MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
Contenido
INTRODUCCIÓN ............................................................................................. 3
OBJETIVO........................................................................................................ 3
JUSTIFICACIONES DE DISEÑO ..................................................................... 3
NORMAS CONSIDERADAS ................................................................. 3
ESPECIFICACIONES DE LOS MATERIALES ...................................... 3
Acero de refuerzo .............................................................................................. 3
Concreto ............................................................................................................ 3
Suelo de cimentación ........................................................................................ 4
2
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
INTRODUCCIÓN
OBJETIVO
Presentar la metodología respecto del diseño estructural que aplica para la construcción
de las canalizaciones en concreto para el cableado de control y protecciones para la
ampliación en la Subestación Santa Helena 115 kV, localizada en el municipio de
Villavicencio, en el departamento del Meta.
JUSTIFICACIONES DE DISEÑO
NORMAS CONSIDERADAS
Fundación: NSR-10
Hormigón: NSR-10
Categoría de uso: Institucional
Acero de refuerzo
El acero de refuerzo utilizado en el diseño es aquel que cumple con la Norma ASTM
A-706, el cual tiene como límite de fluencia mínimo fy=420 Mpa (4200 kgf/cm2)
incluye desde diámetro 3/8” o Numero 3 hasta 1” o Numero 8.
Concreto
La estructura se diseñó tomando para el concreto un valor del módulo de elasticidad
Ec de acuerdo con la Ecuación 1 extraída de la NSR-10 (Sección C.8.5.1). Para el
3
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
𝐸𝑐 = 4700√𝑓 ′ 𝐶 Ecuación 1
Suelo de cimentación
Como dato inicial se parte del estudio de suelos consignado en la ingeniería básica
entregada por el cliente, ya que es pertinente por la proximidad a las obras actuales
construidas bajo las mismas condiciones y parámetros.
El estudio de suelos referido es el documento IP285-SE-SUR-GEN-ES-0050 donde se
consignan las siguientes propiedades:
EVALUACIÓN DE CARGAS
Las cargas se establecen como las debidas al peso propio de los elementos constructivos
a emplear en la construcción de las canalizaciones, como el concreto, cargas de
transporte de equipos, y tránsito de vehículos.
4
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
e B e
0.60
H
0.60
=
x
A
B d
Datos:
Espesor piso (d) = 0.150 m
Espesor paredes (e) = 0.150 m
Pestaña de estabilización (x) = 0.000 m
Concreto = 210.000 kg/cm2
Peso Unitario Concreto = 2400.000 kg/m3
Acero de refuerzo = 4200.000 kg/cm2
Recubrimiento acero = 0.075 m
Peso Unitario Relleno = 2260.000 kg/m3
Capacidad carga terreno = 2800.000 kg/cm2 (seco)
Capacidad carga terreno = 2800.000 kg/cm2 (saturado)
Angulo fricción interna = 25.000 °
Nivel de saturación = 0.600 m Y2
Coeficiente = 0.577
Ancho efectivo = 0.750 m
Altura de relleno = 0.600 m
Cálculos de Momentos
5
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
Seguridad contra la
subpresión
Peso del piso estructura = 324.000 kg/m
Peso de la pared = 216.000 kg/m
Peso del suelo = 0.000 kg/m
Fuerza de Subpresión = 675.000 kg/m
Factor de Seguridad = 1.120
Comprobación de Factor = Aceptado
Cálculos de Momentos
Presión del agua = 180.000 kg/m
Peso del Agua en el piso = 600.000 kg/m
Momento en Punto A = 36.000 kgm/m
Momento en Punto B = 42.188 kgm/m
6
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
Paredes laterales
a. Parte Externa
Iteraciones
b. Parte Interna
Iteraciones
Piso
7
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
a. Parte Superior
Iteraciones
b. Parte Inferior
Iteraciones
Resumen de Refuerzos
8
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
Piso
Paredes laterales
Piso de Estructura
Control de Agrietamiento
Paredes Laterales
Espaciamiento entre barras 250 mm
Recubrimiento 75 mm
Diámetro de Acero Asumido 9.525 mm
Espesor de paredes (h) 150 mm
Ancho de paredes 1000 mm
fy 420 N/mm2
f'c 21 N/mm2
Relación Modular (n) 18
acr 143.52 mm
Altura efectiva de la sección (d) 70.24 mm
Constante (r) 0.004058
Profundidad del eje neutro (X) 22.201 mm
Ancho de la rajadura categoría
1
9
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
10
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
Resumen de refuerzo
Refuerzo Refuerzo
Elemento
longitudinal* transversal**
Muros #3 @ 0.25 m (Max) #3 @ 0.25 m (Max)
Losa de fondo #3 @ 0.25 m (Max) #3 @ 0.25 m (Max)
cárcamo externo
#4 @ 0.20 m (Max) #4 @ 0.20 m (Max)
Losa de fondo
cárcamo interno
Tapas cárcamo 2#3 U. E. 5#3 U. E.
externo
11
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
338msnm Cota 2 H
e 0.2m
L2 0.6m
337.4msnm Cota 3
e 0.2m
e L1 e
0.6m
0.15m 0.15m
12
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
Datos
Cota Nivel Hidráulico (Cota 4) 0.60 msnm Peso Específico del Relleno 2260 kg/m3
Cota Cara Superior (Cota 2) 338.00 msnm Angulo Reposo Relleno 30 °
Cota Piso (Cota 3) 337.40 msnm Presión Admisible Fundación 2.80 kg/cm2
Espesor de losa inferior (e) 0.20 m Acero de refuerzo (f'y) 3.000 kg/cm2
Espesor de muros (e) 0.15 m Tren de Carga 5
3
Ancho de Box (L1) 0.60 m Peso Específico del Concreto 2400 kg/m
Cota de Terreno (Cota 1) 338.01 msnm Carga por impacto 590.77 kg/m
Espesor de losa canal (ec) 0.20 m
Factor de Presión Neutra 0.5000
Solución Distancia entre ejes 4.27 m
Altura interna Box (L2) 0.60 m Carga eje posterior 29029.91 kg
Sobrecarga 1500.00 kg/m Carga eje delantero 7257.48 kg
Carga por impacto 590.77 kg/m Coeficiente de Impacto 0.3938
Peso de losa Superior 432 kg/m Carga Relleno placa superior 22.60 kg/m2
Peso de losa Inferior 432 kg/m
Peso de la Estructura 1296 kg/m
Análisis Estructural
Carga Losa Superior 2833.37 kg/m
Reacción del Terreno 4489.37 kg/m2
Carga Losa Inferior 2833.37 kg/m2
Carga Pared Lateral Superior 11.30 kg/m2
Carga Pared Lateral Inferior 89.30 kg/m2
Momentos de Empotramiento
Losa Superior 151.11 kg-m
Losa Inferior 151.11 kg-m
Pared Lateral Punto Superior 1.99 kg-m
Pared Lateral Punto Inferior 2.72 kg-m
Momentos Iniciales
2.72 -2.72
D
-151.11
C
151.11
89.30
D C 89.30
2833.37 2833.37
13
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
A-B A 0.5 151.11 0 151.11 -74.560 37.280 113.83 -37.189 76.64 0.00
B 0.5 -151.11 0 -151.11 74.560 -37.280 -113.83 37.189 -76.64 0.00
B-C B 0.5 1.99 0 1.99 74.560 -37.097 39.46 37.189 76.64
C 0.5 -2.72 0 -2.72 -74.195 37.280 -39.64 -37.189 -76.83 0.00
C-D C 0.5 151.11 0 151.11 -74.195 37.097 114.02 -37.189 76.83
D 0.5 -151.11 0 -151.11 74.195 -37.097 -114.02 37.189 -76.83 0.00
D-A D 0.5 2.72 0 2.72 74.195 -37.280 39.64 37.189 76.83
A 0.5 -1.99 0 -1.99 -74.560 37.097 -39.46 -37.189 -76.64
14
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
Momentos (kg-m)
X (L - X) Losa Losa
Superior Inferior
0.00 0.75 0.00 0.00
0.04 0.71 40.23 40.23
0.08 0.67 75.93 75.93
0.12 0.63 107.10 107.10
0.16 0.59 133.73 133.73 Diagrama de Momentos Flectores
0.2 0.55 155.84 155.84
0.24 0.51 173.40 173.40
0.28 0.47 186.44 186.44
0.32 0.43 194.94 194.94
0.36 0.39 198.90 198.90
0.40 0.35 198.34 198.34
76.64 76.64 76.64
75.93
76.64
40.23
Distribución de Momentos Losas Laterales
- 0.00 0.00
2 2 76.64
X (L - X) X (L - X) L + X X (L - X )MOMENTOS B
0.00 0.80 0.00 0.80 0.00 0.00 76.64
A
0.04 0.76 0.03 0.84 0.03 0.59
0.08 0.72 0.06 0.88 0.05 1.15
0.12 0.68 0.08 0.92 0.08 1.68
0.16 0.64 0.10 0.96 0.10 2.18
0.20 0.60 0.12 1.00 0.12 2.63
0.24 0.56 0.13 1.04 0.14 3.03
0.28 0.52 0.15 1.08 0.16 3.38 -4.0 4.02
0.32 0.48 0.15 1.12 0.17 3.66
0.36 0.44 0.16 1.16 0.18 3.88
0.40 0.40 0.16 1.20 0.19 4.02
0.44 0.36 0.16 1.24 0.20 4.09
0.48 0.32 0.15 1.28 0.20 4.06
0.52 0.28 0.15 1.32 0.19 3.95
0.56 0.24 0.13 1.36 0.18 3.73
0.60 0.20 0.12 1.40 0.17 3.41
0.64 0.16 0.10 1.44 0.15 2.97 76.83 C
0.68 0.12 0.08 1.48 0.12 2.42 76.83 -76.83
0.72 0.08 0.06 1.52 0.09 1.75 D 76.83 76.83
0.76 0.04 0.03 1.56 0.05 0.94 76.83
0.80 0.00 0.00 1.60 0.00 0.00 0.00 0
-40.23
-75.93
15
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
Momentos de Empotramiento
Losa Superior 544.56 kg-m
Losa Inferior -544.56 kg-m
Pared Lateral Punto Superior 15.07 kg-m
Pared Lateral Punto Inferior 22.30 kg-m
22.30 -22.30
689.30
D C 689.30
D
-544.56 544.56
C
-11617.23 -11617.23
Coeficiente
Moment Incremen Moment Distribució
Tramo Nodos de Distibución 2 Total Diferencia
o Inicial to o n1
Distribución
A-B A 0.5 544.56 0 544.56 -264.745 132.373 412.184 -131.469 280.716 0.00
B 0.5 -544.56 0 -544.56 264.745 -132.373 -412.184 131.469 -280.716 0.00
B-C B 0.5 15.07 0 15.07 264.745 -130.565 149.247 131.469 280.716
C 0.5 -22.30 0 -22.30 -261.130 132.373 -151.056 -131.469 -282.524 0.00
C-D C 0.5 544.56 0 544.56 -261.130 130.565 413.993 -131.469 282.524
D 0.5 -544.56 0 -544.56 261.130 -130.565 -413.993 131.469 -282.524 0.00
D-A D 0.5 22.30 0 22.30 261.130 -132.373 151.056 131.469 282.524
A 0.5 -15.07 0 -15.07 -264.745 130.565 -149.247 -131.469 -280.716
16
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
17
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
799.26
280.72 280.72
280.72
164.96
0.00
0.00
- A B
280. 280.72
72
-
28.0 28.02
2
- D C
282. 00.00 282.52
52 -
164.96
-
- - 282.52
282.52 282.52
-
799.27
18
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
Cálculo de Refuerzos
19
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
Resumen de Refuerzos
Paredes
Losa Inferior
20
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
Losa Superior
Paredes
Máximo esfuerzo cortante unitario (vmax ) 7.3612 kg/cm2
Fuerza Cortante Máxima (V) 187.580 kg
Esfuerzo cortante unitario (v) 0.1251 kg/cm2
Comprobación de esfuerzo cortantes Satisface la condicón de Diseño
Losa Inferior
Control de Agrietamiento
Losa Superior
Espaciamiento entre barras 250 mm
Recubrimiento 100 mm
Diámetro de Acero Asumido 12.7 mm
Espesor de paredes (h) 200 mm
Ancho de paredes 1000 mm
fy 420 N/mm2
f'c 30 N/mm2
Relación Modular (n) 15
acr 157.77 mm
Altura efectiva de la sección (d) 93.65 mm
Constante (r) 0.005411
3
Esfuerzo de Tracción en el Acero 321.728 N/mm2
Término
de Refuerzo
de Apoyo
(Fs ) izquierdo 1 2.521
Término de Apoyo izquierdo 2 11.425
Función de Fs -8.662
Área de Acero de Refuerzo en
Tracción (A s )
3.046 mm2/m
Esfuerzo de compresión en el 0.06345 N/mm2
Condición(f1cb)
Concreto Cumple con la Condición
Condición 2 Cumple con la Condición
Condición 3 Cumple con la Condición
21
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
Paredes Laterales
Espaciamiento entre barras 250 mm
Recubrimiento 70 mm
Diámetro de Acero Asumido 12.7 mm
Espesor de paredes (h) 150 mm
Ancho de paredes 1000 mm
fy 420 N/mm2
f'c 30 N/mm2
Relación Modular (n) 15
acr 140.12 mm
Altura efectiva de la sección (d) 73.65 mm
Losa Inferior
Espaciamiento entre barras 250 mm
Recubrimiento 100 mm
Diámetro de Acero Asumido 12.7 mm
Espesor de paredes (h) 200 mm
Ancho de paredes 1000 mm
fy 420 N/mm2
f'c 30 N/mm2
Relación Modular (n) 15
acr 157.77 mm
Altura efectiva de la sección (d) 93.65 mm
Constante (r) 0.00541065
22
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
Resumen de refuerzo
Refuerzo Refuerzo
Elemento
longitudinal* transversal**
#4 @ 0.25 m #3 @ 0.25 m
Muros
(Max) (Max)
Losa de #4 @ 0.25 m #4 @ 0.25 m
fondo (Max) (Max)
#4 @ 0.25 m #4 @ 0.25 m
Losa superior
(Max) (Max)
23
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
ANALISIS ESTRUCTURAL
R1= 12.15 KN M1= 24.30 KN-m
R2= 12.15 KN M2= 24.30 KN-m
MmaxCL= 6.08 KN-m
Av= 0.71
refuerzo barra N° barra N° 3
REFUERZO PRINCIPAL
ρ Calc. ρ real As S
ρ+ 0.0032 0.0033 4.75 15.00 15cm 1Barra N° 3 /15cm
ρ+ 0.0032 0.0033 4.75 15.00 15cm 1Barra N° 3 /15cm
ρ- 0.0008 0.0033 4.75 15.00 15cm 1Barra N° 3 /15cm
24
MEMORIA DE CÁLCULO CIMENTACIÓN CANALIZACIONES DE PATIO (CÁRCAMOS,
BANCO DE DUCTOS Y BOX CULVERT)
CONCLUSIONES
Se define el diseño para las canalizaciones en concreto que se construirán para la ampliación
de la subestación Santa Helena pórtico 3, los cárcamos externos se unen al cárcamo existente
que viene de la caseta de control y comunica con la caseta de tableros 2, y el tramo que sale
de la caseta 2 y comunica con las bahías a lo largo del patio, el paso de vía que consta del
box culvert, comunica el cárcamo a construir que viene de la caseta de control y comunica a
la caseta de tableros 2.
Las canalizaciones a construir serán cubiertas con tapas en concreto para cárcamo externo,
tapas metálicas para cárcamo interno y placas para box culvert.
RECOMENDACIONES
Garantizar un buen curado del concreto, de acuerdo con lo establecido por la NSR10.
El material para cualquier relleno del proyecto deberá cumplir con las siguientes
especificaciones de material seleccionado: Limite liquido ‹ 25%, Índice de plasticidad ‹ 6%,
porcentaje material que pasa el tamiz de 4.75 mm: entre 30% y 70%, porcentaje material
que pasa el tamiz 0.074 mm entre 0 y 15%, compactado al 95% P.M.
Los recubrimientos mínimos serán: concreto en contacto con el terreno 7,5 cm y 4,0 cm en
otras condiciones.
En las zonas donde la estructura esté en contacto directo con el suelo, garantizar la fundición
de un solado de limpieza en concreto de 𝑓’𝑐 = 14 𝑀𝑝𝑎 de al menos 5 cm.
Todos los elementos que componen la estructura, serán construidos con un concreto con
resistencia nominal de 𝑓′𝑐 = 21 𝑀𝑝𝑎.