Ø1 Ø2
CALCULO DE LA CORRIENTE A PLENA CARGA
Ø3
746 𝑋 1000
𝐼𝑃𝐶 =
4160𝑉 𝑋 3 𝑋 0.88 𝑋 0.94
𝐼PC = 𝟏𝟐𝟓. 𝟏𝟔𝟐𝑨
CALCULO DE LA CORRIENTE A ROTOR BLOQUEADO
9R VALOR DE TABLA 430-7 (b) EN KVA X HP DEL MOTOR
𝐾𝑉𝐴 = 4.49 X 1000 = 4490
4490𝐾𝑉𝐴
𝐼𝑅𝐵 = 4.16𝐾𝑉 𝑋 = 623.149 A
3
CONTROL
CALCULO DE LA CORRIENTE DE INRUSH
51-1 𝐼𝑖𝑛𝑟𝑢𝑠ℎ = 1.6 X IRB
𝐼𝑖𝑛𝑟𝑢𝑠ℎ = 1.6 X 623.149 = 𝟗𝟗𝟕. 𝟎𝟑𝟖𝐀
51-2
𝑇𝐶𝑠 200: 5
51-3
CALCULO DE LA CORRIENTE DE AJUSTE
51-N COMO EL FS =1.0 SE AJUSTA AL 15% (1.15)
I𝑎𝑗𝑢𝑠𝑡𝑒 = IPC X 1.15
𝐼𝑎𝑗𝑢𝑠𝑡𝑒 = 125.162 𝑥 1.15 = 𝟏𝟒𝟑. 𝟗𝟑𝑨
𝑇𝐶 25: 5 50G
CALCULO PARA SELECCIÓN DE TCs
SE CONSIDERA UN TC DE 25:5 PARA PROTECCION
DE FALLA A TIERRA (SECUANCIA CERO) POR QUE LOS 𝐼𝑃𝐶 𝑋 1.20 = 150.19𝐴
VALORES DE PU DE AJUSTE SON BAJOS. YA QUE SE 𝐼𝑃𝐶 𝑋 1.40 = 175.22𝐴
CONSIDERA EL 10% DE LA CORRIENTE A PLENA
CARGA ( IPC ) CALCULO DE PU
𝐼𝑎𝑗𝑢𝑠𝑡𝑒
IG𝑎𝑗𝑢𝑠𝑡𝑒 = IPC X 0.1 𝑃𝑈 =
𝑅𝑇𝐶
IGajuste= 125.162 X 0.1 = 12.51 143.93
𝐼𝐺𝑎𝑗𝑢𝑠𝑡𝑒
𝑃𝑈 = 40
= 3.59
MOTOR RTC =
25
=5 𝑃𝑈 =
1000HP 5 𝑅𝑇𝐶
CALCULO DE FUSUBLE
12.51 𝐼𝑃𝐶 𝑋 7
𝑃𝑈 = = 𝟐. 𝟓 𝐹𝑈𝑆𝐼𝐵𝐸(𝑅) =
5 100
125.162 𝑋 7
𝐹𝑈𝑆𝐼𝐵𝐸(𝑅) =
POTENCIA = 1000 HP 100
VOLTAJE = 4160 V.
FACTOR DE SERVICIO = 1.0 𝐹𝑈𝑆𝐼𝐵𝐸(𝑅) = 𝟖. 𝟕𝟔 9R
FACTOR DE POTENCIA (COSØ ) = 88%
EFICIENCIA ƞ = 94%