Está en la página 1de 6

1:10 mm

WinEve V3.2 Frequencia nominal: 1440 Hz


Página:1 señal de arranque: LINEA 1 GYB IB L1_GYB CORPOELEC EDELCA

t [ms] -100 0 100 200 300 400

D_87B BARRA I
D_87B BARRA II

VAN L1_GYB 22.76 kV/mm

VBN L1_GYB 22.76 kV/mm

VCN L1_GYB 22.76 kV/mm

IA L1_GYB 1.061 kA/mm

IB L1_GYB 1.061 kA/mm

IC L1_GYB 1.061 kA/mm

c3I0_L1_GYB 1.061 kA/mm

IA L2_GYB 0.848 kA/mm

IB L2_GYB 0.848 kA/mm

IC L2_GYB 0.848 kA/mm

c3I0_L2_GYB 0.848 kA/mm

IA_BAUX_2 0.141 kA/mm

IB_BAUX_2 0.141 kA/mm

IC_BAUX_2 0.141 kA/mm

3I0 L2_BAUXILUM 0.141 kA/mm

t [ms] -100 0 100 200 300 400


C:\ARCHIV~1\Wineve\Events\051630.EVE P.I. "B" 14-Mar-2013 07:45:32.830
1:10 mm
WinEve V3.2 Frequencia nominal: 1440 Hz
Página:1 señal de arranque: LINEA 1 GYB IA L1_GYB CORPOELEC EDELCA

t [ms] -100 0 100 200 300 400

VAN L1_GYB 17.07 kV/mm

VBN L1_GYB 17.07 kV/mm

VCN L1_GYB 17.07 kV/mm

IA L1_GYB 0.424 kA/mm

IB L1_GYB 0.424 kA/mm

IC L1_GYB 0.424 kA/mm

VAN L2_GYB 17.07 kV/mm

VBN L2_GYB 17.07 kV/mm

VCN L2_GYB 17.07 kV/mm

IA L2_GYB 0.424 kA/mm

IB L2_GYB 0.424 kA/mm

IC L2_GYB 0.424 kA/mm

IA_BAUX_2 0.028 kA/mm

IB_BAUX_2 0.028 kA/mm

IC_BAUX_2 0.028 kA/mm

3I0 L2_BAUXILUM 0.028 kA/mm

t [ms] -100 0 100 200 300 400


C:\ARCHIV~1\Wineve\Events\051629.EVE P.I. "B" 14-Mar-2013 07:45:32.346
1:10 mm
WinEve V3.2 Frequencia nominal: 1440 Hz
Página:1 señal de arranque: L1_PIB - GYB IB_L1_PIB CORPOELEC EDELCA

t [ms] -100 0 100 200 300 400

VAN_L1_PIB 17.07 kV/mm

VBN_L1_PIB 17.07 kV/mm

VCN_L1_PIB 17.07 kV/mm

IA_L1_PIB 0.848 kA/mm

IB_L1_PIB 0.848 kA/mm

IC_L1_PIB 0.848 kA/mm

3IoL1_PIB 1.697 kA/mm

VAN_L2_PIB 17.07 kV/mm

VBN_L2_PIB 17.07 kV/mm

VCN_L2_PIB 17.07 kV/mm

IA_L2_PIB 0.848 kA/mm

IB_L2_PIB 0.848 kA/mm

IC_L2_PIB 0.848 kA/mm

3IoL2_PIB 0.848 kA/mm

t [ms] -100 0 100 200 300 400


C:\ARCHIV~1\Wineve\Events\032785.EVE GUAYANA "B" CR#2 14-Mar-2013 07:45:32.913
EDELCA, ELECTRIFICACIÓN DEL CARONÍ C.A. 14/Mar/2013
DIVISIÓN DE OPERACIONES 08:23:30 a.m
REPORTE POR PERIODO DEL: 14/03/13 A LAS 07:40:00 AL 14/03/13 A LAS 08:25:00

Fecha Hora Subestación Punto Texto de Alarma Estado


14/03/13 07:41:43 S.GER.80 VOLT.REF CO cambiador de derivaciones falla subiendo hsalas
14/03/13 07:41:47 UNARE115 T2 LB 11:13 I EXCEDIDO LIMITE ALTO = 1781.93AMPS
14/03/13 07:41:47 UNARE115 D9 ALIM 6. PROTECCION DE SOBRECORRIENTE ARRNQ
14/03/13 07:41:47 UNARE115 D9 ENLAC. PROTECCION DE SOBRECORRIENTE ARRNQ
14/03/13 07:41:47 UNARE115 D9 T1 LB 11:13 PROTECCION DE SOBRECORRIENTE ARRNQ
14/03/13 07:41:47 UNARE115 D9 T2 LB 11:13 PROTECCION DE SOBRECORRIENTE ARRNQ
14/03/13 07:41:48 UNARE115 61 ALIM 6 SOBRECORRIENTE DE FASE DISPAR
14/03/13 07:41:48 UNARE115 64 ALIM 6 SOBRECORRIENTE A TIERRA DISPAR
14/03/13 07:41:48 UNARE115 D9 ENLAC. PROTECCION DE SOBRECORRIENTE NORMAL
14/03/13 07:41:48 UNARE115 D9 T1 LB 11:13 PROTECCION DE SOBRECORRIENTE NORMAL
14/03/13 07:41:48 UNARE115 D9 T2 LB 11:13 PROTECCION DE SOBRECORRIENTE NORMAL
14/03/13 07:41:49 UNARE115 T2 LB 11:13 I EXCEDIDO LIMITE ALTO = 691.56AMPS RTN
14/03/13 07:41:49 UNARE115 ALI6 13,8 IA EXCEDIDO LIMITE ALTO = 719.98AMPS
14/03/13 07:41:49 UNARE115 61 ALIM 6 SOBRECORRIENTE DE FASE NORMAL
14/03/13 07:41:50 UNARE115 I D605 ALIM 6 NO AUTORIZADO ABRTO
14/03/13 07:41:50 UNARE115 64 ALIM 6 SOBRECORRIENTE A TIERRA NORMAL
14/03/13 07:41:50 UNARE115 D9 ALIM 6. PROTECCION DE SOBRECORRIENTE NORMAL
14/03/13 07:41:51 UNARE115 ALI6 13,8 IA EXCEDIDO LIMITE ALTO = 0.00AMPS RTN
14/03/13 07:42:04 ARENOSA I Z120 HQT NO AUTORIZADO CERRD
14/03/13 07:45:25 P.IND.B BXL1 115 VB EXCEDIDO LIMITE BAJO = 54.76kV RTN
14/03/13 07:45:28 P.IND.B BXL1 115 VB EXCEDIDO LIMITE BAJO = 0.00kV
14/03/13 07:45:28 P.IND.B 8E OPERACION OSCILOPERTURBOGRAFO ACTUO
14/03/13 07:45:29 P.IND.B 8E OPERACION OSCILOPERTURBOGRAFO NORMAL
14/03/13 07:45:29 P.IND.B 05 GYB1 115 ARRANQUE PP DE DISTANCIA ARRNQ
14/03/13 07:45:29 P.IND.B 06 GYB1 115 ARRANQUE PS DE DISTANCIA ARRNQ
14/03/13 07:45:29 P.IND.B I H805 BXL1 NO AUTORIZADO ABRTO
14/03/13 07:45:29 P.IND.B 05 GYB1 115 ARRANQUE PP DE DISTANCIA NORMAL
14/03/13 07:45:29 P.IND.B 06 GYB1 115 ARRANQUE PS DE DISTANCIA NORMAL
14/03/13 07:45:29 P.IND.B I H1005 PPC1 NO AUTORIZADO ABRTO
14/03/13 07:45:29 P.IND.B I H905 BXL2 NO AUTORIZADO ABRTO
14/03/13 07:45:29 MCGUA115 8E OPERACION OSCILOPERTURBOGRAFO ACTUO
14/03/13 07:45:29 P.IND.B I H605 GYB2 NO AUTORIZADO ABRTO
14/03/13 07:45:29 P.IND.B I H305 SDT NO AUTORIZADO ABRTO
14/03/13 07:45:29 P.IND.B I H405 FRV NO AUTORIZADO ABRTO
14/03/13 07:45:29 P.IND.B 05 GYB2 115 ARRANQUE PP DE DISTANCIA ARRNQ
14/03/13 07:45:29 P.IND.B 06 GYB2 115 ARRANQUE PS DE DISTANCIA ARRNQ
14/03/13 07:45:29 P.IND.B 52 GYB2 115 RECEPCION ALTA FRECUENCIA PP ACTUO
14/03/13 07:45:29 P.IND.B 53 GYB2 115 RECEPCION ALTA FRECUENCIA PS ACTUO
14/03/13 07:45:29 P.IND.B I H705 GYB1 NO AUTORIZADO ABRTO
14/03/13 07:45:30 P.IND.B 05 GYB2 115 ARRANQUE PP DE DISTANCIA NORMAL
14/03/13 07:45:30 P.IND.B 06 GYB2 115 ARRANQUE PS DE DISTANCIA NORMAL
14/03/13 07:45:30 P.IND.B 52 GYB2 115 RECEPCION ALTA FRECUENCIA PP NORMAL
14/03/13 07:45:30 P.IND.B 53 GYB2 115 RECEPCION ALTA FRECUENCIA PS NORMAL
14/03/13 07:45:30 P.IND.B I H130 ACOP NO AUTORIZADO ABRTO
14/03/13 07:45:30 P.IND.B 3D B1 115 PROTECCION DIFERENCIAL DISPAR
14/03/13 07:45:30 P.IND.B 3D B2 115 PROTECCION DIFERENCIAL DISPAR
14/03/13 07:45:30 P.IND.B 3D B1 115 PROTECCION DIFERENCIAL NORMAL
14/03/13 07:45:30 P.IND.B I H1105 PPC2 NO AUTORIZADO ABRTO
14/03/13 07:45:30 P.IND.B 3D B2 115 PROTECCION DIFERENCIAL NORMAL
14/03/13 07:45:30 P.IND.B 17 PPC2 115 DEFECTO PP DE DISTANCIA DEFECT
14/03/13 07:45:30 P.IND.B 8E OPERACION OSCILOPERTURBOGRAFO ACTUO
14/03/13 07:45:30 P.IND.B 17 PPC2 115 DEFECTO PP DE DISTANCIA NORMAL
14/03/13 07:45:30 P.IND.B 8E OPERACION OSCILOPERTURBOGRAFO NORMAL
14/03/13 07:45:30 P.IND.B 0B H805 BXL1 BAJA PRESION DE AIRE ALARMA
14/03/13 07:45:30 P.IND.B S H804 BXL1 SECCIONADOR HACIA BARRA 1 TRNST
14/03/13 07:45:30 P.IND.B I H805 BXL1 NO AUTORIZADO CERRD
14/03/13 07:45:31 ORINOCO 8E OPERACION OSCILOPERTURBOGRAFO ACTUO
14/03/13 07:45:31 P.IND.B FRV 115 VA EXCEDIDO LIMITE MUY BAJO = 115.41kV
14/03/13 07:45:31 P.IND.B FRV 115 VB EXCEDIDO LIMITE BAJO = 0.00kV
14/03/13 07:45:31 P.IND.B FRV 115 VC EXCEDIDO LIMITE MUY BAJO = 116.60kV
14/03/13 07:45:31 P.IND.B FRV 115 P EXCEDIDO LIMITE BAJO = 0.00MW
14/03/13 07:45:31 P.IND.B BXL1 115 VA EXCEDIDO LIMITE MUY BAJO = 114.08kV
14/03/13 07:45:31 P.IND.B BXL1 115 VC EXCEDIDO LIMITE MUY BAJO = 119.34kV
14/03/13 07:45:31 P.IND.B BXL2 115 VA EXCEDIDO LIMITE MUY BAJO = 114.22kV

Pág. 1
EDELCA, ELECTRIFICACIÓN DEL CARONÍ C.A. 14/Mar/2013
DIVISIÓN DE OPERACIONES 08:23:30 a.m
REPORTE POR PERIODO DEL: 14/03/13 A LAS 07:40:00 AL 14/03/13 A LAS 08:25:00

Fecha Hora Subestación Punto Texto de Alarma Estado


14/03/13 07:45:31 P.IND.B PPC1 115 VA EXCEDIDO LIMITE MUY BAJO = 115.13kV
14/03/13 07:45:31 P.IND.B PPC1 115 VC EXCEDIDO LIMITE MUY BAJO = 116.46kV
14/03/13 07:45:31 P.IND.B PPC2 115 VA EXCEDIDO LIMITE MUY BAJO = 115.13kV
14/03/13 07:45:31 P.IND.B PPC2 115 VC EXCEDIDO LIMITE BAJO = 0.00kV
14/03/13 07:45:31 GUAYAN.B 8E INDAC CR1 OSCILOPERTURBOGRAFO ACTUO
14/03/13 07:45:31 GUAYAN.B 8E INDAC CR1 OSCILOPERTURBOGRAFO NORMAL
14/03/13 07:45:31 GUAYAN.B 16 SR81 115 DEFECTO PROTECCION DE DISTANCIA DEFECT
14/03/13 07:45:31 GUAYAN.B 16 SR71 115 DEFECTO PROTECCION DE DISTANCIA DEFECT
14/03/13 07:45:31 P.IND.B B7 H1105PPC2 CIRCUITO DE DISPARO FALLA
14/03/13 07:45:31 GUAYAN.B 16 SR81 115 DEFECTO PROTECCION DE DISTANCIA NORMAL
14/03/13 07:45:31 GUAYAN.B 16 SR71 115 DEFECTO PROTECCION DE DISTANCIA NORMAL
14/03/13 07:45:32 GUAYAN.B 8E OPRCN.CR4 OSCILOPERTURBOGRAFO ACTUO
14/03/13 07:45:32 P.IND.B B7 H1005PPC1 CIRCUITO DE DISPARO FALLA
14/03/13 07:45:32 P.IND.B 1F H805 BXL1 DISCREPANCIA DE POLOS ALARMA
14/03/13 07:45:33 CLARITAS 0D T2 40:23 BAJA TENSION AISLADOR PASATAPA ALARMA
14/03/13 07:45:33 MCGUA115 8E OPERACION OSCILOPERTURBOGRAFO NORMAL
14/03/13 07:45:34 P.IND.B BXL2 115 VC EXCEDIDO LIMITE MUY BAJO = 36.09kV
14/03/13 07:45:34 P.IND.A 64 ALI1 13.8 SOBRECORRIENTE A TIERRA DISPAR
14/03/13 07:45:34 P.IND.A I D105 ALI1 NO AUTORIZADO ABRTO
14/03/13 07:45:35 CLARITAS 0D T2 40:23 BAJA TENSION AISLADOR PASATAPA NORMAL
14/03/13 07:45:35 GUAYAN.B 8E OPRCN.CR4 OSCILOPERTURBOGRAFO NORMAL
14/03/13 07:45:36 P.IND.A 64 ALI1 13.8 SOBRECORRIENTE A TIERRA NORMAL
14/03/13 07:45:41 P.IND.A 4C ALI1 13.8 REENGANCHADOR O RECIERRE ACTUO
14/03/13 07:45:41 P.IND.A I D105 ALI1 NO AUTORIZADO CERRD
14/03/13 07:45:44 P.IND.A 4C ALI1 13.8 REENGANCHADOR O RECIERRE NORMAL
14/03/13 07:46:01 P.IND.B 1F H805 BXL1 DISCREPANCIA DE POLOS NORMAL
14/03/13 07:46:01 P.IND.B 9F BXL1 115 FALLA CIRCUITO DE DISPARO FALLA
14/03/13 07:46:28 P.IND.B I H805 BXL1 EXPIRO TIEMPO DE CONTROL
14/03/13 07:47:43 UNARE115 I D605 ALIM 6 AUTORIZADO CERRD
14/03/13 07:47:43 UNARE115 I D605 ALIM 6. NO AUTORIZADO FUERA
14/03/13 07:48:52 ORINOCO 8E OPERACION OSCILOPERTURBOGRAFO NORMAL
14/03/13 07:50:03 P.IND.B S H804 BXL1 SECCIONADOR HACIA BARRA 1 ABRTO
14/03/13 07:51:05 P.IND.B S H803 BXL1 SECCIONADOR DE LINEA ABRTO
14/03/13 07:54:32 P.IND.B I H605 GYB2 EXPIRO TIEMPO DE CONTROL
14/03/13 07:55:00 P.IND.B I H605 GYB2 EXPIRO TIEMPO DE CONTROL
14/03/13 07:55:57 P.IND.B 10C RTU 88 ESTADO DE LA REMOTA FALLA
14/03/13 07:55:58 P.IND.B I H705 GYB1 EXPIRO TIEMPO DE CONTROL
14/03/13 07:56:03 P.IND.B 10C RTU 88 ESTADO DE LA REMOTA NORMAL
14/03/13 07:56:34 P.IND.B B7 H1005PPC1 CIRCUITO DE DISPARO NORMAL
14/03/13 07:56:38 P.IND.B B7 H1105PPC2 CIRCUITO DE DISPARO NORMAL
14/03/13 07:57:01 P.IND.B I H705 GYB1 AUTORIZADO CERRD
14/03/13 07:57:13 P.IND.B I H130 ACOP AUTORIZADO CERRD
14/03/13 07:57:39 SISTEMA Z PROHIBIDA CO ZONA PROHIBIDA NO VALIDA
14/03/13 07:58:47 SISTEMA Z PROHIBIDA CO ZONA PROHIBIDA NO VALIDA
14/03/13 07:58:51 SISTEMA Z PROHIBIDA CO ZONA PROHIBIDA NO VALIDA
14/03/13 07:58:55 SISTEMA Z PROHIBIDA CO ZONA PROHIBIDA NO VALIDA
14/03/13 07:59:15 SISTEMA Z PROHIBIDA CO ZONA PROHIBIDA NO VALIDA
14/03/13 07:59:17 SISTEMA Z PROHIBIDA CO ZONA PROHIBIDA NO VALIDA
14/03/13 07:59:19 YARACUY I Z450 RE 4 AUTORIZADO ABRTO
14/03/13 07:59:21 SISTEMA Z PROHIBIDA CO ZONA PROHIBIDA NO VALIDA
14/03/13 07:59:23 SISTEMA Z PROHIBIDA CO ZONA PROHIBIDA NO VALIDA
14/03/13 08:00:13 P.IND.B I H605 GYB2 AUTORIZADO CERRD
14/03/13 08:00:38 P.IND.A 64 ALI1 13.8 SOBRECORRIENTE A TIERRA DISPAR
14/03/13 08:00:38 P.IND.A I D105 ALI1 NO AUTORIZADO ABRTO
14/03/13 08:00:39 P.IND.A 64 ALI1 13.8 SOBRECORRIENTE A TIERRA NORMAL
14/03/13 08:00:48 P.IND.A 4C ALI1 13.8 REENGANCHADOR O RECIERRE ACTUO
14/03/13 08:00:48 P.IND.A I D105 ALI1 NO AUTORIZADO CERRD
14/03/13 08:00:52 P.IND.A 4C ALI1 13.8 REENGANCHADOR O RECIERRE NORMAL
14/03/13 08:00:55 P.IND.B I H305 SDT AUTORIZADO CERRD
14/03/13 08:01:22 P.IND.B I H905 BXL2 AUTORIZADO CERRD
14/03/13 08:01:25 P.IND.B BXL2 115 VA EXCEDIDO LIMITE MUY BAJO = 117.80kV RTN
14/03/13 08:01:25 P.IND.B BXL2 115 VC EXCEDIDO LIMITE MUY BAJO = 117.73kV RTN
14/03/13 08:04:53 P.IND.B 8E OPERACION OSCILOPERTURBOGRAFO ACTUO
14/03/13 08:04:54 P.IND.B 05 BXL2 115 ARRANQUE PP DE DISTANCIA ARRNQ
14/03/13 08:04:54 P.IND.B 06 BXL2 115 ARRANQUE PS DE DISTANCIA ARRNQ

Pág. 1
EDELCA, ELECTRIFICACIÓN DEL CARONÍ C.A. 14/Mar/2013
DIVISIÓN DE OPERACIONES 08:23:30 a.m
REPORTE POR PERIODO DEL: 14/03/13 A LAS 07:40:00 AL 14/03/13 A LAS 08:25:00

Fecha Hora Subestación Punto Texto de Alarma Estado


14/03/13 08:04:54 P.IND.B 06 BXL2 115 ARRANQUE PS DE DISTANCIA NORMAL
14/03/13 08:04:54 P.IND.B 05 BXL2 115 ARRANQUE PP DE DISTANCIA NORMAL
14/03/13 08:04:54 P.IND.B 8E OPERACION OSCILOPERTURBOGRAFO NORMAL
14/03/13 08:05:51 SISTEMA Z PROHIBIDA CO ZONA PROHIBIDA NO VALIDA
14/03/13 08:05:59 SISTEMA Z PROHIBIDA CO ZONA PROHIBIDA NO VALIDA
14/03/13 08:06:25 GURI4B80 I Z120 GE 11 NO AUTORIZADO ABRTO
14/03/13 08:06:35 GURI4B80 I Z320 GE 11 NO AUTORIZADO ABRTO
14/03/13 08:06:47 GURI4B80 48 GEN11 PROTECCION DE RESPALDO NORMAL
14/03/13 08:06:47 GURI4B80 B9 GEN11 PROTECCION PRINCIPAL NORMAL
14/03/13 08:06:47 GURI4B80 S Z1193 GE11 SECCIONADOR DE LINEA TRNST
14/03/13 08:07:11 GURI4B80 S Z1193 GE11 SECCIONADOR DE LINEA CERRD
14/03/13 08:07:22 CALLAO40 10C RTU 04 ESTADO DE LA REMOTA FALLA
14/03/13 08:07:53 P.IND.B I H1105 PPC2 AUTORIZADO CERRD
14/03/13 08:07:55 P.IND.B PPC2 115 VA EXCEDIDO LIMITE MUY BAJO = 117.30kV RTN
14/03/13 08:07:55 P.IND.B PPC2 115 VC EXCEDIDO LIMITE BAJO = 118.08kV RTN
14/03/13 08:08:28 CALLAO40 10C RTU 04 ESTADO DE LA REMOTA NORMAL
14/03/13 08:09:32 P.IND.B I H1005 PPC1 AUTORIZADO CERRD
14/03/13 08:09:34 P.IND.B PPC1 115 VA EXCEDIDO LIMITE MUY BAJO = 117.66kV RTN
14/03/13 08:09:34 P.IND.B PPC1 115 VC EXCEDIDO LIMITE MUY BAJO = 118.08kV RTN
14/03/13 08:10:00 MCGUA115 S H381A MC23 SECCIONADOR DE LINEA TRNST
14/03/13 08:10:04 MCGUA115 S H381A MC23 SECCIONADOR DE LINEA ABRTO
14/03/13 08:11:01 MCGUA115 2E H383/4/6 FALLA ALIMENTACION MOTOR NORMAL
14/03/13 08:11:07 SISTEMA Z PROHIBIDA CO ZONA PROHIBIDA NO VALIDA
14/03/13 08:11:40 S.GER.80 VOLT.REF CO cambiador de derivaciones falla bajando srodrig
14/03/13 08:12:09 SISTEMA Z PROHIBIDA CO ZONA PROHIBIDA NO VALIDA
14/03/13 08:12:17 SISTEMA Z PROHIBIDA CO ZONA PROHIBIDA NO VALIDA
14/03/13 08:12:17 SISTEMA Z PROHIBIDA CO ZONA PROHIBIDA NO VALIDA
14/03/13 08:12:21 SISTEMA Z PROHIBIDA CO ZONA PROHIBIDA NO VALIDA
14/03/13 08:12:23 SISTEMA Z PROHIBIDA CO ZONA PROHIBIDA NO VALIDA
14/03/13 08:12:25 SISTEMA Z PROHIBIDA CO ZONA PROHIBIDA NO VALIDA
14/03/13 08:12:25 SISTEMA Z PROHIBIDA CO ZONA PROHIBIDA NO VALIDA
14/03/13 08:13:14 P.IND.B 52 GYB2 115 RECEPCION ALTA FRECUENCIA PP ACTUO
14/03/13 08:13:14 P.IND.B 53 GYB2 115 RECEPCION ALTA FRECUENCIA PS ACTUO
14/03/13 08:13:14 P.IND.B 52 GYB2 115 RECEPCION ALTA FRECUENCIA PP NORMAL
14/03/13 08:13:14 P.IND.B 53 GYB2 115 RECEPCION ALTA FRECUENCIA PS NORMAL
14/03/13 08:13:14 P.IND.B 8E OPERACION OSCILOPERTURBOGRAFO ACTUO
14/03/13 08:13:14 P.IND.B I H405 FRV AUTORIZADO CERRD
14/03/13 08:13:16 P.IND.B FRV 115 VA EXCEDIDO LIMITE MUY BAJO = 118.22kV RTN
14/03/13 08:13:16 P.IND.B FRV 115 VB EXCEDIDO LIMITE BAJO = 118.50kV RTN
14/03/13 08:13:16 P.IND.B FRV 115 VC EXCEDIDO LIMITE MUY BAJO = 118.22kV RTN
14/03/13 08:13:17 GUAYAN.B 8E INDAC CR1 OSCILOPERTURBOGRAFO ACTUO
14/03/13 08:13:17 GUAYAN.B 8E INDAC CR1 OSCILOPERTURBOGRAFO NORMAL
14/03/13 08:13:17 P.IND.B 8E OPERACION OSCILOPERTURBOGRAFO NORMAL
14/03/13 08:14:42 S.GER.80 I Z150 RE 1 AUTORIZADO ABRTO
14/03/13 08:14:45 SISTEMA Z PROHIBIDA CO ZONA PROHIBIDA NO VALIDA
14/03/13 08:14:45 SISTEMA Z PROHIBIDA CO ZONA PROHIBIDA NO VALIDA
14/03/13 08:14:46 S.GER.80 RE 1 800 I EXCEDIDO LIMITE BAJO = 0.00AMPS
14/03/13 08:16:31 CLARITAS E6 T1 40:23 FUERA DE PASO REGULACION PARALELO ALARMA
14/03/13 08:17:25 CLARITAS E6 T1 40:23 FUERA DE PASO REGULACION PARALELO NORMAL
14/03/13 08:17:47 HORQUETA 34 Z820 MANDO LOCAL:REMOTO DE INT REMOTO
14/03/13 08:17:47 HORQUETA 34 VOLT.REF MANDO LOCAL:REMOTO DE INT REMOTO
14/03/13 08:18:30 GURI4B80 I Z320 GE 11 NO AUTORIZADO CERRD