Está en la página 1de 26

Clculo espesor del Aislante

h= a + b v^n [Kcal/h C m^2]


he [Kcal/h C m^2]
31.2389
v> 5 [m/s]
8
a
0
b
6.17
n
0.78
hi [Kcal/h C m^2]
14.7300
v< 5 [m/s]
3
a
4.83
b
3.3
n
1
e [m]
0.2638
e [mm]
263.8377
kaisl. [kcal/h. m^2 C]
0.02665
Tcam [C]
-20
Text [C]
40
T [C]
60
q [Kcal/h.m^2]
6

1 [cal]

pesor del Aislante

.---------------------->

Diseo Panel
250mm (30Kg/m3) B&A QUALITY
e [m]
e [mm]
kaisl. [kcal/h. m^2 C]
Tcam [C]
Text [C]
T [C]
q [Kcal/h.m^2]

4,1858 [J]

o Panel
/m3) B&A QUALITY
0.25
250
0.02665
-20
40 Modificable
60
6.3286

Carga de Transmisin
q [Kcal/h.m^2]
6.33
Q = q . A [kcal/h]
7238.02
A [m^2]
1143.70
Q [KW]
8.42

Carga del Producto


Pescado
Q [kcal]
344020.258970806
Q [kJ]
1440000
Tin [C]
-10
Tf [C]
-20
T [C]
10
m [kg]
40000
Cp [KJ/Kg.C]
3.60
Cp [Kcal/kg.C]
0.86
Q [Kcal/h]
43002.53
Q [KW]
50
Palets
Q [kJ]
112288
Masa por unidad [kg]
29
n palets
40
Masa toal [kg]
1160
Cp [kJ/kgC]
1.76
Tin
35
Tex
-20
T [C]
55
Q [KW]
3.90
Cajas
Vol [m^3]
0.00228
Densidad [Kg/m^3]
476.2
Masa [Kg]
1.09
Cp [KJ/KgC]
1.25
n cajas
1680
T [C]
55
Q [KJ]
125402.51
Q [KW]
4.35

Energa
Energa

Potencia
Potencia
Energa

Potencia

Potencia

Carga Interna
Mquinas
Q [KW]

3.60
Iluminacin
A [m^2]
268.25
Q [KW]
1.34
Personas
Cantidad Pers.
1
Tiempo p/ palet [s]
180
n palets
40
Carga p/ persona [W]
390
Q [KW]
0.10
Autoelevador
Cantidad Sampi
1
Tiempo p/ palet [s]
180
n palets
40
Carga p/ sampi [W]
475
Q [KW]
0.12

Potencia

Potencia

Potencia

Potencia

Carga de Infiltracin de aire


Vol cmara [m^3]
2468
Renov/da
2.2
Densidad aire (-20) [Kg/m^3]
1.394
Densidad aire (5) [Kg/m^3]
1.16
Cp (-20) [KJ/Kg.C]
1.006
Cp (5) [KJ/Kg.C]
1.007
Entalpa aire (-20) [KJ/Kg]
254.518
Entalpa aire (5) [KJ/Kg]
269.876
Q [KJ]
106486.22 Energa
Q [KW]
3.70 Potencia

Carga del equipo


Q [KW]

7.55 Potencia

TOTAL
Sumatoria 1
Sumatoria 2
Sumatoria 3
FS
Q FINAL [KW]
Q FINAL [Kcal /h]

TOTAL
71.92
75.52
83.07
10%
91.4 Potencia
78700 Potencia

Pevap [bar]
Pcond [bar]
Tevap [C]
Tcond [C]
T2' [C]
h1 [KJ/Kg]
h2 [KJ/Kg]
h2' [KJ/Kg]
h3 [KJ/Kg]
h4 [KJ/Kg]
c
s
Mr [Kg/s]
Lc [KJ/Kg]
Pc [KW]
h1-h4
Qf [KW]
Qc [KW]
COP [KW/KW]

Diagrama P-h
2.08
16.3
-30
35
50
Temperatura de descarga
350
392
400
255
255
0.8
0.85
0.96
Caudal refrigerante
50 Trabajo de compresin por Kg
48.09
Potencia de compresin
95
Efecto frigorfico por Kg
91.38 Potencia frigorfica suministrada
139.47 Potencia cedida al condensador
1.52

120120.87 {Kcal/h]

Qf [Kcal/h]
SHR
Qf' [Kcal/h]
Ti [C]
Wi [Kg/Kg]
hi [KJ/Kg]
Ti* [C]
Wi* [Kg/Kg]
hi* [KJ/Kg]
Ts [C]
Ws [Kg/Kg]
hs [KJ/Kg]
h sensible [KJ/Kg]
h total [KJ/Kg]

Evaporador
78700
0.92
85561
-20
0.0006
-18.371
-20
0.0003
-19.242
-30
0.0003
-29.233
9.991
10.862

Carga trmica
Potencia frigorfica requerida
(85% HR)

(39,5% HR)

(100% HR)

CAAMAO XL 5-25 TE
4 evap.
Fs
1.13
Qo (catlogo) [Kcal/h]
21896
Q [Kcal/h]
24742.48
QTOTAL [Kcal/h]
98969.9
Caudal [m^3/h]
17000.0
rea de intercambio [m^2]
101.37
Cantidad de ventiladores
2

Seleccin de Compresor
Fabricante
Modelo
Cilindros
Velocidad [rpm]
Oil cooler
Volumen barrido [m^3/h]
Volumen succin [m^3/h]
Rendimiento volumtrico
Capacidad [KW]
Capacidad [Kcal/h]
Potencia absorbida [KW]

MYCOM
F8WB
8
1000
agua
637
403
0.633
121.1
104296.65
76.2

Clculo terico
Pc [KW]
Qf [KW]
Qf [Kcal/h]
Qf' [Kcal/h]
c
s
v
Pc' [KW]
mr'' [Kg/h]
mr''/v

48.09
Potencia de compresin
91.38
Potencia frigorfica suministrada
78699.88101
Potencia frigorfica suministrada
85560.81549
Potencia frigorfica requerida
0.8
Rendimiento mecnico
0.85
Rendimiento isoentrpico
0.60
Rendimiento volumtrico
60.12
Potencia elctrica necesaria
273.02 Caudal volumtrico requerido
455.04 Caudal volumtrico requerido/v

Casco y Tubo BIMA BCT4


Calor de Condensacin
Calor de Condensacin
Toneladas de Refr.
Caudal Msico Refr.

Caudal de agua [Kg/s]


Caudal de agua [m^3/h]
Densidad del agua (30 C) [Kg/m^3]
Cp del agua (30 C) [J/Kg C]
T ent ref [C]
T sal ref [C]
Tent. Agua [C]
T sal agua [C]
DTML DISEO
Catlogo
BCT 5 (Fc=120120/179000=0,68)
Calor de catlogo (halogenados)
T sal ref [C]
Tent. Agua [C]
T sal agua [C]
DTML Fa+bricante
Calor seleccionado
Calor corregido
Calor extraible real

Casco y Tubo BIMA BCT4


Qcond.=Mr*(h2'-h3) [KW]
Qcond.=Mr*(h2'-h3) [Kcal/h]
TR
Mr [Kg/s]
h2' [KJ/Kg]
h3 [KJ/Kg]

T1=T2
t1
t2
Catlogo
BCT 5 (Fc=120120/179000=0,68)
Qcond.=Mr*(h2'-h3)/0,65 [Kcal/h]
T1=T2
t1
t2
Qsel [Kcal/h]
Qreal [kcal/h]
Qext [kcal/h]

139.4736780203
120120.9
32.1
0.9619
400.00
255
13.36
48.33
995.02
4178.00
50.00
35.00
28.00
30.50
5.6587937352

184801.340034287
35.00
29.00
31.50
4.638812599
145000
176882.569429882
120280.14721232

Torre de Enfriamiento
Aire
Hum. Rel.

Temperatura ambiente
Humedad relativa

Acercamiento
Salto trmico
Caudal de agua [lts/h]
Factor de performance
Ton. Ref. coregida

T [C]
HR %
Tbulbo hum. [C]

35
??

Agua
Ta. Ent. = T sal CyT
Ta Sal.
Tacerc [C]
T [C]
Fp
TRC

Catlogo
FAVRA SERIE 190 (TR 60)

24
30.50
28.00
4.00
2.50
48330
0.675
47.9

La temperatura del agua debe ser mayor a la de bulbo hmedo del aire
MAX Tbulbo hum

de bulbo hmedo del aire

Long Equivalente[m]
Codos
26
T
10
Valvulas
31

54.85
29.1
410

Grafico A
Linea de succin
Correcion linea de succion
Correcion por longitud (succion)
Linea de succin corregida
Linea de succin corregida
Linea de descarga
Correcion linea de descarga
Correcion por longitud (descarga)
Linea de descarga corregida

Linea de descarga corregida


Linea de liquido
Correcion por longitud (liquido)
Linea de liquido corregida
Linea de liquido corregida
Vmin linea de succion
Vmin linea de descarga

Diametro interior [mm]

Diametro interior [mm]


Diametro interior [mm]
Diametro interior [mm]

Diametro interior [mm]

[m/s]
[m/s]

80
0.95
1.23
93.48
99
45
1.125
0.65
32.90625

32
25
1.27
31.75
32
12
3.75

Identificacin
Entrada General Evaporadores
Colector General Salida Evaporadores
Tubera hacia Sala de Mquinas - Entrada Compresor
Tubera desde Compresor hacia Condensador
Tubera desde Condensador hacia Recibidor de Lquido
Retorno a Entrada Genral Evaporadores desde Sala de Mquinas
SUMA TOTAL
SUMA TOTAL CON ACCESORIOS

Separadores de succion
Q=Vesp*Qmasico*3600
Separador de aceite
A=Q/V
Recibidor de liquido
Vol liquido
Vol descarga
Vol succion
Vol evaporador (x4)
Vol caso y tubos
Total

Informacin
Permetro Cmara [m]

Distancia
66

Permetro Cmara [m]


[m]
[m]
[m]
[m]
[m]
[m]

66
19.2
5
8
19.2
183.4
677.35
Divisin
Tubera de Lquido
Tubera de Descarga
Tubera de Succin

273.024

0.0266

Volumen

Masa [Kg]
0.0749558874 92.9453004
0.0040212386 0.2892879
0.6558429664 8.30297196
0.14
87.6862
1.0825954988 77.8819202
267.10568 215.40781 [lts]

Entrada General Evaporadores + Tubera desde Condensador hacia


Recibidor de Lquido + Retorno a Entrada Genral Evaporadores desde 93.2
Sala de Mquinas
Tubera desde Compresor hacia Condensador
Colector General Salida Evaporadores + Tubera hacia Sala de
Mquinas - Entrada Compresor

5
85.2