DISE
APROB
CLARO CAV
PLAZA
IMPERIAL
INGERPROYECTOS
JULIO DE 2015
TABLERO DE RED NORMAL , TN - 208/120V
DESCRIPCIN
CIRCUITO
R
Salida para tomas en back office
11
10
Horno
12
13
15
17
Reservas
ING. JAIME
CUESTAS B
SALIDAS
POTENCIA
CIRCUITO
VA
TOTAL
CORRIENT
E NOMINAL
180
2360
19.67 A
24.58 A
3 x No.12
20 A
180
1080
9.00 A
11.25 A
3 x No.12
20 A
180
900
7.50 A
9.38 A
3 x No.12
20 A
180
720
6.00 A
7.50 A
3 x No.12
20 A
180
720
6.00 A
7.50 A
3 x No.12
20 A
180
900
7.50 A
9.38 A
3 x No.12
20 A
180
900
7.50 A
9.38 A
3 x No.12
20 A
180
720
6.00 A
7.50 A
3 x No.12
20 A
1000
1000
8.33 A
10.42 A
3 x No.12
20 A
180
1080
9.00 A
11.25 A
3 x No.12
20 A
180
720
6.00 A
7.50 A
3 x No.12
20 A
750
750
6.25 A
7.81 A
3 x No.12
20 A
500
500
4.17 A
5.21 A
3 x No.12
20 A
180
900
7.50 A
9.38 A
3 x No.12
20 A
55
110
0.92 A
1.15 A
3 x No.12
20 A
12
100
1200
10.00 A
12.50 A
3 x No.12
20 A
300
600
5.00 A
6.25 A
3 x No.12
20 A
200
600
5.00 A
6.25 A
3 x No.12
20 A
500
1500
12.50 A
15.63 A
3 x No.12
20 A
14
16
Salida Aviso
18
19
Reservas
21
23
Reservas
20
Reservas
22
Reservas
24
TOTAL DE ELEMENTOS
77
17260
17,260 VA
13,630 VA
USO DE LA INSTALACIN
ALIMENTACIN DE CIRCUITOS DE
RED NORMAL PARA OFICINAS Y
TOMAS DE SHOW ROOM
% MX. DESBALANCE
PORCENTAJE DE CARGA POR FASE
50.67 Amperios
FASE S
43.93 Amperios
FASE T
47.38 Amperios
13.31%
FASE R
35.69%
FASE S
30.94%
FASE T
33.37%
17,260 VA
13,630 VA
CORRIENTE DE DISEO
50.67 Amperios
PROTECCIN SELECCIONADA
CONSTANTE DE REGULACIN
3.22112E-03
10.00 m
0.44%
EMT
1 1/2" O CARCAMO
FECHA
INGERPROYECTOS
DISE
APROB
DESCRIPCIN
180
720
6.00 A
7.50 A
180
720
6.00 A
7.50 A
180
900
7.50 A
9.38 A
180
720
6.00 A
7.50 A
180
900
7.50 A
9.38 A
180
900
7.50 A
9.38 A
180
720
6.00 A
7.50 A
500
500
4.17 A
5.21 A
11
500
500
4.17 A
5.21 A
12
Reserva
10
Reserva
TOTAL DE ELEMENTOS
33
6580
6,580 VA
6,580 VA
USO DE LA INSTALACIN
ALIMENTACIN DE CIRCUITOS DE
RED NORMAL PARA OFICINAS Y
TOMAS DE SERVICIO
FASE R
22.50 Amperios
FASE S
22.08 Amperios
FASE T
23.96 Amperios
% MX. DESBALANCE
7.83%
6,580 VA
6,580 VA
CORRIENTE DE DISEO
23.96 Amper
PROTECCIN SELECCIONADA
3x30Amperios, Tipo
CLCULO DEL ALIMENTADOR
10.00 m
CONSTANTE DE REGULACIN
5.04614E-0
0.33%
EMT
1" o CAR
ALIMENTADOR EN CABLE: 3x86F + 1x8N + 1x8T THHN-AWG 600V 75C EN TUBERA EMT
TABLERO DE 12 CIRCUITOS
1"
CLARO CAV
PLAZA
IMPERIAL
APROB
EGULADO , TR - 208/120V
CLCULO DE PROTECCIONES Y ALIMENTADORES
CABLEADO
PROTECCIN
THHN-AWG
3 x No.12
20 A
3 x No.12
20 A
3 x No.12
20 A
3 x No.12
20 A
3 x No.12
20 A
3 x No.12
20 A
3 x No.12
20 A
3 x No.12
20 A
3 x No.12
20 A
6,580 VA
6,580 VA
PORCENTAJE DE CARGA POR FASE
FASE R
32.83%
FASE S
32.22%
FASE T
34.95%
PROTECCIN PRINCIPAL
6,580 VA
6,580 VA
23.96 Amperios
3x30Amperios, Tipo Industrial
DEL ALIMENTADOR
10.00 m
Cable No.:8 APLICANDO REGULACION
5.04614E-03
0.33%
EMT
1" o CARCAMO
1"
FECHA
DISE
APROB
JULIO 2.015
INGERPROYECTOS
CIRCUITO
DESCRIPCIN
R
Salida para circuito de iluminacin Pasillo y
Salon Multiple
33
12
18.0
216
1.80 A
2.25 A
3x12
20 A
12
33
18.0
486
4.05 A
5.06 A
3x12
20 A
16
33
18.0
528
4.40 A
5.50 A
3x12
20 A
18.0
234
1.95 A
2.44 A
3x12
20 A
33
4
CLARO CAV
PLAZA
IMPERIAL
13
14
33
462
3.85 A
4.81 A
3x12
20 A
16
33
528
4.40 A
5.50 A
3x12
20 A
6
7
Reserva
Reserva
11
Alumbrado 24 horas
Reserva
10
Reserva
12
TOTAL DE ELEMENTOS
58
30
2454
2,454 VA
2,454 VA
USO DE LA INSTALACIN
FASE R
10.19 Amperios
FASE S
9.88 Amperios
FASE T
5.50 Amperios
% MAX. DESBALANCE
PORCENTAJE DE CARGA POR FASE
46.01%
FASE R
39.85%
FASE S
38.63%
FASE T
21.52%
2,454 VA
CORRIENTE DE DISEO
10.2 Amperios
PROTECCIN SELECCIONADA
10.00 m
CONSTANTE DE REGULACIN
5.04614E-03
ALIMENTADOR EN CABLE: 3x6F + 1x6N + 1x8T THHN-AWG 600V 90C EN TUBERA EMT
0.12%
EMT
1"
1"