Documentos de Académico
Documentos de Profesional
Documentos de Cultura
kVA por
No Usuario kVA kVA Trafo % USO kVA por kVA kVA Trafo % USO kVA por
Usuarios 1-2 Totales 1φ Usuario 3-4 Totales 1φ Usuario 5-6
1 1.19 1.19 3 39.81 2.75 2.75 3 91.52 3.72
2 0.83 1.66 3 55.41 1.55 3.10 3 103.47 2.28
3 0.71 2.13 3 71.01 1.15 3.46 5 69.26 1.81
4 0.65 2.60 3 86.58 0.96 3.82 5 76.43 1.57
5 0.61 3.06 3 102.15 0.90 4.50 5 90.00 1.42
6 0.59 3.53 3 117.72 0.85 5.09 5 101.74 1.33
6 0.59 3.53 3 117.72 0.85 5.09 5 101.74 1.33
7 0.57 4.00 3 133.35 0.81 5.68 5 113.53 1.26
8 0.56 4.47 3 148.92 0.78 6.25 10 62.53 1.21
9 0.55 4.94 5 98.74 0.76 6.85 10 68.53 1.17
10 0.54 5.40 5 108.09 0.74 7.44 10 74.43 1.14
11 0.53 5.87 5 117.32 0.73 8.03 10 80.29 1.11
12 0.53 6.34 5 126.79 0.72 8.62 10 86.18 1.09
13 0.52 6.81 5 136.19 0.71 9.21 10 92.08 1.07
14 0.52 7.28 5 145.53 0.70 9.80 10 97.97 1.06
15 0.52 7.74 10 77.42 0.69 10.38 10 103.82 1.04
16 0.51 8.21 10 82.08 0.69 10.97 10 109.73 1.03
17 0.51 8.68 10 86.75 0.68 11.56 10 115.59 1.02
18 0.51 9.14 10 91.45 0.68 12.15 15 81.00 1.01
19 0.51 9.61 10 96.10 0.67 12.74 15 84.93 1.00
20 0.50 10.08 10 100.80 0.67 13.33 15 88.86 0.99
21 0.50 10.55 10 105.46 0.66 13.91 15 92.74 0.99
22 0.50 11.02 10 110.19 0.66 14.50 15 96.69 0.98
23 0.50 11.49 10 114.89 0.66 15.09 15 100.60 0.98
DT=Na*0,5 50 DT=Na*0,66 0 DT=Na*0,98
Na 100 Na Na
I.nominal
135
175
205
250
KVA X LONG
TRAYECTORIA TRAMO LONG (m) ABONADOS KVA (div max) Me. Tramo Me. Acum
1 a-b 30 39 38.22 1146.6 1146.6
1 b-c 25 31 30.38 759.5 1906.1
1 c-d 28 8 9.65 270.2 2176.3
2176.3
4051.96
2 a-f 50 32 31.36 1568 1568 0.00197
2 f-g 35 14 14.78 517.3 2085.3 0.00197
2085.3
CALIBRE
% REG= K.REG X M4 Tramo
2.06388 4/0 fp= 0,9
3.348072
4.0828788
4.7407932
0
0
0 4.0828788
0
0
0
0
0
0
0
0
0
3.08896 1/0 fp= 0,9
4.108041
0
0
0
Autor:
tabla eep
5686.36
2 a-h 39 41 40.18 1567.02 1567.02 0.00117
2 h-i 30 12 13.08 392.4 1959.42 0.00117
2 h-j 30 19 19.03 570.9 2530.32 0.00117
2 j-k 40 9 10.52 420.8 2951.12 0.00117
2951.12
K- TRIFÁSICA. 1/(kVA.m)
K- MONOFÁSICA. 1/(kVA.m)
4391.72
CALIBRE
% REG= K.REG X M4 Tramo
1.857492 4/0 fp= 0,9
4.1690376
4.647942
5.611086
6.2917452
6.6530412
0 4.0828788
0
0
0
0
0
0
0
0
0
1.8334134 1/0 fp= 0,9
2.2925214
2.9604744
3.4528104
0
0
0
K- TRIFÁSICA. 1/(kVA.m)
CALIBRE
(AWG) FACTOR DE FACTOR DE
POTENCIA POTENCIA
0.8 0.9
2 0.00185 0.00203
0
0
0
0
0
0
0
0
0
0
1.685502
3.5189154 4/0
3.9780234
4.6459764
5.1383124
0
0
0
K- MONOFÁSICA. 1/(kVA.m)
FACTOR DE FACTOR DE
POTENCIA POTENCIA
0.8 0.9
0.00279 0.00305
0.00182 0.00197
0.00149 0.00159
0.00111 0.00117
conductor % reg
momneto electrico
fases neutro k
kVA usuario
corriente A
trayectoria
longitud m
acumulada
kVAXm
tramo
parcial
calibre
calibre
Nro
TA 20 39 1.188 46.332 926.64 926.64 2 2 AWG 0.005659
AB 18 35 1.188 41.58 748.44 1675.1 2 2 AWG 0.005659
1
BC 35 8 1.829 14.632 512.12 2187.2 2 2 AWG 0.005659
CD 20 3 2.43 7.29 145.8 2333 2 2 AWG 0.005659
0.002299
0.0056591
0.0036195
0.00290679
1173.789157 3.411959
perd. de
potencia
acumulados
kW/tramo
kW
%
Considérese el circuito radial alimentado por el transformador 0706024 de 50 kVA. monofásico de la red
fundadores a 13.2 kV y ubicado en el barrio San Jorge de la ciudad de Manizales (ver figura 10.20). Dicho
transformador está montado en un poste de ferroconcreto de 12 metros a través de un collarín para
transformador y alimenta una red monofásica trifilar (radial) y construción áerea.
El circuito en mención se encuentra en calibre número 2 AWG de cobre aislado en sistema monofásico
trifilar 120 / 240 V y espaciados 10 cm; y alimenta un total de 77 usuarios de estrato 4 clase media, la carga total
del trasnformador es de 77 x 1.118 = 91.476 kVA.
Usando la demanda diversificada para clase media a 8 años mostrada en la tabla 10.14 se requiere:
• Hacer los cálculos de % Reg y % pérdidas.
• Hallar los kW totales de pérdidas para el circuito.
• Hacer un diagnóstico sobre el estado actual de funcionamiento de la red: sobrecargas en tramos y
transformador de distribución, regulación máxima encontrada, costo de las pérdidas en los próximos 10 años
• Establecer unas recomendaciones para mejorar el funcionamiento eléctrico tratando de conservar en
conductor actual.
• Hacer efectivas las soluciones dadas y encontrar para ellas el costo de las pérdidas.
• Para una proyección de 10 años hallar el valor presente de las pérdidas recuperadas.
• Presentar los diagramas con flujos de carga.
dia, la carga total
inicio final longitud m nro de usuarios DMD KVA
𝐷𝑀𝐷𝑛=𝐷𝑀𝐷(1+(𝐼/100)) 〖 ^𝑁 〗
DMDn=DMD(1+(I/100)) DMD X L (m)
DMD 15 años KVA Me Me acumulado conductor k
conductor % reg
momneto electrico
fases neutro k
longitud m
acumulada
kVAXm
tramo
parcial
calibre
calibre
Nro
ACUM
DE 40 20 19.88 795.2 795.2 2 2 AWG 2 0.00305 2.42536 2.42536
EH 28 9 10.52 294.6 1089.8 2 2 AWG 2 0.00305 0.898408 3.323768
1
HI 25 4 6.27 156.8 1246.5 2 2 AWG 2 0.00305 0.4780875 3.8018555
EF 38 8 9.65 366.7 1613.2 2 2 AWG 2 0.00305 1.118435 4.9202905
1613.2 4.9202905
DC 45 16 16.48 741.6 741.6 1/0 1/0 AWG 1/0 0.0027 2.00232 2.00232
CB 50 12 13.08 654 1395.6 1/0 1/0 AWG 1/0 0.0027 1.7658 3.76812
BA 46 7 8.82 405.7 1801.3 1/0 1/0 AWG 1/0 0.0027 1.095444 4.863564
1801.3 4.863564
perd. de
potencia vnom crit reg
corriente A
acumulados
kW/tramo
Vreg.
kW
%
240 2.5
234
228.3246576 87.07 0.645
220.7356757 47.66 0.353
212.3436243 29.53 0.219
217.0904212 44.45 0.329
229.3145712 71.87
220.673723 59.27
209.9411152 42.01
Carga alumbrado pub
momneto electrico
neutro k
kVAXm
tramo
I. NOMINAL
calibre
calibre
Parcia Acum ohmios por km
a-b 8 7 4.0 0.4 4.4 34.9 34.9 1/0 AWG 1/0 0.0 175.0
b-d 20 6 3.5 0.0 3.5 70.6 105.5 1/0 AWG 1/0 0.0 175.0
d-e 20 4 2.6 0.0 2.6 52.0 157.5 1/0 AWG 1/0 0.0 175.0
e-f 13 3 2.1 0.0 2.1 27.7 185.2 1/0 AWG 1/0 0.0 175.0
185.2
a-c 20 46 23.0 0.4 23.4 467.2 467.2 1/0 AWG 1/0 0.0 175.0
c-h 35 46 23.0 0.2 23.2 811.3 1278.5 1/0 AWG 1/0 0.0 175.0
h-i 24 15 7.7 0.2 7.9 190.1 1468.6 1/0 AWG 1/0 0.0 175.0
i-j 20 6 3.5 0.2 3.7 74.2 1542.8 1/0 AWG 1/0 0.0 175.0
1
i-k 16 5 3.1 0.2 3.2 51.8 51.8 1/0 AWG 1/0 0.0 175.0
k-l 15 2 1.7 0.0 1.7 24.9 76.7 1/0 AWG 1/0 0.0 175.0
h-m 16 7 4.0 0.2 4.2 66.9 66.9 1/0 AWG 1/0 0.0 175.0
m-g 15 3 2.1 0.2 2.3 34.7 101.5 1/0 AWG 1/0 0.0 175.0
h-D 25 21 10.6 0.2 10.7 268.3 268.3 1/0 AWG 1/0 0.0 175.0
D-E 22 14 7.3 0.2 7.5 164.1 432.4 1/0 AWG 1/0 0.0 175.0
E-F 23 7 4.0 0.2 4.2 96.1 528.5 1/0 AWG 1/0 0.0 175.0
2434.7 2434.7
a-c 20 47 23.5 0.0 23.5 470.0 470.0 1/0 AWG 1/0 0.0 175.0
c-o 20 39 19.5 0.2 19.7 393.6 863.6 1/0 AWG 1/0 0.0 175.0
o-p 10 28 14.0 0.2 14.2 141.8 1005.4 1/0 AWG 1/0 0.0 175.0
p-q 20 18 9.1 0.2 9.3 186.4 1191.8 1/0 AWG 1/0 0.0 175.0
q-r 10 8 4.5 0.2 4.6 46.5 1238.3 1/0 AWG 1/0 0.0 175.0
r-s 20 4 2.6 0.4 3.0 59.2 1297.5 1/0 AWG 1/0 0.0 175.0
s-t 24 2 1.7 0.4 2.0 48.5 1346.0 1/0 AWG 1/0 0.0 175.0
c-A 20 8 4.5 0.2 4.6 93.0 93.0 1/0 AWG 1/0 0.0 175.0
A-G 23 2 1.7 0.2 1.8 42.3 135.3 1/0 AWG 1/0 0.0 175.0
2 o-z 20 9 4.9 0.0 4.9 98.8 98.8 1/0 AWG 1/0 0.0 175.0
z-B 25 3 2.1 0.2 2.3 57.8 156.6 1/0 AWG 1/0 0.0 175.0
2
p-x 20 8 4.5 0.2 4.6 93.0 93.0 1/0 AWG 1/0 0.0 175.0
x-y 17 2 1.7 0.2 1.8 31.3 124.3 1/0 AWG 1/0 0.0 175.0
q-v 20 8 4.5 0.2 4.6 93.0 93.0 1/0 AWG 1/0 0.0 175.0
v-w 17 2 1.7 0.4 2.0 34.3 127.3 1/0 AWG 1/0 0.0 175.0
r-u 28 2 1.7 0.0 1.7 46.5 46.5 1/0 AWG 1/0 0.0 175.0
1936.0 1936.0
% reg
perd. de potencia vnom crit reg
corriente A
kW acumulados
acumulada
Resistencia
kW/tramo
parcial
Vreg.
240 2.5
234.0
0.0 0.9 0.9 231.8 70.6 197.0 197
0.0 1.6 2.5 226.0 70.0 339.5 536.52
0.0 0.4 2.9 219.5 23.9 27.2 563.7
0.0 0.1 3.0 212.8 11.2 5.0 568.67
219.5
0.0 0.1 0.1 219.2 9.8 3.0 3.0322
0.0 0.0 0.2 218.9 5.0 0.7 3.7784
226.0
0.0 0.1 0.1 225.7 12.6 5.0 5.0468
0.0 0.1 0.2 225.3 7.0 1.4 6.4918
226.0
0.0 0.5 0.5 224.8 32.4 52.0 51.962
0.0 0.3 0.9 222.9 22.5 22.1 74.065
0.0 0.2 1.0 220.6 12.6 7.3 81.319
4.8 4.8
Tipo de
fusible
(K)
(A)
4
Carga alumbrado pub
momneto electrico
neutro k
kVAXm
tramo
calibre
calibre
ACUM
0-1 20 32 50.8 0 50.8 1016 1016 2/0 AWG 2/0 0.00075669
1-2. 20 27 44.61 0 44.61 892.2 1908.2 2/0 AWG 2/0 0.00075669
2-3. 20 16 29.4 0 29.4 588 2496.2 2/0 AWG 2/0 0.00075669
3-4. 20 11 23.35 0 23.35 467 2963.2 2/0 AWG 2/0 0.00075669
4-5. 20 7 16.19 0 16.19 323.8 3287 2/0 AWG 2/0 0.00075669
5-6. 20 3 10.15 0 10.15 203 3490 2/0 AWG 2/0 0.00075669
2
2
% reg
perd. de potencia vnom
corriente A
kW acumulados
acumulada
I. NOMINAL
Resistencia
kW/tramo
parcial
Vreg.
240
%
ohmios por km 220
240 0.0002988 0.768797 0.768797 218.3086465 133.3154 318.634 318.634
240 0.0002988 0.6751188 1.4439159 215.1564533 117.0709 245.714 564.348
240 0.0002988 0.4449337 1.8888496 211.0924716 77.15499 106.723 671.072
240 0.0002988 0.3533742 2.2422238 206.3593059 61.27786 67.3192 738.391
240 0.0002988 0.2450162 2.48724 201.2266547 42.48773 32.3638 770.755
240 0.0002988 0.1536081 2.6408481 195.9125644 26.63684 12.7203 783.475
2.6408481 783.475
1.4439159 215.1564533 564.348
0.0009432 0.8072 2.2511159 210.3130323 52.48639 155.901 720.249
0.0009432 0.57513 2.8262459 204.3690689 37.39655 79.144 799.393
0.0009432 0.330952 3.1571979 197.9167331 21.51942 26.2069 825.6
1.713282 261.252
crit reg
2.5