue
220 kV
5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 5% 50% 95% 50% 50% 95% 95% 50% 50%

Temuco Cautín C2 7SA612 0,95 1,02 1,02 --- --- --- --- --- --- 0,99 1,02 1,02 1,02 --- --- --- --- --- --- --- --- 1,02 1,02 3,31 0,38 --- ---

Cautín Temuco C2 7SA612 3,21 3,21 --- --- --- --- --- --- --- 3,21 --- --- --- --- --- --- --- --- --- --- --- --- --- 1,09 0,66 --- ---

Valdivia Rahue C2 7SA612 --- --- --- --- 3,31 3,31 3,31 3,31 3,31 --- --- --- --- --- --- 3,31 3,31 3,31 3,31 --- 3,31 --- --- --- --- 0,61 ---

Valdivia Rahue C2 D60 --- --- --- --- 3,33 3,33 3,33 3,33 3,33 --- --- --- --- --- --- 3,33 3,33 3,33 3,33 --- 3,33 --- --- --- --- 0,63 ---

Rahue Valdivia C2 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61 ---

Rahue Valdivia C2 7SA87 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,61 ---

Valdivia Rahue C1 7SA612 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,17

Valdivia Rahue C1 P443 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 0,02

Rahue Valdivia C1 7SA612 --- --- --- 4,27 3,92 3,62 2,47 1,01 0,61 --- --- --- --- --- 4,24 3,60 2,43 1,01 3,94 --- 4,29 --- --- --- --- --- 0,61

Rahue Valdivia C1 D60 --- --- --- 4,28 3,93 3,63 2,48 1,03 0,63 --- --- --- --- --- 4,25 3,61 2,44 1,03 3,95 --- 4,30 --- --- --- --- --- 0,63

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
186-
285

ANEXO III. ESQUEMAS DE DISTANCIA Y CURVAS DE SOBRECORRIENTE

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
187-
285

DIgSIL ENT
180,
[pri.Ohm]
160,
140,

Figura. III.1 – Característica de fase protecciones 7SA612 y REL670


120,
100,
80,0

ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES


60,0
40,0

PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”


20,0
-260, -240, -220, -200, -180, -160, -140, -120, -100, -80,0 -60,0 -40,0 -20,0 20,0 40,0 60,0 80,0 100, 120, 140, 160, 180, 200, 220, [pri.Ohm]

SERVICIOS DE INGENIERÍA DE DISEÑO


-20,0
-40,0

DESSAU INGENIERÍA S.p.A.


-60,0
Paño Cautín C2 S/E Ciruelos

-80,0
-100,
-120,
-140,
-160,

STA3534-C252-01E-IN-C043
-180,
Ciruelos 220kV\L4\Cir-Cau 7SA612 C2
Ciruelos 220kV\L4\Cir-Cau REL670 C2
Cir-Cau C2 Date: 10/6/2016
Annex:

23.12.2016
REV. 0
III.1.
188-
285

DIgSIL ENT
360,
[pri.Ohm]
320,
280,

Figura. III.2 – Característica Residual protecciones 7SA612 y REL670


240,
200,
160,
120,

ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES


80,0
40,0

PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”


-520, -480, -440, -400, -360, -320, -280, -240, -200, -160, -120, -80,0 -40,0 40,0 80,0 120, 160, 200, 240, 280, 320, 360, 400, 440, [pri.Ohm]

SERVICIOS DE INGENIERÍA DE DISEÑO


-40,0
-80,0

DESSAU INGENIERÍA S.p.A.


-120,
-160,
-200,
-240,
-280,
-320,

STA3534-C252-01E-IN-C043
-360,
Ciruelos 220kV\L4\Cir-Cau 7SA612 C2
Ciruelos 220kV\L4\Cir-Cau REL670 C2
Cir-Cau C2 Date: 10/6/2016

23.12.2016
Annex:

REV. 0
189-
285

220,00 kV 100

1000
100
0,1

[s]
10
1
Ciruelos 220kV\L4\Cir-Cau 7SA612 C2
1000
Ciruelos 220kV\L4\Cir-Cau REL670 C2
10000
Time-Overcurrent Plot(2)

[pri.A]
Annex:
Date: 10/6/2016

100000

DIgSIL ENT

Figura. III.3 – Característica sobrecorriente residual direccional protecciones 7SA612 y REL670

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
190-
285

DIgSIL ENT
90,0
[pri.Ohm]
80,0
70,0

Figura. III.4 – Característica de fase protecciones 7SA612 y D60


60,0
50,0
40,0

ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES


30,0
20,0

PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”


10,0
-130, -120, -110, -100, -90,0 -80,0 -70,0 -60,0 -50,0 -40,0 -30,0 -20,0 -10,0 10,0 20,0 30,0 40,0 50,0 60,0 70,0 80,0 90,0 100, 110, [pri.Ohm]

SERVICIOS DE INGENIERÍA DE DISEÑO


-10,0
-20,0

DESSAU INGENIERÍA S.p.A.


-30,0
Paño Ciruelos C2 S/E Cautín

-40,0
-50,0
-60,0
-70,0
-80,0

STA3534-C252-01E-IN-C043
-90,0
Cautin\Cub_0.2\Cau-Cir 7SA612 C2
Cautin\Cub_0.2\Cau-Cir D60 C2
Cau-Cir C2 Date: 10/6/2016
Annex:

23.12.2016
REV. 0
III.2.
191-
285

DIgSIL ENT
225,
[pri.Ohm]
200,
175,
150,

Figura. III.5 – Característica Residual protecciones 7SA612 y D60


125,
100,
75,0

ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES


50,0
25,0

PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”


-325, -300, -275, -250, -225, -200, -175, -150, -125, -100, -75,0 -50,0 -25,0 25,0 50,0 75,0 100, 125, 150, 175, 200, 225, 250, 275, [pri.Ohm]

SERVICIOS DE INGENIERÍA DE DISEÑO


-25,0
-50,0

DESSAU INGENIERÍA S.p.A.


-75,0
-100,
-125,
-150,
-175,
-200,

STA3534-C252-01E-IN-C043
-225,
Cautin\Cub_0.2\Cau-Cir 7SA612 C2
Cautin\Cub_0.2\Cau-Cir D60 C2
Cau-Cir C2 Date: 10/6/2016

23.12.2016
Annex:

REV. 0
192-
285

220,00 kV 100
0,1

[s]

10
1
Cautin\Cub_0.2\Cau-Cir 7SA612 C2
1000
Cautin\Cub_0.2\Cau-Cir D60 C2
10000
Time-Overcurrent Plot(2)

[pri.A]
Annex:
Date: 10/6/2016

100000

DIgSIL ENT

Figura. III.6 – Característica sobrecorriente residual direccional protecciones 7SA612 y D60

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
193-
285

DIgSIL ENT
90,0
[pri.Ohm]
80,0
70,0

Figura. III.7 – Característica de fase protecciones 7SA612 y REL670


60,0
50,0
40,0

ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES


30,0
20,0

PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”


10,0
-130, -120, -110, -100, -90,0 -80,0 -70,0 -60,0 -50,0 -40,0 -30,0 -20,0 -10,0 10,0 20,0 30,0 40,0 50,0 60,0 70,0 80,0 90,0 100, 110, [pri.Ohm]

SERVICIOS DE INGENIERÍA DE DISEÑO


-10,0
-20,0

DESSAU INGENIERÍA S.p.A.


-30,0
Paño Valdivia C2 S/E Ciruelos

-40,0
-50,0
-60,0
-70,0
-80,0

STA3534-C252-01E-IN-C043
-90,0
Ciruelos 220kV\L3\Cir-Val 7SA612 C2
Ciruelos 220kV\L3\Cir-Val REL670 C2
Cir-Val C2 Date: 10/6/2016
Annex:

23.12.2016
REV. 0
III.3.
194-
285

DIgSIL ENT
225,
[pri.Ohm]
200,
175,

Figura. III.8 – Característica Residual protecciones 7SA612 y REL670


150,
125,
100,
75,0

ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES


50,0
25,0

PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”


-325, -300, -275, -250, -225, -200, -175, -150, -125, -100, -75,0 -50,0 -25,0 25,0 50,0 75,0 100, 125, 150, 175, 200, 225, 250, 275, [pri.Ohm]

SERVICIOS DE INGENIERÍA DE DISEÑO


-25,0
-50,0

DESSAU INGENIERÍA S.p.A.


-75,0
-100,
-125,
-150,
-175,
-200,

STA3534-C252-01E-IN-C043
-225,
Ciruelos 220kV\L3\Cir-Val 7SA612 C2
Ciruelos 220kV\L3\Cir-Val REL670 C2
Cir-Val C2 Date: 10/6/2016

23.12.2016
Annex:

REV. 0
195-
285

220,00 kV 100

100
0,1

[s]
10
1
Ciruelos 220kV\L3\Cir-Val 7SA612 C2
1000
Ciruelos 220kV\L3\Cir-Val REL670 C2
10000
Time-Overcurrent Plot(3)

[pri.A]
Annex:
Date: 10/6/2016

100000

DIgSIL ENT

Figura. III.9 – Característica sobrecorriente residual direccional protecciones 7SA612 y REL670

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
196-
285

III.4. Paño Ciruelos C2 S/E Valdivia

-130,
-120,
-110,
Val\52J4\Val-Cir D60 C2
Val\52J4\Val-Cir 7SA612 C2

-100,
-90,0
-80,0
-70,0
-60,0
-50,0
-40,0
-30,0
-20,0

[pri.Ohm]
-10,0
-90,0

-80,0

-70,0

-60,0

-50,0

-40,0

-30,0

-20,0

-10,0

10,0

20,0

30,0

40,0

50,0

60,0

70,0

80,0

90,0
10,0
20,0
30,0
40,0
50,0
60,0
70,0
80,0
90,0
100,
110,
Val-Cir C2

[pri.Ohm]
Annex:
Date: 10/6/2016

DIgSIL ENT

Figura. III.10 – Característica de fase protecciones 7SA612 y D60

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
197-
285

DIgSIL ENT
225,
[pri.Ohm]
200,
175,

Figura. III.11 – Característica Residual protecciones 7SA612 y D60


150,
125,
100,
75,0

ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES


50,0
25,0

PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”


-325, -300, -275, -250, -225, -200, -175, -150, -125, -100, -75,0 -50,0 -25,0 25,0 50,0 75,0 100, 125, 150, 175, 200, 225, 250, 275, [pri.Ohm]

SERVICIOS DE INGENIERÍA DE DISEÑO


-25,0
-50,0

DESSAU INGENIERÍA S.p.A.


-75,0
-100,
-125,
-150,
-175,
-200,

STA3534-C252-01E-IN-C043
-225,
Val\52J4\Val-Cir 7SA612 C2
Val\52J4\Val-Cir D60 C2
Val-Cir C2 Date: 10/6/2016

23.12.2016
Annex:

REV. 0
198-
285

220,00 kV 100

100
0,1

[s]
10
1
Val\52J4\Val-Cir 7SA612 C2
1000
Val\52J4\Val-Cir D60 C2
10000
Time-Overcurrent Plot(4)

[pri.A]
Annex:
Date: 10/6/2016

100000

DIgSIL ENT

Figura. III.12 – Característica sobrecorriente residual direccional protecciones 7SA612 y D60

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
199-
285

ANEXO IV. ESTUDIO DE CORTOCIRCUITOS

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
200-
285

IV.1. Escenario 1. Hidrología Húmeda y Demanda Alta

Tabla IV.1 – Valores de Cortocircuito en barras, Escenario 1 (HH-DA)


Falla Falla Bifásica
Falla Bifásica a tierra Falla Monofásica
Trifásica Aislada
Barra
Ikss B Ikss C Ikss B Ikss C I0x3 Ikss A I0x3
Ikss [A]
[A] [A] [A] [A] [kA] [A] [kA]
Cautín 220 kV 8,02 7,04 7,04 7,67 8,05 7,09 7,64 7,64
Ciruelos 220 kV 5,50 4,79 4,79 5,23 5,49 4,85 5,18 5,18
Valdivia 220kV 4,95 4,31 4,31 5,16 5,57 6,43 5,64 5,64
Tap Rio Tolten 220 kV 5,67 4,94 4,94 5,29 5,47 4,29 4,92 4,92
Central Valdivia 220 kV 5,37 4,68 4,68 5,10 5,37 4,72 5,06 5,06
Mariquina 220 kV 5,49 4,78 4,78 5,21 5,48 4,82 5,16 5,16
Mulchen 220 kV 14,32 12,86 12,86 13,72 13,41 9,21 11,64 11,64
Temuco 220 kV 7,93 6,96 6,96 7,60 8,00 7,16 7,63 7,63
Rahue 220 kV 4,30 3,77 3,77 4,46 4,57 5,01 4,69 4,69
Tap Pichirrahue 220 kV 4,30 3,77 3,77 4,46 4,56 5,00 4,68 4,68

IV.2. Escenario 2. Hidrología Húmeda y Demanda Baja

Tabla IV.2 – Valores de Cortocircuito en barras, Escenario 1 (HH-DB)


Falla Falla Bifásica
Falla Bifásica a tierra Falla Monofásica
Trifásica Aislada
Barra
Ikss B Ikss C Ikss B Ikss C I0x3 Ikss A I0x3
Ikss [A]
[A] [A] [A] [A] [kA] [A] [kA]
Cautín 220 kV 7,95 6,98 6,98 7,61 7,98 7,07 7,60 7,60
Ciruelos 220 kV 5,48 4,78 4,78 5,21 5,48 4,84 5,17 5,17
Valdivia 220kV 4,94 4,30 4,30 5,15 5,56 6,42 5,63 5,63
Tap Rio Tolten 220 kV 5,64 4,92 4,92 5,26 5,45 4,28 4,91 4,91
Central Valdivia 220 kV 5,36 4,66 4,66 5,09 5,35 4,72 5,05 5,05
Mariquina 220 kV 5,47 4,76 4,76 5,20 5,46 4,81 5,15 5,15
Mulchen 220 kV 13,99 12,58 12,58 13,44 13,13 9,16 11,50 11,50
Temuco 220 kV 7,85 6,90 6,90 7,54 7,94 7,14 7,59 7,59
Rahue 220 kV 4,30 3,77 3,77 4,46 4,56 5,01 4,69 4,69
Tap Pichirrahue 220 kV 4,29 3,77 3,77 4,45 4,56 5,00 4,68 4,68

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
201-
285

IV.3. Escenario 3. Hidrología Seca y Demanda Alta

Tabla IV.3 – Valores de Cortocircuito en barras, Escenario 3 (HS-DA)


Falla Falla Bifásica
Falla Bifásica a tierra Falla Monofásica
Trifásica Aislada
Barra
Ikss B Ikss C Ikss B Ikss C I0x3 Ikss A I0x3
Ikss [A]
[A] [A] [A] [A] [kA] [A] [kA]
Cautín 220 kV 8,07 7,05 7,05 7,69 8,07 7,13 7,64 7,64
Ciruelos 220 kV 6,44 5,61 5,61 6,07 6,26 5,16 5,76 5,76
Valdivia 220kV 6,23 5,44 5,44 6,48 6,84 7,74 6,97 6,97
Tap Rio Tolten 220 kV 5,88 5,12 5,12 5,47 5,64 4,34 5,03 5,03
Central Valdivia 220 kV 6,26 5,45 5,45 5,89 6,09 5,01 5,60 5,60
Mariquina 220 kV 6,42 5,59 5,59 6,05 6,24 5,13 5,74 5,74
Mulchen 220 kV 11,95 10,47 10,47 11,44 11,28 8,95 10,36 10,36
Temuco 220 kV 7,97 6,96 6,96 7,62 8,03 7,20 7,64 7,64
Rahue 220 kV 4,47 3,92 3,92 4,62 4,72 5,12 4,84 4,84
Tap Pichirrahue 220 kV 4,47 3,92 3,92 4,61 4,71 5,11 4,83 4,83

IV.4. Escenario 4. Hidrología Seca y Demanda Baja

Tabla IV.4 – Valores de Cortocircuito en barras, Escenario 4 (HS-DB)


Falla Falla Bifásica
Falla Bifásica a tierra Falla Monofásica
Trifásica Aislada
Barra
Ikss B Ikss C Ikss B Ikss C I0x3 Ikss A I0x3
Ikss [A]
[A] [A] [A] [A] [kA] [A] [kA]
Cautín 220 kV 7,98 6,97 6,97 7,63 7,99 7,11 7,59 7,59
Ciruelos 220 kV 6,40 5,58 5,58 6,04 6,22 5,15 5,74 5,74
Valdivia 220kV 6,18 5,40 5,40 6,45 6,80 7,72 6,93 6,93
Tap Rio Tolten 220 kV 5,84 5,09 5,09 5,44 5,60 4,34 5,00 5,00
Central Valdivia 220 kV 6,22 5,42 5,42 5,86 6,05 5,00 5,58 5,58
Mariquina 220 kV 6,38 5,56 5,56 6,02 6,20 5,12 5,72 5,72
Mulchen 220 kV 11,74 10,29 10,29 11,27 11,10 8,91 10,26 10,26
Temuco 220 kV 7,88 6,89 6,89 7,55 7,95 7,17 7,58 7,58
Rahue 220 kV 4,45 3,91 3,91 4,60 4,70 5,11 4,82 4,82
Tap Pichirrahue 220 kV 4,45 3,91 3,91 4,60 4,69 5,10 4,82 4,82

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
202-
285

IV.5. Escenario 5. Hidrología Humeda y Demanda Alta considerando interruptor Tap Off Rio
Tolten abierto

Tabla IV.5 – Valores de Cortocircuito en barras, Escenario 5 (HH-DA-2)


Falla Falla Bifásica
Falla Bifásica a tierra Falla Monofásica
Trifásica Aislada
Barra
Ikss B Ikss C Ikss B Ikss C I0x3 Ikss A I0x3
Ikss [A]
[A] [A] [A] [A] [kA] [A] [kA]
Cautín 220 kV 7,89 6,93 6,93 7,50 7,85 6,72 7,37 7,37
Ciruelos 220 kV 5,44 4,74 4,74 5,16 5,42 4,74 5,10 5,10
Valdivia 220kV 4,90 4,28 4,28 5,12 5,53 6,39 5,59 5,59
Tap Rio Tolten 220 kV 5,51 4,81 4,81 5,06 5,16 3,49 4,31 4,31
Central Valdivia 220 kV 5,31 4,63 4,63 5,03 5,30 4,63 4,98 4,98
Mariquina 220 kV 5,42 4,73 4,73 5,14 5,40 4,72 5,08 5,08
Mulchen 220 kV 14,25 12,81 12,81 13,66 13,36 9,18 11,59 11,59
Temuco 220 kV 7,80 6,85 6,85 7,43 7,82 6,80 7,38 7,38
Rahue 220 kV 4,28 3,76 3,76 4,45 4,55 5,00 4,68 4,68
Tap Pichirrahue 220 kV 4,28 3,76 3,76 4,44 4,55 4,99 4,67 4,67

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
203-
285

ANEXO V. DESPACHO DE GENERACIÓN

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
204-
285

V.1. Despacho de Centrales Convencionales

Tabla V-1: Despacho de generación, Centrales Convencionales


Hidrología Húmeda Hidrología Seca
Central Demanda
Demanda Alta Demanda Alta Demanda Baja
Baja
Alfalfal U1 85,0 30,0 85,0 38,0
Ancoa (pasada) 25,0 15,0 15,0 15,0
Angostura U1 135,0 135,0 --- ---
Angostura U2 135,0 135,0 --- ---
Angostura U3 45,0 45,0 40,0 40,0
Antilhue U1 --- --- 44,0 44,0
Antilhue U2 --- --- 50,0 50,0
Antuco U1 150,0 100,0 100,0 100,0
Antuco U2 150,0 --- --- ---
Arauco 8,0 8,0 8,0 8,0
Blanco (Aconcagua U1) 50,0 50,0 50,0 50,0
Bocamina U1 --- --- 120,0 120,0
CMPC Cordillera 10,0 10,0 10,0 10,0
CMPC Tissue 5,0 5,0 5,0 5,0
Callao 0,6 0,6 0,6 0,6
Campiche 270,0 270,0 270,0 270,0
Canutillar U1 50,0 65,0 50,0 50,0
Canutillar U2 65,0 65,0 --- ---
Capullo 5,0 5,0 5,0 5,0
Carena 8,0 8,0 8,0 8,0
Celco 7,0 7,0 7,0 7,0
Chacayes U1 45,0 45,0 45,0 45,0
Chacayes U2 45,0 45,0 45,0 45,0
Chiburgo U1 1,0 1,0 1,0 1,0
Cholguán 8,0 8,0 20,0 8,0
Cipreses U1 29,0 --- 29,0 ---
Cipreses U2 29,0 --- 29,0 ---
Cipreses U3 29,0 --- 29,0 ---
Colbún U1 200,0 --- 200,0 100,0
Comasa U1 25,0 25,0 25,0 25,0
Comasa U2 20,0 20,0 20,0 20,0
Confluencia U1 82,0 82,0 82,0 82,0
Coya 10,0 10,0 10,0 10,0
Curacautin U1-U3 0,8 0,8 0,8 0,8
Curacautin U2 1,1 1,1 1,1 1,1
Curillinque 70,0 35,0 70,0 35,0
EPSA U1 4,0 4,0 4,0 4,0

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
205-
285

Hidrología Húmeda Hidrología Seca


Central Demanda
Demanda Alta Demanda Alta Demanda Baja
Baja
EPSA U2 9,0 9,0 9,0 9,0
EPSA U3 3,0 3,0 3,0 3,0
El Manzano 2,0 2,0 2,0 2,0
El Paso U1 17,0 12,0 17,0 12,0
El Paso U2 17,0 12,0 17,0 12,0
El Toro U1 100,0 100,0 --- ---
El Toro U2 100,0 100,0 100,0 100,0
El Toro U3 100,0 --- --- ---
El Toro U4 100,0 --- --- ---
El Volcán 13,0 13,0 13,0 13,0
Energía BioBio 7,0 7,0 7,0 7,0
Energía Pacífico 14,0 14,0 14,0 14,0
FPC 10,0 10,0 10,0 10,0
FPC U2 2,0 2,0 2,0 2,0
Florida 21,0 21,0 21,0 21,0
Gen Carilafquen 21,6 21,6 21,6 21,6
Gen Malalcahuello 9,9 9,9 9,9 9,9
Guacolda U1 149,0 149,0 149,0 149,0
Guacolda U2 149,0 149,0 149,0 149,0
Guacolda U3 149,0 149,0 149,0 149,0
Guacolda U4 149,0 149,0 149,0 149,0
Guacolda U5 --- --- 149,0 ---
Guayacán U1-U2 12,0 12,0 12,0 12,0
Hornitos 52,0 52,0 52,0 52,0
Isla U1 30,0 25,0 30,0 25,0
Isla U2 30,0 --- 30,0 ---
Juncal (Aconcagua U2) 27,0 27,0 27,0 27,0
La Higuera U1 75,0 50,0 75,0 50,0
La Higuera U2 75,0 50,0 75,0 50,0
La Mina 33,0 15,0 15,0 15,0
Laja (Energía Verde) 7,0 7,0 7,0 7,0
Las Nalcas 1,4 1,4 1,4 1,4
Licanten 6,0 6,0 6,0 6,0
Licán 4,0 4,0 4,0 4,0
Lircay U1 8,0 8,0 8,0 8,0
Lircay U2 8,0 8,0 8,0 8,0
Llauquereo 1,0 1,0 1,0 1,0
Loma Alta 32,0 15,0 32,0 15,0
Loma Los Colorados I (x2) 0,7 0,7 0,7 0,7
Loma Los Colorados II (x14) 16,8 16,8 16,8 16,8

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
206-
285

Hidrología Húmeda Hidrología Seca


Central Demanda
Demanda Alta Demanda Alta Demanda Baja
Baja
Los Hierros II 1,0 1,0 1,0 1,0
Los Hierros U1 3,0 3,0 3,0 3,0
Los Quilos U1 12,0 12,0 12,0 12,0
Los Quilos U2 12,0 12,0 12,0 12,0
Los Quilos U3 12,0 12,0 12,0 12,0
Machicura U1 22,0 22,0 22,0 22,0
Maitenes U1-U2-U3 12,0 12,0 12,0 12,0
Mallarauco 2,8 2,8 2,8 2,8
Mampil U1 8,0 6,0 8,0 6,0
Mariposas 2,0 2,0 2,0 2,0
Masisa 8,0 9,0 8,0 9,0
Nehuenco U2 TG 240,0 150,0 240,0 240,0
Nehuenco U2 TV 120,0 75,0 120,0 120,0
Nueva Aldea U1 11,0 11,0 11,0 11,0
Nueva Aldea U3 8,0 8,0 8,0 8,0
Nueva Renca TG 150,0 100,0 200,0 150,0
Nueva Renca TV 75,0 50,0 100,0 75,0
Nueva Ventanas 270,0 180,0 270,0 180,0
Ojos de Agua 8,0 8,0 8,0 8,0
Orafti 1,0 1,0 1,0 1,0
Pacífico 1 14,0 14,0 14,0 14,0
Pacífico 2 25,0 25,0 25,0 25,0
Palmucho 26,0 26,0 26,0 ---
Pangue U1 200,0 200,0 150,0 ---
Pangue U2 200,0 200,0 --- ---
Pehuenche U1 250,0 180,0 250,0 120,0
Pehuenche U2 200,0 180,0 --- 120,0
PetroPower 65,0 --- 65,0 65,0
Peuchen U2 13,0 10,0 13,0 10,0
Picoiquén 2,0 2,0 2,0 2,0
Pilmaiquen U1 4,0 4,0 4,0 4,0
Pilmaiquen U2 4,0 4,0 4,0 4,0
Pilmaiquen U3 4,0 4,0 4,0 4,0
Pilmaiquen U4 10,0 10,0 10,0 10,0
Pilmaiquen U5 10,0 10,0 10,0 10,0
Providencia U1 0,7 0,7 0,7 0,7
Providencia U2 0,7 0,7 0,7 0,7
Pulelfu U1 1,5 1,5 1,5 1,5
Pulelfu U2 1,5 1,5 1,5 1,5
Pullinque U1 10,0 10,0 10,0 10,0

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
207-
285

Hidrología Húmeda Hidrología Seca


Central Demanda
Demanda Alta Demanda Alta Demanda Baja
Baja
Pullinque U2 10,0 10,0 10,0 10,0
Pullinque U3 10,0 10,0 10,0 ---
Queltehues U1 13,0 13,0 13,0 13,0
Queltehues U2 13,0 13,0 13,0 13,0
Queltehues U3 13,0 13,0 13,0 13,0
Quilleco U1 12,0 12,0 12,0 12,0
Quilleco U2 12,0 12,0 12,0 12,0
Quintero TG1A 120,0 --- 120,0 120,0
Quintero TG1B 120,0 --- 120,0 ---
Ralco U1 168,7 166,5 187,2 122,2
Ralco U2 300,0 170,0 250,0 100,0
Renaico 6,0 6,0 6,0 6,0
Rucatayo 50,0 50,0 15,0 15,0
Rucue U1 27,0 27,0 70,0 27,0
Rucue U2 27,0 27,0 70,0 27,0
Río Huasco 0,4 0,4 0,4 0,4
San Andrés U1 20,0 15,0 20,0 15,0
San Andrés U2 20,0 15,0 20,0 15,0
San Clemente 1,0 1,0 1,0 1,0
San Ignacio 24,0 --- 24,0 ---
San Isidro U1 TG --- --- 220,0 ---
San Isidro U1 TV --- --- 106,0 ---
San Isidro U2 TG --- --- 240,0 ---
San Isidro U2 TV --- --- 120,0 ---
Santa Fe Energía 5,0 5,0 5,0 5,0
Santa Fé 2 30,0 30,0 30,0 30,0
Santa Fé 3 30,0 30,0 30,0 30,0
Santa Marta 12,0 12,0 12,0 12,0
Santa María 200,0 120,0 350,0 350,0
Sauzal U1 25,0 15,0 25,0 15,0
Sauzal U2 25,0 15,0 25,0 15,0
Sauzal U3 25,0 15,0 25,0 15,0
Sauzalito 12,0 12,0 12,0 12,0
Truful-Truful 0,3 0,3 0,3 0,3
Valdivia 70,0 70,0 70,0 70,0
Ventanas U1 115,0 80,0 115,0 80,0
Ventanas U2 200,0 --- 200,0 180,0
Viñales 25,0 25,0 25,0 25,0

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
208-
285

V.2. Despacho de Centrales de ERNC

Tabla V-2: Despacho de generación, Centrales Convencionales


Hidrología Húmeda Hidrología Seca
ERNC
Demanda Alta Demanda Baja Demanda Alta Demanda Baja
Carrera Pinto 6,29 5,24 6,29 5,24
Chañares 11,28 9,40 11,28 9,40
Conejo 31,20 26,00 31,20 26,00
Cuel x10 4,50 3,75 4,50 3,75
Cuel x12 5,40 4,50 5,40 4,50
Dda Solar_01 0,99 0,82 0,99 0,83
Dda Solar_02 0,89 0,74 0,89 0,74
Dda Solar_03 2,38 1,98 2,38 1,98
Dda Solar_04 2,57 2,14 2,57 2,15
Dda Solar_05 2,57 2,14 2,57 2,15
Dda Solar_06 0,20 0,16 0,20 0,17
El Arrayán 35,20 29,34 35,20 29,34
Javiera_01 9,49 7,91 9,49 7,91
Javiera_02 9,49 7,91 9,49 7,91
La Esperanza 3,24 2,70 3,24 2,70
Lalackama 17,38 14,49 17,38 14,49
LlanodeLlampos_01 19,24 16,03 19,24 16,03
LlanodeLlampos_02 11,97 9,97 11,97 9,97
Loma Los Colorados FV 0,32 0,27 0,32 0,27
Los Buenos Aires 7,20 6,00 7,20 6,00
Los Cururos 34,20 28,50 34,20 28,50
Luz del Norte 40,44 33,70 40,44 33,70
PE Renaico 21,12 17,60 21,12 17,60
PE San Juan 44,40 37,00 44,40 37,00
PE Taltal 29,70 24,75 29,70 24,75
PV Salvador 21,06 17,55 21,06 17,55
Pampa Solar Norte 21,91 18,26 21,91 18,26
RTS 0,86 0,72 0,86 0,72
SDGx1_A 0,15 0,13 0,15 0,13
SDGx1_B 0,15 0,13 0,15 0,13
San Andrés PV_01 4,70 3,92 4,70 3,92
San Andrés PV_02 4,70 3,92 4,70 3,92
San Andrés PV_03 1,71 1,42 1,71 1,42
San Andrés PV_04 3,85 3,21 3,85 3,21
Talinay Poniente_A 8,40 7,00 8,40 7,00
Talinay Poniente_B 10,80 9,00 10,80 9,00
Totoral 13,66 11,39 13,66 11,39
Ucuquer2 (x5) 3,00 2,50 3,00 2,50
PV Olmue 45,60 38,00 45,60 38,00
PV Quilapilun 31,20 26,00 31,20 26,00
San Pedro 9,00 9,00 9,00 9,00

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
209-
285

ANEXO VI. PRINT OUT NUEVAS PROTECCIONES SE CIRUELOS

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
210-
285

VI.1 S/E Ciruelos paño Cautín C2

VI.1 Protección 7SA612

Device configuration
No. Settings Ajuste
103 Setting group change Option Disabled
110 Trip Mode 1-/3 pole
114 21 Distance Protection Pickup program Z<(quadrilat.)
119 Additional Threshold Iph>(Z1) Disabled
120 68 Power swing detection Enabled
121 85-21 Pilot Protection for distance prot. PUTT (Z1B)
122 DTT Direct Transfer Trip Disabled
124 50HS Instantaneous SOTF Enabled
125 Weak Infeed (Trip and/or Echo) Disabled
126 50(N)/51(N) BackUp O/C Time Overcurrent Curve IEC
131 50N/51N Earth Fault O/C Time Overcurrent Curve IEC
132 85-67N Pilot Protection Earth O/C Directional Comparison Pickup
133 79 Auto-Reclose Function 1 AR-Cycle
134 Auto-Reclose control Mode With trip and Action Time
135 25 Synchro-Check Enabled
136 81 Over/Underfrequency Protection Disabled
137 27, 59 Under/Overvoltage Protection Disabled
138 Fault Locator Enabled
139 50BF Breaker Failure Protection Enabled w/3Io>
140 74TC Trip Circuit Supervision Disabled
142 49 Thermal Overload Disabled

Power System Data 1


Transformers
No. Settings Ajuste
201 Ct Starpoint Towards Line
203 Rated Primary Voltage 230
204 Rated Secondary Voltage (Ph-Ph) 115 V
205 CT rated Primary Current 800
206 CT Rated Secondary Current 5
210 V4 Voltage Transformer is Vsy2 transformer
211 Matching ratio phase-VT to open-Delta-VT 1,73
212 VT connection for Vsy2 L2-E
214A Angle adjustment Vsy2-Vsy1 0°
215 Matching ratio Vsy1/Vsy2 1

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
211-
285

220 I4 Current Transformers is Neutral Current (of the protected line)


221 Matching ratio I4/Iph for CT`s 1

Power System
No. Settings Ajuste
207 System Startpoint is Solid Grounded
230 Rated Frequency 50 Hz
235 Phase Sequence ABC
236 Distance measurement unit km
237 Setting format for zero seq.comp. forma Zero seq. comp. factor K0 and angle(K0)
238A 50N/51N Gnd O/C: setting for 1p. 79 AR all elements together

Breaker
No. Settings Ajuste
239 Closing (operating) time of 52 (CB) 0,06 Seg
240A Minimum TRIP Command Duration 0,1 Seg
241A Maximum Close Command Duration 0,1 Seg
242 Dead Time for CB test-autoreclosure 0,1 Seg

Power System Data 2


Load Line End
No. Settings Ajuste
1103 Measurem:FullScaleVoltage(Equipm.rating) 220 kV
1104 Measurem:FullScaleCurrent(Equipm.rating) 800
1105 Line Angle 71
1211 Angle of inclination, distance charact. 71
1107 P,Q operational measured values sign Not reversed
1110 x' - Line Reactance per length unit 0,0328
1111 Line Length 109,9
1120 Zero seq. comp. factor K0 for zone Z1 0,76
1121 Zero seq. comp. angle for zone Z1 10,8
1122 Zero seq.comp.factor K0,higher zones >Z1 0,76
1123 Zero seq. comp. angle, higher zones >Z1 10,8

Line Status
No. Settings Ajuste
1130A Pole Open Current Threshold 0,5 A
1131A Pole Open Voltage Threshold 30 V
1132A Seal-in Time after ALL closures 0,05 seg
1134 Recognition of Line Closures with CBpos(52a) OR I or ManCl
1135 RESET of Trip Command Current Open Pole
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
212-
285

1136 open pole detector with Measurement


1140A CT Saturation Threshold 40 A
1150A Seal-in Time after MANUAL closures 0,3 Seg
1151 Manual CLOSE COMMAND generation With Sync-check
1152 MANUAL Closure impulse after CONTROL None

Trip 1-/3-pole
No. Settings Ajuste
1155 3 pole coupling with Trip
1156A Trip type with 2 phase faults 3 pole

21 Distance Protection
General
No. Settings Ajuste
1201 21 Distance protection is ON
1202 Phase Current threshold for dist. meas. 1,25 A
1211 Angle of inclination, distance charact 71
1208 Series compensated line No
1232 Instantaneous trip after SwitchOnToFault Zone Z1B
1241 R load, minimum Load Impedance (ph-g) 10,3 Ohm
1242 PHI load, maximum Load Angle (ph-g) 30
1243 R load, minimum Load Impedance (ph-ph) 10,3 Ohm
1244 PHI load, maximum Load Angle (ph-ph) 30
1317A Single pole trip for faults in Z2 No
1357 Z1B enabled before 1st AR (int. or ext.) No

Ground Faults
No. Settings Ajuste
1203 3I0 threshold for neutral current pickup 0,5 A
1204 3V0 threshold zero seq. voltage pickup 5V
1207A 3I0>-pickup-stabilisation (3I0>/ Iphmax) 0,1
1209A Criterion of ground fault recognition 3I0> OR 3V0>
1221A Loop selection with 2Ph-G faults All loops

Time Delay
No. Settings Ajuste
1210 21 Condition for zone timer start With Distance Pickup
1305 T1-1phase, delay for single phase faults 0,00 Seg
1306 T1multi-ph, delay for multi phase faults 0,00 Seg
1315 T2-1phase, delay for single phase faults 0,60 Seg
1316 T2multi-ph, delay for multi phase faults 0,60 Seg
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
213-
285

1325 T3 delay oo Seg


1335 T4 delay 1,20 Seg
1345 T5 delay oo Seg
1365 T6 delay oo seg
1355 T1B-1phase, delay for single ph. faults 0,00 Seg
1356 T1B-multi-ph, delay for multi ph. faults 0,00 Seg

Zone Z1
No. Settings Ajuste
1301 Operating mode Z1 Forward
1302 R(Z1), Resistance for ph-ph-faults 2,18 Ohm
1303 X(Z1), Reactance 2,18 Ohm
1304 RG(Z1), Resistance for ph-gnd faults 6,53 Ohm
1305 T1-1phase, delay for single phase faults 0,00 seg
1306 T1multi-ph, delay for multi phase faults 0,00 seg
1307 Zone Reduction Angle (load compensation) 0

Zone Z1b
No. Settings Ajuste
1351 Operating mode Z1B Forward
1352 R(Z1B), Resistance for ph-ph-faults 5,69 Ohm
1353 X(Z1B), Reactance 5,69 Ohm
1354 RG(Z1B), Resistance for ph-gnd faults 17,06 Ohm
1355 T1B-1phase, delay for single phase faults 0,00 seg
1356 T1B-multi-ph, delay for multi phase faults 0,00 seg
1357 Z1B enabled before 1st AR (int. or ext.) No

Zone Z2
No. Settings Ajuste
1311 Operating mode Z2 Forward
1312 R(Z2), Resistance for ph-ph-faults 5,69 Ohm
1313 X(Z2), Reactance 5,69 Ohm
1314 RG(Z2), Resistance for ph-gnd faults 17,06 Ohm
1315 T2-1phase, delay for single phase faults 0,60 seg
1316 T2multi-ph, delay for multi phase faults 0,60 seg
1317A Single pole trip for faults in Z2 NO

Zone Z3
No. Settings Ajuste
1321 Operating mode Z3 Reverse
1322 R(Z3), Resistance for ph-ph-faults 4,88 Ohm
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
214-
285

1323 X(Z3), Reactance 2,13 Ohm


1324 RG(Z3), Resistance for ph-gnd faults 11,2 Ohm
1325 T3 delay oo seg

Zone Z4
No. Settings Ajuste
1331 Operating mode Z4 Forward
1332 R(Z4), Resistance for ph-ph-faults 11,06 Ohm
1333 X(Z4), Reactance 11,06 Ohm
1334 RG(Z4), Resistance for ph-gnd faults 20,46 Ohm
1335 T4 delay 1,20 seg

Zone Z5
No. Settings Ajuste
1341 Operating mode Z5 Non Directional
1342 R(Z5), Resistance for ph-ph-faults 13,27 Ohm
1343 X(Z5), Reactance 13,27 Ohm
1344 RG(Z5), Resistance for ph-gnd faults 24,55 Ohm
1345 T5 delay oo seg
1346 X(Z5)-, Reactance for Reverse Direction 13,27 Ohm

Zone Z6
No. Settings Ajuste
1361 Operating mode Z6 Inactive
1362 R(Z6), Resistance for ph-ph-faults 15,00 Ohm
1363 X(Z6), Reactance 15,00 Ohm
1364 RG(Z6), Resistance for ph-gnd faults 15,00 Ohm
1365 T6 delay oo seg
1366 X(Z6)-, Reactance for Reverse Direction 4,00 Ohm

Power Swing Blocking


No. Settings Ajuste
2002 Power Swing Operation Mode. All Zones Block
2006 Power Swing Trip NO
2007 Trip After Power Swing Blocking 0,08 Seg

85-21 Pilot Prot. For Distance prot.


No. Settings Ajuste
2101 85-21 Pilot Prot. for Distance prot. ON
2102 Type of Line Two Terminal

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
215-
285

2103A Time for send signal prolongation 0,08 Seg


2109A Transient Block: Duration external flt. 0,03 Seg
2110A Transient Block: Blk.T. after ext. flt. 0,15 Seg
2112A DIS transient block by EF NO
2113 Memorize receive signal NO

50HS Instantaneous SOTF


No. Settings Ajuste
2401 50HS Instantaneous SOTF-O/C is ON
2404 50HS SOTF-O/C PICKUP 12,5 A

50(N)/51(N) Backup OverCurrent; Group 50(N)-B1


General
No. Settings Ajuste
2601 Operating Mode ON:with VT loss
2680 Trip time Delay after SOFT 0,00 seg

50(N)-B1
No. Settings Ajuste
2610 50-B1 Pickup oo A
2611 50-B1 Delay oo Seg
2612 50N-B1 Pickup oo A
2613 50N-B1 Delay oo seg
2614 Instantaneous trip via Pilot Prot./BI NO
2615 Instantaneous trip after SwitchOnToFault NO

50(N)-B2
No. Settings Ajuste
2620 50-B2 Pickup oo A
2621 50-B2 Delay oo Seg
2622 50N-B2 Pickup oo A
2623 50N-B2 Delay oo Seg
2624 Instantaneous trip via Pilot Prot./BI NO
2625 Instantaneous trip after SwitchOnToFault NO

51(N)-B
No. Settings Ajuste
2640 51-B Pickup 6,0 A
2642 51-B Time Dial for IEC characteristic 0,05

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
216-
285

2646 51-B Additional Time Delay 0,00 seg


2650 51N-B Pickup 0,75 A
2652 51N-B Time Dial for IEC characteristic 0,6 seg
2656 51N-B Additional Time Delay 0,0 seg
2660 IEC Curve Normal Inverse
2670 Instantaneous trip via Pilot Prot./BI NO
2671 Instantaneous trip after SwitchOnToFault NO

50(N)-STUB
No. Settings Ajuste
2630 50-STUB Pickup oo A
2631 50-STUB Delay oo seg
2632 50N-STUB Pickup oo A
2633 50N-STUB Delay oo seg
2634 Instantaneous trip via Pilot Prot./BI NO
2635 Instantaneous trip after SwitchOnToFault NO

Measurement Supervision
Balance/Summ
No. Settings Ajuste
2901 Measurement Supervision ON
2902A Voltage Threshold for Balance Monitoring 50 V
2903A Balance Factor for Voltage Monitor 0,75
2904A Current Threshold for Balance Monitoring 2,5 A
2905A Balance Factor for Current Monitor 0,5
2906A Summated Current Monitoring Threshold 0,5 A
2907A Summated Current Monitoring Factor 0,1
2908A T Balance factor for Voltage Monitor 5,00 seg
2909A T Current Balance Monitor 5,00 seg

Volt. Fail
No. Settings Ajuste
2910 Fuse Failure Monitor ON
2911A Minimun Voltage Threshold V> 22 V
2912A Maximum Current Threshold I< 1,1 A
2913A Maximum Voltage Threshold V< 5V
2914A Differential Current Threshold 0,5 A
2915 Voltage Failure Supervision With current supervision
2916A Delay Voltage Failure Supervision 3,00 seg

VT mcb

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
217-
285

No. Settings Ajuste


2921 VT mcb operating time 0,00 mseg

Load Angle
No. Settings Ajuste
2941 Limit setting PhiA 200°
2942 Limit setting PhiB 340°
2943 Minimum value I1> 0,25 A
2944 Minimum value U1> 20 V

50N/51N Ground OverCurrent


General
No. Settings Ajuste
3101 50N/51N Ground Overcurrent ON
3102 Block 50N/51N for Distance protection every PICKUP
3174 Block 50N/51N for Pickup 21 in each zone
3103 Block 50N/51N for 1pole Dead time YES
3104A Stabilisation Slope with Iphase 10%
3105 3I0-Min threshold for Pilot Prot.schemes 2,50 A
3109 Single pole trip with ground flt.prot. NO
3170 2nd harmonic ratio for inrush restraint 15%
3171 Max.Current, overriding inrush restraint 7,5 A
3172 Instantaneous mode after SwitchOnToFault with Pickup and direction
3173 Trip time delay after SOTF 0,00 sec

50N-1
No. Settings Ajuste
3110 Operating mode Forward
3111 Pickup 8,15 A
3112 Time Delay 0,30 seg
3113 Instantaneous trip via Pilot Prot./BI YES
3114 Instantaneous trip after SwitchOnToFault NO
3115 Inrush Blocking NO

50N-2
No. Settings Ajuste
3120 Operating mode Inactive
3121 Pickup oo A
3122 Time Delay oo seg
3123 Instantaneous trip via Pilot Prot./BI NO
3124 Instantaneous trip after SwitchOnToFault NO
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
218-
285

3125 Inrush Blocking NO

50N-3
No. Settings Ajuste
3130 Operating mode Inactive
3131 Pickup oo A
3132 Time Delay oo seg
3133 Instantaneous trip via Pilot Prot./BI NO
3134 Instantaneous trip after SwitchOnToFault NO
3135 Inrush Blocking NO

50N-4 Def. Time


No. Settings Ajuste
3140 Operating mode Forward
3141 Pickup 0,75 A
3143 3I0p Time Dial 0,6
3147 Additional Time Delay 0,00 Seg
3148 Instantaneous trip via Pilot Prot./BI YES
3149 Instantaneous trip after SwitchOnToFault NO
3150 Inrush Blocking NO
3151 IEC Curve Very Inverse

Direction
No. Settings Ajuste
3160 Polarization U0 + IY or U2
3162A ALPHA, lower angle for forward direction 338
3163A BETA, upper angle for forward direction 122
3164 Min. zero seq.voltage 3Vo for polarizing 0,5 V
3166 Min. neg. seq. polarizing voltage 3V2 0,5 V
3167 Min. neg. seq. polarizing current 3I2 0,25 A
3168 Compensation angle PHI comp. for Sr 255
3169 Forward direction power treshold 0,5 VA
3186A 3V0 min for forward direction 0,0 V
3187A Reactance X of series Capacitor 0,00 Ohm

85-67N Pilot Prot. For Ground Overcurrent


No. Settings Ajuste
3201 85-67N Pilot Prot. for Dir.Ground O/C ON
3202 Line Configuration Two Terminal
3203A Time for send signal prolongation 0,08 Seg
3209A Transient Block.: Duration external flt. 0,03 Seg
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
219-
285

3210A Transient Block.: Blk.T. after ext. flt. 0,15 Seg


3212A EF transient block by DIS NO

79 Auto Reclosing
General
No. Settings Ajuste
3401 79 Auto-Reclose Function ON
3402 52-ready interrogation at 1st trip NO
3403 Reclaim time after successful AR cycle 3,00 Seg
3404 AR blocking duration after manual close 1,00 Seg
3406 Evolving fault recognition with Trip
3407 Evolving fault (during the dead time) starts 3pole AR-cycle
3408 AR start-signal monitoring time 0,2 Seg
3409 Circuit Breaker (CB) Supervision Time 3,00 Seg
3410 Send delay for remote close command oo Seg
3411A Maximum dead time extension oo Seg

1st AR-Cycle
No. Settings Ajuste
3450 Start of AR allowed in this cycle Yes
3451 Action time 0,5 seg
3456 Dead time after 1pole trip 1,2 seg
3457 Dead time after 3pole trip 0,5 seg
3458 Dead time after evolving fault 1,2 seg
3459 52-ready interrogation before reclosing YES
3460 Request for synchro-check after 3pole AR YES

3pTrip
No. Settings Ajuste
3430 3pole TRIP by AR Yes
3431 Dead Line Check or Reduced Dead Time Without
3435 1pole Trip Allowed No
3438 Supervision time for dead/ live voltage 0,1 seg
3440 Voltage Threshold for live line or bus 48 V
3441 Voltage threshold for dead line or bus 30 V

Star AR with
No. Settings Ajuste
3420 AR with 21 Yes
3423 AR with 50N/51N Yes
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
220-
285

3424 AR with DTT No


3425 AR with 50(N)-B No

25 Synchronism and Voltage


General
No. Settings Ajuste
3501 25 Synchronism and Voltage Check ON
3502 Voltage threshold dead line / bus 13 V
3503 Voltage threshold live line / bus 47 V
3504 Maximum permissible voltage 70 V
3507 Maximum duration of synchronism-check 1,00 seg
3508 Synchronous condition stability timer 0,00 seg
3509 Synchronizable circuit breaker None

with AR
No. Settings Ajuste
3510 Operating mode with AR without consideration of 52 closing time
3511 Maximum voltage difference 6,4 V
3512 Maximum frequency difference 0,2 Hz
3513 Maximum angle difference 30
3515A 79 at Vsy2>, Vsy1>, and Synchr. Yes
3516 79 at Vsy1< and Vsy2> Yes
3517 79 at Vsy1> and Vsy2< Yes
3518 79 at Vsy1< and Vsy2< No
3519 Override of any check before 79 No

Manual Close
No. Settings Ajuste
3530 Operating mode with Man. Cl without consideration of 52 closing time
3531 Maximum voltage difference 6,4 V
3532 Maximum frequency difference 0,2 Hz
3533 Maximum angle difference 30
3535A Manual at Vsy2>, Vsy1>, and Synchr. Yes
3536 Manual at Vsy1< and Vsy2> Yes
3537 Manual at Vsy1> and Vsy2< Yes
3538 Manual at Vsy1< and Vsy2< Yes
3539 Override of any check before Man. Cl No

Fault Locator
No. Settings Ajuste
3802 Start fault locator with Pickup
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
221-
285

3806 Load Compensation No

Breaker Failure
No. Settings Ajuste
3901 FCT BreakerFail ON
3902 I> BF 2,85 A
3903 1p-RETRIP (T1) YES
3904 T1-1pole 0,01 sec
3905 T1-3pole 0,01 sec
3906 T2 0,2 sec
3907 T3-BkrDefective 0,00 sec
3908 Trip BkrDefect NO
3909 Chk BRK CONTACT YES
3912 3I0> BF 1,5 A
3913 T2StartCriteria Parallel withT1
3921 End Flt. stage OFF
3922 T-EndFault 2,00 sec
3931 PoleDiscrepancy OFF
3932 T-PoleDiscrep. 2,00 sec

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
222-
285

VI.12 Protección REL670

ZMQPDIS (21) Group settings Zona Z1


Name Unit Step Setting
Operation - - Enabled
IBase A 1 800
VBase kV 0,05 230
OperationDir - - Forward
X1 ohm/p 0,01 27,19
R1 ohm/p 0,01 11,14
X0 ohm/p 0,01 92,75
R0 ohm/p 0,01 22,46
RFPP ohm/l 0,01 54,38
RFPG ohm/l 0,01 81,57
OperationPP - - Enabled
Timer tPP - - Enabled
tPP s 0,001 0
OperationPG - - Enabled
Timer tPG - - Enabled
tPG s 0,001 0
IMinPUPP %IB 1 20
IMinPUPG %IB 1 20
IMinOpIR %IB 1 5
ZMQAPDIS (21) Group settings (basic) Zona 2
Name Unit Step Setting
Operation - - Enabled
IBase A 1 800
Vbase kV 0,05 230
OperationDir - - Forward
X1 ohm/p 0,01 71,06
R1 ohm/p 0,01 20,39
X0 ohm/p 0,01 242,42
R0 ohm/p 0,01 41,11
RFPP ohm/l 0,01 142,13
RFPG ohm/l 0,01 213,19
OperationPP - - Enabled
Timer tPP - - Enabled
tPP s 0,001 0,6
OperationPG - - Enabled
Timer tPG - - Enabled
tPG s 0,001 0,6

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
223-
285

IMinPUPP %IB 1 20
IMinPUPG %IB 1 20
ZMQAPDIS (21) Group settings (basic) Zona 3
Name Unit Step Setting
Operation - - Enabled
IBase A 1 800
Vbase kV 0,05 230
OperationDir - - Forward
X1 ohm/p 0,01 138,23
R1 ohm/p 0,01 29,25
X0 ohm/p 0,01 554
R0 ohm/p 0,01 85,2
RFPP ohm/l 0,01 276,45
RFPG ohm/l 0,01 255,72
OperationPP - - Enabled
Timer tPP - - Enabled
tPP s 0,001 1,2
OperationPG - - Enabled
Timer tPG - - Enabled
tPG s 0,001 1,2
IMinPUPP %IB 1 20
IMinPUPG %IB 1 20
ZMQAPDIS (21) Group settings (basic) Zona 4
Name Unit Step Setting
Operation - - Enabled
IBase A 1 800
Vbase kV 0,05 230
OperationDir - - Reverse
X1 ohm/p 0,01 26,62
R1 ohm/p 0,01 7,99
X0 ohm/p 0,01 35,78
R0 ohm/p 0,01 7,29
RFPP ohm/l 0,01 121,96
RFPG ohm/l 0,01 140,04
OperationPP - - Enabled
Timer tPP - - Enabled
tPP s 0,001 60
OperationPG - - Enabled
Timer tPG - - Enabled
tPG s 0,001 60
IMinPUPP %IB 1 20
IMinPUPG %IB 1 20
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
224-
285

ZDRDIR (21D) Group settings (basic)


Name Unit Step Setting
IBase A 1 800
VBase kV 0,05 230
IMinPUPP %IB 1 10
IMinPUPG 1 1 5
AngNegRes 1 1 115
AngDir 1 1 15
FDPSPDIS (21) Group settings (basic)
Name Unit Step Setting
IBase A 1 800
VBase kV 0,01 230
3I0BLK_PP %IPh 1 40
3I0Enable_PG %IPh 1 20
RLdFwd ohm/p 0,01 128,75
RldRev ohm/p 0,01 128,75
LdAngle Deg 1 30
X1 ohm/p 0,01 199,05
X0 ohm/p 0,01 797,76
RFltFwdPP ohm/l 0,01 331,74
RFltRevPP ohm/l 0,01 146,35
RFltFwdPG ohm/l 0,01 306,86
RFltRevPG ohm/l 0,01 168,05
IMinPUPP %IB 1 10
IMinPUPG %IB 1 5
OperationZ< - - Enabled
OperationI> - - Disabled
IPh> %IB 1 120
Pickup_N %IB 1 20
TimerPP - - Disabled
tPP s 0,001 3
TimerPE - - Disabled
tPG s 0,001 3
Instantaneous phase overcurrent protection PHPIOC (50)
Name Unit Step Setting
Operation - - Disabled
IBase A 1 800
OpModeSel - - 1 out of 3
Pickup %IB 1 200
MultPU - 0,1 1.0
Instantaneous residual overcurrent protection EFPIOC (50N)

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
225-
285

Name Unit Step Setting


Operation - - Disabled
IBase A 1 800
Pickup %IB 1 200
MultPU - 0,1 1.0
OC4PTOC (51_67) Group settings
Name Unit Step Setting
Operation - - On
IBase A 1 800
Vbase kV 0,05 230
AngleRCA Deg 1 65
AngleROA Deg 1 80
NumPhSel - - 1 out of 3
DirModeSel1 - - Non-directional
Characterist1 - - IEC Norm. inv.
Pickup1 %IB 1 120
t1 s 0,001 0
TD1 - 0,01 0,05
IMin1 %IB 1 20
t1Min s 0,001 0
MultPU1 - 0,1 1
DirModeSel2 - - Disabled
Characterist2 - - ANSI Def. Time
Pickup2 %IB 1 500
t2 s 0,001 0,4
TD2 - 0,01 0,05
IMin2 %IB 1 50
t2Min s 0,001 0
MultPU2 - 0,1 2
DirModeSel3 - - Disabled
Characterist3 - - ANSI Def. Time
Pickup3 %IB 1 250
t3 s 0,001 0,8
TD3 - 0,01 0,05
IMin3 %IB 1 33
t3Min s 0,001 0
MultPU3 - 0,1 2
DirModeSel4 - - Disabled
Characterist4 - - ANSI Def. Time
Pickup4 %IB 1 175
t4 s 0,001 2
TD4 - 0,01 0,05

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
226-
285

IMin4 %IB 1 17
t4Min s 0,001 0
MultPU4 - 0,1 2
PUMinOpPhSel %IB 1 7
2ndHarmStab %IB 1 20
ResetTypeCrv1 - - Instantaneous
tReset1 s 0,001 0,02
tPCrv1 - 0,001 1
tACrv1 - 0,001 13,5
tBCrv1 - 0,01 0
tCCrv1 - 0,1 1
tPRCrv1 - 0,001 0,5
tTRCrv1 - 0,001 13,5
tCRCrv1 - 0,1 1
HarmRestrain1 - - Disabled
ResetTypeCrv2 - - Instantaneous
tReset2 s 0,001 0,02
tPCrv2 - 0,001 1
tACrv2 - 0,001 13,5
tBCrv2 - 0,01 0
tCCrv2 - 0,1 1
tPRCrv2 - 0,001 0,5
tTRCrv2 - 0,001 13,5
tCRCrv2 - 0,1 1
HarmRestrain2 - - Disabled
ResetTypeCrv3 - - Instantaneous
tReset3 s 0,001 0,02
tPCrv3 - 0,001 1
tACrv3 - 0,001 13,5
tBCrv3 - 0,01 0
tCCrv3 - 0,1 1
tPRCrv3 - 0,001 0,5
tTRCrv3 - 0,001 13,5
tCRCrv3 - 0,1 1
HarmRestrain3 - - Disabled
ResetTypeCrv4 - - Instantaneous
tReset4 s 0,001 0,02
tPCrv4 - 0,001 1
tACrv4 - 0,001 13,5
tBCrv4 - 0,01 0
tCCrv4 - 0,1 1
tPRCrv4 - 0,001 0,5

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
227-
285

tTRCrv4 - 0,001 13,5


tCRCrv4 - 0,1 1
HarmRestrain4 - - Disabled
EF4PTOC (51N67N) Group settings
Name Unit Step Setting
Operation - - ON
IBase A 1 800
VBase kV 0,05 230
AngleRCA Deg 1 65
polMethod - - Voltage
VPolMin %VB 1 1
IPolMin %IB 1 5
RNPol ohm 0,01 5
XNPol ohm 0,01 40
INDirPU %IB 1 10
2ndHarmStab % 1 20
BlkParTransf - - Disabled
Use_PUValue - - ST4
SOTF - - Disabled
SOTFSel - - Open
StepForSOTF - - Step 2
EnHarmRestSOTF - - Disabled
tSOTF s 0,001 0,2
t4U s 0,001 1
ActUndrTimeSel - - CB position
tUnderTime s 0,001 0,3
DirModeSel1 - - Forward
Characterist1 - - IEC Def. Time
Pickup1 %IB 1 163
t1 s 0,001 0,3
TD1 - 0,01 0
IMin1 %IB 1 15
t1Min s 0,001 0
MultPU1 - 0,1 1
ResetTypeCrv1 - - Instantaneous
tReset1 s 0,001 0,02
HarmRestrain1 - - Enabled
tPCrv1 - 0,001 1
tACrv1 - 0,001 13,5
tBCrv1 - 0,01 0
tCCrv1 - 0,1 1
tPRCrv1 - 0,001 0,5

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
228-
285

tTRCrv1 - 0,001 13,5


tCRCrv1 - 0,1 1
DirModeSel2 - - Forward
Characterist2 - - IEC Very Inverse
Pickup2 %IB 1 15
t2 s 0,001 0
TD2 - 0,01 0,6
IMin2 %IB 1 15
t2Min s 0,001 0
MultPU2 - 0,1 2
ResetTypeCrv2 - - Instantaneous
tReset2 s 0,001 0,02
HarmRestrain2 - - Off
tPCrv2 - 0,001 1
tACrv2 - 0,001 13,5
tBCrv2 - 0,01 0
tCCrv2 - 0,1 1
tPRCrv2 - 0,001 0,5
tTRCrv2 - 0,001 13,5
tCRCrv2 - 0,1 1
DirModeSel3 - - Non Directional
Characterist3 - - IEC Very Inverse
Pickup3 %IB 1 15
t3 s 0,001 0
TD3 - 0,01 0,6
IMin3 %IB 1 15
t3Min s 0,001 0
MultPU3 - 0,1 2
ResetTypeCrv3 - - Instantaneous
tReset3 s 0,001 0,02
HarmRestrain3 - - Disabled
tPCrv3 - 0,001 1
tACrv3 - 0,001 13,5
tBCrv3 - 0,01 0
tCCrv3 - 0,1 1
tPRCrv3 - 0,001 0,5
tTRCrv3 - 0,001 13,5
tCRCrv3 - 0,1 1
DirModeSel4 - - Disabled
Characterist4 - - ANSI Def. Time
Pickup4 %IB 1 17
t4 s 0,001 1,2

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
229-
285

TD4 - 0,01 0,05


IMin4 %IB 1 17
t4Min s 0,001 0
MultPU4 - 0,1 2
ResetTypeCrv4 - - Instantaneous
tReset4 s 0,001 0,02
HarmRestrain4 - - Disabled
tPCrv4 - 0,001 1
tACrv4 - 0,001 13,5
tBCrv4 - 0,01 0
tCCrv4 - 0,1 1
tPRCrv4 - 0,001 0,5
tTRCrv4 - 0,001 13,5
tCRCrv4 - 0,1 1
AutomaticSOFT(PSOF), ZCVPSOF
Name Unit Step Setting
Operation - - Enabled
IBase A 1 800
VBase kV 0,05 230
Mode - - VILvl&Imp
AutoInit - - Disabled
IphPickup %IB 1 100
UVPickup %VB 1 70
tDuration s 0,001 0,04
tSOTF s 0,001 1
tDLD s 0,001 0,2
Power Swing Detection (RPSB,68), ZMRPSB
Name Unit Step Setting
Operation - - Enabled
X1InFw ohm 0,01 158,96
R1LIn ohm 0,01 33,64
R1FInFw ohm 0,01 158,96
X1InRv ohm 0,01 158,96
R1FInRv ohm 0,01 158,96
OperationLdCh - - Enabled
RLdOutFw ohm 0,01 423,89
LdAngle Deg 1 30
RLdOutRv ohm 0,01 423,89
kLdRFw Mult 0,01 0,75
kLdRRv Mult 0,01 0,75
tGF s 0,001 15
IMinPUPG %IB 1 10
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
230-
285

IBase A 1 800
tP1 s 0,001 0,05
tP2 s 0,001 0,02
tW s 0,001 0,2
tH s 0,001 0,5
tR1 s 0,001 0,3
tR2 s 0,001 2
Undervoltage protection UV2PTUV (27)
Name Unit Step Setting
Operation - - Disabled
VBase kV 0,05 230
OperationStep1 - - Disabled
Characterist1 - - Definite time
OpMode1 - - 1 out of 3
Pickup1 %VB 1 70
t1 s 0,01 3
t1Min s 0,001 3
TD1 - 0,01 0,05
IntBlkSel1 - - Disabled
IntBlkStVal1 %VB 1 20
tBlkUV1 s 0,001 0
HystAbs1 %VB 0,1 0,5
OperationStep2 - - Disabled
Characterist2 - - Definite time
OpMode2 - - 1 out of 3
Pickup2 %VB 1 50
t2 s 0,001 5
t2Min s 0,001 5
TD2 - 0,01 0,05
IntBlkSel2 - - Disabled
IntBlkStVal2 %VB 1 20
tBlkUV2 s 0,001 0
HystAbs2 %VB 0,1 0,5
tReset1 s 0,001 0,025
ResetTypeCrv1 - - Disabled
tIReset1 s 0,001 0,025
ACrv1 - 0,001 1
BCrv1 - 0,01 1
CCrv1 - 0,1 0
DCrv1 - 0,001 0
PCrv1 - 0,001 1
CrvSat1 % 1 0

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
231-
285

tReset2 s 0,001 0,025


ResetTypeCrv2 - - Disabled
tIReset2 s 0,001 0,025
ACrv2 - 0,001 1
BCrv2 - 0,01 1
CCrv2 - 0,1 0
DCrv2 - 0,001 0
PCrv2 - 0,001 1
CrvSat2 % 1 0
Overvoltage protection OV2PTOV (59)
Name Unit Step Setting
Operation - - Disabled
VBase kV 0,05 230
OperationStep1 - - Disabled
Characterist1 - - Definite time
OpMode1 - - 1 out of 3
Pickup1 %VB 1 110
t1 s 0,01 3
t1Min s 0,001 5
TD1 - 0,01 0,05
HystAbs1 %VB 0,1 0,5
OperationStep2 - - Disabled
Characterist2 - - Definite time
OpMode2 - - 1 out of 3
Pickup2 %VB 1 120
t2 s 0,001 0,5
t2Min s 0,001 5
TD2 - 0,01 0,05
HystAbs2 %VB 0,1 0,5
tReset1 s 0,001 0,025
ResetTypeCrv1 - - Instantaneous
tIReset1 s 0,001 0,025
ACrv1 - 0,001 1
BCrv1 - 0,01 1
CCrv1 - 0,1 0
DCrv1 - 0,001 0
PCrv1 - 0,001 1
CrvSat1 % 1 0
tReset2 s 0,001 0,025
ResetTypeCrv2 - - Instantaneous
tIReset2 s 0,001 0,025
ACrv2 - 0,001 1

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
232-
285

BCrv2 - 0,01 1
CCrv2 - 0,1 0
DCrv2 - 0,001 0
PCrv2 - 0,001 1
CrvSat2 % 1 0
Fuse failure supervision SDDRFUF
Name Unit Step Setting
Operation - - Enabled
IBase A 1 800
VBase kV 0,05 230
OpModeSel - - V0I0 OR V2I2
3V0PU %VB 1 60
3I0PU %IB 1 20
3V2PU %VB 1 60
3I2PU %IB 1 20
OpDVDI - - Enabled
DVPU %VB 1 70
DIPU %IB 1 15
VPPU %VB 1 70
IPPU %IB 1 10
SealIn - - Enabled
VSealInPU %VB 1 70
IDLDPU %IB 1 20
VDLDPU %VB 1 70
Autorecloser SMBRREC (79)
Name Unit Step Setting
Operation - - External ctrl
ARMode - - 3 phase
t1 1Ph s 0,001 0,5
t1 3Ph s 0,001 0,5
t1 3PhHS s 0,001 0,5
tReset s 0,01 15
tSync s 0,01 1
tTrip s 0,001 0,2
tPulse s 0,001 0,2
tCBClosedMin s 0,01 5
tUnsucCl s 0,01 30
Priority - - None
tWaitForMaster s 0,01 60
NoOfShots - - 1
StartByCBOpen - - Off
CBAuxContType - - NormOpen
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
233-
285

CBReadyType - - CO
t1 2Ph s 0,001 1
t2 3Ph s 0,01 30
t3 3Ph s 0,01 30
t4 3Ph s 0,01 30
t5 3Ph s 0,01 30
Extended t1 - - Disabled
tExtended t1 s 0,001 0,5
tInhibit s 0,001 5
CutPulse - - Disabled
Follow CB - - Disabled
AutoCont - - Disabled
tAutoContWait s 0,001 2
UnsucClByCBChk - - NoCBCheck
BlockByUnsucCl - - Disabled
ZoneSeqCoord - - Disabled
Breaker failure protection CCRBRF (50BF)
Name Unit Step Setting
Operation - - Enabled
IBase A 1 800
FunctionMode - - Current & Contact
BuTripMode - - 1 out of 4
RetripMode - - No CBPos Check
Pickup_PH %IB 1 57
Pickup_N %IB 1 30
t1 s 0,001 0,01
t2 s 0,001 0,2
t2MPh s 0,001 0,2
tPulse s 0,001 0,2
Pickup_BlkCont %IB 1 20
t3 s 0,001 0,03
tCBAlarm s 0,001 5
Scheme communication logic for distance or
overcurrent protection ZCPSCH (85)
Name Unit Step Setting
Operation - - Enabled
SchemeType - - Permissive UR
tCoord s 0,001 0
tSecurity s 0,001 0,1
Unblock - - Disabled
tSecurity s 0,001 0,035
Current reversal and WEI logic for distance protection 3-
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
234-
285

phase ZCRWPSCH
Name Unit Step Setting
CurrRev - - Enabled
tPickUpRev s 0,001 0,15
tDelayRev s 0,001 0,03
WEI - - Off
tPickUpWEI s 0,001 0,01
UBase kV 0,05 230
UPP< %UB 1 70
UPN< %UB 1 35
Scheme communication logic for residual overcurrent
protection ECPSCH (85)
Name Unit Step Setting
Operation - - Enabled
SchemeType - - Permissive UR
tCoord s 0,001 0
tSecurity s 0,001 0,1
Unblock - - Disabled
tSecurity s 0,001 0,035
Current reversal and WEI logic for residual overcurrent
protection ECRWPSCH
Name Unit Step Setting
CurrRev - - Enabled
tPickUpRev s 0,001 0,15
tDelayRev s 0,001 0,03
WEI - - Off
tPickUpWEI s 0,001 0,01
UBase kV 0,05 230
3VOPU %UB 1 25
Synchronizing, synchrocheck and energizing check (RSYN,
25)
SESRSYN_25 (SYN1-) function
Name Unit Step Setting
Operation - - Enabled
SelPhaseBus1 - - phase2
SelPhaseBus2 - - Phase2
SelPhaseLine1 - - Phase2
SelPhaseLine2 - - Phase2
CBConfig .- - No voltage sel
UBase kV 0.001 230
PhaseShift Deg 5 0

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
235-
285

URatio - 0.001 1
OperationSynch - - On
UHighBus Synch % 1.0 80
UHighLineSynch % 1.0 80
UDiffSynch % 1.0 10
FreqDiffMin Hz 0.001 0,01
FreqDiffMax Hz 0.001 0,2
FreqRateChange Hz/s 0.001 0,3
tBreaker s 0.001 0,08
tClosePulse s 0.001 0,2
tMaxSynch s 0.01 600
tMinSynch s 0.001 2
OperationSC - - On
UHighBusSC %UB 1.0 80
UHighLineSC %UB 1.0 80
UDiffSC %UB 1.0 15
FreqDiffA Hz 0.001 0,2
FreqDiffM Hz 0.001 0,2
PhaseDiffA Deg 1.0 30
PhaseDiffM Deg 1.0 30
tSCA s 0.001 0,1
tSCM s 0.001 0,1
AutoEnerg - - DBLL
ManEnerg - - Both
ManEnergDBDL - - Off
UHighBusEnerg %UB 1.0 80
UHighLineEnerg %UB 1.0 80
ULowBusEnerg %UB 1.0 40
ULowLineEnerg %UB 1.0 40
UMaxEnerg %UB 1.0 115
tAutoEnerg s 0.001 0,1
tManEnerg s 0.001 0,1

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
236-
285

VI.2 S/E Ciruelos paño Valdivia C2

VI.21 Protección 7SA612

Device configuration
No. Settings Ajuste
103 Setting group change Option Disabled
110 Trip Mode 1-/3 pole
114 21 Distance Protection Pickup program Z<(quadrilat.)
119 Additional Threshold Iph>(Z1) Disabled
120 68 Power swing detection Enabled
121 85-21 Pilot Protection for distance prot. PUTT (Z1B)
122 DTT Direct Transfer Trip Disabled
124 50HS Instantaneous SOTF Enabled
125 Weak Infeed (Trip and/or Echo) Disabled
126 50(N)/51(N) BackUp O/C Time Overcurrent Curve IEC
131 50N/51N Earth Fault O/C Time Overcurrent Curve IEC
132 85-67N Pilot Protection Earth O/C Directional Comparison Pickup
133 79 Auto-Reclose Function 1 AR-Cycle
134 Auto-Reclose control Mode With trip and Action Time
135 25 Synchro-Check Enabled
136 81 Over/Underfrequency Protection Disabled
137 27, 59 Under/Overvoltage Protection Disabled
138 Fault Locator Enabled
139 50BF Breaker Failure Protection Enabled w/3Io>
140 74TC Trip Circuit Supervision Disabled
142 49 Thermal Overload Disabled

Power System Data 1


Transformers
No. Settings Ajuste
201 Ct Starpoint Towards Line
203 Rated Primary Voltage 230
204 Rated Secondary Voltage (Ph-Ph) 115 V
205 CT rated Primary Current 800
206 CT Rated Secondary Current 5
210 V4 Voltage Transformer is Vsy2 transformer
211 Matching ratio phase-VT to open-Delta-VT 1,73
212 VT connection for Vsy2 L2-E
214A Angle adjustment Vsy2-Vsy1 0°
215 Matching ratio Vsy1/Vsy2 1

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
237-
285

220 I4 Current Transformers is Neutral Current (of the protected line)


221 Matching ratio I4/Iph for CT`s 1

Power System
No. Settings Ajuste
207 System Startpoint is Solid Grounded
230 Rated Frequency 50 Hz
235 Phase Sequence ABC
236 Distance measurement unit km
237 Setting format for zero seq.comp. forma Zero seq. comp. factor K0 and angle(K0)
238A 50N/51N Gnd O/C: setting for 1p. 79 AR all elements together

Breaker
No. Settings Ajuste
239 Closing (operating) time of 52 (CB) 0,06 Seg
240A Minimum TRIP Command Duration 0,1 Seg
241A Maximum Close Command Duration 0,1 Seg
242 Dead Time for CB test-autoreclosure 0,1 Seg

Power System Data 2


Load Line End
No. Settings Ajuste
1103 Measurem:FullScaleVoltage(Equipm.rating) 220 kV
1104 Measurem:FullScaleCurrent(Equipm.rating) 800
1105 Line Angle 71
1211 Angle of inclination, distance charact. 71
1107 P,Q operational measured values sign Not reversed
1110 x' - Line Reactance per length unit 0,0328
1111 Line Length 39,3
1120 Zero seq. comp. factor K0 for zone Z1 0,76
1121 Zero seq. comp. angle for zone Z1 10,6
1122 Zero seq.comp.factor K0,higher zones >Z1 0,76
1123 Zero seq. comp. angle, higher zones >Z1 10,6

Line Status
No. Settings Ajuste
1130A Pole Open Current Threshold 0,5 A
1131A Pole Open Voltage Threshold 30 V
1132A Seal-in Time after ALL closures 0,05 seg
1134 Recognition of Line Closures with I OR U or ManCl
1135 RESET of Trip Command Current Open Pole
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
238-
285

1136 open pole detector with Measurement


1140A CT Saturation Threshold 40 A
1150A Seal-in Time after MANUAL closures 0,3 Seg
1151 Manual CLOSE COMMAND generation With Sync-check
1152 MANUAL Closure impulse after CONTROL None

Trip 1-/3-pole
No. Settings Ajuste
1155 3 pole coupling with Trip
1156A Trip type with 2 phase faults 3 pole

21 Distance Protection
General
No. Settings Ajuste
1201 21 Distance protection is ON
1202 Phase Current threshold for dist. meas. 1,0 A
1211 Angle of inclination, distance charact 71
1208 Series compensated line No
1232 Instantaneous trip after SwitchOnToFault Zone Z1B
1241 R load, minimum Load Impedance (ph-g) 10,3 Ohm
1242 PHI load, maximum Load Angle (ph-g) 30
1243 R load, minimum Load Impedance (ph-ph) 10,3 Ohm
1244 PHI load, maximum Load Angle (ph-ph) 30
1317A Single pole trip for faults in Z2 No
1357 Z1B enabled before 1st AR (int. or ext.) No

Ground Faults
No. Settings Ajuste
1203 3I0 threshold for neutral current pickup 0,5 A
1204 3V0 threshold zero seq. voltage pickup 5V
1207A 3I0>-pickup-stabilisation (3I0>/ Iphmax) 0,1
1209A Criterion of ground fault recognition 3I0> OR 3V0>
1221A Loop selection with 2Ph-G faults All loops

Time Delay
No. Settings Ajuste
1210 21 Condition for zone timer start With Distance Pickup
1305 T1-1phase, delay for single phase faults 0,00 Seg
1306 T1multi-ph, delay for multi phase faults 0,00 Seg
1315 T2-1phase, delay for single phase faults 0,30 Seg
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
239-
285

1316 T2multi-ph, delay for multi phase faults 0,30 Seg


1325 T3 delay oo Seg
1335 T4 delay 1,20 Seg
1345 T5 delay oo Seg
1365 T6 delay oo seg
1355 T1B-1phase, delay for single ph. faults 0,00 Seg
1356 T1B-multi-ph, delay for multi ph. faults 0,00 Seg

Zone Z1
No. Settings Ajuste
1301 Operating mode Z1 Forward
1302 R(Z1), Resistance for ph-ph-faults 0,89 Ohm
1303 X(Z1), Reactance 0,89 Ohm
1304 RG(Z1), Resistance for ph-gnd faults 3,58 Ohm
1305 T1-1phase, delay for single phase faults 0,00 seg
1306 T1multi-ph, delay for multi phase faults 0,00 seg
1307 Zone Reduction Angle (load compensation) 0

Zone Z1b
No. Settings Ajuste
1351 Operating mode Z1B Forward
1352 R(Z1B), Resistance for ph-ph-faults 1,92 Ohm
1353 X(Z1B), Reactance 1,92 Ohm
1354 RG(Z1B), Resistance for ph-gnd faults 9,59 Ohm
1355 T1B-1phase, delay for single phase faults 0,00 seg
1356 T1B-multi-ph, delay for multi phase faults 0,00 seg
1357 Z1B enabled before 1st AR (int. or ext.) No

Zone Z2
No. Settings Ajuste
1311 Operating mode Z2 Forward
1312 R(Z2), Resistance for ph-ph-faults 1,92 Ohm
1313 X(Z2), Reactance 1,92 Ohm
1314 RG(Z2), Resistance for ph-gnd faults 9,59 Ohm
1315 T2-1phase, delay for single phase faults 0,3 seg
1316 T2multi-ph, delay for multi phase faults 0,3 seg
1317A Single pole trip for faults in Z2 NO

Zone Z3
No. Settings Ajuste
1321 Operating mode Z3 Reverse
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
240-
285

1322 R(Z3), Resistance for ph-ph-faults 2,32 Ohm


1323 X(Z3), Reactance 1,31 Ohm
1324 RG(Z3), Resistance for ph-gnd faults 10,85 Ohm
1325 T3 delay oo seg

Zone Z4
No. Settings Ajuste
1331 Operating mode Z4 Forward
1332 R(Z4), Resistance for ph-ph-faults 5,46 Ohm
1333 X(Z4), Reactance 5,46 Ohm
1334 RG(Z4), Resistance for ph-gnd faults 16,38 Ohm
1335 T4 delay 1,20 seg

Zone Z5
No. Settings Ajuste
1341 Operating mode Z5 Non Directional
1342 R(Z5), Resistance for ph-ph-faults 6,55 Ohm
1343 X(Z5), Reactance 6,55 Ohm
1344 RG(Z5), Resistance for ph-gnd faults 19,66 Ohm
1345 T5 delay oo seg
1346 X(Z5)-, Reactance for Reverse Direction 6,55 Ohm

Zone Z6
No. Settings Ajuste
1361 Operating mode Z6 Inactive
1362 R(Z6), Resistance for ph-ph-faults 15,00 Ohm
1363 X(Z6), Reactance 15,00 Ohm
1364 RG(Z6), Resistance for ph-gnd faults 15,00 Ohm
1365 T6 delay oo seg
1366 X(Z6)-, Reactance for Reverse Direction 4,00 Ohm

Power Swing Blocking


No. Settings Ajuste
2002 Power Swing Operation Mode. All Zones Block
2006 Power Swing Trip NO
2007 Trip After Power Swing Blocking 0,08 Seg

85-21 Pilot Prot. For Distance prot.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
241-
285

No. Settings Ajuste


2101 85-21 Pilot Prot. for Distance prot. ON
2102 Type of Line Two Terminal
2103A Time for send signal prolongation 0,08 Seg
2109A Transient Block: Duration external flt. 0,03 Seg
2110A Transient Block: Blk.T. after ext. flt. 0,15 Seg
2112A DIS transient block by EF NO
2113 Memorize receive signal NO

50HS Instantaneous SOTF


No. Settings Ajuste
2401 50HS Instantaneous SOTF-O/C is ON
2404 50HS SOTF-O/C PICKUP 12,5 A

50(N)/51(N) Backup OverCurrent; Group 50(N)-B1


General
No. Settings Ajuste
2601 Operating Mode ON:with VT loss
2680 Trip time Delay after SOFT 0,00 seg

50(N)-B1
No. Settings Ajuste
2610 50-B1 Pickup oo A
2611 50-B1 Delay oo Seg
2612 50N-B1 Pickup oo A
2613 50N-B1 Delay oo seg
2614 Instantaneous trip via Pilot Prot./BI NO
2615 Instantaneous trip after SwitchOnToFault NO

50(N)-B2
No. Settings Ajuste
2620 50-B2 Pickup oo A
2621 50-B2 Delay oo Seg
2622 50N-B2 Pickup oo A
2623 50N-B2 Delay oo Seg
2624 Instantaneous trip via Pilot Prot./BI NO
2625 Instantaneous trip after SwitchOnToFault NO

51(N)-B

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
242-
285

No. Settings Ajuste


2640 51-B Pickup 6,0 A
2642 51-B Time Dial for IEC characteristic 0,07
2646 51-B Additional Time Delay 0,00 seg
2650 51N-B Pickup 1,0 A-sec
2652 51N-B Time Dial for IEC characteristic 0,27 seg
2656 51N-B Additional Time Delay 0,0 seg
2660 IEC Curve Normal Inverse
2670 Instantaneous trip via Pilot Prot./BI NO
2671 Instantaneous trip after SwitchOnToFault NO

50(N)-STUB
No. Settings Ajuste
2630 50-STUB Pickup oo A
2631 50-STUB Delay oo seg
2632 50N-STUB Pickup oo A
2633 50N-STUB Delay oo seg
2634 Instantaneous trip via Pilot Prot./BI NO
2635 Instantaneous trip after SwitchOnToFault NO

Measurement Supervision
Balance/Summ
No. Settings Ajuste
2901 Measurement Supervision ON
2902A Voltage Threshold for Balance Monitoring 50 V
2903A Balance Factor for Voltage Monitor 0,75
2904A Current Threshold for Balance Monitoring 2,5 A
2905A Balance Factor for Current Monitor 0,5
2906A Summated Current Monitoring Threshold 0,5 A
2907A Summated Current Monitoring Factor 0,1
2908A T Balance factor for Voltage Monitor 5,00 seg
2909A T Current Balance Monitor 5,00 seg

Volt. Fail
No. Settings Ajuste
2910 Fuse Failure Monitor ON
2911A Minimun Voltage Threshold V> 22 V
2912A Maximum Current Threshold I< 2A
2913A Maximum Voltage Threshold V< 5V
2914A Differential Current Threshold 0,5 A
2915 Voltage Failure Supervision With current supervision

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
243-
285

2916A Delay Voltage Failure Supervision 3,00 seg

VT mcb
No. Settings Ajuste
2921 VT mcb operating time 0,00 mseg

Load Angle
No. Settings Ajuste
2941 Limit setting PhiA 200°
2942 Limit setting PhiB 340°
2943 Minimum value I1> 0,25 A
2944 Minimum value U1> 20 V

50N/51N Ground OverCurrent


General
No. Settings Ajuste
3101 50N/51N Ground Overcurrent ON
3102 Block 50N/51N for Distance protection every PICKUP
3174 Block 50N/51N for Pickup 21 in each zone
3103 Block 50N/51N for 1pole Dead time YES
3104A Stabilisation Slope with Iphase 10%
3105 3I0-Min threshold for Pilot Prot.schemes 2,50 A
3109 Single pole trip with ground flt.prot. NO
3170 2nd harmonic ratio for inrush restraint 15%
3171 Max.Current, overriding inrush restraint 7,5 A
3172 Instantaneous mode after SwitchOnToFault with Pickup and direction
3173 Trip time delay after SOTF 0,00 sec

50N-1
No. Settings Ajuste
3110 Operating mode Forward
3111 Pickup 13,15 A
3112 Time Delay 0,30 seg
3113 Instantaneous trip via Pilot Prot./BI YES
3114 Instantaneous trip after SwitchOnToFault NO
3115 Inrush Blocking NO

50N-2
No. Settings Ajuste
3120 Operating mode Inactive

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
244-
285

3121 Pickup oo A
3122 Time Delay oo seg
3123 Instantaneous trip via Pilot Prot./BI NO
3124 Instantaneous trip after SwitchOnToFault NO
3125 Inrush Blocking NO

50N-3
No. Settings Ajuste
3130 Operating mode Inactive
3131 Pickup oo A
3132 Time Delay oo seg
3133 Instantaneous trip via Pilot Prot./BI NO
3134 Instantaneous trip after SwitchOnToFault NO
3135 Inrush Blocking NO

50N-4 Def. Time


No. Settings Ajuste
3140 Operating mode Forward
3141 Pickup 1,00 A
3143 3I0p Time Dial 0,27
3147 Additional Time Delay 0,00 Seg
3148 Instantaneous trip via Pilot Prot./BI YES
3149 Instantaneous trip after SwitchOnToFault NO
3150 Inrush Blocking NO
3151 IEC Curve Normal Inverse

Direction
No. Settings Ajuste
3160 Polarization U0 + IY or U2
3162A ALPHA, lower angle for forward direction 338
3163A BETA, upper angle for forward direction 122
3164 Min. zero seq.voltage 3Vo for polarizing 0,5 V
3166 Min. neg. seq. polarizing voltage 3V2 0,5 V
3167 Min. neg. seq. polarizing current 3I2 0,25 A
3168 Compensation angle PHI comp. for Sr 255
3169 Forward direction power treshold 0,5 VA
3186A 3V0 min for forward direction 0,0 V
3187A Reactance X of series Capacitor 0,00 Ohm

85-67N Pilot Prot. For Ground Overcurrent


No. Settings Ajuste

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
245-
285

3201 85-67N Pilot Prot. for Dir.Ground O/C ON


3202 Line Configuration Two Terminal
3203A Time for send signal prolongation 0,08 Seg
3209A Transient Block.: Duration external flt. 0,03 Seg
3210A Transient Block.: Blk.T. after ext. flt. 0,15 Seg
3212A EF transient block by DIS NO

79 Auto Reclosing
General
No. Settings Ajuste
3401 79 Auto-Reclose Function ON
3402 52-ready interrogation at 1st trip NO
3403 Reclaim time after successful AR cycle 3,00 Seg
3404 AR blocking duration after manual close 1,00 Seg
3406 Evolving fault recognition with Trip
3407 Evolving fault (during the dead time) starts 3pole AR-cycle
3408 AR start-signal monitoring time 0,2 Seg
3409 Circuit Breaker (CB) Supervision Time 3,00 Seg
3410 Send delay for remote close command oo Seg
3411A Maximum dead time extension oo Seg

1st AR-Cycle
No. Settings Ajuste
3450 Start of AR allowed in this cycle Yes
3451 Action time 0,4 seg
3456 Dead time after 1pole trip 1,2 seg
3457 Dead time after 3pole trip 0,4 seg
3458 Dead time after evolving fault 1,2 seg
3459 52-ready interrogation before reclosing YES
3460 Request for synchro-check after 3pole AR YES

3pTrip
No. Settings Ajuste
3430 3pole TRIP by AR Yes
3431 Dead Line Check or Reduced Dead Time Without
3435 1pole Trip Allowed No
3438 Supervision time for dead/ live voltage 0,1 seg
3440 Voltage Threshold for live line or bus 48 V
3441 Voltage threshold for dead line or bus 30 V

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
246-
285

Star AR with
No. Settings Ajuste
3420 AR with 21 Yes
3423 AR with 50N/51N Yes
3424 AR with DTT No
3425 AR with 50(N)-B No

25 Synchronism and Voltage


General
No. Settings Ajuste
3501 25 Synchronism and Voltage Check ON
3502 Voltage threshold dead line / bus 13 V
3503 Voltage threshold live line / bus 47 V
3504 Maximum permissible voltage 70 V
3507 Maximum duration of synchronism-check 1,00 seg
3508 Synchronous condition stability timer 0,00 seg
3509 Synchronizable circuit breaker None

with AR
No. Settings Ajuste
3510 Operating mode with AR without consideration of 52 closing time
3511 Maximum voltage difference 6,4 V
3512 Maximum frequency difference 0,2 Hz
3513 Maximum angle difference 30
3515A 79 at Vsy2>, Vsy1>, and Synchr. Yes
3516 79 at Vsy1< and Vsy2> Yes
3517 79 at Vsy1> and Vsy2< Yes
3518 79 at Vsy1< and Vsy2< No
3519 Override of any check before 79 No

Manual Close
No. Settings Ajuste
3530 Operating mode with Man. Cl without consideration of 52 closing time
3531 Maximum voltage difference 6,4 V
3532 Maximum frequency difference 0,2 Hz
3533 Maximum angle difference 30
3535A Manual at Vsy2>, Vsy1>, and Synchr. Yes
3536 Manual at Vsy1< and Vsy2> Yes
3537 Manual at Vsy1> and Vsy2< Yes
3538 Manual at Vsy1< and Vsy2< Yes

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
247-
285

3539 Override of any check before Man. Cl No

Fault Locator
No. Settings Ajuste
3802 Start fault locator with Pickup
3806 Load Compensation No

Breaker Failure
No. Settings Ajuste
3901 FCT BreakerFail ON
3902 I> BF 5,65 A
3903 1p-RETRIP (T1) YES
3904 T1-1pole 0,01 sec
3905 T1-3pole 0,01 sec
3906 T2 0,2 sec
3907 T3-BkrDefective 0,00 sec
3908 Trip BkrDefect NO
3909 Chk BRK CONTACT YES
3912 3I0> BF 1,5 A
3913 T2StartCriteria Parallel withT1
3921 End Flt. stage OFF
3922 T-EndFault 2,00 sec
3931 PoleDiscrepancy OFF
3932 T-PoleDiscrep. 2,00 sec

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
248-
285

VI.2 Protección REL670

ZMQPDIS (21) Group settings Zona Z1


Name Unit Step Setting
Operation - - Enabled
IBase A 1 800
VBase kV 0,05 230
OperationDir - - Forward
X1 ohm/p 0,01 11,18
R1 ohm/p 0,01 3,87
X0 ohm/p 0,01 38,11
R0 ohm/p 0,01 7,86
RFPP ohm/l 0,01 22,36
RFPG ohm/l 0,01 44,73
OperationPP - - Enabled
Timer tPP - - Enabled
tPP s 0,001 0
OperationPG - - Enabled
Timer tPG - - Enabled
tPG s 0,001 0
IMinPUPP %IB 1 20
IMinPUPG %IB 1 20
IMinOpIR %IB 1 5
ZMQAPDIS (21) Group settings (basic) Zona 2
Name Unit Step Setting
Operation - - Enabled
IBase A 1 800
Vbase kV 0,05 230
OperationDir - - Forward
X1 ohm/p 0,01 23,97
R1 ohm/p 0,01 8,16
X0 ohm/p 0,01 81,7
R0 ohm/p 0,01 16,58
RFPP ohm/l 0,01 47,94
RFPG ohm/l 0,01 119,85
OperationPP - - Enabled
Timer tPP - - Enabled
tPP s 0,001 0,3
OperationPG - - Enabled
Timer tPG - - Enabled
tPG s 0,001 0,3

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
249-
285

IMinPUPP %IB 1 20
IMinPUPG %IB 1 20
ZMQAPDIS (21) Group settings (basic) Zona 3
Name Unit Step Setting
Operation - - Enabled
IBase A 1 800
Vbase kV 0,05 230
OperationDir - - Forward
X1 ohm/p 0,01 68,25
R1 ohm/p 0,01 19
X0 ohm/p 0,01 234,39
R0 ohm/p 0,01 43,38
RFPP ohm/l 0,01 136,51
RFPG ohm/l 0,01 204,76
OperationPP - - Enabled
Timer tPP - - Enabled
tPP s 0,001 1,2
OperationPG - - Enabled
Timer tPG - - Enabled
tPG s 0,001 1,2
IMinPUPP %IB 1 20
IMinPUPG %IB 1 20
ZMQAPDIS (21) Group settings (basic) Zona 4
Name Unit Step Setting
Operation - - Enabled
IBase A 1 800
Vbase kV 0,05 230
OperationDir - - Reverse
X1 ohm/p 0,01 16,37
R1 ohm/p 0,01 3,42
X0 ohm/p 0,01 13,09
R0 ohm/p 0,01 2,69
RFPP ohm/l 0,01 57,9
RFPG ohm/l 0,01 135,67
OperationPP - - Enabled
Timer tPP - - Enabled
tPP s 0,001 60
OperationPG - - Enabled
Timer tPG - - Enabled
tPG s 0,001 60
IMinPUPP %IB 1 20
IMinPUPG %IB 1 20
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
250-
285

ZDRDIR (21D) Group settings (basic)


Name Unit Step Setting
IBase A 1 800
VBase kV 0,05 230
IMinPUPP %IB 1 10
IMinPUPG 1 1 5
AngNegRes 1 1 115
AngDir 1 1 15
FDPSPDIS (21) Group settings (basic)
Name Unit Step Setting
IBase A 1 800
VBase kV 0,01 230
3I0BLK_PP %IPh 1 40
3I0Enable_PG %IPh 1 20
RLdFwd ohm/p 0,01 128,75
RldRev ohm/p 0,01 128,75
LdAngle Deg 1 30
X1 ohm/p 0,01 98,29
X0 ohm/p 0,01 337,52
RFltFwdPP ohm/l 0,01 163,81
RFltRevPP ohm/l 0,01 69,35
RFltFwdPG ohm/l 0,01 245,71
RFltRevPG ohm/l 0,01 162,81
IMinPUPP %IB 1 10
IMinPUPG %IB 1 5
OperationZ< - - Enabled
OperationI> - - Disabled
IPh> %IB 1 120
Pickup_N %IB 1 20
TimerPP - - Disabled
tPP s 0,001 3
TimerPE - - Disabled
tPG s 0,001 3
Instantaneous phase overcurrent protection PHPIOC (50)
Name Unit Step Setting
Operation - - Disabled
IBase A 1 800
OpModeSel - - 1 out of 3
Pickup %IB 1 200
MultPU - 0,1 1.0
Instantaneous residual overcurrent protection EFPIOC (50N)

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
251-
285

Name Unit Step Setting


Operation - - Disabled
IBase A 1 800
Pickup %IB 1 200
MultPU - 0,1 1.0
OC4PTOC (51_67) Group settings
Name Unit Step Setting
Operation - - Disabled
IBase A 1 800
Vbase kV 0,05 230
AngleRCA Deg 1 65
AngleROA Deg 1 80
NumPhSel - - 1 out of 3
DirModeSel1 - - Non Directional
Characterist1 - - IEC Norm. Inverse
Pickup1 %IB 1 120
t1 s 0,001 0
TD1 - 0,01 0,07
IMin1 %IB 1 20
t1Min s 0,001 0
MultPU1 - 0,1 1
DirModeSel2 - - Disabled
Characterist2 - - ANSI Def. Time
Pickup2 %IB 1 500
t2 s 0,001 0,4
TD2 - 0,01 0,05
IMin2 %IB 1 50
t2Min s 0,001 0
MultPU2 - 0,1 2
DirModeSel3 - - Disabled
Characterist3 - - ANSI Def. Time
Pickup3 %IB 1 250
t3 s 0,001 0,8
TD3 - 0,01 0,05
IMin3 %IB 1 33
t3Min s 0,001 0
MultPU3 - 0,1 2
DirModeSel4 - - Disabled
Characterist4 - - ANSI Def. Time
Pickup4 %IB 1 175
t4 s 0,001 2
TD4 - 0,01 0,05

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
252-
285

IMin4 %IB 1 17
t4Min s 0,001 0
MultPU4 - 0,1 2
PUMinOpPhSel %IB 1 7
2ndHarmStab %IB 1 20
ResetTypeCrv1 - - Instantaneous
tReset1 s 0,001 0,02
tPCrv1 - 0,001 1
tACrv1 - 0,001 13,5
tBCrv1 - 0,01 0
tCCrv1 - 0,1 1
tPRCrv1 - 0,001 0,5
tTRCrv1 - 0,001 13,5
tCRCrv1 - 0,1 1
HarmRestrain1 - - Disabled
ResetTypeCrv2 - - Instantaneous
tReset2 s 0,001 0,02
tPCrv2 - 0,001 1
tACrv2 - 0,001 13,5
tBCrv2 - 0,01 0
tCCrv2 - 0,1 1
tPRCrv2 - 0,001 0,5
tTRCrv2 - 0,001 13,5
tCRCrv2 - 0,1 1
HarmRestrain2 - - Disabled
ResetTypeCrv3 - - Instantaneous
tReset3 s 0,001 0,02
tPCrv3 - 0,001 1
tACrv3 - 0,001 13,5
tBCrv3 - 0,01 0
tCCrv3 - 0,1 1
tPRCrv3 - 0,001 0,5
tTRCrv3 - 0,001 13,5
tCRCrv3 - 0,1 1
HarmRestrain3 - - Disabled
ResetTypeCrv4 - - Instantaneous
tReset4 s 0,001 0,02
tPCrv4 - 0,001 1
tACrv4 - 0,001 13,5
tBCrv4 - 0,01 0
tCCrv4 - 0,1 1
tPRCrv4 - 0,001 0,5

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
253-
285

tTRCrv4 - 0,001 13,5


tCRCrv4 - 0,1 1
HarmRestrain4 - - Disabled
EF4PTOC (51N67N) Group settings
Name Unit Step Setting
Operation - - ON
IBase A 1 800
VBase kV 0,05 230
AngleRCA Deg 1 65
polMethod - - Voltage
VPolMin %VB 1 1
IPolMin %IB 1 5
RNPol ohm 0,01 5
XNPol ohm 0,01 40
INDirPU %IB 1 10
2ndHarmStab % 1 20
BlkParTransf - - Disabled
Use_PUValue - - ST4
SOTF - - Disabled
SOTFSel - - Open
StepForSOTF - - Step 2
EnHarmRestSOTF - - Disabled
tSOTF s 0,001 0,2
t4U s 0,001 1
ActUndrTimeSel - - CB position
tUnderTime s 0,001 0,3
DirModeSel1 - - Forward
Characterist1 - - IEC Def. Time
Pickup1 %IB 1 263
t1 s 0,001 0,3
TD1 - 0,01 0
IMin1 %IB 1 15
t1Min s 0,001 0
MultPU1 - 0,1 1
ResetTypeCrv1 - - Instantaneous
tReset1 s 0,001 0,02
HarmRestrain1 - - Enabled
tPCrv1 - 0,001 1
tACrv1 - 0,001 13,5
tBCrv1 - 0,01 0
tCCrv1 - 0,1 1
tPRCrv1 - 0,001 0,5

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
254-
285

tTRCrv1 - 0,001 13,5


tCRCrv1 - 0,1 1
DirModeSel2 - - Forward
Characterist2 - - IEC Normal Inverse
Pickup2 %IB 1 20
t2 s 0,001 0
TD2 - 0,01 0,27
IMin2 %IB 1 15
t2Min s 0,001 0,2
MultPU2 - 0,1 2
ResetTypeCrv2 - - Instantaneous
tReset2 s 0,001 0,02
HarmRestrain2 - - Off
tPCrv2 - 0,001 1
tACrv2 - 0,001 13,5
tBCrv2 - 0,01 0
tCCrv2 - 0,1 1
tPRCrv2 - 0,001 0,5
tTRCrv2 - 0,001 13,5
tCRCrv2 - 0,1 1
DirModeSel3 - - Non Directional
Characterist3 - - IEC Normal Inverse
Pickup3 %IB 1 20
t3 s 0,001 0
TD3 - 0,01 0,27
IMin3 %IB 1 15
t3Min s 0,001 0
MultPU3 - 0,1 2
ResetTypeCrv3 - - Instantaneous
tReset3 s 0,001 0,02
HarmRestrain3 - - Disabled
tPCrv3 - 0,001 1
tACrv3 - 0,001 13,5
tBCrv3 - 0,01 0
tCCrv3 - 0,1 1
tPRCrv3 - 0,001 0,5
tTRCrv3 - 0,001 13,5
tCRCrv3 - 0,1 1
DirModeSel4 - - Disabled
Characterist4 - - ANSI Def. Time
Pickup4 %IB 1 17
t4 s 0,001 1,2

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
255-
285

TD4 - 0,01 0,05


IMin4 %IB 1 17
t4Min s 0,001 0
MultPU4 - 0,1 2
ResetTypeCrv4 - - Instantaneous
tReset4 s 0,001 0,02
HarmRestrain4 - - Disabled
tPCrv4 - 0,001 1
tACrv4 - 0,001 13,5
tBCrv4 - 0,01 0
tCCrv4 - 0,1 1
tPRCrv4 - 0,001 0,5
tTRCrv4 - 0,001 13,5
tCRCrv4 - 0,1 1
AutomaticSOFT(PSOF), ZCVPSOF
Name Unit Step Setting
Operation - - Enabled
IBase A 1 800
VBase kV 0,05 230
Mode - - VILvl&Imp
AutoInit - - Disabled
IphPickup %IB 1 100
UVPickup %VB 1 70
tDuration s 0,001 0,04
tSOTF s 0,001 1
tDLD s 0,001 0,2
Power Swing Detection (RPSB,68), ZMRPSB
Name Unit Step Setting
Operation - - Enabled
X1InFw ohm 0,01 78,49
R1LIn ohm 0,01 21,85
R1FInFw ohm 0,01 78,49
X1InRv ohm 0,01 78,49
R1FInRv ohm 0,01 78,49
OperationLdCh - - Enabled
RLdOutFw ohm 0,01 209,31
LdAngle Deg 1 30
RLdOutRv ohm 0,01 209,31
kLdRFw Mult 0,01 0,75
kLdRRv Mult 0,01 0,75
tGF s 0,001 15
IMinPUPG %IB 1 10
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
256-
285

IBase A 1 800
tP1 s 0,001 0,05
tP2 s 0,001 0,02
tW s 0,001 0,2
tH s 0,001 0,5
tR1 s 0,001 0,3
tR2 s 0,001 2
Undervoltage protection UV2PTUV (27)
Name Unit Step Setting
Operation - - Disabled
VBase kV 0,05 230
OperationStep1 - - Disabled
Characterist1 - - Definite time
OpMode1 - - 1 out of 3
Pickup1 %VB 1 70
t1 s 0,01 3
t1Min s 0,001 3
TD1 - 0,01 0,05
IntBlkSel1 - - Disabled
IntBlkStVal1 %VB 1 20
tBlkUV1 s 0,001 0
HystAbs1 %VB 0,1 0,5
OperationStep2 - - Disabled
Characterist2 - - Definite time
OpMode2 - - 1 out of 3
Pickup2 %VB 1 50
t2 s 0,001 5
t2Min s 0,001 5
TD2 - 0,01 0,05
IntBlkSel2 - - Disabled
IntBlkStVal2 %VB 1 20
tBlkUV2 s 0,001 0
HystAbs2 %VB 0,1 0,5
tReset1 s 0,001 0,025
ResetTypeCrv1 - - Disabled
tIReset1 s 0,001 0,025
ACrv1 - 0,001 1
BCrv1 - 0,01 1
CCrv1 - 0,1 0
DCrv1 - 0,001 0
PCrv1 - 0,001 1
CrvSat1 % 1 0

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
257-
285

tReset2 s 0,001 0,025


ResetTypeCrv2 - - Disabled
tIReset2 s 0,001 0,025
ACrv2 - 0,001 1
BCrv2 - 0,01 1
CCrv2 - 0,1 0
DCrv2 - 0,001 0
PCrv2 - 0,001 1
CrvSat2 % 1 0
Overvoltage protection OV2PTOV (59)
Name Unit Step Setting
Operation - - Disabled
VBase kV 0,05 230
OperationStep1 - - Disabled
Characterist1 - - Definite time
OpMode1 - - 1 out of 3
Pickup1 %VB 1 110
t1 s 0,01 3
t1Min s 0,001 5
TD1 - 0,01 0,05
HystAbs1 %VB 0,1 0,5
OperationStep2 - - Disabled
Characterist2 - - Definite time
OpMode2 - - 1 out of 3
Pickup2 %VB 1 120
t2 s 0,001 0,5
t2Min s 0,001 5
TD2 - 0,01 0,05
HystAbs2 %VB 0,1 0,5
tReset1 s 0,001 0,025
ResetTypeCrv1 - - Instantaneous
tIReset1 s 0,001 0,025
ACrv1 - 0,001 1
BCrv1 - 0,01 1
CCrv1 - 0,1 0
DCrv1 - 0,001 0
PCrv1 - 0,001 1
CrvSat1 % 1 0
tReset2 s 0,001 0,025
ResetTypeCrv2 - - Instantaneous
tIReset2 s 0,001 0,025
ACrv2 - 0,001 1

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
258-
285

BCrv2 - 0,01 1
CCrv2 - 0,1 0
DCrv2 - 0,001 0
PCrv2 - 0,001 1
CrvSat2 % 1 0
Fuse failure supervision SDDRFUF
Name Unit Step Setting
Operation - - Enabled
IBase A 1 800
VBase kV 0,05 230
OpModeSel - - V0I0 OR V2I2
3V0PU %VB 1 60
3I0PU %IB 1 20
3V2PU %VB 1 60
3I2PU %IB 1 20
OpDVDI - - Enabled
DVPU %VB 1 70
DIPU %IB 1 15
VPPU %VB 1 70
IPPU %IB 1 10
SealIn - - Enabled
VSealInPU %VB 1 70
IDLDPU %IB 1 20
VDLDPU %VB 1 70
Autorecloser SMBRREC (79)
Name Unit Step Setting
Operation - - Enabled
ARMode - - 3 phase
t1 1Ph s 0,001 0,4
t1 3Ph s 0,001 0,4
t1 3PhHS s 0,001 0,4
tReset s 0,01 15
tSync s 0,01 1
tTrip s 0,001 0,2
tPulse s 0,001 0,2
tCBClosedMin s 0,01 5
tUnsucCl s 0,01 30
Priority - - None
tWaitForMaster s 0,01 60
NoOfShots - - 1
StartByCBOpen - - Off
CBAuxContType - - NormOpen
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
259-
285

CBReadyType - - CO
t1 2Ph s 0,001 1
t2 3Ph s 0,01 30
t3 3Ph s 0,01 30
t4 3Ph s 0,01 30
t5 3Ph s 0,01 30
Extended t1 - - Disabled
tExtended t1 s 0,001 0,5
tInhibit s 0,001 5
CutPulse - - Disabled
Follow CB - - Disabled
AutoCont - - Disabled
tAutoContWait s 0,001 2
UnsucClByCBChk - - NoCBCheck
BlockByUnsucCl - - Disabled
ZoneSeqCoord - - Disabled
Breaker failure protection CCRBRF (50BF)
Name Unit Step Setting
Operation - - Enabled
IBase A 1 800
FunctionMode - - Current & Contact
BuTripMode - - 1 out of 4
RetripMode - - No CBPos Check
Pickup_PH %IB 1 113
Pickup_N %IB 1 30
t1 s 0,001 0,01
t2 s 0,001 0,2
t2MPh s 0,001 0,2
tPulse s 0,001 0,2
Pickup_BlkCont %IB 1 20
t3 s 0,001 0,03
tCBAlarm s 0,001 5
Scheme communication logic for distance or
overcurrent protection ZCPSCH (85)
Name Unit Step Setting
Operation - - Enabled
SchemeType - - Permissive UR
tCoord s 0,001 0
tSecurity s 0,001 0,1
Unblock - - Disabled
tSecurity s 0,001 0,035
Current reversal and WEI logic for distance protection 3-
STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO
REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
260-
285

phase ZCRWPSCH
Name Unit Step Setting
CurrRev - - Enabled
tPickUpRev s 0,001 0,15
tDelayRev s 0,001 0,03
WEI - - Off
tPickUpWEI s 0,001 0,01
UBase kV 0,05 230
UPP< %UB 1 70
UPN< %UB 1 35
Scheme communication logic for residual overcurrent
protection ECPSCH (85)
Name Unit Step Setting
Operation - - Enabled
SchemeType - - Permissive UR
tCoord s 0,001 0
tSecurity s 0,001 0,1
Unblock - - Disabled
tSecurity s 0,001 0,035
Current reversal and WEI logic for residual overcurrent
protection ECRWPSCH
Name Unit Step Setting
CurrRev - - Enabled
tPickUpRev s 0,001 0,15
tDelayRev s 0,001 0,03
WEI - - Off
tPickUpWEI s 0,001 0,01
UBase kV 0,05 230
3VOPU %UB 1 25
Synchronizing, synchrocheck and energizing check (RSYN,
25)
SESRSYN_25 (SYN1-) function
Name Unit Step Setting
Operation - - Enabled
SelPhaseBus1 - - phase2
SelPhaseBus2 - - Phase2
SelPhaseLine1 - - Phase2
SelPhaseLine2 - - Phase2
CBConfig .- - No voltage sel
UBase kV 0.001 230
PhaseShift Deg 5 0

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
261-
285

URatio - 0.001 1
OperationSynch - - On
UHighBus Synch % 1.0 80
UHighLineSynch % 1.0 80
UDiffSynch % 1.0 10
FreqDiffMin Hz 0.001 0,01
FreqDiffMax Hz 0.001 0,2
FreqRateChange Hz/s 0.001 0,3
tBreaker s 0.001 0,08
tClosePulse s 0.001 0,2
tMaxSynch s 0.01 600
tMinSynch s 0.001 2
OperationSC - - On
UHighBusSC %UB 1.0 80
UHighLineSC %UB 1.0 80
UDiffSC %UB 1.0 15
FreqDiffA Hz 0.001 0,2
FreqDiffM Hz 0.001 0,2
PhaseDiffA Deg 1.0 30
PhaseDiffM Deg 1.0 30
tSCA s 0.001 0,1
tSCM s 0.001 0,1
AutoEnerg - - DBLL
ManEnerg - - Both
ManEnergDBDL - - Off
UHighBusEnerg %UB 1.0 80
UHighLineEnerg %UB 1.0 80
ULowBusEnerg %UB 1.0 40
ULowLineEnerg %UB 1.0 40
UMaxEnerg %UB 1.0 115
tAutoEnerg s 0.001 0,1
tManEnerg s 0.001 0,1

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
262-
285

VI.3 S/E Ciruelos

VI.31 Protección 7SJ80, paño seccionador

General, Functional Scope


No. Settings Ajuste
103 Grp Chge OPTION Disabled
104 OSC. FAULT REC. Disabled
112 Charac. Phase Disabled
113 Charac. Ground Disabled
115 67/67-TOC Disabled
116 67N/67N-TOC Disabled
117 Coldload Pickup Disabled
122 InrushRestraint Disabled
127 50 1Ph Disabled
130 S.Gnd.F.Dir.Ch cos φ / sin φ
131 Sens. Gnd Fault Disabled
133 INTERM.EF Disabled
134 Dir. Interm. EF Disabled
135 E Flt(ext) Disabled
140 46 Disabled
142 49 Disabled
150 27/59 Disabled
154 81 O/U Disabled
155 27/Q-Protection Disabled
161 25 Function 1 Disabled
170 50BF Enabled
171 79 Auto Recl. Disabled
172 52 B.WEAR MONIT Disabled
180 Fault Locator Disabled
181 L-sections FL 1 Section
182 74 Trip Ct Supv Disabled
617 ServiProt (CM) Disabled
General, Power System Data
No. Settings Ajuste
201 CT Starpoint towards Line
202 Vnom PRIMARY 230 kV
203 Vnom SECONDARY 115 V
204 CT PRIMARY 1500 A
205 CT SECONDARY 5A
206A Vph / Vdelta 1,73

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
263-
285

209 PHASE SEQ. ABC


210A TMin TRIP CMD 0,15 sec
211A TMax CLOSE CMD 1,00 sec
213 VT Connect. 3ph Van, Vbn, Vcn
214 Rated Frequency 50 Hz
215 Distance Unit km
217 Ignd-CT PRIM 1500 A
218 Ignd-CT SEC 5,00 A
220 Threshold BI 1 Thresh. BI 176V
221 Threshold BI 2 Thresh. BI 176V
222 Threshold BI 3 Thresh. BI 176V
223 Threshold BI 4 Thresh. BI 176V
224 Threshold BI 5 Thresh. BI 176V
225 Threshold BI 6 Thresh. BI 176V
226 Threshold BI 7 Thresh. BI 176V
227 Threshold BI 8 Thresh. BI 176V
228 Threshold BI 9 Thresh. BI 176V
229 Threshold BI 10 Thresh. BI 176V
230 Threshold BI 11 Thresh. BI 176V
232 VXnom PRIMARY 220.00 kV
233 VXnom SECONDARY 110 V
235A ATEX100 NO
238 Ignd2-CT PRIM. 1500 A
239 Ignd2-CT SEC. 5,00 A
250A 50/51 2-ph prot OFF
251A CT Connect. A, B, C, (Gnd)
252 Ph LPCT pol. not reversed
260 Ir-52 3150 A
261 OP.CYCLES AT Ir 10000
262 Isc-52 50000 A
263 OP.CYCLES Isc 50
264 Ix EXPONENT 2
265 Cmd.via control none
266 T 52 BREAKTIME 80 ms
267 T 52 OPENING 65 ms
280 Holmgr. for Σi NO
310 Iph-PRIM ref. 1500 A
311 Iph-LPCT PRIM 1500 A
312 Ignd-PRIM ref. 1500 A
313 Ignd-LPCT PRIM 1500 A
314 Vph-LPCT SEC 225,0 mV
315 Vgnd-LPCT SEC 225,0 mV

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
264-
285

320A Corr.factor IL1 10000


321A Corr.factor IL2 10000
322A Corr.factor IL3 10000
323A Corr.factor IE 10000
324A Corr.factor IEE 10000
330 V-LPVT SEC 3,25 V
332A V-LPVT PHA 0,00 °
613A Gnd O/Cprot. w. 3I0
614A OP. QUANTITY 59 Vphph
615A OP. QUANTITY 27 V1
616 STATIC GEN. NO
Power System Data 2
No. Settings Ajuste
1101 FullScaleVolt. 220.00 kV
1102 FullScaleCurr. 1500 A
1103 RE/RL 1,00
1104 XE/XL 1,00
1106 x' 0,0300 Ω/km
1108 P,Q sign not reversed P,Q
1109 Line angle 85 °
1110 Line length 100,0 km
6001 S1: RE/RL 1,00
6002 S1: XE/XL 1,00
6004 S1: x' 0,0300 Ω/km
6005 S1: Line angle 85 °
6007 S1: Line length 100,0 km
6011 S2: RE/RL 1,00
6012 S2: XE/XL 1,00
6014 S2: x' 0,0300 Ω/km
6015 S2: Line angle 85 °
6017 S2: Line length 100,0 km
6021 S3: RE/RL 1,00
6022 S3: XE/XL 1,00
6024 S3: x' 0,0300 Ω/km
6025 S3: Line angle 85 °
6027 S3: Line length 100,0 km
Breaker Failure Protection 50BF
No. Settings Ajuste
7001 50BF Breaker Failure Protection ON
7004 Chk BRK CONTACT OFF
7005 TRIP-Timer 0,20 sec

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
265-
285

7006 50BF PICKUP 4,77 A


7007 50BF PICKUP IE> 1,5 A

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
266-
285

VI.32 Protección 7SJ80, paño Acoplador

General, Functional Scope


No. Settings Ajuste
103 Grp Chge OPTION Disabled
104 OSC. FAULT REC. Disabled
112 Charac. Phase Disabled
113 Charac. Ground Disabled
115 67/67-TOC Disabled
116 67N/67N-TOC Disabled
117 Coldload Pickup Disabled
122 InrushRestraint Disabled
127 50 1Ph Disabled
130 S.Gnd.F.Dir.Ch cos φ / sin φ
131 Sens. Gnd Fault Disabled
133 INTERM.EF Disabled
134 Dir. Interm. EF Disabled
135 E Flt(ext) Disabled
140 46 Disabled
142 49 Disabled
150 27/59 Disabled
154 81 O/U Disabled
155 27/Q-Protection Disabled
161 25 Function 1 Disabled
170 50BF Enabled
171 79 Auto Recl. Disabled
172 52 B.WEAR MONIT Disabled
180 Fault Locator Disabled
181 L-sections FL 1 Section
182 74 Trip Ct Supv Disabled
617 ServiProt (CM) Disabled
General, Power System Data
No. Settings Ajuste
201 CT Starpoint towards Line
202 Vnom PRIMARY 230 kV
203 Vnom SECONDARY 115 V
204 CT PRIMARY 800 A
205 CT SECONDARY 5A
206A Vph / Vdelta 1,73
209 PHASE SEQ. ABC
210A TMin TRIP CMD 0,15 sec

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
267-
285

211A TMax CLOSE CMD 1,00 sec


213 VT Connect. 3ph Van, Vbn, Vcn
214 Rated Frequency 50 Hz
215 Distance Unit km
217 Ignd-CT PRIM 800 A
218 Ignd-CT SEC 5,00 A
220 Threshold BI 1 Thresh. BI 176V
221 Threshold BI 2 Thresh. BI 176V
222 Threshold BI 3 Thresh. BI 176V
223 Threshold BI 4 Thresh. BI 176V
224 Threshold BI 5 Thresh. BI 176V
225 Threshold BI 6 Thresh. BI 176V
226 Threshold BI 7 Thresh. BI 176V
227 Threshold BI 8 Thresh. BI 176V
228 Threshold BI 9 Thresh. BI 176V
229 Threshold BI 10 Thresh. BI 176V
230 Threshold BI 11 Thresh. BI 176V
232 VXnom PRIMARY 220.00 kV
233 VXnom SECONDARY 110 V
235A ATEX100 NO
238 Ignd2-CT PRIM. 800 A
239 Ignd2-CT SEC. 5,00 A
250A 50/51 2-ph prot OFF
251A CT Connect. A, B, C, (Gnd)
252 Ph LPCT pol. not reversed
260 Ir-52 3150 A
261 OP.CYCLES AT Ir 10000
262 Isc-52 50000 A
263 OP.CYCLES Isc 50
264 Ix EXPONENT 2
265 Cmd.via control none
266 T 52 BREAKTIME 80 ms
267 T 52 OPENING 65 ms
280 Holmgr. for Σi NO
310 Iph-PRIM ref. 800 A
311 Iph-LPCT PRIM 800 A
312 Ignd-PRIM ref. 800 A
313 Ignd-LPCT PRIM 800 A
314 Vph-LPCT SEC 225,0 mV
315 Vgnd-LPCT SEC 225,0 mV
320A Corr.factor IL1 10000
321A Corr.factor IL2 10000

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
268-
285

322A Corr.factor IL3 10000


323A Corr.factor IE 10000
324A Corr.factor IEE 10000
330 V-LPVT SEC 3,25 V
332A V-LPVT PHA 0,00 °
613A Gnd O/Cprot. w. 3I0
614A OP. QUANTITY 59 Vphph
615A OP. QUANTITY 27 V1
616 STATIC GEN. NO
Power System Data 2
No. Settings Ajuste
1101 FullScaleVolt. 220.00 kV
1102 FullScaleCurr. 800 A
1103 RE/RL 1,00
1104 XE/XL 1,00
1106 x' 0,0300 Ω/km
1108 P,Q sign not reversed P,Q
1109 Line angle 85 °
1110 Line length 100,0 km
6001 S1: RE/RL 1,00
6002 S1: XE/XL 1,00
6004 S1: x' 0,0300 Ω/km
6005 S1: Line angle 85 °
6007 S1: Line length 100,0 km
6011 S2: RE/RL 1,00
6012 S2: XE/XL 1,00
6014 S2: x' 0,0300 Ω/km
6015 S2: Line angle 85 °
6017 S2: Line length 100,0 km
6021 S3: RE/RL 1,00
6022 S3: XE/XL 1,00
6024 S3: x' 0,0300 Ω/km
6025 S3: Line angle 85 °
6027 S3: Line length 100,0 km
Breaker Failure Protection 50BF
No. Settings Ajuste
7001 50BF Breaker Failure Protection ON
7004 Chk BRK CONTACT ON
7005 TRIP-Timer 0,20 sec
7006 50BF PICKUP 2,85 A
7007 50BF PICKUP IE> 1,5 A

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
269-
285

ANEXO VII. BARRIDOS DE CORTOCIRCUITO Y TABLAS DE COORDINACIÓN


INSTALACIONES MT

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
270-
285

VI.4 Barridos de cortocircuito

VI.41 Barridos desde S/E Mulchén hacia S/E Rahue

En las Figuras VII.4.1 y VII.4.2, es posible apreciar la coordinación de las protecciones, para fallas trifásicas y
monofásicas respectivamente, a lo largo del conjunto de circuitos números 1 estudiados.

DIgSILENT
1,00

[-]

0,80

0,60

0,40

0,20

0,00
0,0000 79,134 158,27 237,40 316,53 [km] 395,67
Reference: Mulch\R2\Mul-Cau D60 C2

Est.366 C1
Est.14 C1 Ciruelos B1
Reactor de L.. Est.169 C1 Est.356 C1 Valdivia J1
Mulchen J2 Cautin J2 Tap Rio Tolt.. Est.327 C1 Est.473 C1

x-Axis: Length Cautin\Cub_0.3\Cau-Cir D60 C1 Cautin\Cub_0.3\Cau-Tol-Cir D60 C1 Ciruelos 220kV\R2\Cir-Val D60 C1


Mulch\R2\Mul-Cau D60 C2 Val\52J6\Val-Rah 7SA612

Figura VII.4.1: Barrido de cortocircuito, fallas trifásicas


CDEC-SIC
entre S/E Mulchén y S/E Rahue (Circuitos 1). T_D Date: 1/9/2017
Annex: /5

Ajustes nuevos.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
271-
285

DIgSILENT
1,00

[-]

0,80

0,60

0,40

0,20

0,00
0,0000 79,134 158,27 237,40 316,53 [km] 395,67
Reference: Mulch\R2\Mul-Cau D60 C2 Res

Est.366 C1
Est.14 C1 Ciruelos B1
Reactor de L.. Est.169 C1 Est.356 C1 Valdivia J1
Mulchen J2 Cautin J2 Tap Rio Tolt.. Est.327 C1 Est.473 C1

x-Axis: Length Cautin\Cub_0.3\Cau-Cir D60 Res Cautin\Cub_0.3\Cau-Tol-Cir D60 Res Ciruelos 220kV\R2\Cir-Val D60 C1 Res
Mulch\R2\Mul-Cau D60 C2 Res Val\52J6\Val-Rah 7SA612

CDEC-SIC T_D Date: 1/9/2017


Figura VII.4.2: Barrido de cortocircuito, fallas monofásicas entre S/E Mulchén y S/E Rahue (Circuitos 1). Annex: /5

Ajustes nuevos.

Análogamente, en las Figuras VII.4.3 y VII.4.4, es posible apreciar la coordinación de las protecciones, para
fallas trifásicas y monofásicas respectivamente, a lo largo del conjunto de circuitos números 2 estudiados.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
272-
285

DIgSILENT
1,00

[-]

0,80

0,60

0,40

0,20

0,00
0,0000 79,134 158,27 237,40 316,53 [km] 395,67
Reference: Mulch\L2\Mul-Cau D60 C1

Est.366 C2
Est.14 C2 Ciruelos B2
Reactor de L.. Est.169 C2 Est.356 C2 Vadivia J2 Rahue J2
Mulchen J1 Cautin J1 Tap Rio Tolt.. Est.327 C2 Est.473 C2 Tap Pichirra..

x-Axis: Length Cautin\Cub_0.2\Cau-Cir D60 C2 Ciruelos 220kV\L3\Cir-Val REL670 C2 Mulch\L2\Mul-Cau D60 C1


Val\52J3\Val-Pto D60

CDEC-SIC T_D Date: 1/9/2017


Figura VII.4.3: Barrido de cortocircuito, fallas trifásicas entre S/E Mulchén y S/E Rahue (Circuitos 2). Annex: /5

Ajustes nuevos.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
273-
285

DIgSILENT
1,00

[-]

0,80

0,60

0,40

0,20

0,00
0,0000 79,134 158,27 237,40 316,53 [km] 395,67
Reference: Mulch\L2\Mul-Cau D60 C1

Est.366 C2
Est.14 C2 Ciruelos B2
Reactor de L.. Est.169 C2 Est.356 C2 Vadivia J2 Rahue J2
Mulchen J1 Cautin J1 Tap Rio Tolt.. Est.327 C2 Est.473 C2 Tap Pichirra..

x-Axis: Length Cautin\Cub_0.2\Cau-Cir D60 C2 Res Ciruelos 220kV\L3\Cir-Val REL670 C2 Mulch\L2\Mul-Cau D60 C1 Res
Val\52J3\Val-Pto D60 Res

CDEC-SIC T_D Date: 1/9/2017


Figura VII.4.4: Barrido de cortocircuito, fallas monofásicas entre S/E Mulchén y S/E Rahue (Circuitos 2). Annex: /5

Ajustes nuevos.

Cabe destacar que para unificar los criterios de las líneas 2x220kV Ciruelos – Valdivia, ya que se modificarán
los tiempos de zona 2 en los extremos Ciruelos, se proponen cambios para los tiempos de zona 2 de los
extremos Valdivia. Lo anterior, no afecta la coordinación ya que se disminuyen los tiempos de despeje para
dicha zona de operación (en Anexo se muestran los barridos de cortocircuito entre S/E Rahue y S/E Mulchén
con los cambios de tiempo de Zona 2 en los paños de S/E Valdivia).

VI.42 Barridos desde S/E Rahue hacia S/E Mulchén

En las Figuras VII.4.5 y VII.4.6, es posible apreciar la coordinación de las protecciones, para fallas trifásicas y
monofásicas respectivamente, a lo largo del conjunto de circuitos números 1 estudiados.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
274-
285

DIgSILENT
1,00

[-]

0,80

0,60

0,40

0,20

0,00
0,0000 79,150 158,30 237,45 316,60 [km] 395,75

Est.327 C1
Est.356 C1 Cautin J2
Est.473 C1 Ciruelos B1 Tap Rio Tolt.. Reactor de L..
Rahue J2 Valdivia J1 Est.366 C1 Est.169 C1 Est.14 C1 Mulchen J2

x-Axis: Length Cautin\Cub_0.5\Cau-Mul D60 C2 Ciruelos 220kV\R1\Cir-Cau D60 C1 Ciruelos 220kV\R1\Cir-Tol-Cau D60 C1
Rahu\1\Rah-Val D60 Val\52J5\Val-Cir 7SA612 C1

CDEC-SIC T_D Date: 1/13/2017


Annex: /5

Figura VII.4.5: Barrido de cortocircuito, fallas trifásicas entre S/E Rahue y S/E Mulchén (Circuitos 1).
Ajustes nuevos.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
275-
285

DIgSILENT
1,00

[-]

0,80

0,60

0,40

0,20

0,00
0,0000 79,150 158,30 237,45 316,60 [km] 395,75

Est.327 C1
Est.356 C1 Cautin J2
Est.473 C1 Ciruelos B1 Tap Rio Tolt.. Reactor de L..
Rahue J2 Valdivia J1 Est.366 C1 Est.169 C1 Est.14 C1 Mulchen J2

x-Axis: Length Cautin\Cub_0.5\Cau-Mul D60 C2 Res Ciruelos 220kV\R1\Cir-Cau D60 C1 Res Ciruelos 220kV\R1\Cir-Tol-Cau D60 C1 Res
Rahu\1\Rah-Val D60 Res Val\52J5\Val-Cir 7SA612 C1

CDEC-SIC T_D Date: 1/9/2017


Annex: /5

Figura VII.4.6: Barrido de cortocircuito, fallas monofásicas entre S/E Rahue y S/E Mulchén (Circuitos 1).
Ajustes nuevos.

Análogamente, en las Figuras VII.4.7 y VII.4.8, es posible apreciar la coordinación de las protecciones, para
fallas trifásicas y monofásicas respectivamente, a lo largo del conjunto de circuitos números 2 estudiados.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
276-
285

DIgSILENT
1,00

[-]

0,80

0,60

0,40

0,20

0,00
0,0000 79,150 158,30 237,45 316,60 [km] 395,75

Est.327 C2
Est.356 C2 Cautin J1
Tap Pichirra.. Est.473 C2 Ciruelos B2 Tap Rio Tolt.. Reactor de L..
Rahue J2 Vadivia J2 Est.366 C2 Est.169 C2 Est.14 C2 Mulchen J1

x-Axis: Length Cautin\Cub_0.6\Cau-Mul 7SA612 C1 Ciruelos 220kV\L4\Cir-Cau 7SA612 C2 Rahu\5\Ra-Pich-Val 7SA612


Val\52J4\Val-Cir D60 C2

CDEC-SIC T_D Date: 1/13/2017


Annex: /5

Figura VII.4.7: Barrido de cortocircuito, fallas trifásicas entre S/E Rahue y S/E Mulchén (Circuitos 2).
Ajustes nuevos.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
277-
285

DIgSILENT
1,00

[-]

0,80

0,60

0,40

0,20

0,00
0,0000 79,150 158,30 237,45 316,60 [km] 395,75

Est.327 C2
Est.356 C2 Cautin J1
Tap Pichirra.. Est.473 C2 Ciruelos B2 Tap Rio Tolt.. Reactor de L..
Rahue J2 Vadivia J2 Est.366 C2 Est.169 C2 Est.14 C2 Mulchen J1

x-Axis: Length Cautin\Cub_0.6\Cau-Mul 7SA612 C1 Ciruelos 220kV\L4\Cir-Cau 7SA612 C2 Rahu\5\Ra-Pich-Val 7SA612


Val\52J4\Val-Cir D60 Res C2

CDEC-SIC T_D Date: 1/9/2017


Annex: /5

Figura VII.4.8: Barrido de cortocircuito, fallas monofásicas entre S/E Rahue y S/E Mulchén (Circuitos 2).
Ajustes nuevos.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
278-
285

VI.5 Veificaciones de coordinación con MT

VI.51 Verificación de coordinación de los paños J4, J5 de S/E Valdivia y J6, J5 de S/E Cautín con
SSEE Mariquina, Planta Valdivia y Río Toltén.

 Escenario HH-DA (hidrología húmeda – demanda alta).


o Con Tap Río Toltén.
 Fallas entre barra 220kV de S/E Ciruelos y barra 15kV de S/E Planta Valdivia:

Falla trifásica Tiempos de operación (s)


Falla Falla Falla
Barra Barra
Barra 1% 50% 99%
220kV 15kV
Paño Relé S/E 220kV desde desde desde
Planta Planta
Ciruelos S/E S/E S/E
Valdivia Valdivia
Ciruelos Ciruelos Ciruelos
J6 7SA61 Cautín 0.61 0.61 0.61 0.61 0.61 ---
J6 D60 Cautín 0.63 0.63 0.63 0.63 0.63 ---
J5 7SA61 Cautín 0.61 0.61 0.61 0.61 0.61 ---
J5 D60 Cautín 0.63 0.63 0.63 0.63 0.63 ---
J4 7SA61 Valdivia 0.31 0.31 0.31 0.31 0.31 ---
J4 D60 Valdivia 0.33 0.33 0.33 0.33 0.33 ---
J5 7SA61 Valdivia 0.31 0.31 0.31 0.31 0.31 ---
J5 P443 Valdivia 0.31 0.31 0.31 0.31 0.31 ---
J3 7SD52 Valdivia --- 0.00 0.00 0.00 --- ---
J3 7SJ64 Valdivia --- 0.055 0.055 0.056 0.056 0.289

Falla monofásica Tiempos de operación (s)


Falla Falla Falla
Barra Barra
Barra 1% 50% 99%
220kV 15kV
Paño Relé S/E 220kV desde desde desde
Planta Planta
Ciruelos S/E S/E S/E
Valdivia Valdivia
Ciruelos Ciruelos Ciruelos
J6 7SA61 Cautín 0.61 0.61 0.61 0.61 0.61 ---
J6 D60 Cautín 0.63 0.63 0.63 0.63 0.63 ---
J5 7SA61 Cautín 0.61 0.61 0.61 3.31 3.31 ---
J5 D60 Cautín 0.64 0.64 0.64 0.64 0.64 ---
J4 7SA61 Valdivia 0.31 0.31 0.31 0.31 0.31 ---
J4 D60 Valdivia 0.34 0.34 0.34 0.34 0.34 ---
J5 7SA61 Valdivia 0.31 0.31 0.31 0.31 0.31 ---
J5 P443 Valdivia 0.31 0.31 0.31 0.31 0.31 ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
279-
285

J3 7SD52 Valdivia --- 0.00 0.00 0.00 --- ---


J3 7SJ64 Valdivia 1.032 0.063 0.064 0.066 0.066 ---

 Fallas entre barra 220kV de S/E Ciruelos y barra 23kV de S/E Mariquina:

Falla trifásica Tiempos de operación (s)


Barra Barra Barra
Paño Relé S/E 220kV 220kV 23kV
Ciruelos Mariquina Mariquina
J6 7SA61 Cautín 0.61 0.61 ---
J6 D60 Cautín 0.63 0.63 ---
J5 7SA61 Cautín 0.61 0.61 ---
J5 D60 Cautín 0.63 0.63 ---
J4 7SA61 Valdivia 0.31 0.31 ---
J4 D60 Valdivia 0.33 0.33 ---
J5 7SA61 Valdivia 0.31 0.31 ---
J5 P443 Valdivia 0.31 0.31 ---

Falla monofásica Tiempos de operación (s)


Barra Barra Barra
Paño Relé S/E 220kV 220kV 23kV
Ciruelos Mariquina Mariquina
J6 7SA61 Cautín 0.61 0.61 ---
J6 D60 Cautín 0.63 0.63 ---
J5 7SA61 Cautín 0.61 0.61 ---
J5 D60 Cautín 0.64 0.64 ---
J4 7SA61 Valdivia 0.31 0.31 ---
J4 D60 Valdivia 0.34 0.34 ---
J5 7SA61 Valdivia 0.31 0.31 ---
J5 P443 Valdivia 0.31 0.31 ---

 Fallas entre barra 220kV de S/E Tap Río Toltén y barra 23kV de S/E Melipeuco:

Falla trifásica Tiempos de operación (s)


Barra Barra
Tap Río
Paño Relé S/E 110kV 23kV
Toltén
Melipeuco Melipeuco
J6 7SA61 Cautín --- --- ---
J6 D60 Cautín --- --- ---
J5 7SA61 Cautín 0.61 --- ---
J5 D60 Cautín 0.63 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
280-
285

J1 7SA61 Ciruelos 0.61 --- ---


J1 D60 Ciruelos 0.63 --- ---
J4 7SA61 Valdivia --- --- ---
J4 D60 Valdivia --- --- ---
J5 7SA61 Valdivia 3.21 --- ---
J5 P443 Valdivia --- --- ---
J1 7SA87 Río Toltén 0.02 --- ---
J1 7SA87 Río Toltén 0.02 --- ---

Falla monofásica Tiempos de operación (s)


Barra Barra
Tap Río
Paño Relé S/E 110kV 23kV
Toltén
Melipeuco Melipeuco
J6 7SA61 Cautín --- --- ---
J6 D60 Cautín --- --- ---
J5 7SA61 Cautín 0.61 --- ---
J5 D60 Cautín 0.64 --- ---
J1 7SA61 Ciruelos 0.61 --- ---
J1 D60 Ciruelos 0.64 --- ---
J4 7SA61 Valdivia --- --- ---
J4 D60 Valdivia --- --- ---
J5 7SA61 Valdivia --- --- ---
J5 P443 Valdivia --- --- ---
J1 7SA87 Río Toltén 0.02 --- ---
J1 7SA87 Río Toltén 0.02 --- ---

Cabe destacar que las instalaciones de Río Toltén cuentan con doble protección diferencial de
transformador y doble esquema diferencial de línea entre las barras de 110kV de las SSEE Río
Toltén y Melipeuco, obteniendo redundancia en la operación instantánea para fallas dentro de sus
instalaciones.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
281-
285

 Escenario HH-DA (hidrología húmeda – demanda alta).


o Sin Tap Río Toltén.
 Fallas entre barra 220kV de S/E Ciruelos y barra 15kV de S/E Planta Valdivia:

Falla trifásica Tiempos de operación (s)


Falla Falla Falla
Barra Barra
Barra 1% 50% 99%
220kV 15kV
Paño Relé S/E 220kV desde desde desde
Planta Planta
Ciruelos S/E S/E S/E
Valdivia Valdivia
Ciruelos Ciruelos Ciruelos
J6 7SA61 Cautín 0.61 0.61 0.61 0.61 0.61 ---
J6 D60 Cautín 0.63 0.63 0.63 0.63 0.63 ---
J5 7SA61 Cautín 0.41 0.41 0.41 0.41 0.41 ---
J5 D60 Cautín 0.43 0.43 0.43 0.43 0.43 ---
J4 7SA61 Valdivia 0.31 0.31 0.31 0.31 0.31 ---
J4 D60 Valdivia 0.33 0.33 0.33 0.33 0.33 ---
J5 7SA61 Valdivia 0.31 0.31 0.31 0.31 0.31 ---
J5 P443 Valdivia 0.31 0.31 0.31 0.31 0.31 ---
J3 7SD52 Valdivia --- 0.00 0.00 0.00 --- ---
J3 7SJ64 Valdivia --- 0.055 0.056 0.057 0.057 0.290

Falla monofásica Tiempos de operación (s)


Falla Falla Falla
Barra Barra
Barra 1% 50% 99%
220kV 15kV
Paño Relé S/E 220kV desde desde desde
Planta Planta
Ciruelos S/E S/E S/E
Valdivia Valdivia
Ciruelos Ciruelos Ciruelos
J6 7SA61 Cautín 0.61 0.61 0.61 0.61 0.61 ---
J6 D60 Cautín 0.63 0.63 0.63 0.63 0.63 ---
J5 7SA61 Cautín 3.21 3.21 3.21 3.21 3.21 ---
J5 D60 Cautín 3.24 3.24 3.24 3.24 3.24 ---
J4 7SA61 Valdivia 0.31 0.31 0.31 0.31 0.31 ---
J4 D60 Valdivia 0.34 0.34 0.34 0.34 0.34 ---
J5 7SA61 Valdivia 0.31 0.31 0.31 0.31 0.31 ---
J5 P443 Valdivia 0.31 0.31 0.31 0.31 0.31 ---
J3 7SD52 Valdivia --- 0.00 0.00 0.00 --- ---
J3 7SJ64 Valdivia 1.004 0.064 0.066 0.067 0.067 ---

 Fallas entre barra 220kV de S/E Ciruelos y barra 23kV de S/E Mariquina:

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
282-
285

Falla trifásica Tiempos de operación (s)


Barra Barra Barra
Paño Relé S/E 220kV 220kV 23kV
Ciruelos Mariquina Mariquina
J6 7SA61 Cautín 0.61 0.61 ---
J6 D60 Cautín 0.63 0.63 ---
J5 7SA61 Cautín 0.41 0.41 ---
J5 D60 Cautín 0.43 0.43 ---
J4 7SA61 Valdivia 0.31 0.31 ---
J4 D60 Valdivia 0.33 0.33 ---
J5 7SA61 Valdivia 0.31 0.31 ---
J5 P443 Valdivia 0.31 0.31 ---

Falla monofásica Tiempos de operación (s)


Barra Barra Barra
Paño Relé S/E 220kV 220kV 23kV
Ciruelos Mariquina Mariquina
J6 7SA61 Cautín 0.61 0.61 ---
J6 D60 Cautín 0.63 0.63 ---
J5 7SA61 Cautín 3.21 3.21 ---
J5 D60 Cautín 3.24 3.24 ---
J4 7SA61 Valdivia 0.31 0.31 ---
J4 D60 Valdivia 0.34 0.34 ---
J5 7SA61 Valdivia 0.31 0.31 ---
J5 P443 Valdivia 0.31 0.31 ---

 Fallas entre barra 220kV de S/E Tap Río Toltén y barra 23kV de S/E Melipeuco:

Falla trifásica Tiempos de operación (s)


Barra Barra
Tap Río
Paño Relé S/E 110kV 23kV
Toltén
Melipeuco Melipeuco
J6 7SA61 Cautín --- --- ---
J6 D60 Cautín --- --- ---
J5 7SA61 Cautín 0.02 --- ---
J5 D60 Cautín 0.03 --- ---
J1 7SA61 Ciruelos 0.02 --- ---
J1 D60 Ciruelos 0.03 --- ---
J4 7SA61 Valdivia --- --- ---
J4 D60 Valdivia --- --- ---
J5 7SA61 Valdivia 3.21 --- ---

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
283-
285

J5 P443 Valdivia --- --- ---


J1 7SA87 Río Toltén --- --- ---
J1 7SA87 Río Toltén --- --- ---

Falla monofásica Tiempos de operación (s)


Barra Barra
Tap Río
Paño Relé S/E 110kV 23kV
Toltén
Melipeuco Melipeuco
J6 7SA61 Cautín --- --- ---
J6 D60 Cautín --- --- ---
J5 7SA61 Cautín 0.02 --- ---
J5 D60 Cautín 0.03 --- ---
J1 7SA61 Ciruelos 0.02 --- ---
J1 D60 Ciruelos 0.04 --- ---
J4 7SA61 Valdivia --- --- ---
J4 D60 Valdivia --- --- ---
J5 7SA61 Valdivia --- --- ---
J5 P443 Valdivia --- --- ---
J1 7SA87 Río Toltén --- --- ---
J1 7SA87 Río Toltén --- --- ---

Cabe destacar que las instalaciones de Río Toltén cuentan con doble protección diferencial de
transformador y doble esquema diferencial de línea entre las barras de 110kV de las SSEE Río
Toltén y Melipeuco, obteniendo redundancia en la operación instantánea para fallas dentro de sus
instalaciones.

VI.52 Análisis de alcance Reactivo de las Zonas 2 de los paños J4, J5 de S/E Valdivia y J6, J5 de
S/E Cautín (pasada a barras de MT).

Reactancias vistas hacia Mariquina:

Falla trifásica Reactancias vistas (Ohm-sec)


Barra Barra % del
Alcance
Paño S/E 220kV S/E 23kV S/E transformador
Zona 2
Mariquina Mariquina visto
J4 Valdivia 11.86 6.34 121.46 4.8
J5 Valdivia 10.80 6.13 93.14 5.4
J6 Cautín 39.53 25.78 378.94 3.9
J5 Cautín 48.30 26.03 466.76 5.1

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
284-
285

Falla monofásica Reactancias vistas (Ohm-sec)


Barra Barra % del
Alcance
Paño S/E 220kV S/E 23kV S/E transformador
Zona 2
Mariquina Mariquina visto
J4 Valdivia 11.86 10.01 72.48 3.0
J5 Valdivia 10.80 9.40 47.55 3.7
J6 Cautín 39.53 33.22 174.49 4.5
J5 Cautín 48.30 38.74 419.51 2.5

Reactancias vistas hacia Planta Valdivia:

Falla trifásica Reactancias vistas (Ohm-sec)


Barra Barra % del
Alcance
Paño S/E 220kV S/E 15kV S/E transformador
Zona 2
P. Valdivia P. Valdivia visto
J4 Valdivia 11.86 8.20 153.05 2.5
J5 Valdivia 10.80 7.89 132.91 2.3
J6 Cautín 39.53 27.09 182.28 8.0
J5 Cautín 48.30 27.36 192.74 12.7

Falla monofásica Reactancias vistas (Ohm-sec)


Barra Barra % del
Alcance
Paño S/E 220kV S/E 15kV S/E transformador
Zona 2
P. Valdivia P. Valdivia visto
J4 Valdivia 11.86 11.12 51.90 1.8
J5 Valdivia 10.80 10.44 19.08 4.2
J6 Cautín 39.53 34.88 162.82 3.6
J5 Cautín 48.30 40.61 144.61 7.4

Reactancias vistas hacia Río Toltén:

Falla trifásica Reactancias vistas (Ohm-sec)


220kV Barra % del
Alcance
Paño S/E Tap Río 110kV S/E transformador
Zona 2
Toltén Río Toltén visto
J4 Valdivia 11.86 44.22 176.07 -24.5
J5 Valdivia 10.80 41.81 146.43 -29.6

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.
285-
285

Falla monofásica Reactancias vistas (Ohm-sec)


220kV Barra % del
Alcance
Paño S/E Tap Río 110kV S/E transformador
Zona 2
Toltén Río Toltén visto
J4 Valdivia 11.86 51.92 156.88 -38.2
J5 Valdivia 10.80 48.19 130.36 -45.5

Cabe destacar que los paños analizados en las últimas dos tablas corresponden a la S/E Valdivia,
por lo que es lógico que el porcentaje del transformador visto desde Río Toltén sea negativo, ya que
alcanzan a ver sólo un porcentaje del tramo Ciruelos – Tap Río Toltén.

STA3534-C252-01E-IN-C043 SERVICIOS DE INGENIERÍA DE DISEÑO


REV. 0 PROYECTO “AMPLIACIÓN DE LA S/E CIRUELOS”
23.12.2016 ESTUDIO DE COORDINACION Y AJUSTE DE PROTECCIONES
DESSAU INGENIERÍA S.p.A.

También podría gustarte