Está en la página 1de 1

VENTANA O VIDRIO EXTERIOR 0921A1

VENTANA O VIDRIO EXTERIOR


0792S: SILICONA TRANSPARENTE
0921G : TIPO ESPECIFICADO GENERAL NOTES FOR METAL STUD PARTITIONS
ENTRE VIDRIO INTERIOR Y EXTERIOR 0844C: COMO SEA ESPECIFICADO 0921F : SOLERA INFERIOR FIJA
0790S: SILICONA TRANSPARENTE ENTRE
AL DECK O LOSA, TÍPICO A. METAL STUD FRAMING:
VIDRIO INTERIOR Y EXTERIOR 0610P 0844M : PINTADO

5mm MAX
0921A2 : SELLADOR DE MÍNIMO UNLESS REQUIRED OTHERWISE ON A SPECIFIC DETAIL ALL METAL STUD FRAMING SHALL BE AS FOLLOWS:
0844T: CANALES EXTRUIDOS DE DE 1/8", TÍPICO
0921G
ALUMINIO PARA VIDRIO DE
0784S :SELLADOR CORTAFUEGO 1. STUD SIZE: PROVIDE STUDS SIZES AS REQUIRED. STUD SIZE NOTATION SHALL BE AS FOLLOWS:
1"X1"X1/8, PARA LA PARTE TABIQUE ESPECIFICADO
EN CADA CARA, TÍPICO. A = ITEM 0921F, 1 5/8" DEEP H = ITEM 0921F, 7/8" DEEP HAT CHANNEL
SUPERIOR Y LA BASE DE LA LUZ, 0844T: CANALES EXTRUIDOS DE ALUMINIO B = ITEM 0921F, 2 1/2" DEEP R = ITEM 0921F, 1/2" DEEP RESILIENT CHANNEL Arquitectos:
ACABADO PARA EMPAREJAR EL PARA VIDRIO DE 1"X1"X1/8, PARA LA PARTE C = ITEM 0921F, 3 5/8" DEEP S4 = ITEM 0921F, 4" DEEP SHAFTWALL SASAKI
SISTEMA DE PERFILERÍA INTERIOR. SUPERIOR Y LA BASE DE LA LUZ, ACABADO D = ITEM 0921F, 6" DEEP S6 = ITEM 0921F, 6" DEEP SHAFTWALL 64 Pleasant Street
0880N1: FIJAR EN EL BOLSILLO DEL PARA EMPAREJAR EL SISTEMA DE PERFILERÍA
VERIFICAR EN OBRA E = ITEM 0540C6, 6" DEEP Z = ITEM 0921F, 1 1/2" DEEP Z-FURRING Watertown, MA 02472
ACRISTALAMIENTO DEL MARCO DE INTERIOR.
0.01 m 0.01 m F =ITEM 0540C8, 8" DEEP Z3 = ITEM 0921F, 3" DEEP Z-FURRING USA
ALUMINIO, CABEZAL Y BASE, ANCLAR 0880N1: FIJAR EN EL BOLSILLO DEL
0.01 m AMBOS A MARCO DE ACRISTALAMIENTO DEL MARCO DE ALUMINIO,
TIPO ESPECIFICADO BASE TABIQUE, TABIQUE ACÚSTICO Tel: +1 (617) 926-3300
2. HEIGHT: EXCEPT FOR TYPE H, R AND Z FURRING ALL STUDS SHALL BE FULL HEIGHT FROM FLOOR TO UNDERSIDE OF FLOOR OR ROOF ABOVE. STUDS SHALL BE
ACRISTALAMIENTO EXISTENTE CABEZAL Y BASE, ANCLAR AMBOS A MARCO DE VERIFICAR EN OBRA RESISTENTE AL FUEGO
VERIFICAR EN OBRA CUT SHORT AT HEAD TRACK/RUNNER TO ALLOW FOR DIFFERENTIAL LIVE LOAD DEFLECTION AS REQUIRED HEREIN. Ingeniero Estructural:
ACRISTALAMIENTO EXISTENTE A. TYPE H, R AND Z FURRING SHALL EXTEND FROM FLOOR TO FOUR-INCHES ABOVE FINISHED CEILING, OR IF THERE IS NO CEILING, TO STRUCTURAL DECK
VIDRIO INTERIOR A DETALLE DE VIDRIADO TABIQUE A DETALLE DE VIDRIADO TABIQUE A DETALLE DE MULLION GCAQ
0921G : TIPO ESPECIFICADO ABOVE. Av. República de Colombia 671, Piso 8
3. SPACING: ALL STUDS SHALL BE SPACED AS REQUIRED TO SUPPORT APPLIED FINISHES AND LOADS, BUT NOT MORE THAN 16" ON CENTER. TYPE "S" STUDS San Isidro, Lima 27
0921F : SOLERA INFERIOR FIJA
TÍPICO DETALLE DE MURO CORTINA SHALL BE SPACED AT 24" ON CENTER. Perú
7 AL DECK O LOSA, TÍPICO 4. DOOR AND BORROWED LIGHT OPENINGS: PROVIDE FULL HEIGHT, UNPUNCHED, DOUBLE STUDS AT ALL JAMB AND HEAD CONDITIONS. Tel: +51 (1) 440-7254

5mm MAX
0784S : SELLADOR CORTAFUEGO 5. TRACKS/RUNNERS : PROVIDE MINIMUM 20 GAUGE TRACKS/RUNNERS TO MATCH STUD SIZE URO. AT HEAD PROVIDE TRACKS/RUNNERS WITH VERTICAL LEGS OF
1:8
EN CADA CARA, TÍPICO. SUFFICIENT HEIGHT TO ACCOMMODATE DIFFERENTIAL LIVE LOAD DEFLECTION DIMENSION BETWEEN FLOORS. Ingeniero Sanitario:
A. PARTITIONS WITHIN 15 FEET OF A COLUMN LINE: ALLOW FOR 1/2" LIVE LOAD DEFLECTION. EQUIPO G S.A.
B. PARTITIONS MORE THAN 15 FEET BUT LESS THAN 30 FEET FROM A COLUMN LINE: ALLOW FOR 3/4" LIVE LOAD DEFLECTION. Av. Javier Prado Este 1544
C. PARTITIONS MORE THAN 30 FEET FROM A COLUMN LINE: ALLOW FOR 1" LIVE LOAD DEFLECTION. San Isidro, Lima 27
6. AT PARTITIONS EXTENDING OVER ROUGH OPENINGS (DOORS, SIDELIGHTS, BORROWED LIGHTS AND THE LIKE), IN EXCESS OF 6'-4" WIDE PROVIDE LIGHT GAUGE Perú
METAL FRAMING (ITEM 54C) OF DEPTH TO MATCH ABUTTING PARTITIONS. PROVIDE CONCEALED DIAGONAL BRACING TO STRUCTURE ABOVE AT 4'-0" OC, Tel: +51 (1) 225-2234
CONFIGURED TO CLEAR STRUCTURAL, MECHANICAL AND ELECTRICAL SYSTEMS.
CARA DE PARED/TABIQUE CARA DE PARED/TABIQUE 0921F8 FURRING 7. AT PARTITIONS FRAMED WITH STUD SIZE C (3 5/8"), PROVIDE DIAGONAL BRACING AT 4'-0" OC EXTENDING FROM 12" ABOVE CEILING TO DECK ABOVE AT 12/12 Ingeniero Eléctrico y mecánico:
0921F : FIJO AL ARMAZÓN DEL 0921C : NO FIJE LA ESTRUCTURA BASE TABIQUE CHANNELS, 7/8”, 20 SLOPE, CONFIGURED TO CLEAR STRUCTURAL, MECHANICAL AND ELECTRICAL SYSTEMS. AT CONSULTORES
VER PLANOS PARA SUSTRATO GA @ 16" OC MAX
TABIQUE ADYACENTE, VER SUSPENDIDA A LA PARED/TABIQUE RESISTENTE AL FUEGO 8. PROVIDE BLOCKING IN PARTITIONS FOR ALL SUPPORTED/ATTACHED ITEMS/SYSTEMS. Av. Los Ingenieros 398

1 1/2"
NOTAS, TÍPICO. DETALLE DE VER NOTAS, TÍPICO. A. PROVIDE WOOD BLOCKING FROM 2'-0" ABOVE FLOOR TO 4'-0" ABOVE FLOOR IN ALL ACCESSIBLE (HANDICAP) TOILET STALLS. La Molina, Lima 12
CIELO RASO, TÍPICO. B. PROVIDE WOOD BLOCKING REQUIRED FOR WALL MOUNTED OWNER PROVIDED EQUIPMENT. COORDINATE WITH OWNER FOR TYPE, SIZE AND LOCATION Perú
0921T : JUNTA DE CONTROL. 0921A1
APLIQUE ANTES DE PINTAR OF BLOCKING REQUIRED. Tel: +51 (1) 348-2612
0921T : JUNTA DE CONTROL. 0921G
0921G : TIPO ESPECIFICADO 9. WHERE FRAMING CONNECTS TO CEMENTITIOUS FIREPROOFING COATED STRUCTURAL STEEL/DECK PROVIDE Z-FURRING FASTENED TO STRUCTURAL
APLICAR ANTES DE PINTAR 0921G : TIPO QUE SEA ESPEFICIDADO TIPO 1V0
STEEL/DECK PRIOR TO APPLICATION OF FIREPROOFING. Z-FURRING SHALL MATCH FIREPROOFING THICKNESS AND SHALL BE CONFIGURED AS REQUIRED FOR Consultores Life Safety:
0921G : TIPO QUE SEA ESPEFICIDADO 0921F : SOLERA INFERIOR FIJA TABIQUE PROPER SUPPORT/ATTACHMENT OF FRAMING. MINIMUM GAUGE AND SPACING SHALL MATCH FRAMING REQUIREMENTS.
AL DECK O LOSA, TÍPICO ESSAC
0921F 10. WHERE A SINGLE LAYER PARTITION TYPE ALIGNS WITH A MULTILAYER LAYER PARTITION TYPE, ADJUST FRAMING LOCATION TO ALIGN FINISHED FACES OF Av. Republica de Panama 4575 Piso 8 Oficina 803-804

6 5/8" @ D, E
0792S : SELLADOR 0921A2 : SELLADOR DE MÍNIMO

4 1/4" @ C
0921T : SELLADOR WALL BOARD ACROSS PARTITION TYPES UNLESS REQUIRED OTHERWISE. Surquillo, Lima 34

5mm MAX
+/- 5MM DE 1/8", TÍPICO 11. FRAMING IS INDICATED DIAGRAMMATICALLY TYPICALLY IN THE DOCUMENTS. IT IS NOT THE INTENT OF THE DOCUMENTS TO DELINEATE EVERY CONDITION Perú
+/- 5MM 0921A3 :SELLADOR ACÚSTICO NOR MEMBER SIZE REQUIRED. THE CONTRACTOR SHALL PROVIDE CONFIGURATIONS OF FRAMING AS REQUIRED BY THE DOCUMENTS TO MAINTAIN THE SHAPE AND Tel: +51 (1) 445-8215 Anexo. 158
EN CADA CARA, TÍPICO. PROFILES OF SURFACES/MATERIALS REQUIRED, COORDINATE WITH THE BUILDING STRUCTURE, AND SUPPORT THE REQUIRED LOADS.
TÍPICA CONEXIÓN CIELO RASO A PARED/TABIQUE TÍPICA CONEXIÓN PARED/TABIQUE A CIELO RASO COLGADO
0921G 12. FORM RADIUS/CURVED WORK TO TRUE RADIUS WITHOUT SEGMENTATION, FACETING, BUCKLING, WARPING OR OTHERWISE ALTERING MEMBER DIMENSION OR Consultores LEED:
APPEARANCE.
TIPO 1C0, 1D0, 1E0 SUMAC
13. PROVIDE FRAMING LOCATED TO CLEAR CEILING/WALL MOUNTED DEVICES/EQUIPMENT. COORDINATE FRAMING WITH DEVICE/EQUIPMENT REQUIREMENTS FOR Av. Javier Pradro Este 318
0921C : CORTAR PERFIL "C" EN JUNTAS DE
0921F : VER NOTAS, DOBLE
CONTROL, PROVEER UN PERFIL TABIQUE CLEARANCES AND SUPPORT. DEVICE SHALL TAKE PRECEDENCE. Piso 6
PERFIL EN JUNTAS DE 14. WHERE UTILITIES SUCH AS ELECTRICAL, TELEDATA, PLUMBING AND THE LIKE CAN NOT BE CONCEALED ABOVE CEILINGS PROVIDE PUNCHED STUDS San Isidro, Lima 27
OMEGA A CADA LADO DE LA JUNTA
CONTROL, TÍPICO. 0921F CONFIGURED TO PERMIT UTILITY DISTRIBUTION WITHIN THE FRAMING. WHERE SUCH PUNCHES ARE PROVIDED THEY SHALL BE ALIGNED WITHIN THE FRAMING TO Perú
DE CONTROL,VER NOTAS, TÍPICO BASE TABIQUE, TABIQUE ACÚSTICO

7 1/4" @ D, E
PERMIT STRAIGHT UTILITY RUNS WITH MINIMAL OFFSETS. COORDINATE WITH UTILITIES FOR SIZE, NUMBER AND LOCATIONS OF PUNCHES REQUIRED.

4 7/8" @ C
Tel: +51(1) 253-5355 Anexo. 10
0921T : JUNTA DE CONTROL. NO RESISTENTE AL FUEGO
APLICAR ANTES DE PINTAR 0921T : JUNTA DE CONTROL. B. WALLBOARD:
APLICAR ANTES DE PINTAR UNLESS REQUIRED OTHERWISE ALL WALLBOARD SHALL BE AS FOLLOWS:
0921G : TIPO QUE SEA
ESPEFICIDADO 0921G : TIPO QUE SEA 0921G : TIPO ESPECIFICADO
ESPEFICIDADO 0921G 1. THICKNESS: 5/8" UNLESS REQUIRED OTHERWISE.
TIPO 2C0, 2D0, 2E0 2. HEIGHT: ALL GYPSUM WALL BOARD SHALL EXTEND FULL HEIGHT OF PARTITION FROM SLAB TO LIVE LOAD DEFLECTION DIMENSION FROM DECK.
0792S : SELLADOR 0921T : SELLADOR

5mm MAX
0921F : SOLERA INFERIOR FIJA 3. BOARD TYPE: PROVIDE FIRE-RESISTIVE CORE WALLBOARD (ITEM 0921G) FOR ALL PARTITION TYPES EXCEPT AS NOTED HEREIN:
+/- 5MM +/- 5MM
AL DECK O LOSA, TÍPICO TABIQUE 0921F A. SHAFTWALL LINER BOARD: PROVIDE AT ALL SHAFTWALL (TYPE S) PARTITIONS ON THE SHAFT SIDE OF THE PARTITION.
B. HIGH-STRENGTH CEILING BOARD: PROVIDE FOR ALL CEILING/SOFFIT BOARD.
TÍPICO MONTAJE DE CIELO RASO/SOFFIT TÍPICO CIELO RASO COLGADO

7 1/4" @ D, E
C. BACKER-BOARD: PROVIDE AS THE FIRST LAYER (NOT EXPOSED) AT ALL MULTIPLE LAYER APPLICATIONS.

4 7/8" @ C
D. MOISTURE RESISTANT BOARD: PROVIDE AS OUTER LAYER ON PARTITIONS WHERE FINISH IS PAINT IN TOILET ROOMS. DO NOT USE MOISTURE
TÍPICO DETALLE DE JUNTAS DE CONTROL DE CIELO RESISTANTWALLBOARD ON CEILINGS.
E. ABUSE RESISTANT BOARD: PROVIDE AS OUTER LAYER IN ALL CORRIDORS AND ELEVATOR LOBBIES, AND AT THE FOLLOWING LOCATIONS:
RASO RM. 2-C14 SCHOOL COMMITTEE ROOM
6 NOTA:
1. TABIQUES CON RESISTENCIA AL FUEGO 1 HORA 0921G
RM. 2-E13 BREAK-OUT AREA
1:4 BASE TABIQUE DEBEN CONFORMAR CON LA PRUEBA NO. 465
RM. 2-L15 OPEN AREA
RM. 2-M04 MULTI-PURPOSE ROOM
NO RESISTENTE AL FUEGO 2. TABIQUES ACÚSTICOS: DEBEN TENER UN STC RM. 2-N08 CALL CENTER
RATING DE 40 MIN. RM. 2-R04 OPEN OFFCE
NOTA: SE UTILIZÓ TABIQUE CON DOBLE CAPA SOLO COMO EJEMPLO. VER RM. 6-E11 PREFUNCTION SPACE
0929F2: ARMAZÓN DE PERFILES A SOPORTAR CIELO NOTAS PARA DETALLES RESPECTO LA CANTIDAD DE CAPAS. TIPO 1C1, 1D1, 1E1 F. IMPACT-RESISTANT BOARD: PROVIDE AS OUTER LAYER IN ALL STORAGE ROOMS.
RASO A 4'-0" CTRO., COLGADO DE LA ESTRUCTURA H. CEMENTITIOUS BACKERBOARD: PROVIDE AS SUBSTRATE FOR CERAMIC WALL TILE.
TABIQUE
ENCIMA, PROVEER TRABAS SI ES REQUERIDO, TÍPICO
0921G NOTE: GYPSUM PLASTER BASE, MOISTURE RESISTANT, ABUSE RESISTANT, AND IMPACT RESISTANT BOARD SHALL BE SUBSTITUTED FOR FACE/OUTER LAYER
DETALLE TÍPICO BASE DE TABIQUES OF WALLBOARD IN ACCORDANCE REQUIREMENTS HEREIN AND FINISH SYSTEM(S) REQUIRED. SEE FINISH INFORMATION (PLANS/SCHEDULE) FOR ADDITIONAL

7 7/8" @ D, E
0921L: ENCAJAR ENTRE
3

5 1/2" @ C
REQUIREMENTS.

0.09 m
MONTANTES 0921F
1:8
+/- 125 mm

COLGAR DE LA ESTRUCTURA DISPONIBLE DE PARANTES 4. MULTI-LAYER WALLBOARD: PROVIDE ALTERNATING ORIENTATION (VERTICAL/HORIZONTAL) OF WALLBOARD LAYERS IN MULTI- LAYER PARTITION TYPES.

0.02 m
DIM. REQUERIDA PARA PERMITIR DEFLEXIÓN,
DE TABIQUERÍA DE YESO/DRYWALL VERTICALES, STAGGER JOINTS IN LAYERS EACH WAY. SECURE EACH LAYER TO FRAMING WITH SCREWS.
PARANTES QUE CORRAN PERPENDICULARES Y
DEJANDO SEPARACIONES ENTRE EL ARMAZÓN, TÍPICO 0921A1 : AISLAR VACÍO, TÍPICO.
NOTA: TABIQUES CON RESISTENCIA AL FUEGO 1 C. FIRE-RESISTIVE RATED PARTITIONS:
HORA DEBEN CONFORMAR CON LA PRUEBA NO. U465 0921G SEE PLANS FOR DEFINITION OF SCOPE OF FIRE-RESISTIVE PARTITIONS. ALL FIRE-RESISTIVE PARTITIONS SHALL CONFORM TO THE FOLLOWING:
NOTA: CIELO RASO RESISTENTE AL FUEGO DEBE 0921B: 1/2" PLANCHAS,CAPA INTERIOR Y

12.5MM MINIMUM
0921A3 : SEGÚN DISEÑO UL., TÍPICO.
CONFORMAR CON LA PRUEBA NER-258 O AER-09038 EXTERIOR, SOLO (1) UNA CAPA ES REQUERIDA TIPO 1C2, 1D2, 1E2 1. WHERE AN UNDERWRITERS LABORATORY OR OTHER TESTING AGENCY NUMBER IS INDICATED ON THE PARTITION TYPE DETAIL, THE PARTITION SHALL BE
PARA RESISTENCIA AL FUEGO DE 1 HORA CONSTRUCTED IN STRICT ACCORDANCE WITH THE DICTATES OF THE TESTED ASSEMBLY.
0921F : SOLERA SUPERIOR DEBE SER ATORNILLADA TABIQUE
AL DECK ÚNICAMENTE, NO A LOS PERFILES, 2. OVERSIZE "CUT-OUTS" FOR ELECTRICAL DEVICE BOXES WILL NOT BE PERMITTED.
0921G
TIPO CS4 - RESISTENCIA AL FUEGO DE 1 Y 2 HORAS TÍPICO. 3. PROVIDE FIRESTOP SYSTEM AT ALL PENETRATIONS OF FIRE-RESISTIVE RATED PARTITIONS AND AT ALL OTHER LOCATIONS NECESSARY TO MAINTAIN THE FIRE

8 1/2" @ D, E
RESISTIVE INTEGRITY OF THE ASSEMBLY.

6 1/8" @ C
CIELO RASO RESISTENTE AL FUEGO COLGADO EN SISTEMA DE MEMBRANA 0921F : RECORTE/TRABA ENTRE PERFILES, 4. PROVIDE FIRE RESISTIVE JOINT SYSTEM AT TOP OF ALL FIRE-RESISTIVE RATED PARTITIONS AT DECK ABOVE AND AT CONTROL JOINTS.
0921F 5. WHERE FIRE RATED PARTITION INTERSECTS NON-RATED PARTITION FIRE RATED PARTITION SHALL EXTEND THROUGH NON- RATED PARTITIONS. WHERE TWO
FIJADO A LOS PERFILES, TÍPICO.
FIRE RATED PARTITIONS INTERSECT GREATER FIRE RESISTANCE RATING SHALL EXTEND THROUGH LESSER FIRE RATED PARTITION.
0929F2: PERFILES SE EXTIENDEN DE MANERA
+/- 80 mm

HORIZONTAL ENTRE PERFILES VERTICALES Y O 0921G D. WALLBOARD CONTROL JOINT REQUIREMENTS :


0921A1: EXTENDER HASTA SOLERA SUPERIOR, TÍPICO.
ESTRUCTURA, TÍPICO NOTA: PROVIDE CONTROL JOINTS IN HORIZONTAL AND VERTICAL WALLBOARD SURFACES IN ACCORDANCE WITH THE REQUIREMENTS OF THE SPECIFICATIONS AND AS
1. TABIQUES CON RESISTENCIA AL FUEGO 2 HORAS DEBEN NOTED BELOW. SEE ELEVATIONS AND PLANS FOR JOINT LOCATIONS, OR, WHERE NOT INDICATED, PROVIDE CONTROL JOINTS AS FOLLOWS:
0929B: TIPO QUE SEA ESPEFICIDADO
0921G : ATORNILLAR A LOS PERFILES CONFORMAR CON LA PRUEBA NO. U495 OR NO. U419.
ÚNICAMENTE, VER NOTAS, TÍPICO. 2. TABIQUES ACÚSTICOS: DEBEN TENER UN STC RATING DE 1. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR APPROVAL OF CONTROL JOINT LOCATIONS PRIOR TO INSTALLATION OF FRAMING.
APLICAR ACABADO ESPECIFICADO 52 MIN. 2. PROVIDE CONTROL JOINTS AT 30' MAXIMUM OC. PROVIDE CONTROL JOINTS WHERE WALLBOARD ABUTS DISSIMILAR MATERIALS. CONTROL JOINTS AT
TIPO C1B0 - SIN RESISTENCIA AL FUEGO DISSIMILAR MATERIALS SHALL BE L BEAD/EDGE TRIM AND SEALANT AS SPECIFIED.
TIPO 2C2, 2D2, 2E2 3. WHERE CONTROL JOINTS ARE REQUIRED IN A SURFACE THEY SHALL BE CONFIGURED TO COORDINATE WITH THE BUILDING GEOMETRY/LAYOUT. PROVIDE
DRYWALL EN ARMAZÓN DE PERFILES "C" (ÍTEM 0929F2) TABIQUE ACÚSTICO PERPENDICULAR A LOS VALLES
TABIQUE ADDITIONAL CONTROL JOINTS AT EACH END OF OPENINGS OVER 8' IN ANY DIMENSION.
DEL DECK, SIN RESISTENCIA AL FUEGO 4. PROVIDE CONTROL JOINTS AT THE EDGE OF HORIZONTAL WALLBOARD WHERE IT ABUTS VERTICAL WALLBOARD SURFACES BELOW.
LINEA DE PISO/TECHO ESTRUCTURA 0921F 5. PROVIDE CONTROL JOINTS IN WALLBOARD WHERE CONTROL JOINTS ARE REQUIRED IN FINISHES OR WHERE CONTROL JOINTS OCCUR IN SUBSTRATES.

VARÍA. VER PLANO PARA DIM.


6. PROVIDE CONTROL JOINTS IN ACCORDANCE WITH THE REQUIREMENTS ABOVE AT HORIZONTAL WALL BOARD CEILINGS/SOFFITS.
0929S: COLGANTE DE ALAMBRE A 48" CTRO. A CADA
7. PROVIDE CUSTOM FORMED RADIUS CONTROL JOINT TRIM AT RADIUS WORK. TRIM SHALL BE EXTRUDED ALUMINUM.
LADO, ANCLADO A LA ESTRUCTURA ENCIMA, TÍPICO
DIM. REQUERIDA PARA PERMITIR DEFLEXIÓN,

0929S: LARGERO/SOPORTE DE 1 1/2" DE ESPESOR A E.ACOUSTICAL PERFORMANCE PARTITIONS :


VARÍA

0921G SEE ARCHITECTURAL FLOOR PLANS FOR DEFINITION OF SCOPE OF ACOUSTICAL PERFORMANCE PARTITIONS. ANY PARTITION SYMBOL SHOWN WITH NOTE "A"
48" CTRO., COLGADO DE COLGANTE DE ALAMBRE
SHALL BE BY DEFINITION AN ACOUSTICAL PERFORMANCE PARTITION. ALL ACOUSTICAL PERFORMANCE PARTITIONS SHALL PROVIDE THE STC RATINGS INDICATED
0929R: PERFIL OMEGA A 16" CTRO., AND SHALL CONFORM TO THE FOLLOWING:
12.5MM MINIMUM

PERPENDICULAR AL LARGERO/SOPORTE 0921F : SOLERA SUPERIOR DEBE SER ATORNILLADA AL


+/- 75mm

DECK ÚNICAMENTE, NO A LOS PERFILES, TÍPICO. 1. JOINTS IN WALLBOARD: SHALL BE TAPED AND FINISHED AS REQUIRED BELOW EVEN IN CONCEALED LOCATIONS SUCH AS ABOVE SUSPENDED CEILINGS.
0929B: TIPO QUE SEA REQUERIDO, UTILICE DOBLE 2. ELECTRICAL DEVICES BOXES: BOXES FACING OPPOSITE SIDES OF THE PARTITION SHALL NOT BE LOCATED BACK-TO-BACK OR BE LOCATED WITHIN THE SAME
(2) CAPA EN CIELO RASO DE TIPO C2HO 0921F CAVITY BETWEEN STUDS.
TIPO 1CC1, 1DD1, 1EE1 3. ACOUSTICAL SEALANT: PROVIDE ACOUSTICAL SEALANT IN ACCORDANCE WITH SECTION 07920 AND AS FOLLOWS: No. Descripción Fecha
APLICAR ACABADO ESPECIFICADO 0921F : RECORTE/TRABA ENTRE PERFILES, A. CONTINUOUSLY AROUND PENETRATIONS AT OUTER LAYER OF WALL BOARD AT EACH FACE.
FIJADO A LOS PERFILES, TÍPICO. TABIQUE
TIPO C1H0, C2H0 - SIN RESISTENCIA AL FUEGO B. CONTINUOUSLY BETWEEN CONCRETE FLOORS AND OUTER LAYER OF WALL BOARD AT EACH FACE. REVISIÓN

4 5/8" @ S4, 6 5/8" @ S6


0921B1 C. CONTINUOUSLY BETWEEN TOP OF OUTER LAYER OF WALLBOARD AND DECK ABOVE AT EACH FACE.
DRYWALL EN ESTRUCTURA COLGANTE (ÍTEM 0929S) D. CONTINUOUSLY UNDER BASE RUNNER TRACKS.
0921G : ATORNILLAR A LOS PERFILES 4. ACOUSTICAL INSULATION: PROVIDE ACOUSTICAL INSULATION AS FOLLOWS:
0921S
ÚNICAMENTE, VER NOTAS, TÍPICO. A. BETWEEN STUDS FOR FULL DEPTH AND HEIGHT OF PARTITION.
B. AT TOP OF PARTITION TO FILL THE VOIDS AT METAL DECK INTERFACE. NOTE, IF PARTITION IS ALSO A FIRE RESISTIVE RATED PARTITION FOLLOW NOTES Sello

TÍPICO DETALLE DE CIELO RASO DE DRYWALL HEREIN.


5 TABIQUE PERPENDICULAR A LOS VALLES DEL DECK, SIN RESISTENCIA AL FUEGO C. ACOUSTICAL INSULATION IS NOT TYPICALLY SHOWN IN THE DRAWINGS.
1:8 0921G
NOTE: TABIQUES CON RESISTENCIA AL FUEGO 1 HORA F.TRIM:
DEBEN CONFORMAR CON LA PRUEBA NO. U415 PROVIDE METAL TRIM SCREWED TO FRAMING AT ALL EXPOSED GYPSUM WALLBOARD EDGES OR CORNERS EXCEPT WHERE CEMENTITIOUS BACKERBOARD, ITEM
DIM. REQUERIDA PARA PERMITIR DEFLEXIÓN,

CARA DE PARED/TABIQUE 0921G1, IS REQUIRED. WHERE RADIUS TRIM IS REQUIRED PROVIDE CUSTOM FORMED EXTRUDED ALUMINUM TRIM. WHERE CEMENTITIOUS BACKBOARD, ITEM
CARA DE PARED/TABIQUE TIPO S4, S6 - RESISTENCIA AL FUEGO 1 HORA 0921G1, IS REQUIRED PROVIDE PLASTIC TRIM. NO PAPER OR COMBINATION PAPER/METAL OR PAPER/PLASTIC TRIM SHALL BE PERMITTED/ACCEPTED.
0921F : VER NOTAS, DOBLE
PERFIL EN JUNTAS DE TABIQUE G. FINISH: Plano
0921F : VER NOTAS, DOBLE CONTROL, TÍPICO. 0921F : LAMINA DE ACERO DE 20GA CONTINUA. EN PROVIDE LEVEL 4 FINISH AT ALL EXPOSED GYPSUM WALLBOARD SURFACES EXTENDING TO NOT LESS THAN 4" ABOVE FINISHED CEILING.
12.5MM MINIMUM

PERFIL EN JUNTAS DE PARTE SUPERIOR DEL TABIQUE, 12" ANCHO 0921B1


CONTROL, TÍPICO. 0921G : JUNTA DEBE SER IGUAL A LA MIN, ATORNILLADO AL DECK, EXTENDER
JUNTA DE CONTROL EN LA CAPA 1. PROVIDE LEVEL 1 FINISH AT SURFACES ABOVE CEILINGS, EXCEPT FIRE RESISTIVE RATED PARTITIONS.
0921T : JUNTA DE CONTROL. APLIQUE SOBRE VACÍO, TÍPICO. 2. PROVIDE LEVEL 3 IN MECHANICAL AND ELECTRICAL TYPE ROOMS.
BASE, VER NOTAS, TÍPICO.

7 1/4" @ S6
5 1/4" @ S4
ANTES DE PINTAR, TODA LA 3. PROVIDE LEVEL 3 FINISH AT SURFACES OF FIRE RESISTANCE RATED PARTITIONS ABOVE CEILINGS.
PROFUNDIAD DE CADA CAPA DE 0792S : JUNTA DE CONTROL. APLIQUE 0921F : SOLERA SUPERIOR DEBE SER ATORNILLADA AL DECK 0921S 4. PROVIDE LEVEL 5 FINISH AT THE FOLLOWING LOCATIONS:
0921G, TÍPICO. ANTES DE PINTAR, TODA LA ÚNICAMENTE, NO A LOS PERFILES, TÍPICO. A. ACCENT WALLS IN ALL OFFICES, TEAM ROOMS, CONFERENCE ROOMS, DATA CENTER (RM. NO. 3-E13) AND COMMUNITY ROOMS (RM NOS. 6-K14 AND 6-
PROFUNDIAD DE CADA CAPA DE 0921F : RECORTE/TRABA ENTRE PERFILES, FIJADO A K15).
0921G : TIPO QUE SEA ESPEFICIDADO 0921G, TÍPICO. LOS PERFILES, TÍPICO. 0921G B. ALL GWB SURFACES TO RECEIVE MARKERBOARD PAINT (KEYNOTE 0990M).
0921T : SELLADOR. EN AMBOS C. FURRED GWB SURFACE ON MURAL WALL AT STAIR NO. 1.
+/- 5MM 0792S : SELLADOR LADOS DE LA JUNTA. NOTE: TABIQUES CON RESISTENCIA AL FUEGO 2 HORAS
0921G : ATORNILLAR A LOS PERFILES
+/- 5mm DEBEN CONFORMAR CON LA PRUEBA NO. U415 H. TYPICAL PARTITION DETAILS:
ÚNICAMENTE, VER NOTAS, TÍPICO.
DETAILS DO NOT INDICATE EVERY COMBINATION OF MATERIALS REQUIRED. SEE FLOOR PLAN INDICATIONS FOR PARTITION TYPES REQUIRED.
UNA CAPA, CONEXIÓN CON PARED/TABIQUE DE OTRO MATERIAL DOBLE CAPA, CONEXIÓN CON PARED/TABIQUE DE OTRO MATERIAL TIPO S4, S6 - RESISTENCIA AL FUEGO 2 HORAS
TABIQUE J. WALLBOARD AT EXTERIOR WALL FRAMING:
TABIQUE PARALELO A LOS VALLES DEL DECK, PROVIDE WALLBOARD AT INTERIOR FACE OF ALL EXTERIOR WALL FRAMING EXPOSED TO VIEW OR WHERE REQUIRED FOR ACOUSTICAL OR FIRE RESISTIVE
0921F : VER NOTAS, DOBLE PERFIL EN
0921F : VER NOTAS, DOBLE PERFIL EN SIN RESISTENCIA AL FUEGO REQUIREMENTS. WALLBOARD SHALL CONFORM TO THE REQUIREMENTS HEREIN
AMBOS LADOS DE LA JUNTA DE
AMBOS LADOS DE LA JUNTA DE
CONTROL, TÍPICO. K. CLEANING:
CONTROL, TÍPICO.
0921A1: AISLAR VACÍO, TÍPICO. CLEAN INSIDE OF ALL STUD CAVITIES BEFORE ENCLOSING WALL.
0921G : JUNTA DEBE SER IGUAL A LA CANTIDAD DE CAPAS REQUERIDAS
0921G : TIPO QUE SEA ESPEFICIDADO JUNTA DE CONTROL EN LA CAPA Projecto:
0921F : LAMINA DE ACERO DE 20GA CONTINUA. EN PARTE L.PLYWOOD BACK BOARDS:
AS REQUIRED FOR DEFLECTION,

BASE, VER NOTAS, TÍPICO. TAMAÑO DE LOS PERFILES, VER NOTAS GENERALES
SUPERIOR DEL TABIQUE, 12" ANCHO MIN, ATORNILLADO
0921T : JUNTA DE CONTROL. APLIQUE
ANTES DE PINTAR, TODA LA 0921T : JUNTA DE CONTROL. APLIQUE AL DECK, EXTENDER SOBRE VACÍO, TÍPICO.
PROVIDE 4'x8'x3/4" FIRE-RESISTANT PLYWOOD BACK BOARDS TO LINE ROOM IN TELECOM/DATA ROOMS, ELECTRICAL AND CLOSETS . BACKBOARD SHALL BE
MOUNTED VERTICALLY, 4" ABOVE FLOOR, TIGHT TO PARTITION FACE. WHERE MOUNTED ON MASONRY PARTITION, PAINT FACE OF MASONRY WITH HIGH
NUEVA BIBLIOTECA
12.5MM MINIMUM

PROFUNDIAD DE CADA CAPA DE ANTES DE PINTAR, TODA LA 0921A3 : A 0921G ENTRE LA SOLERA SUPERIOR Y EL CANTIDAD DE CAPAS REQUERIDAS PERFORMANCE INTERIOR COATING TO REDUCE MOISTURE TRANSMISSION. PAINT FACE AND EDGES FLAT BLACK.
0921G, TÍPICO. PROFUNDIAD DE CADA CAPA DE DECK, TÍPICO.
0921G, TÍPICO.
+/- 5MM 0792S : SELLADOR. EN AMBOS 0792S : SELLADOR. EN AMBOS
LADOS DE LA JUNTA.
+/- 5mm
LADOS DE LA JUNTA.
0921F : SOLERA SUPERIOR DEBE SER ATORNILLADA AL DECK Universidad de Lima
ÚNICAMENTE, NO A LOS PERFILES, TÍPICO.
UNA CAPA, RESISTENTE AL FUEGO DOBLE CAPA, RESISTENTE AL FUEGO 2C1 Javier Prado Este Cuadra 46 S/N,
(PRUEBA NO. HW-S-0032 SIM) (PRUEBA NO. WW-S-0004) 0921F : RECORTE/TRABA ENTRE PERFILES, FIJADO A LOS 2A Santiago de Surco Lima 33, Peru
PERFILES, TÍPICO.
NOTAS ESPECIFICAS
0921F : VER NOTAS, DOBLE
0921F : VER NOTAS, DOBLE PERFIL EN JUNTAS DE 0921G : ATORNILLAR A LOS PERFILES A = TABIQUE ACÚSTICO
PERFIL EN JUNSTAS DE CONTROL, TÍPICO. ÚNICAMENTE, VER NOTAS, TÍPICO. S = HUMO Título:
CONTROL, TÍPICO. VER NOTAS GENERALES PARA REQUERIMIENTOS.

0921G : TIPO QUE SEA 0921G : JUNTA DEBE SER IGUAL A LA


JUNTA DE CONTROL EN LA CAPA
0921A1 : EXTENDER HASTA SOLERA SUPERIOR, TÍPICO. RESISTENCIA AL FUEGO TIPO DE PARTICION - DRY
ESPEFICIDADO 1 = 1-HORA
BASE, VER NOTAS, TÍPICO. 2 = 2-HORA WALL
0921T : JUNTA DE CONTROL. 0921T : JUNTA DE CONTROL. VACÍO = SIN RESISTENCIA
APLIQUE ANTES DE PINTAR APLIQUE ANTES DE PINTAR TABIQUE ACÚSTICO PARALELO A LOS VALLES DEL DECK, LA CARA DEL TABIQUE QUE LLEVE LA ANOTACIÓN, ES LA CARA
0792S : SELLADOR. EN AMBOS 0921T : SELLADOR. EN AMBOS CON LA MAYOR CANTIDAD DE CAPAS, SOLO EN CASO DE SER UN
+/- 5 mm SIN RESISTENCIA AL FUEGO
LADOS DE LA JUNTA. LADOS DE LA JUNTA. TABIQUE CON DIFERENTE CANTIDAD DE CAPAS EN SUS CARAS.
+/- 5MM
UNA CAPA, SIN RESISTENCIA AL FUEGO DOBLE CAPA, SIN RESISTENCIA AL FUEGO N° Proyecto: 76389.04 Escala: As indicated
NOTA: SE UTILIZÓ TABIQUE CON DOBLE CAPA SOLO COMO EJEMPLO. VER DIAGRAMAS REPRESENTAN LA CONFIGURACIÓN DE UN TABIQUE TÍPICO.
Dibujado Por: Author
NOTAS PARA DETALLES RESPECTO LA CANTIDAD DE CAPAS. NO TODAS LAS CONFIGURACIONES O REQUISISTOS ESTÁN
NOTA: SOLO UNA CARA DEL TABIQUE ES VISIBLE, JUNTA DE VE SER REPRESENTADOS. VER NOTAS PARA MÁS INFORMACIÓN. Revisado Por: Checker
CONTINUA EN TODAS LAS CARAS DEL TABIQUE, TÍPICO Aprobado Por: Approver
Fecha: 04/29/19

DETALLE TÍPICO JUNTAS DE CONTROL TÍPICO DETALLE DE CABEZAL DE TABIQUES TABIQUES CON PLANCHAS DE YESO
4 2 1 Lámina:
1:4 1:8 1:8
A0-04