Es preciso indicar que en el referido Expediente Técnico Final se incluye también el Estudio Final de la
Coordinación de Protecciones por Ampliación de Potencia Contratada de 250 kW a 1000 kW del
Suministro Eléctrico Existente de MT del Contrato N° 97702 conforme lo requerido por su despacho en
la carta de la referencia.
En tal sentido, solicitamos a su digno despacho proceda a la respectiva revisión del Expediente Técnico
Final y proceder a otorgarnos el Certificado de Conformidad respectivo para iniciar los trámites
necesarios ante su despacho para el Inicio de Obra respectivo.
-------------------------------------------------
ANTHONY HERBERT ANDRADE VASQUEZ
INGENIERO ELECTRICISTA PROYECTISTA
CIP 99580.
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
EXPEDIENTE TECNICO
FINAL
Elaborado por:
Anthony Herbert Andrade Vásquez
Ingeniero Electricista – CIP 99580
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
INDICE
1. MEMORIA DESCRIPTIVA
1.1. GENERALIDADES
1.2. PROPIETARIO
1.3. UBICACIÓN
1.4. PROFESIONAL RESPONSABLE
1.5. ANTECEDENTES Y JUSTIFICACION DEL PROYECTO
1.6. ALCANCES DEL PROYECTO
1.7. TOPOGRAFIA DEL PROYECTO
1.8. CONDICIONES AMBIENTALES
1.9. DESCRIPCION DEL PROYECTO
1.10. OBRAS CIVILES PREVIAS
1.11. EQUIPAMIENTO DE REDES DE MEDIA TENSION PARTICULAR
1.12. MAXIMA DEMANDA
1.13. BASES DE CALCULO
1.14. NORMAS TECNICAS
2. ESPECIFICACIONES TECNICAS DE SUMINISTROS DE EQUIPOS Y MATERIALES
3. ESPECIFICACIONES DE MONTAJE ELECTROMECANICO
4. CALCULOS JUSTIFICATIVOS
5. ESTUDIO DE COORDINACION DE PROTECCIONES
6. METRADO Y PRESUPUESTO
7. CRONOGRAMA DE EJECUCION DE OBRA
8. FINANCIAMIENTO
9. PLANOS
10. ANEXOS
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
1. MEMORIA DESCRIPTIVA
1.1. GENERALIDADES
El presente documento tiene por objetivo actualizar el proyecto de Media Tensión para la
ampliación de la Potencia Contrada de 250 a 1000 kW del Suministro Eléctrico existente
de Media Tensión signado con el número de contrato N° 97702 de propiedad de Clínica
VALLE SUR AUNA cuyo actual suministrador es la Empresa Sociedad Eléctrica del Sur
Oeste S.A. Concesionario de Distribución y Comercialización de Energía Eléctrica en la
Región Arequipa.
1.2. PROPIETARIO
1.3. UBICACIÓN
Departamento : Arequipa
Provincia : Arequipa
Distrito : Cercado
Dirección : Avenida la Salle 116 – 118
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
ANTECEDENTES
La Clínica Valle Sur AUNA S.A. tiene actualmente un suministro eléctrico existente en
Media Tensión con una potencia contratada de 250 kW cuyo número de contrato
corresponde al 97702, dicho suministro de media tensión cuenta con una Subestación
Particular signada por SEAL con el código SEP 4309 que se encuentra equipada con un
transformador trifásico DELCROSA de 500 KVA de 10000/400-230 voltios además cuenta
con una celda de llegada de protección con seccionador de potencia tipo manija con
fusibles de protección HH de 70 Amperios, además cuenta con una celda de
transformación que alimenta con barras aéreas los bushin de Media Tensión del
transformador trifásico DELCROSA de 500 KVA. Actualmente la referida Subestación
Particular SEP 4309 suministra energía eléctrica a la Torre existente de la Clínica Valle
SUR AUNA teniendo una demanda máxima de 163.92 kW
JUSTIFICACION
Bajo la actual coyuntura del COVID-19 y ante la falta de oferta hospitalaria los directivos
de la Clínica Valle Sur AUNA han tomado la decisión de efectuar la Ampliación de sus
Instalaciones habiendo construido una Torre Adicional de 7 pisos con dos sótanos al
costado de la Clínica Existente por lo que se requiere la ampliación de la actual potencia
contratada de 250 kW a 1000 kW, motivo por el cual conforme a lo dispuesto en la Carta
SEAL GG-TEP/387-2021, en el presente Expediente de Media Tensión se está
procediendo a la modernización de la Sub Estación de Distribución Particular signada por
SEAL con el código SEP 4309 que incluye la adquisición y montaje de un nuevo
Transformador de Distribución del tipo Seco de 1600 KVA de 10000/380-220 voltios y la
Adquisición y Montaje de una Nueva Celda de Llegada de Protección con Seccionador de
Potencia e Interruptor en Vacío 24 KV, 630 A, 20 KA, 60Hz, además de la adquisición y
montaje de dos celdas de Salida de Protección con Seccionador de Potencia 24 KV, 630
A, 20 KA, 60Hz y fusibles de protección HH de 100 Amperios, una de las Celdas de Salida
Protección para el nuevo Transformador de Distribución del tipo Seco de 1600 KVA y la
otra Celda de Salida de Protección para el Transformador DELCROSA existente de 500
KVA hasta que llegue el Nuevo Transformador de Distribución del tipo Seco de 1600 KVA
quedando la Segunda Celda de Salida de Protección finalmente como Reserva
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle Sur AUNA
Cabe señalar que una vez culminadas las obras civiles comentadas en los acápites anteriores recién se podrá efectuar el Montaje Electromecánico de
las Celdas y del Transformador Nuevo, debiendo quedar la Distribución del Equipamiento Electromecánico en forma definitiva conforme se detalla en
la vista de planta de la Subestación Proyectada en la que se incluye el nuevo equipamiento Electromecánico de la SEP 4309 de la Clínica AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
La máxima demanda Proyectada final de la Sub Estación Particular de la Clínica Valle Sur AUNA en
media tensión de 10kV es 837.11 KW :
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
PARAMETRO INICIAL
La elaboración del proyecto se ha desarrollado en concordancia con las siguientes normas técnicas
legales vigentes:
• Código Nacional de Electricidad – Utilización 2006 y sus modificatorias.
• Código Nacional de Electricidad Suministro 2011.
• Reglamento Nacional de Edificaciones vigente.
• Norma de Procedimientos para la elaboración de proyectos y ejecución de obras en
sistemas de utilización en media tensión de zonas de concesión de distribución, RD
18-2002-EM-DGE
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
SEGURIDAD PERSONAL
La seguridad personal está asegurada por una serie simple de cerraduras enclavadas
mecánicamente de acuerdo a las normas CEI 17-6 Y IEC 298, impidiendo cualquier
operación incorrecta. La funcionalidad de las cerraduras mecánicas proviene de su
propia simplicidad, y estructura única que permite al interruptor ubicarse en cualquiera
de las tres posiciones: Abierto, Cerrado y aterrado.
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
2. CARACTERISTICAS ESPECIFICAS
Tensión Nominal : 24 KV
Relé de protección :
SEPAM S60 : Digital autoalimentado 50-51/50N-51N +
SENSOR Diferencial + Relé de mínima
Frecuencia 81L y derivada de frecuencia 81R
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Nota:
El modelo de la celda de Llegada de Protección, es invertido
(Parte superior está el interruptor y la parte inferior está el
Seccionador), esta celda ira acoplada mediante barras de
cobre con las celdas de Salida (Seccionador- Fusible)
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Tensión Nominal : 24 KV
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
ACCESORIOS
PRUEBAS EN LABORATORIO CON PRESENCIA DE REPRESENTANTE DEL CLIENTE POR CUENTA DEL FABRICANTE
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
El propietario contara con los siguientes equipos de protección y maniobra antes de la puesta
en servicio y para maniobras futuras, los cuales se ubicarán cerca de la Subestación.
a. Banco de Maniobra
De fibra de vidrio u otro material, deberá soportar un peso mayor de 100 kg. Con las siguientes
características:
Dimensiones : 0.8 x 0.8 m Aislamiento : 30 kV
b. Pértiga
Para trabajo pesado de material aislante de alta resistencia mecánica a la tracción y la flexión,
con espiga para accionar los seccionadores unipolares sin carga, con las siguientes
características:
Longitud : 1.6 m
Aislamiento : 30 kV
c. Guantes Aislantes
De tamaño grande, Nº 10, de jebe u otro aislante para uso eléctrico de las siguientes
características:
Aislamiento : 30kV
Clase : 3
d. Balde con Arena.
De material plástico, de pared gruesa y alta resistencia mecánica, con asas para suspensión
de plástico.
Con una capacidad de aproximadamente 10 Kg de arena seca.
e. Zapatos.
Un par de la talla del operador, con suela y tacones de jebe de alto aislamiento eléctrico, los
que deberán ser clavados con clavijas de madera o cocidos, no se permitirán clavos o partes
metálicas.
Aislamiento : 30 kV
f. Lentes de Seguridad.
Anteojos de Policarbonato 56 CL, con protección lateral y patilla fija, la montura y las lunas
serán a la medida de cada trabajador.
Se fabricarán según Norma Internacional ANSI Z87.1-1989.
g. Casco.
El casco será fabricado de un material aislante para uso eléctrico de una tensión nominal no
menor de 30 kV. y un nivel de aislamiento de 150 kVpico. Son diseñados para reducir el peligro
de explosión a conductores de alto voltaje.
Tipo : 1
Clase : E
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
h. Placa de señalización.
En cada celda llevará una placa de señalización de 300 x 600 mm empernados en las puertas
y de 80 x 200 mm para el símbolo de presencia de corriente eléctrica, construidas de planchas
metálicas de 1/16" de espesor y leyenda "ALTA TENSION PELIGRO DE MUERTE", en letras
y símbolo de color rojo con fondo amarillo.
i. Revelador de tensión.
Con acoplamiento de a pértiga o bastón de maniobra mediante un adaptador universal (CS-U).
Tipo CT con llave conexión/desconexión/prueba. Para una tensión nominal de hasta 36kV.
Fabricado según norma IEC-61243-1.
Características técnicas. Dimensiones : Ø60 x 180mm
Temperatura de trabajo : -5o a 70oC.
Funcionamiento: Indicación sonoro luminosa mediante LED’s de alta luminosidad y
señal acústica de 80 dB +/-1m de distancia.
Alimentación : Batería de 9 VCC
Peso aproximado : Aparato 290 gr.
Frecuencia de Trabajo : 50/60 Hz.
2.4. SISTEMA DE PUESTA A TIERRA PARA LA SUBESTACION PARTICULAR SEP 4309.
La sub estación particular SEP 4309 de propiedad de la Clínica Valle Sur AUNA, es una
Subestación existente de Media Tensión (10000 voltios) a Baja Tensión (380/220 voltios) que
actualmente tiene dos pozos de puesta a tierra que se encuentran interconectados
equipotencialmente, pero separados físicamente a una distancia mayor a 6 metros, a un pozo
de puesta a tierra se conecta toda la aparamenta eléctrica de media tensión con cable desnudo
de cobre temple blando de 35 mm2 y al pozo de puesta a tierra de baja tensión se conecta el
neutro del transformador existente con cable NH-80 de 120 mm2.
Conforme el protocolo de Medición del pozo existente de Puesta a Tierra de Baja Tensión de
la Subestación particular SEP 4309 proporcionado por el Jefe de Mantenimiento de la Clínica
Valle Sur AUNA se ha considerado Repotenciar el mismo, para lo cual se ha considerado
construir un nuevo pozo de Puesta a Tierra de Baja Tensión adicional al existente, el mismo
que se encontrará frente a la sala de Celdas de la Subestación particular SEP 4309, al cual se
conectará el neutro del nuevo transformador de 1600 KVA con un cable NH-80 de 185 mm2 a
través de una Barra Equipotencial de Baja Tensión concordante con el Proyecto de Baja
Tensión proporcionado por la Clínica AUNA a través de la Empresa Supervisora JLV.
Respecto al Pozo de Puesta a Tierra de Media Tensión de la Subestación particular SEP 4309
proporcionado por el Jefe de Mantenimiento de la Clínica Valle Sur AUNA se ha considerado
Repotenciar el mismo, para lo cual se ha considerado un nuevo pozo de Puesta a Tierra de
Media Tensión adicional al existente, el mismo que se encontrará ubicado a 6 metros al
costado del PMI existente correspondiente a la Estructura de Media Tensión codificada por
SEAL con el Número 18271, estructura y/o poste de Media Tensión que corresponde a nuestro
actual punto de entrega del suministro Eléctrico existente de Media Tensión con número de
contrato 97702 de Clínica VALLE SUR AUNA.
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
La Resistencia de puesta a tierra de cada pozo en forma individual no debe ser mayor a 15
ohmios, para lo cual se procederá al tratamiento electrolítico del terreno circundante al
electrodo, mediante cemento conductivo similar al CONDUCRETE en función de la medición
de la Resistividad del Terreno. Los materiales a utilizar para la puesta a tierra son:
a. Conductor de Puesta a Tierra:
Es de cobre electrolítico de 99.99% de pureza, conductibilidad 100% IACS, cableado
concéntrico, temple blando desnudo fabricado bajo las Normas ITINTEC P.370-220,
P.370-221, P.370-223, DGE-019-CA-2/83.
b. Electrodo de Puesta a Tierra.
Será de Cobre electrolítico de ¾” de pulgada de diámetro y 2.4 metros de longitud.
Norma de referencia: UL- 467, NBR 13571, NTP 370.056
c. Borne para Electrodo de Puesta a Tierra
El conexionado entre el electrodo de puesta a tierra de ¾” de pulgada de diámetro, con
cables de cobre calibre de 35 a 185 mm2, se utilizarán grampas de bronce de alta
conductividad eléctrica y alta resistencia a la corrosión; incluye tuercas y arandelas de
presión de bronce silicoso DURIUM (ASTM B99).
Norma de referencia: UL- 467, NBR 13571, NTP 370.056
d. Grapas: Para conectar elementos derivados, se utilizarán grampas perno partido
encobrizado.
e. Caja Registro: Son de concreto con una tapa de concreto armado vibrado de 40 mm de
espesor. Llevan el símbolo de puesta a tierra y cumplen las siguientes características.
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Para el sistema trifásico tendremos el CALCULO POR CAPACIDAD DE CORRIENTE del sistema
usando como referencia la máxima demanda proyectada por el propietario y considerando la potencia
Contratada con el Suministrador SEAL:
𝑀𝐷
𝐼=
√3 ∗ 𝑉 ∗ 𝑐𝑜𝑠∅
Dónde:
MD = Máxima Demanda (kW)
V = Tensión Nominal (kV)
cos(Ø) = Factor de Potencia de Carga (0.9)
PI = Potencia Instalada
Resultados:
PI = 1046.39 kVA
MD = 837.11 kW
V = 10.00 kV
In = 60.485 A
Factor de Diseño = 1.25
Factor de Profundidad (kp) = 0.98
Factor de Agrupamiento (ka) = 100
Id = 77.15 A (Corriente Corregida)
Conclusión:
Por lo tanto, según la capacidad de corriente del conductor elegido, será de tipo N2XSY de tensión de
aislamiento en 8.7/15 kV de sección del conductor de 3 – 1 x 25 mm2.
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Donde la máxima caída de tensión deberá ser menor que el 5% y además tenemos el conductor
seleccionado por capacidad de corriente de 3 – 1 x 25 mm2 N2XSY (8.7/15 kV) en configuración
unipolar con separación de 7cm (Según fabricante) entre ellos para una tensión de 10 kV.
𝑅𝑓 = 𝑅𝑖 ∗ (1 + 𝛼(𝑡𝑓 − 𝑡𝑖 )
Rf = 0.897 Ohm/km
Ri = 0.727 Ohm/km
α = 0.0039
Tf = 80 °C
Ti = 20 °C
X = 0.296 Ohm/km (Configuración Lineal Horizontal con Separación de 7 cm)
ΔV = 14.34 V (% ΔV = 0.143 %)
In = 60.485 A
Id = 77.15 A (Corregida)
L = 150.00 m (0.15 km)
Rf = 0.897 Ohm/km
X = 0.285 Ohm/km
Cos (Ø) = 0.80, Sen (Ø) = 0.60
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Los cables de energía están expuestos a condiciones anormales de operación, como son las altas
corrientes debido a sobrecargas o cortocircuitos.
El calor que se genera debido al Efecto Joule (I²R) puede ocasionar un daño parcial o total a los
componentes del cable (principalmente aislamiento); este calor es función de la magnitud de la corriente
y de su duración de falla.
El dimensionamiento térmico de cables por cortocircuito tiene por objeto determinar las mínimas
secciones que los cables deben soportar por tiempos muy breves y el calor generado por el paso de
una corriente de cortocircuito (Dato de SEAL en el punto de diseño se tiene una potencia de
cortocircuito de Scc de 43.25 MVA por lo cual la corriente de cortocircuito en el punto de diseño
será de 2.5 kA).
Considerando la Norma IEC 60949-1988, tenemos que la capacidad del conductor de cobre frente a
los cortocircuitos es de:
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
143.1 ∗ 𝑆
𝐼𝐴𝐷 =
√𝑡
√𝑡 ∗ 𝐼𝑐𝑐 √𝑡 ∗ 25 ∗ 103
𝑆(𝑚𝑚2) = =
143.1 143.1
Por temas de dimensionamiento el conductor 1-1x25mm2 N2XSY (8.7/15 kV) sería la sección minina
seleccionada por capacidad de cortocircuito (térmico – efecto joule).
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Para protección contra sobretensiones que pudieran afectar al transformador Seco de 1600 KVA se ha
considerado un juego de pararrayos poliméricos que proteja al equipo de sobretensiones peligrosas, a
continuación, se detalla las premisas de cálculo y selección de los mismos.
PREMISAS:
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
𝑉𝑛 = 𝐾𝑒 ∗ 𝑉𝑚𝑎𝑥
2 ∗ 𝑁𝐵𝐴
𝐼𝑑 =
𝑍
𝑈𝑚𝑎𝑥
𝐿𝑓 = 𝐺𝑎 ∗ (𝐹ℎ ∗ )
√3
𝐹ℎ = 1 + 1.25 ∗ (ℎ − 1000) ∗ 10−4
RESULTADOS:
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
PREMISAS
Tension Nominal del Pararrayo Vn 10 kV
Tension Maxima del Sistema Vmax 12 kV
Impeancia de Linea Z 1.420 Ω
Nivel Basico de Aislamiento NBA 91.908 kV
Factor Conexión a Tierra (Sist. N a T) Ke 0.8
Grado de Aislamiento (IEC 60815) Ga 20 mm/kV
Altitud h 2500 m.s.n.m
Tension Maxima en 20% a Vn U.max 12 kV
RESULTADOS
Tension Nominal del Pararrayos Vnn 9.6 kV
Corriente Nominal de Descarga Pararrayos Id 129.492 kA
Factor de Correccion de Altitud Fh 1.1875
Linea de Fuga Minima del Pararrayos Lf 164.740 mm
36
39
45
48
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
En este alcance del presente estudio se hará la coordinación de protecciones del sistema
eléctrico de la Clínica Valle Sur AUNA, el cual comprende los siguientes equipos eléctricos:
- Transformador de Potencia de 1600 kVA, 10/0.38 kV, Dyn5, Zcc de 6%, ANAF.
- Celdas de Salida y Protección 24 kV, 630 A, 20 kA, Seccionador Bajo Carga Porta
Fusible, Fusible Tipo HH de 160 A, 24 kV; adicional hay un Relé de Protección a
Tierra ORION iPR-D.
- Tablero General TG-N (Baja Tensión) con Interruptor de protección de Estado Sólido
DMX3 4000 H Legrand.
Los datos que emplearse para la implementación del sistema son el modelo del sistema de
suministro de la SEAL para lo cual se adjuntó los valores de potencia de corto circuito, tanto
para fallas trifásicas como monofásicas.
Skss (MVA) Ikss (kA) X/R Skss (MVA) Ikss (kA) X/R
El modelo de Barra Equivalente se tendrá una Potencia de Cortocircuito de 43,92 MVA, con
corriente pico de falla de 4286 A, corriente simétrica de falla 2535 A (Con el cual se hacen
los estudios de coordinación de protección).
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
La Celda de Llegada y Protección está compuesta por un Seccionador en SF6 (24 kV, 630
A, 20 kA) y un Interruptor en Vacío (características: 24 kV, 630 A, 20 kA x 3 seg; Tiempo de
despeje de falla de 40 mseg, Tiempo cierre de 55 mseg).
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Fusible Tipo HH de 80 A y 30 A , 24 kV
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
El Cable de Media Tensión es del tipo N2XSY (8.7/15 kV) de sección de 25mm2 (unipolar o
1-core) cuyas características en el modelo son las siguientes:
- Hilos: 7
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
• OBJETIVOS
- Perfiles de Tensión: Obtener los valores de tensión, en diferentes barras del sistema
eléctrico en el escenario de operación normal, comparar los rangos de tensión
recomendados por normas y fabricantes estén dentro de lo establecido por la Norma
Técnica de Calidad del Servicio Eléctrico (NTCSE).
• CRITERIOS DE OPERACIÓN
Para evaluar los resultados obtenidos de las simulaciones se usará el programa DIGSILENT,
se aplican los siguientes criterios de aceptación, los cuales están alineados por la NTCSE
aprobada por el D.S. N 020-97-EM.
- Perfiles de Tensión: Se evalúa los perfiles de tensión del sistema eléctrico según las
siguientes tolerancias:
• ESTANDARES DE REFERENCIA
NORMAS DE REFERENCIA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
➢ IEC 60439-1
➢ NTCSE 1997-10-09
• ESCENARIO DE OPERACIÓN
El propósito del estudio de flujo de potencia es determinar las tensiones, corriente y flujo de
potencia activa y reactiva en el sistema eléctrico, para lo cual se trabajará con un escenario
de operación a plena carga (máxima demanda) o llamado comúnmente como Escenario de
Operación Normal. Donde se dispone de los interruptores y seccionadores cerrados y
operación del transformador en forma normal a máxima demanda de la carga (837 kW, f.d.p.
de 0.80).
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Para el único escenario de evaluación de Máxima Demanda (837 kW, f.d.p. de 0.8) que
contempla la operación normal. Del Estudio del Flujo de Potencia Balanceado se muestra el
resumen a continuación del nivel de tensión (%) y potencias calculadas en las barras del
sistema eléctrico.
Nivel
Nivel
de Potencia Potencia Potencia
de Corriente
Descripción Tensión Activa Reactiva Total %FP
Tensión (A)
Nom. (kW) (kVar) (kVA)
(%)
(kV)
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Celda
10.00 100.0 62.0 837.0 671.0 1073.0 0.78
Llegada
Celda
10.00 100.0 62.0 837.0 671.0 1073.0 0.78
Salida
Tablero
General 0.38 97.5 63.0 837.0 628.0 1046.0 0.80
TG-N
CARGABILIDAD
Nivel de
Ampacidad Cargabilidad
Descripción Tensión
(A) (%)
(kV)
Seccionador
630.0 24.00 30.0
IM6-TD
Interruptor
630.0 24.00 30.0
WL/r24kV
Cable M.T.
25mm2
Fusible HH
100.0 24.00 61.9
100A
Transformador
92.48/2433.83 10.00/0.38 67.0
1600 kVA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
• RECOMENDACIONES
• OBJETIVOS
El objetivo es determinar los niveles de corto circuito en las diferentes barras del sistema
eléctrico, si la capacidad de apertura de los dispositivos de protección y maniobra estarán
en condiciones de despejar la falla para protección del personal y de las instalaciones. Como
objetivos específicos se tienen:
- Determinar la corriente de corto circuito asimétrico y pico en una falla trifásica para
verificar la capacidad de las barras en las celdas de media tensión, así mismo evaluar
las variaciones de las corrientes de corto circuito en las distintas barras de acuerdo
a normas de fabricación.
• CRITERIOS DE DISEÑO
El interruptor está diseñado para despejar (apertura) la falla trifásica franca (solida) al 100%
de la capacidad interrupción nominal.
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Los siguientes ítems nos describen los criterios a tomar de acuerdo a la normativa de
fabricación de cada dispositivo:
½ ciclo 30 ciclos
½ Ciclo
(Red (Red Régimen
(Red Subtransitoria)
Transitoria) Permanente)
Capacidad de
Interruptor Alta Tensión Capacidad C&L -
Interrupción
Capacidad de
Interruptor Baja Tensión - -
Interrupción
Capacidad de
Fusibles - -
Interrupción
Capacidad de
Centros de Fuerza/MCC - -
Interrupción
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
- NORMA IEC 60909: En los cálculos de corto circuito para la norma IEC 60909, se
aplica un factor de tensión c para ajustar el valor de la fuente de tensión equivalente
para los cálculos de corriente mínima y máxima.
Las Normas IEC 60909, utilizan las siguientes definiciones, que son relevantes en los
cálculos y resultados del software:
• Corriente de corto circuito simétrica inicial (I"k): Este es el valor RMS del
componente simétrico de corriente alterna de una corriente de corto circuito
disponible aplicable en el instante de corto circuito si la impedancia
permanece en el valor de tiempo cero.
• Corriente de corto circuito de pico (ip): Este es el valor instantáneo máximo
posible de la corriente de corto circuito disponible.
• Corriente de ruptura simétrica de corto circuito (Ib): Este es el valor RMS
de un ciclo integral de la componente de corriente alterna simétrica de la
corriente de corto circuito disponible en el instante de separación de contacto
del primer polo de un dispositivo de conmutación.
• Corriente de corto circuito en estado estacionario (Ik): Este es el valor
RMS de la corriente de corto circuito, que permanece después de los
fenómenos transitorios.
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Making ip
Making ip
Breaking Ib,symm
Fusibles
Ib,asymm (*) Ib,asymm
• REFERENCIAS
NORMATIVA:
- IEEE Std. 241 Recommended Practice for Electric Power Systems in Commercial
Buildings.
TERMINOLOGIA:
- Falla trifásica: Al ser esta la de mayor intensidad se tomará esta falla para la
verificación de la capacidad de los equipos instalados.
- Falla Bifásica a tierra: corriente de cortocircuito con más frecuencia por lo que se
deberá evaluar para el estudio de coordinación de protecciones.
- Falla monofásica a tierra: Esta es la más frecuente de todas por lo que deberá ser
evaluada.
- Zona Transitoria: A continuación del anterior y que se prolonga hasta 500
milisegundos.
- Zona Sub-transitorio: Corresponde a los 10 ó 20 primeros milisegundos del defecto.
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
• ESCENARIO DE CORTOCIRCUITO
El objetivo del escenario es determinar los niveles de corriente de corto circuito simétrico,
asimétrico y pico en las diferentes barras del sistema eléctrico.
• RESULTADOS
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Estos resultados dan una vista panorámica del corto circuito trifásico, bifásico y monofásico
cuando se tiene el escenario de operación normal de máxima demanda, a continuación, se
muestra el cuadro resumen del estudio de corto circuito según norma IEC 60909.
Celda
10.00 IEC 2.535 2.534 2.534 2.535
Llegada
Celda de
10.00 IEC 2.532 2.532 2.532 2.532
Salida
Tablero
0.380 IEC 30.232 28.547 29.186 26.105
General
El interruptor de potencia (Media Tensión) WL/r24kV que actuara con el relé de protección
SEPAM S60, tiene una capacidad de corto circuito de 20 kA x 3 seg, y tiene un poder de
apertura (interrupción) de 40 kA, comparando los niveles de fallas (monofásica, bifásica y
trifásica) se observa que el interruptor se encuentra sobredimensionado y por lo cual no
habría inconvenientes de seguridad.
Estos resultados son solo para el caso de fallas trifásicas según la metodología ANSI/IEEE
C37, para lo cual se analizarán la corriente de corto circuito simétrica, asimétrica y pico en
el siguiente cuadro:
kV kA kA kA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Celda
10.00 ANSI 2.535 3.645 6.204
Llegada
Celda de
10.00 ANSI 2.532 3.622 6.170
Salida
Tablero
0.380 ANSI 25.195 36.153 61.558
General
El interruptor de potencia (Media Tensión) WL/r24kV que actuara con el relé de protección
SEPAM S60, tiene una capacidad de corto circuito de 20 kA x 3 seg, y tiene un poder de
apertura (interrupción) de 40 kA, comparando los niveles de fallas (simétrica y asimétrica)
por la metodología ANSI/IEEE C37, se observa que el interruptor se encuentra
sobredimensionado y por lo cual no habría inconvenientes de seguridad.
• OBJETIVOS
El objetivo principal es disponer del sistema de protección eficaz contra eventos no deseados
en condiciones de falla del sistema eléctrico, aislando las fallas (despeje) en el menor tiempo
posible, y no comprometer al resto del sistema en sus operaciones que pueden poner en
peligro al ser humano como primera instancia y a los equipos eléctricos como segunda
instancia.
Este estudio permitirá definir los ajustes adecuados de los dispositivos de protección, con la
finalidad de garantizar el cumpliendo con los requisitos de la filosofía de protección como
son: selectividad, confiabilidad, sensibilidad, rapidez y simplicidad.
• CRITERIOS DE DISEÑO
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
• REFERENCIAS
- ANSI/IEEE Std. 242 (Buff book) Recommended Practice for Protection and
Coordination of Industrial and Commercial Power System.
- ANSI/IEEE std. 399 (Brown Book) Recommended Practice for Industrial and
Commercial Systems Analysis.
- IEEE Std. 141-1993 (Red book) Electric Power Distribution for Industrial Plants.
- IEEE Std. C 57.91 Distribution Transformer Loss of Life Evaluation.
- National Electrical Code 2017 (NEC).
- Código Nacional de Electricidad (Perú).
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
• DEFINICIONES
• ANALISIS DE RESULTADOS
En coordinación con el CLIENTE, se entrega las configuraciones del relé de protección, para
el Relé SEPAM S60 y ORION iPR-D (Media Tensión) e Interruptor de Estado Sólido DMX3
4000 H (Baja Tensión).
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
El modelo y capacidad del fusible, interruptor fueron realizados en un diagrama unifilar para
realizar el programa de validación DigSILENT (Media Tensión) y ETAP (Baja Tensión), se
realizarán graficas de coordinación de protecciones para cada nivel de tensión y sus ajustes.
La protección de sobre corriente de fases 50/51 (Fases) son habilitadas como las funciones
Ip (51) y la I> (50), donde se tomara la función 51 será una curva IEC extremely inverse con
corriente primario de 240 A.prim y un time dial de 0.05, la función 50 será una curva de
tiempo definido con un pickup de 780 A.prim y un time setting de 0.01 seg (0.03 seg); el
fusible Tipo HH 80 A se establece como respaldo de protección de fases de fallas
trifásicas.
La protección de sobre corriente de tierra en el Relé SEPAM S60, 51N (Tierra) está habilitada
como las funciones Iep (51N), donde se tomara la función 51N será una curva de tiempo
definido con una curva IEEE definite inverse, current setting de 30 A.prim y un time dial de
0.5. Para el relé ORION iPR-D se tomara como función de 51N con una curva IEEE definite
inverse, current setting de 25 A.prim con time dial de 0.5.
El tablero general TG-N en baja tensión 380/220 V, el cual cuenta con un interruptor de
estado sólido donde estarán habilitadas las protecciones (Térmica y Magnética, Magnética)
donde las funciones térmicas y magnéticas son:
El interruptor de estado sólido DMX3 4000 H y su módulo de protección MP4 LSIg, tienen la
siguiente terminología:
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
La protección térmica y magnética en este equipo son regulables, para lo cual se realizará
un ajuste de las protecciones para las 3 zonas de ajustes.
Instantáneo: Ii (2 – 15)
Para lo cual se seleccionarán los pasos de cada configuración y se deberá de hacer cálculos
selectivos con ayuda del programa ETAP para una correcta coordinación con el fusible de
protección del transformador 1600 kVA, 10/0.38 kV.
In = 2000 A
Ir = 0.9 * In = 1800 A
Isd = 3 * Ir = 5400 A
Ii = 7 * In = 12600 A
tr = 30 seg
Ig = 0.2 * In = 400 A
tg = 0.2 seg
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
• AJUSTES DE PROTECCIONES
Se presenta a continuación una relación en un cuadro de los ajustes de protección del relé
de protección SEPAM S60 (Fases y Tierra), relé de protección ORION iPR-D (Tierra) y del
interruptor de estado sólido DMX3 4000 H (Fases y Tierra).
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
ORION
SEPAM S60
iPR-D
ANSI, Función
FASES TIERRA TIERRA
Range - - - -
Delay
Setting - - - -
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Equipo
Cargas en Baja Tensión
Protegido
Nivel de
0.38 (380/220 V)
Tensión (kV)
Corriente
2000.00
Nominal (A)
FASES TIERRA
ANSI, Función
Ir Tr Isd Tsd Ii Ig Tg
• CONCLUSIONES Y COMENTARIOS
- Para la protección general en media tensión de la celda de llegada 10 kV (protección
del cable de media tensión y transformador) se implementa la protección 50P/51P y
51N en el relé de protección SEPAM S60.
- Para la protección del transformador se realiza en la celda de salida 10 kV (protección
del transformador) se usa el fusible 24 kV tipo HH de 80 A.
- Para la protección de las cargas eléctricas en baja tensión 380 V se usará un
interruptor de estado sólido modelo DMX3 4000 H junto con su unidad de protección
electrónica MP4 LSIg.
- Se escogió el relé SEPAM S60 para implementación a futuro de la protección por
frecuencia (81) para el Esquema de Rechazo de Carga por Mínima Frecuencia
(COES) tanto para la protección por umbral 81U / 81O y para protección derivativa
81R.
- El relé ORION iPR-D solo tiene funciones de protección a tierra (51N/51G y
50N/50G), viene integrado en las Celdas de Salida y Protección.
- Para un futuro se plantea la instalación de protección diferencial del transformador
de potencia tanto para fases y tierra (67P / 67N), y poder realizar el monitoreo de
descargas parciales o fallas internas del transformador.
- El valor de fusible que se recomienda en el punto del Trafomix debe ser Tipo K
de 100 A, 24kV.
- El sistema de gabinetes (Celda de Llegada y Celdas de Salida) tienen un solo
elemento de apertura y cierre por fallas que es el Interruptor en la Celda de Llegada,
el disparo del relé SEPAM S60 al detectar fallas eléctricas mandara un disparo al
Interruptor en Celda de Llegada, ahora el relé ORION iPR-D al detectar fallas a tierra
aguas debajo de la Celda de Salida, enviara un disparo al mismo Interruptor en la
Celda de Llegada (Ver Imagen).
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
SALIDA (REMOTO) AL
INTERRUPTOR DE LA CELDA
LLEGADA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Coordinación de Protecciones (FASES) entre Relé SEPAM S60, Relé ORION iPR-D y del
Relé ABB 630
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Coordinación de Protecciones (TIERRA) entre Relé SEPAM S60, Relé ORION iPR-D y del
Relé ABB 630
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
6. METRADO Y PRESUPUESTO
6.1. METRADO
1 Cable N2XSY Unipolar de 25 mm2 -8.7/15 Kv Marca INDECO o similar Metros 100
2 Terminación Autocontraible Tipo Interior Marca 3M o Similar KIT 4
CELDA COMPACTA DE LLEGADA CON PROTECCIÓN NUMERICA (SECCIONADOR - INTERRUPTOR EN VACIO) 24 KV, 630 A, 20
3 Unidad 1
KA, 60 HZ. MARCA SAREL O SIMILAR ver especificación técnicas en el Expediente.
CELDAS COMPACTAS DE SALIDA CON PROTECCION DE SECCIONADOR FUSIBLE HH BAJO CARGA 24 KV, 630 A, 20 KA, 60
4 MARCA SAREL O SIMILAR ver especificación técnica en el Expediente Unidad 2
TRANSFORMADOR DE DISTRIBUCION SECO ENCAPSULADO EN RESINA EPOXICA DE 1600 KVA 10/0.4-0.231 KV DYN5
5 BOBINADO DE COBRE CON NUCLEO DE ACERO AL SILICIO GRADO M4 INCLUYE ENVOLVENTE METALICO CON GRADO DE
PROTECCION IP21 Transformador de Distribución Seco de 1600 KVA DYN5 10/0.4-0.231 Kv Unidad 1
6 Electrodo de Cobre de 3/4" x 2.4 metros de longitud Unidad 2
7 Conector Tipo Burndy Unidad 4
8 Terreno Vegetal y/o de Cultivo M3 6
9 Cable desnudo de 35 mm2 Metros 200
10 Cable NH-80 de 185 mm2 verde amarillo Metros 100
11 Bolsa de Cemento Conductivo CONDUCRETE o similar Bolsa 8
12 Terminales de Compresión de 25 mm2 Unidad 12
13 Tablero de Aterramiento con Barra equipotencial para cable de hasta 185 mm2, 12 salidas Unidad 2
14 Consumibles para el Trabajo de Media Tensión incluye el Sistema de Puesta a Tierra Global 1
6.2. PRESUPUESTO
PRESUPUESTO DE MATERIALES Y MANO DE OBRA PARA MODERNIZACION DE LA SUBESTACIÓN PARTICULAR DE LA CLINICA VALLE SUR
AUNA SEP 4309
Precio Unitario
Item Descripción Unidad Cantidad Subtotal
en Dólares
1 SUMINISTRO DE MATERIALES Y EQUIPOS PARA MODERNIZACION DE LA SEP 4309 CLINICA VALLE SUR AUNA Global 1 $77,229.20 $77,229.20
2 TRANSPORTE DE MATERIALES Y EQUIPOS A LA UBICACIÓN DE LA SUBESTACION Global 1 $4,633.75 $4,633.75
MONTAJE ELECTROMECANICO PARA MODERNIZACION DE LA SEP 4309 DE LA CLINICA VALLE SUR AUNA SEGÚN
3 Global 1 $24,558.89 $24,558.89
COTIZACION INCLUYE GASTOS GENERALES Y UTILIDAD DEL MONTAJISTA
SUBTOTAL $106,421.84
IGV $19,155.93
TOTAL $125,577.77
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
8. FINANCIAMIENTO
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente de Actualización y Modernización de la SEP 4309 de Clínica Valle
Sur AUNA
9. PLANOS
9.1. IE-01 Planimetría General del Recorrido (Ubicación y Localización).
9.2. IE-02 Detalle de Armado del Poste en el Punto de Entrega o PMI existente.
9.3. IE-03 Detalle de Bajada de Conductor de MT y Buzón en el punto de Entrega existente.
9.4. IE-04 Planimetría de Detalle de Instalaciones Eléctricas de Media Tensión.
9.5. IE-05 Vista de Planta de Distribución Interna de la Subestación 1600 KVA.
9.6. IE-06 Vista de Planta de Subestación Existente de la Clínica Valle Sur AUNA.
9.7. IE-07 Vista de Planta Piso 01 Demolición de Losa para ingreso de Transformador.
9.8. IE-08 Detalle de Ingreso del Transformador 1600 KVA a SEP 4309 de AUNA.
9.9. IE-09 Diagrama Unifilar General de Baja Tensión SEP 4309 de AUNA.
9.10. IE-10 Diagrama Unifilar de Celdas de Media Tensión SEP 4309 de AUNA.
9.11. IE-11 Diagrama de Montaje de Celdas de Media Tensión
9.12. IE-12 Diagrama Eléctrico de Celda de Llegada.
9.13. IE-13 Diagrama Eléctrico de Celdas de Salida.
9.14. IE-14 Diagrama de Control del RELE SEPAM S60 & Medidor de Energía PM-5560.
9.15. IE-15 Diagrama de Control General de Celda de Llegada y Protección N° 1.
9.16. IE-16 Diagrama de Control General de Celda de Salida y Protección N° 2.
9.17. IE-17 Diagrama de Control General de Celda de Salida y Protección N° 3.
9.18. IE-18 Dimensiones del Transformador TP3S 1600 KVA.
9.19. IE-19 Detalle del Sistema de Puesta a Tierra
10. ANEXOS
10.1. FICHAS TECNICAS DE EQUIPAMIENTO ELECTROMECANICO
10.2. PROTOCOLOS DE PRUEBAS A CELDAS, INTERRUPTOR Y SECCIONADOR
Elaborado por: Anthony Herbert Andrade Vásquez Ingeniero Electricista CIP 99580
Expediente Técnico Final de Actualización y
Modernización del Equipamiento de Media Tensión
de la Subestación Particular Existente SEP 4309 de
propiedad de la Clínica Valle SUR AUNA
9. PLANOS
9. PLANOS
9.1. IE-01 Planimetría General del Recorrido (Ubicación y Localización).
9.2. IE-02 Detalle de Armado del Poste en el Punto de Entrega o PMI existente.
9.3. IE-03 Detalle de Bajada de Conductor MT y Buzón en el punto de Entrega existente.
9.4. IE-04 Planimetría de Detalle de Instalaciones Eléctricas de Media Tensión.
9.5. IE-05 Vista de Planta de Distribución Interna de la Subestación 1600 KVA.
9.6. IE-06 Vista de Planta de Subestación Existente de la Clínica Valle Sur AUNA.
9.7. IE-07 Vista de Planta Piso 01 Demolición de Losa para ingreso de Transformador.
9.8. IE-08 Detalle de Ingreso del Transformador 1600 KVA a SEP 4309 de AUNA.
9.9. IE-09 Diagrama Unifilar General de Baja Tensión SEP 4309 de AUNA.
9.10. IE-10 Diagrama Unifilar de Celdas de Media Tensión SEP 4309 de AUNA.
9.11. IE-11 Diagrama de Montaje de Celdas de Media Tensión
9.12. IE-12 Diagrama Eléctrico de Celda de Llegada.
9.13. IE-13 Diagrama Eléctrico de Celdas de Salida.
9.14. IE-14 Diagrama de Control del RELE SEPAM S60 & Medidor de Energía PM-5560.
9.15. IE-15 Diagrama de Control General de Celda de Llegada y Protección N° 1.
9.16. IE-16 Diagrama de Control General de Celda de Salida y Protección N° 2.
9.17. IE-17 Diagrama de Control General de Celda de Salida y Protección N° 3.
9.18. IE-18 Dimensiones del Transformador TP3S 1600 KVA.
9.19. IE-19 Detalle del Sistema de Puesta a Tierra.
Expediente Técnico Final de Actualización y
Modernización del Equipamiento de Media Tensión
de la Subestación Particular Existente SEP 4309 de
propiedad de la Clínica Valle SUR AUNA
10. ANEXOS
WL
Rated voltage
Tensione nominale kV 12 24 36
Tension nominale
Operating sequence
Sequenza operazioni A O-0,3s-CO-3min-CO
Sèquence des opérations
Altitude
Altitudine m ≤1000
Hauteur
Ambient temperature
Temperatura ambiente °C -5÷40
Température ambiante
10
IM6
12÷36 kV
On-load switch
Interruttore di manovra-sezionatore
Interrupteur
Electrical features
Caratteristiche elettriche
Caractéristiques électriques
IM6
Rated voltage
Tensione nominale kV 12 17.5 24 36
Tension nominale
12
ORION ITALIA TR-42
Temperature
Protection Relay (49) TR-42
Temperature
Protection Relay (49)
INSTRUCTION MANUAL
1.DESCRIPTION
The digital temperature relay TR-42 has been created as accessory of primary importance for resin or air insulated three-phase MT
transformer, as protection against dangerous over temperatures on the insulating coil on the winding and to manage the intervention of
cooling fans. Temperature is detected by 3 or 4 thermal detectors PT 100 DIN 43760, three of them dislocated inside the transformer
coils and the fourth in the core.
Features:
- Display of the actual temperature of the 4 RTD - Alarm of TR-42 failure or PT100 disconnection.
- Display & storage of the highest temperature of each RTD - Automatic fan start every week. (bearings problems)
- 3 programmable output contacts from 0° to 220°C level 1, - Insulated RS-485 communication port (Model TR-42C1 only),
level 2 and FAN control. modbus RTU protocol.
- Automatic and manual fan mode
2. INSTALLATION
Install the equipment according the characteristics of humidity and temperature that has been designed to work in. To avoid noise pickup
and interference the relay should be placed away from high current conductors or sources of strong magnetic fields.. The TR-42 has been
designed for the installation on a panel board with a cutout of 92x92 mm using the fixing accessories that come with the relay. Before
doing the installation, it is reccomended to disconnect the power supply on the working area and qualified technician must do the
installation. Orion Italia recommend to follow security procedures during this installation.
3. WIRING CONNECTION
For the connection, follow the diagram (see on page 4). Here in after the description of the different electric connections :
LED “FAULT”: If “flashing”, will indicate that the flashing “In1, In2, In3, In4”, is
in fault. The fault cause will be showed through the °C display when positioned with AUTO
SCAN
OUTPUT
In 1
RELAYS
the arrow buttons on the faulty sensor: ”Fcc” in case of short circuit and “Fco” for L1
FAULT
In 2
open circuit. L2 In 3
DISPLAY BUTTON: If pressed on the first position in any mode will execute a test FAN In 4
to the display and leds. It is also used for changing views or for selecting SCAN
°C MAX
programming values.
SCAN BUTTON: If pressed for 2 seconds in any mode the TR-42 will scan between °C
FM
SET
each RTD temperature showing it on the display every 5 sec allowing the user to see DISPLAY ENTER FAN
all the temperatures automatically. To exit from the “auto scan” function, press any TEMPERATURE RELAY TR-42
arrow button.
FAN BUTTON: it allows to switch between “always ON” or Automatic Fan Operation. In “always ON” mode, the Fan will be always ON
and the led FAN will be ON.
In automatic mode, the Fan will be ON and the fan led will Blink when one RTD reach the corresponding FAN programmed threshold; the
Fan and the fan led will be OFF when temperature does not reach the corresponding FAN programmed threshold.
LED “AUTO SCAN”: If “on” means the user is in the AUTO SCAN mode.
5.1 °C MODE
In this mode the user will see the actual temperature on the “°C” display and the RTD input number on the “SENSOR” display. To see
the other RTD, press the UP/DOWN buttons. The SET/PROG and °C MAX leds are “off”.
6. MAINTENANCE
The TR-42 relay has been constructed principally with solid state technology, so it needs a simple maintenance. The operations of
maintenance are simplified as follows:
Keep the relay dry and clean
Verify that all terminal blocks are well connected
Check periodically the display test by which all leds will be on
Control periodically the right function of the outputs relays.
7. WARRANTY
Orion Italia, s.r.l. warrants this product to be free from defects in material and workmanship for a period of 1 year from date of shipment.
This warranty does not apply to defects resulting from product modification without Orion Italia's express written consent, or misuse of
any product or part. This warranty also does not apply to incorrect connection of probes, incorrect line power, supply voltage greater
10% Vn. During the warranty period, we will, at our option, either repair or replace any product that proves to be defective.
To exercise this warranty, write or call your local Orion Italia representative, or contact Orion Italia in Piacenza, Italia. You will be given
prompt assistance and return instructions product, transportation prepaid, to the indicated service facility. Repaired or replaced products
are warranted for the balance of the original warranty period, or at least 90 days. ORION ITALIA reserves the right to modify the
equipment or the text of this manual without prior notice.
TECHNICAL SPECIFICATIONS
PROG
TEMPERATURE °C SENSOR
SET
PROG
°C
MAX
90 mm
96 mm
AUTO OUTPUT
SCAN RELAYS In 1
FAULT
L1 In 2
L2 In 3
FAN In 4
SCAN
°C MAX
F °C
M
SET
DISPLAY ENTER FAN
TEMPERATURE RELAY TR-42 L1 L2
114 mm
Red
Red PT-100
White Connections
ELECTRICAL WIRING
COMMUNICATION WIRING Used only for
model TR-42C1
( TR-42C1 only )
COM1
_
Converter +
PROG
TR-42 RS-485 a RS-232
+ DATA (+) 24 12
FAN
- DATA (-) 23 25 26 27 28 11
GND 22 10
Pt1 FAULT
21 9
+ To PC 20 8
RECOMENDATION FOR RS-232 7
- * Max. distance 10 mts 19 Pt2 L2
18 6
17 5
16 4
Pt3 L1
+ Rt 3
15
- 39 40 41 42 2
RECOMENDATION FOR RS-485 14
* Use shielded twisted cable 1
Last device * Use only one (1) point of ground 13 Pt4
* Place a Resistor Rt of 120 ohm
on last device
* Max. distance 1000 m L1 L2 SUPPLY VOLTAGE:
24 - 240 Vac/dc
PTFE termorestringente
FILO DI SCHERMATURA
Bianco/
Rosso/
Rosso/
SCHEMA DI COLLEGAMENTO
Bianco/
Rosso/
Rosso/
39
INSTRUCTION MANUAL
TG SERIES
FANS
1MN0096 Rev 0
TECSYSTEM S.r.l.
20094 Corsico (MI)
Tel.: +39-024581861
Fax: +39-0248600783
http://www.tecsystem.it
R. 1.2 20/02/17
ENGLISH
First of all thank you for choosing and using TECSYSTEM product, we strongly suggest you to read carefully this
instruction manual. It will allow you to understand how to use the system and take full advantage of all its features.
WARNING! THIS MANUAL IS VALID AND COMPLETE ONLY FOR THE FANS MODE: TG180, TG360 AND
TG500.
INDEX
PAGE
1) SAFETY REGULATIONS ………………………………… 3
2 TG-180-360-500
SAFETY REGULATIONS
WARNING:
Carefully read the manual before using the fan. Keep these instructions for future reference.
Do not touch /move fans while they are in operation: RISK INJURY.
The product must be installed in a location with limited access to qualified technician. Any work on the appliance
must be left to a qualified repair technician.
Do not touch the motor or power cables: contact with a voltage of 230/120 Volts AC can be fatal. To reduce the
risk of electric shock, do not disassemble or modify in any way the fan motor. Before connecting the device to
make sure that all connections have been made correctly. Always disconnect the fan from power supply before performing
any type of maintenance.
Failure to follow these instructions can cause damage, fire or electric shock, with possible serious injury!
POWER SUPPLY
Before using it make sure that the power supply wires are not damaged, kinked or crushed. Do not tamper with the power
supply wires. Never disconnect the power supply by pulling the cable, avoid touching the pins. Do not perform connection/
disconnection operations with wet hands. Do not use objects as levers to disconnect the power supply of the system.
Disconnect the power immediately if it is evident that the system gives off a burning smell or smoke, please contact
technical support Tecsystem.
LIQUIDS
Do not expose the product to dripping or splashing liquids. Do not allocate in places where humidity is over 90% and never
touch with wet hands.
CLEANING
Before cleaning the fan always disconnect the power supply. To avoid malfunctions, cleaning the fan only using
compressed air to remove dust and dirt. Do not use oils or fats of any kind.
OBJECTS
Never push objects through the air inlet or outlet, if this happens, disconnect the fan and call a technician.
ACCESSORIES
Do not use accessories or replacement parts that are not original, it could cause damage to the fan and put at risk the
safety of the user. In case of failure, contact technical support.
LOCATION
Install the fan indoor protected from splashing water and sunlight. Do not place near heat sources exceed the
parameters specified in this manual. Place the fan in a horizontal and stable surface, away from vibration.
The product must be installed in a location with limited access to qualified technician.
REPAIR
Do not repair or adjust the fan. If any fault occure always contact a qualified technician. Opening the fan tampering
involves the automatic invalidation of the warranty.
PRODUCTION
The date and the batch production of the device are shown on the label attached on the fan. Removing the label implies
the automatic invalidation of the warranty.
TECHNICAL SUPPORT
TG180-360-500 3
TG180 TG360 TG500
TECHNICAL SPECIFICATIONS
POWER SUPPLY AVAILABLE (*) (230Vac –50Hz) —- (230Vac 60Hz) —- (120Vac-60Hz) ±10%
MOTOR MOUNTING 0° 0° 0°
DIAMETER IMPELLER 80 mm 80 mm 80 mm
INSULATION CLASS B B B
(*) Note: The power supplies listed are available on request, or depending on the model purchased. Before connecting
the power supply to the fan always check the parameters of voltage and frequency indicated on the label.
The parameters of current and power and connections shown in this manual are for 230V-50Hz ±10% power supply.
1
MAIN PARTS
1MN0096 REV. 0
4 TG-180-360-500
MOUNTING
DIMENSIONS (mm), MOUNTING HOLES AND CONNECTIONS TG180
1MN0097 Rev 0
1MN0097 Rev 0
3
4
1) Front view
5) Power Connection
(Cable: Brown-Blue-YellowGreen 230Vac 50Hz.)
TG180-360-500 5
DIMENSIONS (mm), MOUNTING HOLES AND CONNECTIONS TG360
1MN0096 Rev 0
1MN0096 Rev 0
3 4
1) Front view
5) Power Connection
(Cable: Brown-Blue-YellowGreen 230Vac 50Hz.)
6 TG-180-360-500
DIMENSIONS (mm), MOUNTING HOLES AND CONNECTIONS TG500
1MN0098 Rev 0
1MN0098 Rev 0
3 4
1) Front view
5) Power Connection
(Cable: Brown-Blue-YellowGreen 230Vac 50Hz.)
TG180-360-500 7
MOUNTING NOTES
Fix the fans using the holes on the back, do not change the mounting holes of the fan. During the handling of the
fans avoid deforming the fins of the impeller. Never change the motor positioning.
If the fan is mounted on board of a transformer the working position of the fan must comply with the safety distance,
indicated in the manual of the transformer, on which you are installing the fan. The fan must be positioned in the
horizontal plane, always make sure, through the help of a level, that the fan is positioned correctly.
WARNING:
Use the fan trying not obstruct the mouth of the inlet / outlet, whether partial or total occlusion of the air vents
can cause malfunction.
POWER SUPPLY
The value of power supply is indicated on the fan label, to see the available fan options see parameters at page 4.
Note: do not power the fan with different values of voltage and frequency, always control those indicated on the label.
Maximum permitted harmonic content in accordance with EN 61000-3-2:
5% 3rd,
6% 5th,
5% 7th,
1.5% 9th,
3.5% 11th,
3% 13th,
0.3% 15th,
2% 17th.
It is not recommended to install the fans in marine environment, if not after treatment of metal parts .
NOTE: wrong installation and critical environmental conditions as: long periods of inactivity, high tempera-
ture high humidity, excessive dust and excessive vibration can anticipate the deterioration of the mechanical
parts of the fans.
MAINTENANCE
In order to maintain the efficiency of the fans, we suggest to perform regularly, every 6 months, a
cleaning operation of the fans (do it using only compressed air). Do not use oils or fats of any kind.
Any prolonged shutdown of the fan may be the cause of failure. The installation of the fans combined with
thermometric Tecsystem avoids any longer standstill. Enabling the HFN Tecsystem present in the unit can be
programmed cycles of activation of fans from 1 to 200 hours, recommended setting every 24 hours (for more
information about the HFN check the manual of the unit).
When the fans are connected with Tecsystem VRT control unit always remember that reporting a defect by
the VRT could be related to the malfunction of the fan. Do not reprogram the VRT without having carried
out a verification of the status of the fans and a possible maintenance (cleaning fans with compressed air).
NOTE: periodic maintenance and activation of the HFN function will allow you to extend the efficiency of the
fans. The maintenance on the fans must be programmed as a function of environmental conditions in
which they operate.
8 TG-180-360-500
TROUBLE SHOOTING CAUSES AND REMEDIES
Remove the power supply and check that: the power connectors
The fan is powered, but the impeller does not
are properly inserted into their home, the connection wires are
turn.
tight, there are no obvious signs of burns on the connectors.
Check the value of the power, using a multimeter, and check the
The fan runs very slow or too fast. correspondence of the values with those reported on the
identification label of the product purchased.
WARRANTY CONDITIONS
The Product purchased is covered by the manufacturer's or seller's warranty at the terms and conditions set forth in the
"Tecsystem s.r.l's General Conditions of Sale", available at www.tecsystem.it and / or in the purchase agreement.
The warranty is considered valid only when the product is damaged by causes attributable to TECSYSTEM srl, such as
manufacturing or components defects.
The warranty is invalid if the Product proves to have been tampered with / modified, incorrectly connected, because of
voltages outside the limits, non-compliance with the assembly and use technical data, as described in this instruction
manual.
EQUIPMENT DISPOSAL
European directives 2012/19/EC (WEEE) and 2011/65/EC (RoHS) have been approved to reduce electrical and elec-
tronic waste and promote the recycling and reuse of the materials and components of said equipment, cutting down on
the disposal of the residues and harmful components of electrical and electronic materials.
All the electrical and electronic equipment supplied after 13 August 2005 is marked with this symbol, pursuant
to European directive 2002/96/EEC on electrical and electronic waste (WEEE). Any electrical or electronic
equipment marked with this symbol must be disposed of separately from normal domestic waste.
Returning used electrical devices: contact TECSYSTEM or your TECSYSTEM agent for information on the correct dis-
posal of the devices.
TECSYSTEM is aware of the impact its products have on the environment and asks its customers active support in the
correct and environmentally-friendly disposal of its devices.
USEFUL CONTACTS
TECHNICAL INFORMATION: ufficiotecnico@tecsystem.it
TG180-360-500 9
TECHNICAL DATASHEET
Safety Standards
General Description
The DRP024V240W1AA is part of the CliQ series of DIN Rail power supplies from one of the world’s largest power supply manufacturers
and solution providers - Delta. This product provides an adjustable output capable of operating from input voltages at 85-264Vac, and a
wide temperature range of -20°C to 75°C. With a rugged, compact plastic case design that meets shock and vibration requirements (in
accordance to IEC60068-2-27 and IEC60068-2-6 respectively), and conformal-coated PCB assembly, this state of the art design is well
suited to a broad variety of industrial applications worldwide.
Model Information
Model Numbering
Specifications
Mechanical
Environment
Protections
Reliability Data
EMC
Block Diagram
Device Description
Dimensions
L x W x D: 121 x 85 x 118.5 mm
Engineering Data
De-rating Note
The power supply unit (PSU) can be mounted on 35mm DIN rails in accordance with EN60715. The device should be installed with input
terminal blocks at the bottom.
Mounting Dismounting
Snap on the DIN rail as shown in Fig. 2.1: To uninstall, pull or slide down the latch with screw driver as
1. Tilt the unit upwards and insert it onto the DIN rail. shown in Fig 2.2. Then slide the power supply unit (PSU) in
2. Push downwards until stopped. the opposite direction, release the latch and pull out the
3. Press against the bottom front side for locking. power supply unit (PSU) from the rail.
4. Shake the unit slightly to ensure that it is secured.
Safety Instructions
Functions
■ Graph illustrating the Start-up Time, Rise Time, and Hold-up Time
Start-up Time
The time required for the output voltage to reach 90% of its set value, after the input voltage is applied.
Rise Time
The time required for the output voltage to change from 10% to 90% of its set value.
Hold-up Time
Hold up time is the time when the AC input collapses and output voltage retains regulation for a certain period of time. The time required
for the output to reach 95% of its set value, after the input voltage is removed.
Overvoltage Protection
The power supply’s overvoltage circuit will be activated when its
internal feedback circuit fails. The output voltage shall not exceed
its specifications defined on Page 3 under “Protections”. Additionally, if the IO is <150% but >100% for a prolong period of
time (depending on the load), the Over Temperature Protection
(OTP) will be activated due to high temperature on critical
components. The power supply will then go into “Hiccup mode”
until the fault is removed.
Operating Mode
Redundancy Operation
In order to ensure proper redundancy
operation for the power supply unit
(PSU), ensure that the output voltage
difference between the two units is kept
at 0.45~0.50V for 24V supplies. Follow
simple steps given below to verify:
Step 1.
Measure output voltage of PSU 1 and
PSU 2. If PSU 1 is the master unit, then
Vo of PSU 1 must be higher than PSU 2.
Step 2.
Connect the right DRR module, 20A as
per the system requirement to the power
Fig. 3.1 Redundancy / Parallel Operation Connection Diagram supply units PSU 1 and PSU 2 at Vin 1 &
Vin 2 respectively.
Step 3.
Connect the system load from Vout.
Please note that output voltage Vout from
DRR module will be = VO (output voltage
*Vdrop will vary from 0.60V to 0.90V (Typical 0.65V) depending on the load current of power supply) – Vdrop* (in DRR
and surrounding air temperature. module).
Parallel Operation
These DRR modules can also be used for Parallel function in order to increase the output power by N+1 (e.g. 2.5A + 2.5A = 5A or 2.5A
+ 2.5A + 2.5A = 7.5A) or current sharing, and thus increasing the power supply and system reliability. Though the DRP024V240W1AA
is not designed for current sharing, a good current sharing between two power supplies can be achieved by following simple steps as
below (Refer to Fig. 3.1 for the Connection Diagram).
Step 1. Step 3.
Set output load condition for both supplies at 50% and measure Connect PSU 1 and PSU 2 with the DRR-20A module and
the output voltages. measure at Vin 1 & Vin 2 to verify the voltage difference. Ensure
the voltages are within ±25mV.
Step 2. Step 4.
Adjust output voltages to the same level or within ±25mV Output voltage from DRR module Vout will be = VO (output
difference. voltage of power supply) – Vdrop* (in DRR module).
*Vdrop will vary from 0.60V to 0.90V (Typical 0.65V) depending on the load current and surrounding air temperature.
Others
Conformal Coating
The Protective Coating Technology
Delta Electronics Group has designed the perfect dipping technique which penetrates everywhere including
under device, and prevents leakage. The conformal coating dipping can be applied to PCBs or circuit board.
The coating preserves the performance of precision electronic primarily by preventing ionizable contaminants
such as salt from reaching circuit nodes, where the material slumps around sharp edges. This can be a problem
especially in highly conversing atmosphere.
Dimensions
Terminal F13
Unit: mm Dimension: 166(L) ×175(W) ×125(H)
Terminal F3
o
Constant Current Discharge Characteristics : A(25 C)
F.V/Time 5MIN 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR
9.60V 97.4 64.54 48.07 26.12 16.64 9.567 6.809 5.463 4.489 3.002 2.599 1.391
10.0V 93.90 62.93 46.53 25.79 16.42 9.374 6.683 5.385 4.449 2.990 2.572 1.380
10.2V 88.38 59.82 45.24 25.39 16.27 9.275 6.624 5.331 4.420 2.963 2.533 1.341
10.5V 79.45 55.93 42.67 24.69 16.07 9.154 6.565 5.252 4.383 2.937 2.520 1.313
10.8V 71.19 52.16 40.26 23.88 15.84 9.079 6.488 5.073 4.362 2.925 2.478 1.260
11.1V 62.28 47.82 37.14 22.97 15.47 8.899 6.361 5.000 4.343 2.901 2.440 1.240
o
Constant Power Discharge Characteristics : W(25 C)
F.V/Time 5MIN 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR
9.60V 1057 707.7 530.5 299.0 199.0 112.7 80.19 65.39 53.78 35.95 31.14 16.69
10.0V 1029 693.1 522.8 295.9 196.1 111.2 78.88 64.46 53.30 35.81 30.84 16.56
10.2V 978.8 665.6 515.9 293.4 194.6 110.3 78.20 63.86 52.98 35.54 30.45 16.13
10.5V 893.4 638.2 489.1 287.4 192.0 109.1 77.63 63.00 52.55 35.24 30.23 15.86
10.8V 806.0 597.0 462.1 280.6 189.5 108.3 76.72 60.88 52.31 35.09 29.77 15.22
11.1V 710.8 555.8 435.2 272.9 185.3 106.8 75.22 60.00 52.12 34.84 29.33 14.98
Storage characteristic
10
100
8 Supplementary charge required
0℃ (Carry out supplementary charge
before use if 100% capacity is
6 80 requires)
Capacity (%)
10℃
Life Expectancy (years)
0
Supplementary charge and storage
2 4 6 8 10 12 14 16 18 20 22 24 guidelines
0 10 20 30 40 50
Battery Temperature (℃) Storage Time (months)
15 120 0.24
13
Charge Volume
14 100 0.20
Charge Voltage
Terminal Voltage (V)
12
Charge Voltage(V)
13 80 0.16
① Discharge
100%(0.05CA×20h) 11
0.05C
12 50%(0.05CA×10h) 60 0.12 0.16C 0.093C
② Charge 0.35C
Charge Voltage2.275V/C
Charge Current0.1CA 10
40 0.08 0.62C
11 ③ Temperature 25 ℃
3C 1C
10 20 0.04 9
Charge Current
0.6 1.2 3 6 12 30 1 2 5 10 20 24
9 0 0
0 2 4 6 8 10 12 14 16 18 20 24 28 min Hr
Charge Time (h) Discharge Time
Constant Current -0.2Cx2h+0.1Cx12h Charge: Max. current 0.3CA, constant voltage 14.4-14.7V charge 24h.
Fast -0.2Cx2h+0.3Cx4h
※ Effect of temperature on float charge voltage: -3mV/℃/Cell.
Bolt M5 M6 M8 ※ Length of service life will be directly affected by the number of discharge
Terminal F3 F4 F13 F18 T25 T26 F8 F11 F12-1 F15 F5 F9 F10 F12 F14 F16 .
cycles, depth of discharge, ambient temperature and charging voltage.
Torque 6~7N-m 8~10N-m 10~12N-m
SHENZHEN RITAR POWER CO.,LTD. Address: Rm405,Tower C, Huahan Building,Langshan Rd16, Nanshan District, ShenZhen, 518057, China
URL:www.ritarpower.com
Tel:+86-755-33981668 Fax:86-755-8347-5180 2015 - Version 0
Hoja de características del METSEPM5560
producto PM5560 analizador con 1mod2eth - hasta 63th H
Características - 1,1M 4DI/2DO 52 alarmas - Panel
Aviso Legal: Esta documentación no pretende sustituir ni debe utilizarse para determinar la adecuación o la fiabilidad de estos productos para aplicaciones específicas de los usuarios
Principal
Gama PowerLogic
Nombre del producto PowerLogic PM5001
Nombre corto del dispositivo PM5560
Tipo de producto o componente Central de medida
Complementario
Análisis de calidad de energía Hasta armónico 63
Aplicación del dispositivo Medición de WAGES
Supervisión de potencia
Gateway ((*))
Multi-tarifa
Tipo de medición Energía
Potencia activa y reactiva
Tensión
Corriente
Frecuencia
Factor de potencia
Tensió de alimentación 125...250 V DC
100...480 V AC (45..0,65 Hz)
Frecuencia de red 50 Hz
60 Hz
[In] Corriente nominal 1A
5A
Tipo de red 1P + N
3P
3P + N
Consumo de potencia en W <= 10 VA at 480 V
Ride-through time 35 ms 120 V AC typical
129 ms 230 V AC typical
Tipo de pantalla LCD retroiluminada
Resolución de la pantalla 128 x 128
07-feb-2019
1
Velocidad de muestreo 128 muestras/ciclos
Corriente de medición 5...10000 mA
Tipo de entrada analógica Corriente (impedancia 0.3 mOhm)
Tensión (impedancia 5 MOhm)
Tensión de medida 20...400 V AC 45..0,65 Hz entre fase y neutro
20...690 V AC 45..0,65 Hz entre fases
Frecuencia 45...65 Hz
Número de entradas 4 digital
Precisión de medida +/- 0.5 % potencia aparente
+/- 0.05 % frecuencia
+/- 0.2 % energía activa
+/- 1 % energía reactiva
+/- 0.2 % potencia activa
+/- 0.1 % tensión
+/- 0.05 % factor de potencia
+/- 0.15 °C corriente
Clase de precisión Clase 0,2S (energía activa según IEC 62053-22)
Número de salidas 2 digital
Información mostrada Tarifa 8
Communication port protocol Modbus RTU y ASCII 2 cables, (pedido por separado)9,6, 19,2 y 38,4 kbaudios, Par/Impar o
ninguna, aislamiento: 2500 V
JBUS
Modbus TCP/IP (pedido por separado)10/100 Mbit/s, aislamiento: 2500 V
Cadena Ethernet Modbus TCP / IP
BACnet IP
Soporte del puerto de comunicación RS485
Ethernet
Pasarela de comunicación Ethernet/Serial ((*))
Registro de dados Registros de dados
Registros de eventos
Valores instantáneos mín./máx.
Sellado de tiempo
Registros de alarmas
Registros de mantenimiento
Capacidad de memoria 1.1 MB
Servicios web Notificación de alarma por correo electrónico
Diagnóstico via páginas web predefinidas
Servidor web
Real time viewing of data ((*))
Servicio Ethernet Cliente SNTP
SNMP-Traps ((*))
Conexiones - terminales Voltage circuit: 4 screw terminal block
Control circuit: 2 screw terminal block
Current transformer: 6 screw terminal block
RS485 link: 4 screw terminal block
Digital input: 8 screw terminal block
Digital output: 4 screw terminal block
Ethernet network: 2 RJ45 connector
Tipo de montaje Montaje enrasado
Soporte de montaje Marco
Normas IEC 60529
IEC 61557-12
IEC 62053-22
EN 50470-1
EN 50470-3
UL 61010-1
IEC 62053-24
Certificaciones de producto CE acorde a IEC 61010-1
CULus acorde a UL 61010-1
BTL
Anchura 96 mm
Profundidad 72 mm
Altura 96 mm
Peso del producto 450 g
2
Entorno
Compatibilidad electromagnética ● Emisiones conducidas e irradiadas clase Clase b, de acuerdo con EN 55022
● limitación de las variaciones de tensión, fluctuaciones de tensión y flicker en baja tensión, de
acuerdo con IEC 61000-3-3
● límites para emisiones de corrientes armónicas clase Clase A, de acuerdo con IEC 61000-3-2
● Conducted rf disturbances clase Nivel 3, de acuerdo con IEC 61000-4-6
● campo magnético a frecuencia eléctrica clase level 4 ((*)), de acuerdo con IEC 61000-4-8
● descarga electroestática clase level 4 ((*)) (8 kV ), de acuerdo con IEC 61000-4-2
● prueba de inmunidad de la radiofrecuencia radiada del campo electromagnético, de acuerdo con
IEC 61000-4-3
● prueba de inmunidad oscilatoria/ráfagas eléctrica clase level 4 ((*)), de acuerdo con IEC 61000-4-4
● prueba de inmunidad frente a sobretensión clase level 4 ((*)), de acuerdo con IEC 61000-4-5
● prueba de inmunidad de huecos y caídas de tensión, de acuerdo con IEC 61000-4-11
Grado de protección IP IP52 (frontal) acorde a IEC 60529
IP30 (cuerpo) acorde a IEC 60529
Humedad relativa 5...95 % 50 °C
Grado de contaminación 2
Temperatura ambiente de -25...70 °C
funcionamiento
Temperatura ambiente de -40...85 °C
almacenamiento
Altitud máxima de funcionamiento 3000 m
Sostenibilidad de la oferta
Estado de la oferta sostenible Producto Green Premium
RoHS (código de fecha: AASS) Conforme - desde 1340 - Declaración de conformidad de Schneider Electric
Declaración de conformidad de Schneider Electric
REACh La referencia no contiene SVHC
La referencia no contiene SVHC
Perfil ambiental del producto Disponible
Perfil ambiental del producto
Instrucciones para el fin del ciclo de DISPONIBLE
vida del producto
Información de fin de vida útil
Información Logística
País de Origen India
3
ORION ITALIA TR-42
Temperature
Protection Relay (49) TR-42
Temperature
Protection Relay (49)
INSTRUCTION MANUAL
1.DESCRIPTION
The digital temperature relay TR-42 has been created as accessory of primary importance for resin or air insulated three-phase MT
transformer, as protection against dangerous over temperatures on the insulating coil on the winding and to manage the intervention of
cooling fans. Temperature is detected by 3 or 4 thermal detectors PT 100 DIN 43760, three of them dislocated inside the transformer
coils and the fourth in the core.
Features:
- Display of the actual temperature of the 4 RTD - Alarm of TR-42 failure or PT100 disconnection.
- Display & storage of the highest temperature of each RTD - Automatic fan start every week. (bearings problems)
- 3 programmable output contacts from 0° to 220°C level 1, - Insulated RS-485 communication port (Model TR-42C1 only),
level 2 and FAN control. modbus RTU protocol.
- Automatic and manual fan mode
2. INSTALLATION
Install the equipment according the characteristics of humidity and temperature that has been designed to work in. To avoid noise pickup
and interference the relay should be placed away from high current conductors or sources of strong magnetic fields.. The TR-42 has been
designed for the installation on a panel board with a cutout of 92x92 mm using the fixing accessories that come with the relay. Before
doing the installation, it is reccomended to disconnect the power supply on the working area and qualified technician must do the
installation. Orion Italia recommend to follow security procedures during this installation.
3. WIRING CONNECTION
For the connection, follow the diagram (see on page 4). Here in after the description of the different electric connections :
LED “FAULT”: If “flashing”, will indicate that the flashing “In1, In2, In3, In4”, is
in fault. The fault cause will be showed through the °C display when positioned with AUTO
SCAN
OUTPUT
In 1
RELAYS
the arrow buttons on the faulty sensor: ”Fcc” in case of short circuit and “Fco” for L1 FAULT
In 2
open circuit. L2 In 3
DISPLAY BUTTON: If pressed on the first position in any mode will execute a test FAN In 4
SCAN
to the display and leds. It is also used for changing views or for selecting °C MAX
programming values.
SCAN BUTTON: If pressed for 2 seconds in any mode the TR-42 will scan between °C
FM
SET
each RTD temperature showing it on the display every 5 sec allowing the user to see DISPLAY ENTER FAN
all the temperatures automatically. To exit from the “auto scan” function, press any TEMPERATURE RELAY TR-42
arrow button.
FAN BUTTON: it allows to switch between “always ON” or Automatic Fan Operation. In “always ON” mode, the Fan will be always ON
and the led FAN will be ON.
In automatic mode, the Fan will be ON and the fan led will Blink when one RTD reach the corresponding FAN programmed threshold; the
Fan and the fan led will be OFF when temperature does not reach the corresponding FAN programmed threshold.
LED “AUTO SCAN”: If “on” means the user is in the AUTO SCAN mode.
5.1 °C MODE
In this mode the user will see the actual temperature on the “°C” display and the RTD input number on the “SENSOR” display. To see
the other RTD, press the UP/DOWN buttons. The SET/PROG and °C MAX leds are “off”.
6. MAINTENANCE
The TR-42 relay has been constructed principally with solid state technology, so it needs a simple maintenance. The operations of
maintenance are simplified as follows:
Keep the relay dry and clean
Verify that all terminal blocks are well connected
Check periodically the display test by which all leds will be on
Control periodically the right function of the outputs relays.
7. WARRANTY
Orion Italia, s.r.l. warrants this product to be free from defects in material and workmanship for a period of 1 year from date of shipment.
This warranty does not apply to defects resulting from product modification without Orion Italia's express written consent, or misuse of
any product or part. This warranty also does not apply to incorrect connection of probes, incorrect line power, supply voltage greater
10% Vn. During the warranty period, we will, at our option, either repair or replace any product that proves to be defective.
To exercise this warranty, write or call your local Orion Italia representative, or contact Orion Italia in Piacenza, Italia. You will be given
prompt assistance and return instructions product, transportation prepaid, to the indicated service facility. Repaired or replaced products
are warranted for the balance of the original warranty period, or at least 90 days. ORION ITALIA reserves the right to modify the
equipment or the text of this manual without prior notice.
TECHNICAL SPECIFICATIONS
PROG
TEMPERATURE °C SENSOR
SET
PROG
°C
MAX
90 mm
96 mm
AUTO OUTPUT
SCAN RELAYS In 1
FAULT
L1 In 2
L2 In 3
FAN In 4
SCAN
°C MAX
F °C
M
SET
DISPLAY ENTER FAN
TEMPERATURE RELAY TR-42 L1 L2
114 mm
Red
Red PT-100
White Connections
ELECTRICAL WIRING
COMMUNICATION WIRING Used only for
model TR-42C1
( TR-42C1 only )
COM1
_
Converter +
PROG
TR-42 RS-485 a RS-232
+ DATA (+) 24 12
FAN
- DATA (-) 23 25 26 27 28 11
GND 22 10
Pt1 FAULT
21 9
+ To PC 20 8
RECOMENDATION FOR RS-232 7
- * Max. distance 10 mts 19 Pt2 L2
18 6
17 5
16 4
Pt3 L1
+ Rt 3
15
- 39 40 41 42 2
RECOMENDATION FOR RS-485 14
* Use shielded twisted cable 1
Last device * Use only one (1) point of ground 13 Pt4
* Place a Resistor Rt of 120 ohm
on last device
* Max. distance 1000 m L1 L2 SUPPLY VOLTAGE:
24 - 240 Vac/dc
The ORION ITALIA SERIES implement a subset of the AEG Modicon Modbus serial communication standard.
Many devices support this protocol directly with suitable interface card, allowing direct connection of relays.
The Modbus protocol is hardware-independent; that is, the physical layer can be any of variety of standard
hardware configurations. This includes RS232, RS422, RS485, fibber optics, etc. The ORION ITALIA RELAYS
include a rear terminal RS422/RS485 port. Modbus is a single master multiple slave protocol suitable for a
multi-drop configuration as provided by RS422/RS485 hardware. In this configuration up to 32 slaves can be
daisy-chained together on a single communication channel.
The ORION ITALIA SERIES is always a Modbus slave. It cannot be programmed as a Modbus master. The
Modbus protocol exists in two versions: Remote Terminal Unit (RTU, binary) and ASCII. Only the RTU version
is supported by the Orion Italia Relay. Monitoring, programming and control functions are possible using read
and write register commands.
2 ELECTRICAL INTERFACE.
In a two-wire RS485 link, data flow is bi-directional. The four-wire RS422 port uses two terminals for receive
lines, and two other terminals for transmit lines. As a result, both RS422 and RS485 ports cannot be used at
the same time. The data flow is half duplex. That is, data is never transmitted and received at the same time.
RS485 and RS422 lines should be connected in a daisy chain configuration (avoid star connections) with
terminating resistors and capacitors installed each end of the link, i.e. at the master end and the slave farthest
from the master. That value of the terminating resistors should be equal to the characteristic impedance of the
line. This is approximately 120 Ohms for standard 24 AWG twisted pair wire. The value of the capacitors
should be 1 nF. Shielded wire should always be used to minimize noise. Polarity is important in RS485
communications. See figure below for more details.
Convertitore Convertitore
TR-42 RS-422 a RS-232 TR-42 RS-485 a RS-232
RxA TxA TXA DATA (+)
RxB TxB
TXA RxA TXB DATA (-)
TXB RxB
GND GND
To PC
RxA TXA To PC
RxB
TXA TXB
TXB
COMMUNICATION 1
TEMPERATURE RELAY TR-42
One data frame of an asynchronous transmission to or from a Orion Italia Relay consists of 1 start bit, 8 data
bits, not parity and 1 stop bit. This produces a 10 bit frame. This is important for transmission though modems
at high bit rates (11 bit data frames are not supported by hayes modems at bit rates of greater than 300 bps).
The rear RS485/RS422 external communication port of the Orion Italia Relay supports operation at
1200,2400,4800 and 9600 baud.
A complete request/response consists of the following bytes transmitted as separate data frames:
A message is terminated when no data is received for a period of 3 1/2 character transmission times.
Consequently, the transmitting device must not allow gaps between bytes larger than this interval (about 3ms
at 9600 baud).
SLAVE ADDRESS: This is the first byte of every message. This byte represents the user-assigned address of
the slave device that is to receive the message sent by the master. Each slave device must be assigned a
unique address, and only the addressed slave will respond to a message that starts with its address. In a
master query message the SLAVE ADDRESS represents the address of the slave to which the request is
being sent. In a slave response message the SLAVE ADDRESS is a confirmation representing the address of
the slave that is sending the response. A master query message with a SLAVE ADDRESS of 0 indicates a
broadcast command. All slaves on the communication link will take action based on the message, but none will
respond to the master.
FUNCTION CODE: This is the second byte of every message. Modbus defines function codes of 1 to 127. The
Orion Italia Relay implements some of this functions. See section 7 for details of the function codes supported
by the Orion Italia Relay Series Modbus Protocol. In a master query message the FUNCTIONS CODE tells the
slave what action to perform. In a slave response message, if the FUNCTION CODE sent from the slave is the
same as the FUNCTION CODE sent from the master then the slave performed the function as requested.
DATA: This will be a variable number of bytes on the FUNCTION CODE. This may include actual values,
setpoints or addresses sent by the master to the slave or by the slave to the master. See section 7 for a
description of the Orion-supported functions and the data required for each.
CRC: This is a two byte error checking code. CRC is sent LSByte first followed by the MSByte. The RTU
version of Modbus includes a two byte CRC-16 (16 bit cyclic redundancy check) with every message. The
CRC-16 algorithm essentially treats the entire data stream (data bits only; start, stop and parity ignored) as one
continuous binary number. This number is first shifted left 16 bits and then divided by a characteristic
2 COMMUNICATION
TEMPERATURE RELAY TR-42
polynomial (11000000000000101B). The 16 bit remainder of the division is appended to the end of the
message, MSByte first. The resulting message including CRC, when divided by the same polynomial at the
receiver will give a zero remainder if no transmission errors have occurred. If a Orion Modbus slave device
receives a message in which an error is indicated by the CRC-16 calculation, the slave device will not respond
to the message. A CRC-16 error indicates that one or more bytes of the message were received incorrectly
and thus the entire message should be ignored in order to avoid the slave device performing any incorrect
operation. The CRC-16 calculation is an industry standard method used for error detection. An algorithm is
included in section 5 CRC-16 algorithm to assist programmers in situations where no standard CRC-16
calculation routines are available.
5 CRC-16 ALGORITHM
Once the following algorithm is completed, the working register "A" will contain the CRC value to be
transmitted. Note that this algorithm requires the characteristic polynomial to be reverse bit ordered. The most
significant bit of the characteristic polynomial is dropped, since it does not affect the value of the remainder.
The following symbols are used in the algorithm:
Symbols:
--> data transfer
A 16 bit working register
Alow low order byte of A
Ahigh high order byte of A
CRC 16 bit CRC-16 value
i,j loop counter
(+) logical EXCLUSIVE-OR operator
N total number of data bytes
Di i-th data byte (i=0 to N-1)
G 16 bit characteristic polynomial =1010000000000001(binary) with MSbit dropped and bit
order reversed
shr(x) right shit operator (the LSbit of x is shifted into a carry lag, a '0' is shifted into the MSbit of x,
all other bits are shifted right one location)
Algorithm:
1. FFFF(hex) --> A
2. O --> i
3. O --> j
4. Di (+) Alow --> Alow
5. j + 1 --> j
6. shr (A)
7. Is there a carry ? No: go to step 8
Yes: G (+) A --> A and continue
8. Is j = 8 ? No: go to 5
Yes: continue
9. i + 1 --> i
10. Is i = N ? No: go to 3
Yes: continue
11. A ----> CRC
COMMUNICATION 3
TEMPERATURE RELAY TR-42
6 MESSAGE TIMING
Communication message synchronization is maintained by timing constraints. The receiving device must
measure the time between the reception of characters. If three and one half character times elapse without a
new character or completion of the message, then the communication link must be reset (i.e. all slaves start
listening for a new query message from the master). Thus at 1200 baud a delay of greater than 3.5 x 1/1200 x
10 = 29.2 msec cause the communication link to be reset. At 9600 baud a delay of greater than 3.5 x 1/9600
x 10 = 3.6 ms will cause the communication link to be reset. Most master query messages will be responded to
in less than 50 ms. The maximum time for the Orion Italia Relay to return a slave response message for any
function code will never exceed 1 second.
The second byte of every message is the function code. Modbus defines function codes of 01h to 7Fh. The
Orion Italia Relay Modbus protocol supports some of these functions, as summarized in Table No. 1
TABLE No. 1
Since some programmable logic controllers only support function codes 03h (or 04h) and 10h, most of the
above Modbus commands can be performed by reading from or writing to special addresses in the Orion Italia
Relay memory map using these function codes.
The Orion Italia Relay implementation of Modbus views "holding registers" as any setpoint or actual values
register in the Orion Italia Relay memory map. Registers are 16 (two byte) values transmitted high order byte
first. Thus all Orion Italia Relay setpoints and actual values in the memory map are sent as two byte registers.
This function code allows the master to read one or more consecutive setpoints or actual values from
addressed slave device.
The slave response to these function codes is the slave address, function code, a count of the number of data
bytes to follow, the data itself and the CRC. Each data item is sent as a two byte number with the high order
byte sent first. The CRC is sent as a two byte number with the low order byte sent first.
The maximum number of values of Setpoints that can be read in a single message is 6 word (12 bytes). The
TR-42 Setpoint data starts at address 0100h.
4 COMMUNICATION
TEMPERATURE RELAY TR-42
The maximum number of values of Actual Values that can be read in a single message is 14 word (28 bytes).
The TR-42 Actual Values data starts at address 0200h.
If the function code or the address of any of the requested data is illegal, the slave will not respond the
message. Otherwise, the slave will respond as follows:
This function code allows the master to request TR-42 to perform specific command operations. The
commands Number Listed in the Commands Area of the Relay memory map correspond to operations codes
for function code 05h.
The Slave Response to this function is to echo the entire master transmission.
The operation codes can also be initiated by writing to the commands area of the memory map using function
codes 06h or 10h.
COMMUNICATION 5
TEMPERATURE RELAY TR-42
This function code allows the master to store single setpoints into the memory map of the TR-42.
The Slave Response to this function is to echo the entire master transmission.
6 COMMUNICATION
TEMPERATURE RELAY TR-42
This function code allows the master to modify the contest of a one or more consecutive setpoint in the
addressed slave device. Setpoint registers are 16 bit (two byte) values transmitted high order byte first.
The maximum number of register values (setpoints) that can be stored in a single message is 6 word (12
bytes). The TR-42 Setpoint data starts at address 0100h.
To store the value of one or more setpoints in the internal memory of the TR-42, the following steps shall be
realized:
a) First shall be read all setpoint group ( 6 word = 12 bytes) with function 03h or 04h.
b) Modify the values of setpoints according to setpoint map.
c) Send all setpoint group, 6 word (12 bytes) with function 10h.
The TR-42 response to this function code is to echo the slave address, function code, starting address, the
number of setpoints stored, and the CRC.
Request slave device 11h to write the value 0064h at setpoint address 0100h, and the value 0070h at setpoint
address 0101h.
COMMUNICATION 7
TEMPERATURE RELAY TR-42
If the function code or the address or value of any of the data, is illegal, the slave will not respond to the
message. Otherwise, the slave will respond as follows:
8 COMMUNICATION
TEMPERATURE RELAY TR-42
The data stored in the TR-42 is grouped as Setpoints, Actual Values, Product ID & Commands. Setpoints can
be read and written by a master computer. Actual Values & Product ID are read only, Commands are Write
Only. All setpoints and Actual Values are stored as two bytes values. Addresses are listed in hexadecimal.
Data values (Setpoint ranges, increments, factory value) are in decimal.
MEMORY MAP
COMMUNICATION 9
TEMPERATURE RELAY TR-42
10 COMMUNICATION
TEMPERATURE RELAY TR-42
COMMUNICATION 11
TEMPERATURE RELAY TR-42
12 COMMUNICATION
TEMPERATURE RELAY TR-42
COMMUNICATION 13
IPR-D
Current
Monitoring & Protection
DESCRIPTION
The Current Protection Relay (IPR-D) has been designed to measure the ground RMS current under normal
conditions or under disturbances. The current signals are sensed throughout a current transformer (CT). This
information is internally processed by the microprocessor in order to take the current protection actions defined
under ANSI, IAC or IEC standard.
APPLICATIONS FEATURES
• Primary and backup ground protection for utility • CT primary ratio selectable in 5 A steps (5 A to
feeders, power plants and industrial distribution 5000 A).
systems. • Ground RMS current measurement.
• 1 trip relay and 3 programmable auxiliary relay.
• Control power drop or internal fault relay.
PROTECTION AND FUNCTIONALITY • Digital inputs: 1 breaker status & 3 programmable.
• Touchpad programming.
• (50G/50N) Instantaneous ground overcurrent. • Breaker operation & trip failure.
• (51G/51N) Inverse time ground overcurrent
• ANSI, IAC or IEC/BS142 curves included: SIGNALLING
Moderately inverse.
Normal inverse. • LED and LCD display indication.
Very inverse. • Ground current indication.
Extremely inverse. • Last trip cause and storage of values.
Definite time. • Indication and storage of fault conditions and their
• Overload alarm pickup level. values.
• Threshold LED for 50G/N, 51G/N.
COMMUNICATION
APPLICABILITY
• Remote communication using a PC or a PLC by 1
RS232 & 2 RS485 ports. Systems: Mono phase, 3 or 4-wire three
• Remote programming of the setpoints. phase system
• Protocol used: Modbus RTU. Frequency 50 and 60 Hz
Protection relay
Quality certified ISO 9001:2000 IPR-D_GBBR_040208
SPECIFICATIONS
SUPPLY VOLTAGE MAX. POWER CONSUPTION
24÷310 Vdc, –15%, +10% 12VA (7W)
24÷240 Vac, -15%, +20% 50/60Hz
FRAME ASSEMBLY
In ABS auto-extinguish with frontal in polycarbonate (IP54). The relay has to be fixed to the structure with the help of
stirrups and screws.
WEIGHT
1.5 Kg
2 Protection relay
Quality certified ISO 9001:2000
EMISSION TEST IMMUNITY TEST
• Radiated emissions • Conducted disturbances induced by RF field
References: EN 55011; Port : enclosure; Class A, at References: EN 61000-4-6; Port: AC mains and
10m signal lines
• Electrostatic discharge
References: EN 61000-4-2; Port: enclosure
• Surge
References: EN 61000-4-5 ; Port: AC mains
ORDER CODE:
3 Protection relay
Quality certified ISO 9001:2000
COLLEGAMENTO CON COLLEGAMENTO
TOROIDE DI TERRA RESIDUO DI TERRA
ZERO SEQUENCE RESIDUAL
GROUND CONNECTION GROUND CONNECTION
A
LINE B
1A o 5A SECONDARIO TA
1A or 5A SECONDARY CTs
1 IPR-D
TRIP
2
3 AUX.1
4
5 AUX.2
6
7 AUX.3
(SERVICE)
PLC / 8
COMPUTER
RS-485 13
DEVICE 1 COM2
14
RS485
RS-485 15
DEVICE 2 COM3
16 FILTER
BREAKER GROUND
GND DI 1 DI 2 DI 3 STATUS SAFETY
GROUND
17 18 19 20 21 22 23 24 31 32 33 34
1 5
INGRESSI DIGITALI (CONTATTI SECCHI)
RS-232 DRY CONTACT DIGITAL INPUTS
PORT
2>tx
3>rx BARRE DI TERRA
6 9 QUADRO ELETTRICO
5>Gnd SWITCHGEAR 24 - 240 Vac/Vdc
GROUND BUS ALIMENTAZIONE
SUPPLY VOLTAGE
O R I O N I T AL I A S r l
Via G. Orsi 35, 29100 Piacenza [PC] –Italia
Phone: + 39 0523591161 – Fax: + 39 0523593898 – www.orionitalia.com
4 Protection relay
Quality certified ISO 9001:2000
1
8
(1)
(2)
(3)
(4)
(1)
(2)
(3)
(4)
(5)
(6)
(1)
= -------------------- ---
–
=
–
–
= ---
–
– – –
– ----------------------
–
–
–
=
26/6/2019 TR-42 - Vigilancia de Temperatura - Orion Italia
español
TR-42
Relé de Vigilancia de Temperatura
El relé de protección para aplicaciones de temperatura TR-42 se ha
creado como un accesorio de gran importancia para los
transformadores MT trifásicos con aislamiento de aire o resina,
como protección contra temperaturas excesivas peligrosas en la
bobina aislante, en el devanado y para gestionar la intervención de
los ventiladores de refrigeración. . La temperatura es detectada por
3 o 4 detectores térmicos PT 100 DIN 43760, tres de ellos están
ubicados en las bobinas del transformador, el cuarto en el núcleo.
https://www.orionitalia.com/es/control-de-temperatura/tr-42-control-de-temperatura 1/3
26/6/2019 TR-42 - Vigilancia de Temperatura - Orion Italia
para cambiar vistas o para seleccionar valores de
programación.
español
BOTÓN DE EXPLORACIÓN: si se presiona durante 2
segundos en cualquier modo, el TR-42 escaneará entre
cada temperatura de RTD y lo mostrará en la pantalla
cada 5 segundos, lo que permitirá al usuario ver todas
Home Protección y Medición Vigilancia de Temperatura Proyectos y Aplicaciones
las temperaturas automáticamente. Para salir de la
función de "escaneo automático", presione cualquier
botón de echa.
Descargar
Folletos
TR-42 Temperature Control Brochure English
Protocolos de Comunicación
TR-42 Communication Protocol English
Manuales de Instrucciones
TR-42 Temperature Control Instruction Manual English
Software Setup
TR-42 Software Setup
¿Necesita
una Email:
Requiero la solución completa "lista para montar". Para más información, haga click aquí
https://www.orionitalia.com/es/control-de-temperatura/tr-42-control-de-temperatura 2/3
26/6/2019 TR-42 - Vigilancia de Temperatura - Orion Italia
©Todos los derechos reservados Orion Italia srl | VAT IT01552780338 | Via Orsi 35, 29122 Piacenza, Italia | Tel. +39 (0523) 591161 | Contáctenos Política de privacidad | Política de cookies |
orionitalia.com
https://www.orionitalia.com/es/control-de-temperatura/tr-42-control-de-temperatura 3/3
ORION ITALIA TR-42
Temperature
Protection Relay (49) TR-42
Temperature
Protection Relay (49)
INSTRUCTION MANUAL
1.DESCRIPTION
The digital temperature relay TR-42 has been created as accessory of primary importance for resin or air insulated three-phase MT
transformer, as protection against dangerous over temperatures on the insulating coil on the winding and to manage the intervention of
cooling fans. Temperature is detected by 3 or 4 thermal detectors PT 100 DIN 43760, three of them dislocated inside the transformer
coils and the fourth in the core.
Features:
- Display of the actual temperature of the 4 RTD - Alarm of TR-42 failure or PT100 disconnection.
- Display & storage of the highest temperature of each RTD - Automatic fan start every week. (bearings problems)
- 3 programmable output contacts from 0° to 220°C level 1, - Insulated RS-485 communication port (Model TR-42C1 only),
level 2 and FAN control. modbus RTU protocol.
- Automatic and manual fan mode
2. INSTALLATION
Install the equipment according the characteristics of humidity and temperature that has been designed to work in. To avoid noise pickup
and interference the relay should be placed away from high current conductors or sources of strong magnetic fields.. The TR-42 has been
designed for the installation on a panel board with a cutout of 92x92 mm using the fixing accessories that come with the relay. Before
doing the installation, it is reccomended to disconnect the power supply on the working area and qualified technician must do the
installation. Orion Italia recommend to follow security procedures during this installation.
3. WIRING CONNECTION
For the connection, follow the diagram (see on page 4). Here in after the description of the different electric connections :
LED “FAULT”: If “flashing”, will indicate that the flashing “In1, In2, In3, In4”, is
in fault. The fault cause will be showed through the °C display when positioned with AUTO
SCAN
OUTPUT
In 1
RELAYS
the arrow buttons on the faulty sensor: ”Fcc” in case of short circuit and “Fco” for L1
FAULT
In 2
open circuit. L2 In 3
DISPLAY BUTTON: If pressed on the first position in any mode will execute a test FAN In 4
to the display and leds. It is also used for changing views or for selecting SCAN
°C MAX
programming values.
SCAN BUTTON: If pressed for 2 seconds in any mode the TR-42 will scan between °C
FM
SET
each RTD temperature showing it on the display every 5 sec allowing the user to see DISPLAY ENTER FAN
all the temperatures automatically. To exit from the “auto scan” function, press any TEMPERATURE RELAY TR-42
arrow button.
FAN BUTTON: it allows to switch between “always ON” or Automatic Fan Operation. In “always ON” mode, the Fan will be always ON
and the led FAN will be ON.
In automatic mode, the Fan will be ON and the fan led will Blink when one RTD reach the corresponding FAN programmed threshold; the
Fan and the fan led will be OFF when temperature does not reach the corresponding FAN programmed threshold.
LED “AUTO SCAN”: If “on” means the user is in the AUTO SCAN mode.
5.1 °C MODE
In this mode the user will see the actual temperature on the “°C” display and the RTD input number on the “SENSOR” display. To see
the other RTD, press the UP/DOWN buttons. The SET/PROG and °C MAX leds are “off”.
6. MAINTENANCE
The TR-42 relay has been constructed principally with solid state technology, so it needs a simple maintenance. The operations of
maintenance are simplified as follows:
Keep the relay dry and clean
Verify that all terminal blocks are well connected
Check periodically the display test by which all leds will be on
Control periodically the right function of the outputs relays.
7. WARRANTY
Orion Italia, s.r.l. warrants this product to be free from defects in material and workmanship for a period of 1 year from date of shipment.
This warranty does not apply to defects resulting from product modification without Orion Italia's express written consent, or misuse of
any product or part. This warranty also does not apply to incorrect connection of probes, incorrect line power, supply voltage greater
10% Vn. During the warranty period, we will, at our option, either repair or replace any product that proves to be defective.
To exercise this warranty, write or call your local Orion Italia representative, or contact Orion Italia in Piacenza, Italia. You will be given
prompt assistance and return instructions product, transportation prepaid, to the indicated service facility. Repaired or replaced products
are warranted for the balance of the original warranty period, or at least 90 days. ORION ITALIA reserves the right to modify the
equipment or the text of this manual without prior notice.
TECHNICAL SPECIFICATIONS
PROG
TEMPERATURE °C SENSOR
SET
PROG
°C
MAX
90 mm
96 mm
AUTO OUTPUT
SCAN RELAYS In 1
FAULT
L1 In 2
L2 In 3
FAN In 4
SCAN
°C MAX
F °C
M
SET
DISPLAY ENTER FAN
TEMPERATURE RELAY TR-42 L1 L2
114 mm
Red
Red PT-100
White Connections
ELECTRICAL WIRING
COMMUNICATION WIRING Used only for
model TR-42C1
( TR-42C1 only )
COM1
_
Converter +
PROG
TR-42 RS-485 a RS-232
+ DATA (+) 24 12
FAN
- DATA (-) 23 25 26 27 28 11
GND 22 10
Pt1 FAULT
21 9
+ To PC 20 8
RECOMENDATION FOR RS-232 7
- * Max. distance 10 mts 19 Pt2 L2
18 6
17 5
16 4
Pt3 L1
+ Rt 3
15
- 39 40 41 42 2
RECOMENDATION FOR RS-485 14
* Use shielded twisted cable 1
Last device * Use only one (1) point of ground 13 Pt4
* Place a Resistor Rt of 120 ohm
on last device
* Max. distance 1000 m L1 L2 SUPPLY VOLTAGE:
24 - 240 Vac/dc
The ORION ITALIA SERIES implement a subset of the AEG Modicon Modbus serial communication standard.
Many devices support this protocol directly with suitable interface card, allowing direct connection of relays.
The Modbus protocol is hardware-independent; that is, the physical layer can be any of variety of standard
hardware configurations. This includes RS232, RS422, RS485, fibber optics, etc. The ORION ITALIA RELAYS
include a rear terminal RS422/RS485 port. Modbus is a single master multiple slave protocol suitable for a
multi-drop configuration as provided by RS422/RS485 hardware. In this configuration up to 32 slaves can be
daisy-chained together on a single communication channel.
The ORION ITALIA SERIES is always a Modbus slave. It cannot be programmed as a Modbus master. The
Modbus protocol exists in two versions: Remote Terminal Unit (RTU, binary) and ASCII. Only the RTU version
is supported by the Orion Italia Relay. Monitoring, programming and control functions are possible using read
and write register commands.
2 ELECTRICAL INTERFACE.
In a two-wire RS485 link, data flow is bi-directional. The four-wire RS422 port uses two terminals for receive
lines, and two other terminals for transmit lines. As a result, both RS422 and RS485 ports cannot be used at
the same time. The data flow is half duplex. That is, data is never transmitted and received at the same time.
RS485 and RS422 lines should be connected in a daisy chain configuration (avoid star connections) with
terminating resistors and capacitors installed each end of the link, i.e. at the master end and the slave farthest
from the master. That value of the terminating resistors should be equal to the characteristic impedance of the
line. This is approximately 120 Ohms for standard 24 AWG twisted pair wire. The value of the capacitors
should be 1 nF. Shielded wire should always be used to minimize noise. Polarity is important in RS485
communications. See figure below for more details.
Convertitore Convertitore
TR-42 RS-422 a RS-232 TR-42 RS-485 a RS-232
RxA TxA TXA DATA (+)
RxB TxB
TXA RxA TXB DATA (-)
TXB RxB
GND GND
To PC
RxA TXA To PC
RxB
TXA TXB
TXB
COMMUNICATION 1
TEMPERATURE RELAY TR-42
One data frame of an asynchronous transmission to or from a Orion Italia Relay consists of 1 start bit, 8 data
bits, not parity and 1 stop bit. This produces a 10 bit frame. This is important for transmission though modems
at high bit rates (11 bit data frames are not supported by hayes modems at bit rates of greater than 300 bps).
The rear RS485/RS422 external communication port of the Orion Italia Relay supports operation at
1200,2400,4800 and 9600 baud.
A complete request/response consists of the following bytes transmitted as separate data frames:
A message is terminated when no data is received for a period of 3 1/2 character transmission times.
Consequently, the transmitting device must not allow gaps between bytes larger than this interval (about 3ms
at 9600 baud).
SLAVE ADDRESS: This is the first byte of every message. This byte represents the user-assigned address of
the slave device that is to receive the message sent by the master. Each slave device must be assigned a
unique address, and only the addressed slave will respond to a message that starts with its address. In a
master query message the SLAVE ADDRESS represents the address of the slave to which the request is
being sent. In a slave response message the SLAVE ADDRESS is a confirmation representing the address of
the slave that is sending the response. A master query message with a SLAVE ADDRESS of 0 indicates a
broadcast command. All slaves on the communication link will take action based on the message, but none will
respond to the master.
FUNCTION CODE: This is the second byte of every message. Modbus defines function codes of 1 to 127. The
Orion Italia Relay implements some of this functions. See section 7 for details of the function codes supported
by the Orion Italia Relay Series Modbus Protocol. In a master query message the FUNCTIONS CODE tells the
slave what action to perform. In a slave response message, if the FUNCTION CODE sent from the slave is the
same as the FUNCTION CODE sent from the master then the slave performed the function as requested.
DATA: This will be a variable number of bytes on the FUNCTION CODE. This may include actual values,
setpoints or addresses sent by the master to the slave or by the slave to the master. See section 7 for a
description of the Orion-supported functions and the data required for each.
CRC: This is a two byte error checking code. CRC is sent LSByte first followed by the MSByte. The RTU
version of Modbus includes a two byte CRC-16 (16 bit cyclic redundancy check) with every message. The
CRC-16 algorithm essentially treats the entire data stream (data bits only; start, stop and parity ignored) as one
continuous binary number. This number is first shifted left 16 bits and then divided by a characteristic
2 COMMUNICATION
TEMPERATURE RELAY TR-42
polynomial (11000000000000101B). The 16 bit remainder of the division is appended to the end of the
message, MSByte first. The resulting message including CRC, when divided by the same polynomial at the
receiver will give a zero remainder if no transmission errors have occurred. If a Orion Modbus slave device
receives a message in which an error is indicated by the CRC-16 calculation, the slave device will not respond
to the message. A CRC-16 error indicates that one or more bytes of the message were received incorrectly
and thus the entire message should be ignored in order to avoid the slave device performing any incorrect
operation. The CRC-16 calculation is an industry standard method used for error detection. An algorithm is
included in section 5 CRC-16 algorithm to assist programmers in situations where no standard CRC-16
calculation routines are available.
5 CRC-16 ALGORITHM
Once the following algorithm is completed, the working register "A" will contain the CRC value to be
transmitted. Note that this algorithm requires the characteristic polynomial to be reverse bit ordered. The most
significant bit of the characteristic polynomial is dropped, since it does not affect the value of the remainder.
The following symbols are used in the algorithm:
Symbols:
--> data transfer
A 16 bit working register
Alow low order byte of A
Ahigh high order byte of A
CRC 16 bit CRC-16 value
i,j loop counter
(+) logical EXCLUSIVE-OR operator
N total number of data bytes
Di i-th data byte (i=0 to N-1)
G 16 bit characteristic polynomial =1010000000000001(binary) with MSbit dropped and bit
order reversed
shr(x) right shit operator (the LSbit of x is shifted into a carry lag, a '0' is shifted into the MSbit of x,
all other bits are shifted right one location)
Algorithm:
1. FFFF(hex) --> A
2. O --> i
3. O --> j
4. Di (+) Alow --> Alow
5. j + 1 --> j
6. shr (A)
7. Is there a carry ? No: go to step 8
Yes: G (+) A --> A and continue
8. Is j = 8 ? No: go to 5
Yes: continue
9. i + 1 --> i
10. Is i = N ? No: go to 3
Yes: continue
11. A ----> CRC
COMMUNICATION 3
TEMPERATURE RELAY TR-42
6 MESSAGE TIMING
Communication message synchronization is maintained by timing constraints. The receiving device must
measure the time between the reception of characters. If three and one half character times elapse without a
new character or completion of the message, then the communication link must be reset (i.e. all slaves start
listening for a new query message from the master). Thus at 1200 baud a delay of greater than 3.5 x 1/1200 x
10 = 29.2 msec cause the communication link to be reset. At 9600 baud a delay of greater than 3.5 x 1/9600
x 10 = 3.6 ms will cause the communication link to be reset. Most master query messages will be responded to
in less than 50 ms. The maximum time for the Orion Italia Relay to return a slave response message for any
function code will never exceed 1 second.
The second byte of every message is the function code. Modbus defines function codes of 01h to 7Fh. The
Orion Italia Relay Modbus protocol supports some of these functions, as summarized in Table No. 1
TABLE No. 1
Since some programmable logic controllers only support function codes 03h (or 04h) and 10h, most of the
above Modbus commands can be performed by reading from or writing to special addresses in the Orion Italia
Relay memory map using these function codes.
The Orion Italia Relay implementation of Modbus views "holding registers" as any setpoint or actual values
register in the Orion Italia Relay memory map. Registers are 16 (two byte) values transmitted high order byte
first. Thus all Orion Italia Relay setpoints and actual values in the memory map are sent as two byte registers.
This function code allows the master to read one or more consecutive setpoints or actual values from
addressed slave device.
The slave response to these function codes is the slave address, function code, a count of the number of data
bytes to follow, the data itself and the CRC. Each data item is sent as a two byte number with the high order
byte sent first. The CRC is sent as a two byte number with the low order byte sent first.
The maximum number of values of Setpoints that can be read in a single message is 6 word (12 bytes). The
TR-42 Setpoint data starts at address 0100h.
4 COMMUNICATION
TEMPERATURE RELAY TR-42
The maximum number of values of Actual Values that can be read in a single message is 14 word (28 bytes).
The TR-42 Actual Values data starts at address 0200h.
If the function code or the address of any of the requested data is illegal, the slave will not respond the
message. Otherwise, the slave will respond as follows:
This function code allows the master to request TR-42 to perform specific command operations. The
commands Number Listed in the Commands Area of the Relay memory map correspond to operations codes
for function code 05h.
The Slave Response to this function is to echo the entire master transmission.
The operation codes can also be initiated by writing to the commands area of the memory map using function
codes 06h or 10h.
COMMUNICATION 5
TEMPERATURE RELAY TR-42
This function code allows the master to store single setpoints into the memory map of the TR-42.
The Slave Response to this function is to echo the entire master transmission.
6 COMMUNICATION
TEMPERATURE RELAY TR-42
This function code allows the master to modify the contest of a one or more consecutive setpoint in the
addressed slave device. Setpoint registers are 16 bit (two byte) values transmitted high order byte first.
The maximum number of register values (setpoints) that can be stored in a single message is 6 word (12
bytes). The TR-42 Setpoint data starts at address 0100h.
To store the value of one or more setpoints in the internal memory of the TR-42, the following steps shall be
realized:
a) First shall be read all setpoint group ( 6 word = 12 bytes) with function 03h or 04h.
b) Modify the values of setpoints according to setpoint map.
c) Send all setpoint group, 6 word (12 bytes) with function 10h.
The TR-42 response to this function code is to echo the slave address, function code, starting address, the
number of setpoints stored, and the CRC.
Request slave device 11h to write the value 0064h at setpoint address 0100h, and the value 0070h at setpoint
address 0101h.
COMMUNICATION 7
TEMPERATURE RELAY TR-42
If the function code or the address or value of any of the data, is illegal, the slave will not respond to the
message. Otherwise, the slave will respond as follows:
8 COMMUNICATION
TEMPERATURE RELAY TR-42
The data stored in the TR-42 is grouped as Setpoints, Actual Values, Product ID & Commands. Setpoints can
be read and written by a master computer. Actual Values & Product ID are read only, Commands are Write
Only. All setpoints and Actual Values are stored as two bytes values. Addresses are listed in hexadecimal.
Data values (Setpoint ranges, increments, factory value) are in decimal.
MEMORY MAP
COMMUNICATION 9
TEMPERATURE RELAY TR-42
10 COMMUNICATION
TEMPERATURE RELAY TR-42
COMMUNICATION 11
TEMPERATURE RELAY TR-42
12 COMMUNICATION
TEMPERATURE RELAY TR-42
COMMUNICATION 13
Expediente Técnico Final de Actualización y
Modernización del Equipamiento de Media Tensión
de la Subestación Particular Existente SEP 4309 de
propiedad de la Clínica Valle SUR AUNA
10. ANEXOS
Il collaudo eseguito in conformità alle sopraindicate norme è risultato POSITIVO SAREL s.r.l. Client
The test carried out according to the above standards has been POSITIVE
Les essais effectués en conformité aux norms sus-mentionnée sont donné des résultats POSITIFS
Via del Commercio n. 12/14 26900 Lodi ITALY Lodi: 25/01/2020 08:23:35
Tel. +39 (0371) 4906.1 – Fax. +39 (0371) 411422
info@sarel.it - www.sarel.it
VERBALE DI COLLAUDO INTERRUTTORI IN VUOTO
TEST-REPORT VACUUM CIRCUIT BREAKER
RAPPORT D’ESSAI DISJONCTEUR SOUS VIDE
Identificazione Identification Identification
Matricola Codice Descrizione
Serial nr. Code Description
Numéro de série Code Description
008-2020000055-001 APP-008-901/40 WL 24KV 630A 20KA 3s Lat. DX
Caratteristiche Characteristics Caracteristiques
Tensione nominale Tensione di tenuta a 50Hz x 1’ Tensione di tenuta ad impulso Frequenza nominale
Rated voltage Withstand voltage at 50Hz x 1’ Impulse withstand voltage Rated frequency
Tension nominale Tension de tenue à 50Hz x 1’ Tension de tenue sous choc Fréquence nominale
Ur (kV) 24 Ud (kV) 50 Up (kV) 125 fr (Hz) 50/60
Corrente nominale Potere di interruzione nominale Corrente di breve durata ammissibil Potere di chiusura
Rated current Rated short-circuit breaking current Rated withstand short-time current Withstand making capacity
Courant nominal Pouvoir de coupure nominal Courant de courte durèe admissible Pouvoir de fermeture
Ir (A) 630 Isc (kA) 20 Ik (kA) x 3 s 20 Ip (kA) 50
Accessori Accessories Accessoires
Motore caricamolle Sganciatore chiusura Primo sganciatore apertura Secondo sganciatore apertura
Spring charging motor Shunt closing release First shunt opening release Second shunt opening release
Moteur d'armement ressorts Bobine de fermeture Premiere bobine d’ouverture Secondaire bobine d’ouverture
MS -MC -MO1 24 Vac/dc -MO2
Sganciatore minima tensione Sganciatore apertura basso consumo
Undervoltage release -----
Bobine à manque de tension -----
-MU -PTU
Prove eseguite in conformità a Test carried out in accordance with Tests réalisés à conformement
IEC EN 62271-100 IEC EN 62271-100 IEC EN 62271-100
Funzionamento meccanico 10 C-O manual 5 C-O a Vnom 5 C-O a Vmax 5 C-O a Vmin 5 C-O con 5 O-t-C
Mechanical tests 10 C-O manual 5 C-O at Vnom 5 C-O at Vmax 5 C-O at Vmin O azionata da t=300ms
Fonctionnement mècanique 10 C-O manual 5 C-O à Vnom 5 C-O à Vmax 5 C-O à Vmin C dei poli
5 C-O with O 5 O-t-C
driven by poles C t=300ms
5 C-O avec O 5 O-t-C
déclenchée par C t=300ms
contacts princ.
Il collaudo eseguito in conformità alle sopraindicate norme è risultato POSITIVO SAREL s.r.l. Client
The test carried out according to the above standards has been POSITIVE
Les essais effectués en conformité aux norms sus-mentionnée sont donné des résultats POSITIFS
Via del Commercio n. 12/14 26900 Lodi ITALY Lodi: 04/02/2020 16:42:10
Tel. +39 (0371) 4906.1 – Fax. +39 (0371) 411422
info@sarel.it - www.sarel.it
VOLTAGE TRANSFORMER TEST CERTIFICATE
EN ALCE 1003199854 MB00
Sarel S.r.l. Via del Commercio no 12/14 26900
Lodi Lo İtalya
Customer
Test Values
Serial No Primary-Sec. Core Burden % VA δ Value [min] %F Value
1003199854 10000/V3-100/V3 1a1-1n %25VA %80xUn 0 -1 0,18
%100xUn 0 -1 0,18
%120xUn 0 0 0,18
%100VA %80xUn 5 -5 -0,08
%100xUn 5 -5 -0,08
%120xUn 5 -5 -0,09
22900/V3-100/V3 1a2-1n %25VA %80xUn 2,5 0 0,16
%100xUn 2,5 1 0,15
%120xUn 2,5 1 0,15
%100VA %80xUn 10 1 0,01
%100xUn 10 1 -0,01
%120xUn 10 2 -0,01
10000/V3-100/V3 2a1-2n %25VA %5xUn 0 0 0,32
%190xUn 0 0 0,34
%100VA %5xUn 5 -5 0,04
%190xUn 5 -7 0,09
22900/V3-100/V3 2a2-2n %25VA %5xUn 3,75 0 2,26
%190xUn 3,75 13 1,4
%100VA %5xUn 15 0 1,9
%190xUn 15 16 1,05
@1.2 Um (pC) 15 15
1003199854 - 1 / 36
@1.2 Um/V3 (pC) 1 1
1003199854 - 2 / 36
VOLTAGE TRANSFORMER TEST CERTIFICATE
EN ALCE 1003199855 MB00
Sarel S.r.l. Via del Commercio no 12/14 26900
Lodi Lo İtalya
Customer
Test Values
Serial No Primary-Sec. Core Burden % VA δ Value [min] %F Value
1003199855 10000/V3-100/V3 1a1-1n %25VA %80xUn 0 -1 0,18
%100xUn 0 -1 0,18
%120xUn 0 0 0,17
%100VA %80xUn 5 -5 -0,08
%100xUn 5 -5 -0,08
%120xUn 5 -5 -0,09
22900/V3-100/V3 1a2-1n %25VA %80xUn 2,5 0 0,15
%100xUn 2,5 1 0,14
%120xUn 2,5 1 0,14
%100VA %80xUn 10 1 -0,02
%100xUn 10 1 -0,02
%120xUn 10 2 -0,03
10000/V3-100/V3 2a1-2n %25VA %5xUn 0 0 0,6
%190xUn 0 0 0,64
%100VA %5xUn 5 -5 0,3
%190xUn 5 -7 0,34
22900/V3-100/V3 2a2-2n %25VA %5xUn 3,75 0 2,36
%190xUn 3,75 13 1,36
%100VA %5xUn 15 0 1,88
%190xUn 15 16 1,03
@1.2 Um (pC) 10 10
1003199855 - 1 / 36
@1.2 Um/V3 (pC) 1 1
1003199855 - 2 / 36
VOLTAGE TRANSFORMER TEST CERTIFICATE
EN ALCE 1003199856 MB00
Sarel S.r.l. Via del Commercio no 12/14 26900
Lodi Lo İtalya
Customer
Test Values
Serial No Primary-Sec. Core Burden % VA δ Value [min] %F Value
1003199856 10000/V3-100/V3 1a1-1n %25VA %80xUn 0 -1 0,17
%100xUn 0 -1 0,16
%120xUn 0 0 0,16
%100VA %80xUn 5 -5 -0,09
%100xUn 5 -5 -0,1
%120xUn 5 -5 -0,11
22900/V3-100/V3 1a2-1n %25VA %80xUn 2,5 0 0,17
%100xUn 2,5 1 0,16
%120xUn 2,5 1 0,15
%100VA %80xUn 10 1 0,01
%100xUn 10 1 -0,01
%120xUn 10 2 -0,01
10000/V3-100/V3 2a1-2n %25VA %5xUn 0 0 0,25
%190xUn 0 0 0,26
%100VA %5xUn 5 -5 -0,08
%190xUn 5 -7 -0,05
22900/V3-100/V3 2a2-2n %25VA %5xUn 3,75 0 1,93
%190xUn 3,75 13 0,96
%100VA %5xUn 15 0 1,29
%190xUn 15 16 0,6
@1.2 Um (pC) 20 20
1003199856 - 1 / 36
@1.2 Um/V3 (pC) 5 5
1003199856 - 2 / 36
CURRENT TRANSFORMER TEST CERTIFICATE
EN 1003199905 MA00
ALCE
Sarel S.r.l. Via del Commercio no 12/14 26900
Lodi Lo İtalya
Customer
Customer Order No 2020-00-0018
Order No 63830/40 Customer Project No
AB24 Customer Product No
Type AB24 Ratio 100-200/5-5 A
Ith 20kA 1sec Idyn 2,5xIthkA kV 24/50/125kV Altitude <=1000mt
F.[Hz] 50Hz Is cl E Standard IEC 61869-2
1003199905 - 1 / 55
Tester Date Approved Date
UĞUR DURSUN 27.01.2020 MEHMET MASRAFOĞLU 27.01.2020
ALCE 117 R00
1003199905 - 2 / 55
CURRENT TRANSFORMER TEST CERTIFICATE
EN 1003199912 MA00
ALCE
Sarel S.r.l. Via del Commercio no 12/14 26900
Lodi Lo İtalya
Customer
Customer Order No 2020-00-0018
Order No 63830/40 Customer Project No
AB24 Customer Product No
Type AB24 Ratio 100-200/5-5 A
Ith 20kA 1sec Idyn 2,5xIthkA kV 24/50/125kV Altitude <=1000mt
F.[Hz] 50Hz Is cl E Standard IEC 61869-2
1003199912 - 1 / 55
Tester Date Approved Date
UĞUR DURSUN 27.01.2020 MEHMET MASRAFOĞLU 27.01.2020
ALCE 117 R00
1003199912 - 2 / 55
CURRENT TRANSFORMER TEST CERTIFICATE
EN 1003199914 MA00
ALCE
Sarel S.r.l. Via del Commercio no 12/14 26900
Lodi Lo İtalya
Customer
Customer Order No 2020-00-0018
Order No 63830/40 Customer Project No
AB24 Customer Product No
Type AB24 Ratio 100-200/5-5 A
Ith 20kA 1sec Idyn 2,5xIthkA kV 24/50/125kV Altitude <=1000mt
F.[Hz] 50Hz Is cl E Standard IEC 61869-2
1003199914 - 1 / 55
Tester Date Approved Date
UĞUR DURSUN 27.01.2020 MEHMET MASRAFOĞLU 27.01.2020
ALCE 117 R00
1003199914 - 2 / 55