Documentos de Académico
Documentos de Profesional
Documentos de Cultura
INTRODUCCION.....................................................................................................
2.
3.
3.1
3.1.1
3.1.2
3.1.3
3.1.4
3.2
3.4.2
3.5
3.6
4.
4.1
4.2
4.3
4.3.1
4.3.2
4.3.3
4.3.4
5.
DISTANCIAS ELCTRICAS..................................................................................
5.1
DISTANCIAS DE SEGURIDAD...........................................................................................
3.2.1
3.2.2
3.2.3
3.3
3.3.1
3.3.2
3.3.3
3.4
3.4.1
5.1.1
5.1.2
5.2
5.2.1
5.2.2
5.2.3
5.2.4
Valor bsico.........................................................................................................................
Zonas de seguridad.............................................................................................................
DISTANCIAS PARA EL DIMENSIONAMIENTO DE LA SUBESTACIN...........................
Ancho de barras...................................................................................................................
Ancho de campo..................................................................................................................
Altura de campo...................................................................................................................
Longitud del campo.............................................................................................................
REFERENCIAS.................................................................................................................
LISTA DE TABLAS
Tabla 1. Parmetros Subestacin Curramba a 220 kV.....................................................................
Tabla 2. Tensin base........................................................................................................................
Tabla 3. Distancia especfica mnima nominal..................................................................................
Tabla 4. Factores de conversin para rango I..................................................................................
Tabla 5. Correlacin entre el nivel de soportabilidad al impulso tipo rayo y las distancias
mnimas en el aire...................................................................................................................
Tabla 6. Paso 1, determinacin de las sobretensiones representativas (Urp).................................
Tabla 7. Paso 2, determinacin de las tensiones de soportabilidad para coordinacin (Ucw)........
Tabla 8. Paso 3, determinacin de las tensiones de soportabilidad requeridas (Urw).....................
Tabla 9. Paso 4, determinacin de las tensiones de soportabilidad normalizadas (Uw).................
Tabla 10. Resumen de las tensiones de soportabilidad requeridas.................................................
Tabla 11. Distancias mnimas en el aire..........................................................................................
Tabla 12. Distancias adoptadas entre equipos de patio 220 kV......................................................
Tabla 13. Distancias de seguridad y dimensionamiento subestacin Curramba a 220 kV.............
LISTA DE FIGURAS
Figura 1. Valor bsico......................................................................................................................
Figura 2. Distancias medias para un operador................................................................................
Figura 3. Ejemplo de la franja de circulacin de personal..............................................................
Figura 4. Distancias de seguridad para circulacin de vehculos....................................................
Figura 5. Franja de circulacin usada para servicios de mantenimiento con herramientas
livianas.....................................................................................................................................
Figura 6. Franja de circulacin usada para servicios de mantenimiento con herramientas
pesadas....................................................................................................................................
Figura 7. Rango del movimiento de conductores flexibles durante cortocircuitos..........................
Figura 8. Ancho de campo determinado por estructura adyacente a seccionador pantgrafo.......
LISTA DE ANEXOS
Anexo 1.CARACTERSTICAS DEL PARARRAYOS EN LA SUBESTACIN CURRAMBA 220
kV...............................................................................................................................................
1.
INTRODUCCION
2.
3.
Voltaje nominal
220 kV
Frecuencia nominal
60 Hz
245 kV
1050 kV
460 kV
Muy pesado
31 mm/kV
7595 mm
40 kA
En Y
50 m
245 kV
200 kV
Ligero
16,0
Medio
20,0
Alto
25,0
Muy alto
31,0
3.1.2.1
Sobretensiones por fallas a tierra
La ocurrencia de una falla a tierra en un determinado punto del sistema lleva a
un aumento de la tensin fase - tierra en las fases sanas cuyo valor depende
del grado de aterrizamiento del sistema.
Si el sistema est slidamente puesto a tierra la norma considera que la
mxima sobretensin eficaz no sobrepasa 1,4 veces la tensin mxima eficaz
fase a tierra del sistema. Para sistemas con neutro aislado las sobretensiones
alcanzan hasta 1,73 veces la tensin eficaz mxima.
U rp ( p e) K *
US
en donde:
K: Factor de falla a tierra (Ver anexo B de la norma IEC 60071-2)
Us: Mxima tensin del sistema, kV
3.1.2.2
Sobretensiones por rechazo de carga
Otra fuente de sobretensiones temporales es el rechazo de carga el cual
produce sobre tensiones que afectan el aislamiento fase fase y fase tierra.
- Fase a tierra U rp ( p e) 1,4 *
US
U et 1,25 U e 2 0,25
U pt 1,25 U p 2 0,43
donde:
Ue2: Valor de la sobretensin fase a tierra que tiene una probabilidad del 2%
3.1.4.3
Pararrayos en la entrada de la lnea energizacin desde el
extremo remoto
Con el fin de controlar las sobretensiones por energizacin de la lnea en el
extremo remoto se instalan pararrayos en la entrada de la lnea con las
siguientes caractersticas de proteccin:
Fase a tierra: U rp ( p e)
Fase a fase: U rp ( p p )
Fase a tierra: U rp ( p e)
Fase a fase: U rp ( p p )
Fase a tierra: U cw U rp K c
Fase a fase: U cw U rp K c
U ps
Fase a tierra:
Fase a fase: 2
U e2
U ps
K cd
U p2
K cd
U ps
Fase a tierra:
Fase a fase: 2
U e2
U ps
K cd
U p2
K cd
A
L
n Lsp La
Donde:
Ucw: Tensin soportable de coordinacin al impulso atmosfrico, kV
Upl: Nivel de proteccin al impulso tipo rayo del pararrayos, kV
A:
Factor dado en la Tabla F.2 de la norma IEC 60071-2 que describe el
comportamiento de la lnea ante las descargas elctricas
atmosfricas, kV
Nmero de lneas conectadas a la subestacin, (n-1)
Separacin equivalente entre el pararrayos ms cercano y el equipo en
consideracin, obtenido de:
n:
L:
L a1 a 2 a 3 a 4
a1:
a2:
a3:
Ra
Rkm
Las sobretensiones de frente rpido afectan los aislamientos fase a fase y fase
a tierra de igual forma.
3.3 DETERMINACIN
REQUERIDAS (Urw)
DE
LAS
TENSIONES
DE
SOPORTABILIDAD
Ka :
Ks :
Factor de seguridad
H
m
8150
Donde:
H
Altura sobre el nivel del mar, m
m:
1,0 para la coordinacin de las tensiones de soportabilidad al impulso
tipo rayo
m:
De acuerdo a la figura 9 de la norma IEC 71-2 para la coordinacin de
las tensiones de soportabilidad al impulso de maniobra
m:
1,0 voltajes de soportabilidad de corta duracin a frecuencia industrial
de distancias en el aire y de aisladores
3.3.3 Tensiones de soportabilidad requeridas
Los valores para las tensiones de soportabilidad requeridas son obtenidos
aplicando la siguiente ecuacin:
U rw U cw K s K a
Fase a tierra
Fase a fase U rw U cw K s K a
Aislamiento interno
U rw U cw K s
Fase a tierra
Fase a fase U rw U cw K s
Fase a tierra:
Fase a fase: U rw U cw K s K a
Fase a tierra:
Fase a fase: U rw U cw K s K a
Aislamiento interno
U rw U cw K s
Fase a tierra:
Fase a fase: U rw U cw K s
Fase a tierra:
Fase a fase: U rw U cw K s K a
Aislamiento interno
U rw U cw K s
Fase a tierra:
Fase a fase: U rw U cw K s
Tensin de
soportabilidad de corta
duracin a frecuencia
industrial
Tensin de
soportabilidad al
impulso tipo rayo
Fase a tierra
0,6+Urw/8500
1,05+Urw/6000
Fase a fase
0,6+Urw/12700
1,05+Urw/9000
0,6
1,3
0,5
1,10
0,5
1,00
Aislamiento
liquido
inmerso
Aislamiento slido
en
Fase a tierra:
Fase a tierra:
Aislamiento interno
SDW U rw 0,5
Fase a tierra:
Fase a tierra:
Fase a tierra:
Aislamiento interno
LIWL U rw 1,1
Fase a tierra:
3.5 SELECCIN
NORMALIZADAS
DE
LAS
TENSIONES
DE
SOPORTABILIDAD
Tensin de soportabilidad al
impulso tipo rayo
kV
Varilla-estructura
Conductor-estructura
20
40
60
75
95
125
145
170
250
325
450
550
650
750
850
950
1050
60
60
90
120
160
220
270
320
480
630
900
1100
1300
1500
1700
1900
2100
1600
1700
1900
NOTA:
-
4.
4.1 SELECCIN
NORMALIZADAS
DE
LAS
TENSIONES
DE
SOPORTABILIDAD
Us phase-to-phase kV
1.0 p.u. en kV (pico)
245
200
Temporaly overvoltages
Earth faults
Earth-fault factor: k =
1.40
Urp (p-e) en kV
198
Load rejection
1.40
Urp (p - e) en kV
Urp (p - p) en kV
198
343
343
Slow-front overvoltages
For line entrance equipment
Re-energization
Ue2 en p.u.
Up2 en p.u.
3.26
4.86
Ue2 en p.u.
Up2 en p.u.
2.09
3.11
Uet en p.u.
Upt en p.u.
3.83
5.65
Uet en p.u.
Upt en p.u.
2.36
3.46
Uet en kV
Upt en kV
765.16
1129.35
Uet en kV
Upt en kV
471.7
691.8
Ups en kV
Upl en kV
375
451
For other equipment
375
750
Urp (p-e) en kV
Urp (p-p) en kV
375
692
Evaluated in step 2
Notas:
1. En el nivel de 220 kV se tiene un sistema slidamente puesto a tierra y de
acuerdo a la recomendacin de la norma el factor de falla a tierra no es
superior a 1,4, siendo un valor conservativo.
2. Las sobretensiones por rechazo de carga producen sobretensiones fase a
fase y fase a tierra del orden de 1,4, valor recomendado por la norma.
3. El nivel de proteccin del pararrayos al impulso de maniobra, Ups es igual
a 375 kV.
4. El nivel de proteccin del pararrayos al impulso tipo rayo, Upl es igual a
451 kV.
5. Los valores de las sobretensiones por energizacin en el extremo local son
seleccionados teniendo en cuenta las mximas sobretensiones esperadas
segn el capitulo 5 de la referencia [6].
Tabla 7. Paso 2, determinacin de las tensiones de soportabilidad para
coordinacin (Ucw)
Step 2: Determination of the coordination withstand voltages (Ucw)
Temporary overvoltages
Phase-to-earth, en kV:
Phase-to-phase, en kV:
Kc factor =
Ucw = Kc x Urp =
Ucw = Kc x Urp =
1.0
198
343
Other equipment
Phase-to-earth
Phase-to-phase
Phase-to-earth
Phase-to-phase
Ups/Ue2=
0.58
2Ups/Up2=
0.77
Ups/Ue2=
0.90
2Ups/Up2=
1.21
Kcd =
1.10
Kcd =
1.03
Kcd =
1.06
Kcd =
1.00
Retained value
Kcd =
1.10
Ucw = Kcd x Urp
Ucw =
413
Retained value
Kcd =
1.06
Ucw = Kcd x Urp
Ucw =
774
Fast-front overvoltages
Parameter A =
Span length Lsp =
Outage rate =
Acceptable failure rate =
Ucw en kV
Ucw en kV
451.00
41.84
49.84
602
631
kV
m
m
4500
400
0.03
0.01
La, en m =
m
km/y
years
222.22
Notas:
1. Para el clculo las sobretensiones de frente rpido se tienen los siguientes
parmetros:
Internal insulation Ks =
External insulation Ks =
1.15
1.05
Altitude H, en m =
50
Phase-to-phase
Phase-to-earth
Phase-to-phase
Valor m =
1.0
0.8
1.0
1.0
Valor Ka =
1.131
1.103
1.131
1.131
Phase-to-phase
Phase-to-earth
Phase-to-earth
Phase-to-phase
Phase-to-earth
Phase-to-phase
Phase-to-earth
Phase-to-phase
Internal
insulation kV
Internal
insulation kV
Internal insulation
kV
394
Line entrance
equipment
External
insulation kV
919
Internal insulation
kV
228
Line entrance
equipment
External
insulation kV
478
693
693
External
insulation kV
External
insulation kV
Other equipment
Other equipment
External
insulation kV
External
insulation kV
235
407
internal insulation
kV
458
Internal
insulation kV
796
749
749
External
insulation kV
External
insulation kV
462
821
Notas:
1. El factor de correccin atmosfrico Ka se toma igual a 1,131 teniendo en
cuenta los requerimientos de la interventora, considerando as que la
subestacin Curramba se encuentra a una altura de 1.000 m sobre el nivel
del mar.
2. El valor de m se considera unitario para las sobretensiones por maniobra
fase-fase y las atmosfricas fase-fase y fase-tierra, mientras que para las
sobretensiones por maniobra fase-tierra toma el valor de 0.8 segn la
figura 9 de la norma IEC-60071-2. Para las sobretensiones a frecuencia
industrial se utiliza el valor de m unitario ya que resulta en valores mas
conservativos.
Tabla 9. Paso 4, determinacin de las tensiones de soportabilidad
normalizadas (Uw)
Step 4: Conversion to withstand voltages normalized to range I
Conversion of switching impulse withstand voltages to
short duration power frequency withstand voltages
Conversion factors
External insulation
- Phase-to-earth
0.6 + Urw/8500
- Phase-to-phase
0.6 + Urw/12700
External insulation
- Phase-to-earth
- Phase-to-phase
1.3
1.05 + Urw/9000
Internal insulation
- Phase-to-earth
- Phase-to-phase
Internal insulation
- Phase-to-earth
- Phase-to-phase
1.1
1.1
0.5
0.5
Conversion factors
Other equipment
Other equipment
External insulation kV
- Phase-to-earth
314
- Phase-to-phase
618
External insulation kV
- Phase-to-earth
302
- Phase-to-phase
546
Internal insulation kV
- Phase-to-earth
229
- Phase-to-phase
398
External insulation kV
- Phase-to-earth
621
- Phase-to-phase
1059
External insulation kV
- Phase-to-earth
600
- Phase-to-phase
937
Internal insulation kV
- Phase-to-earth
504
- Phase-to-phase
875
Aislamiento externo
Equipos entrada
de lnea
Otros equipos
Aislamiento
interno
Urw(s)
Urw(c)
Urw(s)
Urw(c)
Urw(s)
Urw(c)
Frecuencia
industrial
Fase-tierra
235
314
235
302
228
229
Fase-fase
407
618
407
546
394
398
Impulso de
maniobra
Fase-tierra
478
Fase-fase
Fase-tierra
919
749
Fase-fase
749
Impulso
atmosfrico
(1)
462
621
821
749
1059
749
(1)
458
(1)
600
796
693
504
937
693
875
Distancia mnima
(mm)
Fase fase
1175
2350
Fase tierra
Varilla Estructura
Conductor Estructura
1050
1050
2100
1900
Fase fase
1050
2100
Fase tierra
Varilla Estructura
Conductor Estructura
1050
1050
2100
1900
Localizacin
Equipo a la entrada
de la lnea
Otros equipos
Um 245kV
141,5 kV
3
3
Ke: Factor de falla a tierra, que para el caso es de 1,4 por ser el sistema
slidamente puesto a tierra.
TOV 1,4 141,5 kV 198 kV
COV
Ko
141,5 kV
176,8 kV
0.8
Re
TOV
Kt
198kV
172,2 kV
1,15
NPR: Nivel de proteccin al impulso tipo rayo (10 kA): Upl = 451 kV
Descargas atmosfricas
Donde:
W:
Energa absorbida
Tw
Longitud linea km
300m / s
285.5 kJ
4.3.4.2
Descargas atmosfricas
Aunque el nivel cerunico de la zona es cero, se realiza el calculo teniendo en
cuenta que puede existir una descarga en un extremo remoto de la lnea en la
cual el nivel cerunico sea diferente de cero y el pararrayos del extremo local
consuma toda la energa (caso poco probable).
W 2Uf NUpl * (1 ln(2Uf / Upl )) *
Upl * Tl
Z
Donde:
W:
Energa absorbida
Z:
N:
Tl:
98.7 kJ
La capacidad de energa requerida que cumpla para cada uno de los casos
ser de 285.5 kJ que corresponde a una capacidad de energa especfica de
1.49 kJ/kVUr.
El pararrayos a suministrar tiene una capacidad de energa especfica de
10 kJ/kVUr, que corresponde a una capacidad de 1980 kJ, cumpliendo con la
capacidad de energa definida en las caractersticas garantizadas.
5.
DISTANCIAS ELCTRICAS
5.1.2.3
Trabajo sobre equipos o conductores en ausencia de
maquinaria pesada
Se considera que el trabajo sobre los equipos o conductores se realiza con la
subestacin energizada parcial o totalmente. Para estos clculos se tiene en
cuenta los valores previstos en la Figura 2: Horizontalmente se toman
1.750 mm que tiene en promedio una persona con los brazos abiertos, y
verticalmente se toman 1.250 mm que tiene en promedio una persona con una
mano alzada sobre el plano de trabajo. Luego estas distancias estn
determinadas de la siguiente manera:
Distancia Horizontal = 1.750 mm + VB
Distancia Vertical = 1.250 mm + VB
Donde:
VB : Valor bsico [mm]
Distancia horizontal = 1.750 mm + 2.205 mm = 3.955 mm
Distancia Vertical = 1.250 mm + 2.205 mm = 3.455 mm
Ancho de barras
Ancho de campo
Altura de campo
Longitud de campo
Yo
a
1.2 Yo
40
Yo
d min
Yk
5.2.2.1
Templas superiores a lo largo del campo
El ancho del campo se determina por la separacin entre las fases y el
movimiento que tendran los conductores debido a cortocircuitos en las
templas superiores a lo largo del campo.
La separacin entre fases de las templas superiores del campo adoptada para
el diseo es de 4.000 mm. Se verific que no se produjeran acercamientos de
acuerdo al calculo de las tensiones de tendido que se incluye en la gua de
obras civiles, basado en el documento The Mechanical Effects of Short-Circuit
Currents in Open Substations del comit No. 23 del Cigre.
En consecuencia el ancho del campo sera dos veces la separacin entre
fases mas la distancia mnima fase-tierra incrementada, a lado y lado, en un
25% para considerar un posible barraje adyacente.
AC = 2*a + 2*dmin * 1,25
AC = 2*4.000 mm + 2*2.100 * 1,25 = 13.250 mm
5.2.2.2
Estructura adyacente a seccionador pantgrafo
El clculo cuando se tiene la estructura del prtico adyacente a un seccionador
pantgrafo se analiza de acuerdo a la siguiente figura.
b
a
I1/2
I2/2
Ancho de campo
5.2.3.1
Primer nivel
Corresponde a la altura de conexin de los equipos y est determinado por las
distancias de seguridad para la circulacin de personas: Es decir, el valor
bsico (VB) ms la altura de una persona con los brazos levantados
verticalmente.
P.N = VB + 2250 mm
Donde:
VB : Valor bsico [mm]
P.N = 2.205 mm + 2.250 mm = 4.455 mm
Teniendo en cuenta que el pararrayos y el transformador de tensin se
encuentran ubicados al inicio de cada campo y son los equipos de mayor
altura, se elige una altura de conexin para el primer nivel de 5.700 mm para
los equipos a la entrada de la lnea, sin embargo para no incurrir en
estructuras demasiado altas en los dems equipos, se eligi una altura de
conexin para el primer nivel de 5.100 mm, esta ltima altura servir para el
calculo de los niveles superiores.
5.2.3.2
Segundo nivel
5.2.3.3
Tercer nivel
Conformado por las templas superiores, cuya altura debe ser superior a la
altura del barraje, por lo menos en la distancia mnima fase-fase, cable-cable,
ms la flecha mxima de la templa.
T.N = S.N + dmin * 1,1 + YT
donde:
YT : Flecha mxima de la templa superior
dmin: Distancia mnima fase-fase, cable-cable mm
En la prctica, YT 0,03*S, siendo S el vano de la templa flexible. En la
subestacin Curramba 220 kV el vano de la templa flexible tendr una longitud
de 32 m.
Luego:
YT = 0,03*S
T.N = S.N + dmin * 1,1 + 0,03*S
T.N = 11.000 mm + 2.100 mm*1,1 + 0,03*32.000 mm = 14.270 mm
Para el diseo se eligi una altura de conexin para el tercer nivel de
14.500 mm.
5.2.4 Longitud del campo
Est determinada por la configuracin de la subestacin y por las distancias
entre los diferentes equipos. Esta distancia se define bsicamente por
razones de mantenimiento, montaje y esttica. La longitud del campo no se
determina por las distancias mnimas o de seguridad. Las distancias
adoptadas entre los equipos de patio de 220 kV se muestran en la Tabla 12.
Distancia en mm para
Um = 245 kV
3.000
3.000
3.000
3.500
4.000
8.500
4.000
4.000
4.000
4.900
DESCRIPCIN
Distancia mnima fase a tierra
Valor bsico
Altura entre el piso y la parte inferior de la porcelana del
equipo.
Circulacin de personal requerida REP
Campos de Lnea
Movimiento de vehculos
(ancho x alto)
Entradas de Lnea
Separacin entre fases en barras y templas
Separacin entre fases en equipos
Primer nivel
Alturas de campo
Segundo nivel
Tercer nivel
Ancho de campo
Calculada
Adoptada
2.100
2.205
2.100
2.205
2.300
2.300
---3.200 x 3.000
3.200 x 3.000
2.800
2.800
4.455
8.370
14.270
4.500
4.000 x 3.000
4.500 x 3.000
4.000
3.800
5.100
10.500
14.500
En templas
13.250
En estructura adyacente a
seccionadores pantgrafo
12.500
16.000
REFERENCIAS
1
[6]
DATOS TCNICOS
Tipo 3EP2 195-3PG42-2KF1
Marca SIEMENS
Norma
Mxima Altitud de instalacin
Tensin mxima de servicio entre fases
Conexin de neutro
Nivel de aislamiento del equipo que se protege BIL
Tensin nominal del pararrayos
Tensin de operacin continua ( COV )
Intensidad nominal de descarga con onda 8/2Ous
Clase de descarga de lnea
Capacidad de absorcin de energa- trmica
Capacidad de absorcin de energa- Impulso
Intensidad de descarga para onda de larga duracin (2 ms)
Intensidad de cortocircuito ( 0.2 s )
Mxima tensin residual con corrientes de descarga
20 kA 1/2us
5kA 8/20us
10 kA8/0us
20 kA 8/20us
40 kA 8/20us
500 A 30/60us
1 kA 30/60us
2 kA 30/60us
Sobretensiones temporales 1 s
Sobretensiones temporales 10 s
Nivel de aislamiento a frecuencia Ind. (1 min. hmedo) Zno completo
Nivel de aislamiento a impulso atmosfrico Zno completo
Distancia de fuga
Fuerzas mximas admisibles en el cabezal
Esttica
Dinmica
Nmero de unidades
Peso
Altura
Color de la envolvente
IEC-60099-4
3.800 m
245 kV
puesto a tierra rgidamente
1050 kV
192 kV
154 kV
20 kA
4
10 kJ/kVr
5.6 kJ/kVr
1200 A
65.0 kA
528 kV
424 kV
451 kV
496 kV
541 kV
366 kV
375 kV
393 kV
221 kV
206 kV
480 kV
1200 kV
8070 mm
1540 N
3850 N
2
275 kg
3240 mm
Marrn