LOS TRES PRIMEROS SE REFIEREN A LA CALIDAD DE LA POTENCIA ELECTRICA (POWER QUALITY) EXPRESADA COMO
EL PRODUCTO DEL VOLTAJE POR LA CORRIENTE, MIENTRAS QUE EL CUARTO ELEMENTO , SE REFIERE AL TIEMPO
DISPONIBLE DE LA SEÑAL DE VOLTAJE PARA EL USUARIO kkkk
CARGA LINEAL
ES AQUELLA CARGA A LA CUAL SE LE INYECTA UN VOLTAJE SINUSOIDAL Y SE OBTIENE A LA SALIDA UNA CORRIENTE
SINUSOIDAL (R, L, C)
CARGA NO LINEAL
ES AQUELLA CARGA A LA CUAL SE LE INYECTA UN VOLTAJE SINUSOIDAL Y SE OBTIENE A LA SALIDA UNA CORRIENTE
NO SINUSOIDAL O DISTORSIONADA (COMPUTADORES , VARIADORES DE FRECUENCIA)
•LA AMPLITUD DE UNA SEÑAL SINUSOIDAL ES LA DISTANCIA DESDE SU VALOR MEDIO A SU VALOR MAXIMO
•LA AMPLITUD EN AMBAS FIGURAS ES Em , LA FIGURA (a) TIENE UN VALOR MEDIO IGUAL A CERO Y LA FIGURA (b)
TIENE UN VALOR MEDIO E ≠ 0
•EL VALOR PEAK DE UNA SEÑAL DE VOLTAJE O CORRIENTE ES SU VALOR MAXIMO CON RESPECTO A CERO (EJE t)
.PARA LA FIGURA (b) , LA SEÑAL ESTA DIBUJADA SOBRE UNA COMPONENTE MEDIA (E) DIFERENTE DE CERO ,
OBTENIENDO UN VALOR PEAK QUE ES LA SUMA DEL VALOR MEDIO MAS LA AMPLITUD DE LA SEÑAL , ES DECIR
E pe ak =E+ Em
Em : AMPLITUD
E :VALOR MEDIO
CAMBIANDO DE NOMENCLATURA
V peak =V dc +V m
V peak =V m
•EL VALOR MEDIO DE UNA SEÑAL SINUSOIDAL ES
V peak +V min
V dc =
2
SI EL VALOR DE V min ES NEGATIVO SE CONSIDERA EL SIGNO
Vm
V rms =
√2
LA MAYORIA DE LAS SEÑALES QUE APARECEN EN LOS CIRCUITOS ELECTRONICOS TIENEN UNA COMPONENTE
CONTINUA Y UNA COMPONENTE ALTERNA, LUEGO EL VALOR EFECTIVO ES
V rms =√ V dc +V ac
2 2
DONDE
V dc :COMPONENTE CONTINUA
Vm
V ac =
√2
V 2rms
P=
R
EJEMPLO
V max +V min 1+(−1)
V dc = = =0
2 2
LA AMPLITUD DE LA SEÑAL ES
V peak =V dc +V m
V m =V peak −V dc
V m =1−0=1
EJEMPLO
LA AMPLITUD DE LA SEÑAL ES
V peak =V dc +V m
V m =V peak −V dc
V m =5−3=2
EJEMPLO
CALCULAR LA POTENCIA ACTIVA DE UN RESISTOR R=500Ω , CUYA SEÑAL DE VOLTAJE APLICADA ES LA QUE SE
MUESTRA A CONTINUACION
EL VALOR MEDIO ES
V peak =V dc +V m
V m =V peak −V dc
V m =16−12=4 V
Vm
V ac =
√2
4
V ac = =2.83V
√2
V rms =√ V dc +V ac
2 2
V 2rms 12.332
P= =
R 500
P=0.303W
ARMONICO
SEÑAL SINUSOIDAL QUE GIRA A UNA FRECUENCIA MULTIPLE DE LA FRECUENCIA FUNDAMENTAL (f1=50HZ) , o h=1
h=5,7,11,13,17,19,23,25… .. etc
h=6 k +1 :armónicos de sec¿ ¿
SIGNIFICA QUE EN LA FASE R EL ANGULO ES 0 , EN LA FASE S EL ANGULO ES -120 , Y EN LA FASE T EL ANGULO ES 120
ES DECIR
h=6 k −3 , k=1,2,3 , … … n
es decir
ADEMAS GENERAN LOS ARMONICOS DE LOS CONSUMOS 3Ø , VALE DECIR EN TOTAL GENERAN
h=3,5,7,9,11,13,15,17,19… … … etc
EQUIVALE
EQUIVALE
EQUIVALE
t=0 seg
i 3 L 1 ( t=0 ) =I max sen ( 3∗2 π 50∗0∗57.3 )=0
t=0.005 seg
i 3 L 1 ( t )=I max sen ( 3∗2 π 50 t∗0.005∗57.3 )=−I max
t=0.01 seg
i 3 L 1 ( t )=I max sen ( 3∗2 π 50 t∗0.01∗57.3 )=0
t=0.015 seg
i 3 L 1 ( t )=I max sen ( 3∗2 π 50 t∗0.015∗57.3 )=I max
t=0.02 seg
i 3 L 1 ( t )=I max sen ( 3∗2 π 50 t∗0.02∗57.3 )=0
EQUIVALE
SEÑAL DE CORRIENTE
ESPECTRO EN FRECUENCIA
EL CONTENIDO ARMONICO ES
ESQUEMA VDF
SEÑAL DE CORRIENTE Y SU ESPECTRO EN FRECUENCIA VDF
[∫ ]
150 330
1
dt + ∫ I DC dt
2 2 2
I RMS = I DC
360 30 210
2
2 I DC
I RMS = [ 150−30+330−210 ]
360
2
2 I DC
I RMS = [ 240 ]
360
I RMS =
√ 2
3
∗I DC
SU ECUACION ES
2 √3∗I DC 1 1 1
i (t )= (coswt − cos 5 wt + cos 7 wt − cos 11 wt +…)
π 5 7 11
I RMS=
√ 2
∗I , I =0.78 I DC , V DC =2.34∗V fase ,V DC =1.35∗V linea
3 DC 1
EJEMPLO
V DC =2.34∗220=514.80V
I1
I h=
h
P1=Pdc
√ 3∗I 1=1.35∗I dc
I 1=0 . 78∗I dc
[ ]
π
3 √ 3∗V max
6 π
1
V DC =
π
∫ √3∗V max coswtdwt = π
∗( senwt)|−6 π
−π 6
3 6
3 √ 3∗V max
V DC = (0.5+ 0.5)
π
3 √ 3∗V max
V DC =
π
PERO
V linea
V fase =
√3
REEMPLAZANDO
2.34∗V linea
V DC =
√3
V DC =1 .35∗V linea
V DC =1 .35∗380=513V
FP=
Pdc
=
V dc∗I dc
=
π (
3 √ 3∗V max
∗I dc )
√
S 3∗V RMS∗I RMS V 2
3∗( max )∗ ∗I dc
√2 3
EL NUMERO 3 ES PORQUE EL RECTIFICADOR ES 3Ø, ADEMAS V RMS , I RMS SON VARIABLES DE FASE
FP=
( 3 √π 3 )
=
3 √3
π
=0.95
√
1 2 3
3∗( )∗
√2 3 √ 3
OTRA FORMA DE CALCULAR EL FP
FP=DPF∗cosØ dist
1∗I 1
FP=
I RMS
1∗0.78∗I dc
FP= =0.95
√ 2
∗I
3 dc
-VALOR RMS
SEÑAL SINUSOIDAL
√
T
1 V
V RMS= ∫
T 0
V (t )2 dt = MAX
√2
√
T
1 I MAX
I RMS= ∫
T 0
2
I (t ) dt=
√2
SEÑAL NO SINUSOIDAL
PARA EL CASO GENERAL DE VARIAS FUENTES DE VOLTAJE DE MULTIPLES FRECUENCIAS ALIMENTANDO UN RESISTOR
O UNA IMPEDANCIA , LA POTENCIA ACTIVA TOTAL DEMANDADA POR EL CONSUMO ES:
V 12 V 22 VN 2
PT = + +… (1)
R R R
DEFINIENDO VRMS COMO EL VALOR EFECTIVO DE UN VOLTAJE EQUIVALENTE DE UNA SOLA FRECUENCIA QUE
CAUSARIA LA MISMA DISIPACION DE POTENCIA EN LA CARGA, QUE LAS COMPONENTES DE MULTIPLES
FRECUENCIAS , ES DECIR
VRMS 2
PT = (2)
R
VRMS2=V 12 +V 12+ … VN 2
FINALMENTE
√∑
infinito
VRMS= Vh2 =√ V 12 +V 22+ …+VN 2
h=1
DEFINIENDO IRMS COMO EL VALOR EFECTIVO DE UNA CORRIENTE EQUIVALENTE DE UNA SOLA FRECUENCIA QUE
CAUSARIA LA MISMA DISIPACION DE POTENCIA EN LA CARGA, QUE LAS COMPONENTES DE MULTIPLES
FRECUENCIAS , ES DECIR
2
PT =R∗IRMS (4)
√∑
infinito
IRMS= Ih2= √ I 12 + I 22+ …+¿2
h=1
EJEMPLO
EJEMPLO
VOLTAJE
√∑
infinito
2
Vh
h>1
THDV ( % ) = ∗100
V1
LIMITES PERMITIDOS
THDV = √
VRMS −V 1 √ VRMS −V 1
√
2 2 2 2 2 2
VRMS −V 1
= =
V1 √V 1 2
V 12
THDV = √¿ ¿
2
THDV =¿
¿
SACANDO RAIZ CUADRADA
VRMS
=√ THDV 2+1
V1
FINALMENTE
VRMS=V 1 √ THDV + 1
2
EJEMPLO
UN VOLTAJE TIENE UN VALOR RMS DE 485 V , EL CUAL CONTIENE VARIOS ARMONICOS .SI LA FUNDAMENTAL ES 481
V , CALCULAR EL VALOR RMS DE TODOS LOS ARMONICOS Y EL THDV(%)
SOL
Vrms=√ V 1 +Vhrms
2 2
Vhrms= √ Vrms −V 1
2 2
Vhrms=62.16 V
THDV ( % ) =
√ 2
Vrms −V 1
2
∗100=
62.16
∗100=12.92(%)
V1 481
EJEMPLO
SE MIDE UN VOLTAJE DE 4300 VRMS, EL CUAL TIENE UNA DISTORSION DE VOLTAJE DE 26% CALCULAR LOS VALORES
RMS
A) FUNDAMENTAL
B) TODOS LOS ARMONICOS
SOL
A)
THDV =
√ VRMS2−V 12
V1
ELEVANDO AL CUADRADO
2 VRMS2−V 12
THDV = 2
V1
REEMPLAZANDO
2 2
2 4300 −V 1
0.26 = 2
V1
2 2 2
0.0676∗V 1 =4300 −V 1
2 2 2
0.0676∗V 1 +V 1 =4300
2
2 4300
V1=
1.0676
√
2
4300
V 1= =4161.64 V
1.0676
CORRIENTE
√∑
infinito
2
Ih
h>1
THDI ( % )= ∗100
I1
√ IRMS −I 1 √ IRMS −I 1
√
2 2 2 2 2 2
IRMS −I 1
THDI = = =
I1 √ I 12 I1
2
THDI =√ ¿ ¿
THDI 2=¿
¿
SACANDO RAIZ CUADRADA
IRMS
= √ THDI + 1
2
I1
FINALMENTE
IRMS=I 1 √ THDI +1
2
EL THDI NO ESTA EN PORCENTAJE
-UN VALOR DE THDI COMPRENDIDO ENTRE EL 10 Y EL 50 % REVELA UNA DISTORSIÓN ARMÓNICA SIGNIFICATIVA.
EXISTE EL RIESGO DE QUE AUMENTE LA TEMPERATURA, LO QUE IMPLICA EL SOBREDIMENSIONADO DE LOS
CABLES Y LAS FUENTES.
EJEMPLO
UNA CORRIENTE DISTORSIONADA CUYA FRECUENCIA FUNDAMENTAL ES 60 HZ, TIENE UN VALOR RMS DE 62.5 A , Y
TIENE LAS SIGUIENTES COMPONENTES RMS
TAMBIEN ESTAN PRESENTES ARMONICOS DE MAYOR FRECUENCIA, PERO SUS AMPLITUDES SON PEQUEÑAS.
CALCULAR
A) Ihrms
B) THDI(%)
C)EL VALOR RMS DE TODOS LOS ARMONICOS POR ENCIMA DEL SEPTIMO
SOL
A)
20.62
THDI ( % )= ∗100=34.95(%)
59
C)
2 2 2 2 2
Irms =I 1 + I 5 + I 7 + I ¿7
2 2 2 2
I ¿7=I h rms −I 5 −I 7
I ¿7= √ I hrms −I 5 −I 7
2 2 2
D) I 7 max= √ 2∗10.3=14.57 A
EJEMPLO
THDI ( % )=
√ 2 2
42 +26 +18
2
∗100=80.88(% )
65
IRMS=I 1 √ THDI 2 +1
EJEMPLO
EJEMPLO
SOL
A)TENER EL VOLTAJE EN EL INDUCTOR ES EQUIVALENTE A CALCULAR VAB . PARA CALCULAR ESTE VOLTAJE SE DEBE
OBTENER LA IMPEDANCIA PARALELO PARA CADA FRECUENCIA
XL 1=2 π 50∗1300∗10−6=0.41 Ω
1
XC 1= =79.57Ω
2 π 50∗40∗10−6
XL 5=5∗XL1=5∗0.41=2.05 Ω
XC 1 79.57
XC 5= = =15.91 Ω
5 5
Zp5=¿ ¿
|Zp 5|=2.35 Ω
XL 7=7∗XL 1=7∗0.41=2.87Ω
XC 1 79.57
XC 7= = =11.37Ω
7 7
Zp7=ZL=¿ ¿
|Zp 7|=3.84 Ω
VL7=Zp7∗I 7=3.84∗4=15.36 V
XL 11=11∗XL 1=11∗0.41=4.51Ω
XC 1 79.57
XC 11= = =7.23 Ω
11 11
Zp11=¿ ¿
|Zp 11|=11.98 Ω
XL 13=13∗XL1=13∗0.41=5.33 Ω
XC 1 79.57
XC 13= = =6.12Ω
13 13
Zp13=¿ ¿
|Zp 13|=41.29 Ω
B)
VL hrms =√ VL 52 +VL72 +VL112 +VL 132
C)
VL5 47
IC 5= = =2.95 A
XC 5 15.91
VL7 15.36
IC 7= = =1.35 A
XC 7 11.37
VL 11 107.82
IC 11= = =14.91 A
XC 11 7.23
VL 13 330.32
IC 13= = =53.97 A
XC 13 6.12
EJEMPLO
CALCULAR
SOL
A)
rad
w=2 πf ( )
seg
COMO ESTA EXPRESADA EN GRADOS SE REEMPLAZA π POR 180°
18000
f= =50 HZ FUNDAMENTAL
2∗180
126000
f= =350 HZ SEPTIMO ARMONICO
2∗180
B)
850
V 1 RMS= =601.04 V
√2
340
V 5 RMS= =240.41 V
√2
D)
•SE EMPLEA PRINCIPALMENTE PARA LA CORRIENTE Y ES LA TECNICA MAS SIMPLE PARA LA ESTIMACION DE
ARMONICAS
IMAX
FC =
IRMS
•PARA UNA SEÑAL SINUSOIDAL FC=√ 2
•SI FC>√ 2 SOLO ME INDICA QUE HAY ARMONICAS, PERO NO SE SABEN SUS FRECUENCIAS
EJEMPLO
i (t )=100 √ 2 senwt −79 √ 2 sen 3 wt +52 √ 2 sen 5 wt−29 √ 2 sen 7 wt +11 √2 sen 9 wt
CALCULAR FC
IMAX =√ 2(100+79+52+29+11)=383.25 A
383.25
FC = =2.71> √2
141.09
EJEMPLO
22
FC = =4.4
5
PARA LA SEÑAL DE VOLTAJE SE PRESENTA COMO SE ILUSTRA EN LA FIGURA , Y SE CONOCE COMO FLAT-TOP
VOLTAGE (SE APLANA EL VALOR MAXIMO , SE REDUCE).ESTO SE DEBE A LA CAIDA DE VOLTAJE QUE SE PRODUCE EN
EL CONDUCTOR DE ALIMENTACION DEBIDO AL AUMENTO DE LA CARGA , RESULTANDO EL FACTOR DE CRESTA
MENOR A 1.41.
TAMBIEN SE PUEDE DEBER A LOS ARMONICOS DE VOLTAJE , QUE PUEDEN CAUSAR UNA DISMINUCION DEL VALOR
MAXIMO
OTRA CAUSA ES QUE LA FUENTE DE ALIMENTACION DE VOLTAJE NO GENERE SIUFICIENTE CORRIENTE,
DISTORSIONANDO LA SEÑAL
FACTOR K
INDICA LA CAPACIDAD DE UN TRAFO PARA ALIMENTAR CARGAS NO LINEALES, TRABAJANDO A POTENCIA NOMINAL
SIN AUMENTAR SU TEMPERATURA.LOS VALORES NORMALIZADOS DE K SON:
K=4
UN TRAFO CON ESTE VALOR HA SIDO DISEÑADO PARA SUMINISTRAR EL 100% DE SU POTENCIA NOMINAL A CARGAS
LINEALES, MAS EL 50% DE SU POTENCIA A CARGAS NO LINEALES.LAS CORRIENTES ARMONICAS ESTAN REGIDAS POR
LA SIGUIENTE ECUACION
I h (%)= 0 . ( 5∗1
h )
∗I 1 ∗100
ES DECIR
( 5∗13∗I )∗100=16 . 67 % I
I 3 ( % )= 0 . 1 1
I ( % )= ( 0 . ∗I )∗100=10 % I
5∗1
5 1 1
5
ETC
K=9
EL TRAFO PUEDE ACEPTAR UN 163 % DE LA CARGA ARMONICA DEL TRAFO CON K=4
K=13
EL TRAFO PUEDE ACEPTAR UN 200 % DE LA CARGA ARMONICA DEL TRAFO CON K=4
ES DECIR
I ( % )=( ∗I )∗100=20 % I
1
5 1 1
5
ETC
K=20
EL TRAFO PUEDE SUMINISTRAR EL 100% DE SU POTENCIA NOMINAL A CARGAS LINEALES MAS EL 125% A CARGAS
NO LINEALES.
I h (%)= 1 . ( 25∗1
h
∗I 1 ∗100)
ES DECIR
( 25∗1
I 3 ( % )= 1 .
3
∗I )∗100=41 .67 % I
1 1
I ( % ) =( 1 . ∗I )∗100=25 % I
25∗1
5 1 1
5
ETC
K=30
EL TRAFO PUEDE SUMINISTRAR EL 100% DE SU POTENCIA NOMINAL A CARGAS LINEALES MAS EL 150% A CARGAS
NO LINEALES.
I h (%)= 1 . ( 5∗1
h )
∗I 1 ∗100
ES DECIR
( 5∗13∗I )∗100=50 % I
I 3 ( % )= 1 . 1 1
I ( % )= ( 1 . ∗I )∗100=30 % I
5∗1
5 1 1
5
ETC
METODO UL
METODO NORMALIZADO
infinito
K= ∑ 2 2
I h(°/1) h
h=1
Ih(°/1):CORRIENTE RMS DE LA ARMONICA CON RESPECTO A LA CORRIENTE RMS NOMINAL DEL TRAFO
METODO NORMALIZADO
∑ Ih 2∗h2
h=1
K= infinito
∑ Ih
2
h=1
EJEMPLO
METODO UL
K=11.3
METODO NORMALIZADO
1 2.036 1 1 1 1
3 1.633 0.802 0.643 9 5.787
5 1.237 0.607 0.368 25 9.200
7 0.757 0.371 0.137 49 6.713
9 0.318 0.156 0.024 81 1.944
∑ 2.172 ∑ 24.644
24.644
K= =11.34
2.172
KVA S =VRMSS∗IRMS S
KVA T =VRMST ∗IRMST
DONDE
SI
K R=K S=K T =K
ENTONCES
3∗K∗KVA
Ke= =K
3∗KVA
EJEMPLO
VR IR VS IS VT IT
V1=225 V I1=86 A V1=215 V I1=100 A V1=230 V I1=70 A
V3=0 I3=59 A V3=0 I3=72 A V3=0 I3=45 A
V5=20 V I5=42 A V5=15 V I5=47 A V5=12 V I5=31 A
V7=12 V I7=30 A V7=10 V I7=38 A V7=10 V I7=19 A
V9=0 V I9=18 A V9=0 V I9=23 A V9=0 V I9=10 A
V11=8 V I11=10 A V11=5 V I11=15 A V11=6 V I11=5 A
CALCULO DE K R
METODO UL
CALCULO DE K S
METODO UL
h Ih(A) Ih ( A ) I h 2( pu) h
2
I h ∗h
2 2
Ih ( pu )=
139.97
1 100 0.714 0.509 1 0.509
3 72 0.514 0.264 9 2.376
5 47 0.335 0.112 25 2.800
7 38 0.271 0.073 49 3.577
9 23 0.164 0.026 81 2.106
11 15 0.107 0.011 121 1.331
∑ 12.70
CALCULO DE K T
METODO UL
h Ih(A) Ih( A) 2
I h ( pu) h2 I h 2∗h2
Ih ( pu )=
91.50
1 70 0.765 0.585 1 0.585
3 45 0.491 0.241 9 2.169
5 31 0.338 0.114 25 2.850
7 19 0.207 0.043 49 2.107
9 10 0.109 0.012 81 0.972
11 5 0.054 0.0029 121 0.351
∑ 9.03
Ke=11.39
DERRATEO
LOS TRAFOS TRADICIONALES ESTAN DISEÑADOS PARA CARGAS LINEALES CON FORMAS DE ONDA DE VOLTAJE Y
CORRIENTES SINUSOIDALES. A CAUSA DE LAS CORRIENTES NO SINUSOIDALES QUE INYECTAN LAS CARGAS NO
SINUSOIDALES, LOS TRAFOS SUFREN UN MAYOR DESGASTE DEBIDO A LAS PERDIDAS Y AUMENTO DE LA
TEMPERATURA PRODUCIDO POR LAS COMPONENTES ARMONICAS DE LAS CORRIENTES.
LA PALABRA DERRATEO VIENE DEL INGLES DERATING, Y CONSISTE EN DISMINUIR LA CAPACIDAD DE CARGA DEL
TRAFO, CON EL FIN QUE PUEDA ALIMENTAR CARGAS NO LINEALES
AUNQUE SE REDUCE EL STRESS QUE ESTA SOMETIDO EL TRAFO, ESTE SIGUE SIENDO DISEÑADO PARA ALIMENTAR
CARGAS LINEALES, POR LO QUE ESTA SUJETO A UNA MENOR EFICIENCIA Y VIDA UTIL
EN EL DERRATEO SE CORRE EL RIESGO SE CORRE EL RIESGO QUE A FUTURO SE LE AGREGUE MAS CARGA
EL INDICE DE DERRATEO MAS UTILIZADO, PROPUESTO POR CBEMA (COMPUTERS AND BUSINESS EQUIPMENT
MANUFACTURERS ASSOCIATION) ,CONSIDERA EL FACTOR DE CRESTA DE LA CORRIENTE DE CARGA .
THDF= √
2∗IRMS √ 2
= ≤1
IMAX FC
SI EL TRAFO ALIMENTA SOLO CARGAS LINEALES EL THDF=1, NO SE REQUIERE DERRATEAR
EN UN SISTEMA 3Ø SI HAY DIFERENCIAS EN LOS VALORES DE LAS CORRIENTES DE CADA FASE, SE CONSIDERA UN
VALOR PROMEDIO (PARA EL VALOR RMS Y PARA EL MAXIMO)
KVAderrateado=THDF∗KVAplaca
EJEMPLO
SE REALIZARON LAS SIGUIENTES MEDICIONES DE UN TRAFO DE 225 KVA QUE ALIMENTA CARGAS NO LINEALES
SOL
CORRIENTE RMS DE FASE PROMEDIO
410+ 445+435
I= =430 A
3
804+892+ 828
I= =841 A
3
THDF= √
2∗430
=0.723=72.3( %)
841
EL RESULTADO INDICA QUE CON LOS NIVELES DE ARMONICAS PRESENTES EN EL TRAFO, ESTE DEBERA SER
DERRATEADO A UN 72.3(%) C/R A SU VALOR NOMINAL PARA PREVENIR AUMENTOS DE TEMPERATURA
EJEMPLO
CALCULAR THDF
SOL
52.36+58.45+55.80
I= =55.53 A
3
87.48+91.35+89.77
I= =89.53 A
3
THDF= √
2∗55.53
=0.87=87(%)
89.53
POR LO TANTO, LA POTENCIA DEL TRAFO DEBE DERRATEARSE A UN 87% DEL VALOR NOMINAL
EJEMPLO
A) THD CORRIENTE
B) VALOR REAL(AMPERE) DE CADA CORRIENTE
C) EXPRESION DE I(t)
D) THDF
E) FACTOR K (METODO UL)
SOL
A) THDI ( % )= √
0.752 +0.422 +0.222 +0.092
∗100=89.18(%)
1
I 3=0.75∗20.89=15.67 A
I 5=0.42∗20.89=8.77 A
I 7=0.22∗20.89=4.60 A
I 9=0.09∗20.89=1.88 A
B) THDI ( % )= √
15.672 +8.772 + 4.602+ 1.882
∗100=89.19( %)
20.89
C)
i (t )= √ 2∗20.89 sen ( wt )−√ 2∗15.67 sen ( 3 wt ) + √ 2∗8.77 sen ( 5 wt )−√ 2∗4.60 sen ( 7 wt )+ √2∗1.88 sen ( 9 wt )
w=2 πf
D)THDF=
√2∗IRMS
IMAX
D)
THDF= √
2∗28
=0.54
73.27
E)
METODO UL
h Ih(A) Ih( A) 2
I h ( pu) h
2
I h ∗h
2 2
Ih ( pu )=
IRMS
1 20.89 0.7460 0.5560 1 0.5560
3 15.67 0.5596 0.3132 9 2.818
5 8.77 0.3132 0.0980 25 2.45
7 4.60 0.1642 0.0269 49 1.3181
9 1.88 0.0671 0.0045 81 0.3645
∑ 7.51
K=7.51
METODO NORMALIZADO
1 20.89 1 1 1 1
3 15.67 0.75 0.5625 9 5.0625
5 8.77 0.42 0.1764 25 4.41
7 4.60 0.22 0.0484 49 2.3716
9 1.88 0.09 0.0081 81 0.6561
∑ 1.7954 ∑ 13.50
13.50
K= =7.51
1.7954
EJEMPLO
THDI ( % )=
√ 1.632+ 1.232+ 0.752 +0.322 ∗100=107.57 (%)
2.044
ECUACION DE LA CORRIENTE
i (t )= √ 2∗2.044 sen ( wt )− √2∗1.63 sen ( 3 wt ) + √ 2∗1.23 sen ( 5 wt ) −√ 2∗0.75 sen (7 wt ) + √ 2∗0.32 sen ( 9 wt )
w=2 πf
FACTOR DE CRESTA
IMAX
FC =
IRMS
8.44
FC = =2.81> √ 2
3
FACTOR K METODO NORMALIZADO
24.65
K= =11.35
2.170
METODO UL
METODO UL
2 2 2
h Ih(A) Ih( A) I h 2( pu) h I h ∗h
Ih ( pu )=
IRMS
1 2.044 0.681 0.463 1 0.463
3 1.63 0.543 0.294 9 2.646
5 1.23 0.410 0.168 25 4.20
7 0.75 0.250 0.062 49 3.038
9 0.32 0.106 0.011 81 0.891
∑ 11.23
K=11.23
EJEMPLO
UNA ANALIZADOR DE ARMONICOS MIDE LA CORRIENTE RMS DE UNA CARGA NO LINEAL CUYO VALOR ES 10.5 A ,
LOS ARMONICOS SE MUESTRAN EN LA SIGUIENTE TABLA
h PORCENTAJE h PORCENTAJE
1 100 17 2.1
3 70.4 19 0.9
5 28.8 21 1.1
7 0.7 23 0.4
9 3.8 25 0.3
11 1.5 27 0.3
13 3 29 0.4
15 1.2 31 0.3
33 0.5
CALCULAR
SOL
A) IRMS=I 1 √ THDI 2 +1
IRMS
I 1=
√ THDI 2+1
THDI ( % )=
√ 0.7042 +0.288 2+ 0.0072+ 0.0382 +0.0152 +…+0.003 2+0.005 2∗100=76.2 %
1
10.5
I 1= =8.35 A
√ 0.7622 +1
B) I 5=0.288∗8.35=2.404 A
C) I 11=0.015∗8.35=0.125 A
D) PARA CALCULAR EL VALOR MAXIMO SE DEBEN CALCULAR LOS RESTANTES VALORES RMS , LUEGO
I 1=8.35 A I 17=0.175 A
I 3=5.87 A I 19=0.075 A
I 5=2.404 A I 21=0.091 A
I 7=0.0584 A I 23=0.033 A
I 9=0.317 A I 25=0.025 A
I 11=0.125 A I 27=0.025 A
I 13=0.25 A I 29=0.033 A
I 15=0.10 A I 31=0.025 A
I 33=0.041 A
33
I max= √ 2∗∑ I h=25.35 A
h=1
25.35
FC = =2.41
10.5
EJEMPLO
BASADO EN LOS DATOS DE SALIDA DE UN ANALIZADOR DE ARMONICOS, UNA CARGA NO LINEAL TIENE UNA
CORRIENTE RMS DE 43.30 A , ADEMAS DE LOS SIGUIENTES ARMONICOS :
CALCULAR
A) CORRIENTE FUNDAMENTAL EN AMPERE
B) LOS PORCENTAJES DE LOS ARMONICOS 3 , 5 , 7 , 9 CON RESPECTO A LA FUNDAMENTAL
C) THDI (%)
SOL
IRMS=√ I 12 + I 32 + I 5 2+ I 72 + I 92
DESPEJANDO I 1
I 1=34.64 A
B)
22.80
I 3= ∗100=65.81%
34.64
12
I 5= ∗100=34.64 %
34.64
2.20
I 7= ∗100=6.35 %
34.64
2.48
I 9= ∗100=7.15 %
34.64
C)
THDI ( % )= √ 2 2 2
22.80 +12 + 2.20 + 2.48
2
∗100=75 %
34.64
EJEMPLO
A) CORRIENTE FUNDAMENTAL
B) I 3 ( % ) , I 5 ( % ) , I 7 ( % ) , I 9 ( % )
C) THDI (%)
SOL
I 1=√ 75 2−382−212−4.62−3.5 2
I 1=60.88 A
B)
38
I 3= ∗100=62.41 %
60.88
21
I 5= ∗100=34.49 %
60.88
4.6
I 7= ∗100=7.55 %
60.88
3.5
I 9= ∗100=5.74 %
60.88
C)
THDI ( % )= √
2 2 2 2
38 +21 + 4.6 +3.5
∗100=71.94 %
60.88
•EN SISTEMAS CON MUCHAS CARGAS MONOFÁSICAS NO LINEALES, LA CORRIENTE DEL NEUTRO PUEDE, EN LA
PRÁCTICA, SER MAYOR QUE LA CORRIENTE DE CADA UNA DE LAS FASES.
•EL PELIGRO QUE SE PRESENTA EN ESTAS CIRCUNSTANCIAS ES UN SOBRECALENTAMIENTO EXCESIVO DEL NEUTRO,
YA QUE NO SE DISPONE DE UN INTERRUPTOR AUTOMÁTICO DEL CIRCUITO EN DICHO CONDUCTOR QUE LIMITE LA
CORRIENTE, TAL COMO OCURRE CON LOS CONDUCTORES DE FASE.
• UNA CORRIENTE EXCESIVA EN EL NEUTRO PUEDE TAMBIÉN SER CAUSA DE UNA DIFERENCIA DE TENSIÓN EXCESIVA
ENTRE EL CONDUCTOR NEUTRO Y TIERRA
•LA SOLUCION PARA CONTROLAR LA SOBRECARGA EN EL NEUTRO ES AUMENTANDO SU SECCION , POR EJEMPLO AL
DOBLE DE LA SECCION DE LA FASE
•OTRA ALTERNATIVA PARA IMPEDIR EL PASO DE LOS ARMONICOS TRIPLES , AGUAS ARRIBA DEL SUMINISTRO
ELECTRICO , ES EMPLEANDO TRANSFORMADOR CON CONEXIÓN DELTA-ESTRELLA
´
EL ARMONICO TRIPLE QUE ESTA EN LA CONEXIÓN ESTRELLA I 3 PASA A LA CONEXIÓN DELTA CON VALOR I 3 , PERO
NO SE TRASPASA A LAS LINEAS DE ESTA YA QUE SE CANCELA , ES DECIR
´ ´
I R =I S=I T =I 3 sen 3 wt−I 3 sen 3 wt =0
ESTO OCURRE CUANDO DICHO ARMONICO ES EL MISMO EN CADA UNA DE LAS FASES DE LA ESTRELLA(CARGA
BALANCEADA)
EJEMPLO
UN TRAFO 3Ø 300 KVA , 15 KV / 380 V TIENE 50 A DE ARMONICO TRIPLE EN EL SECUNDARIO , CALCULAR EL VALOR
DEL ARMONICO EN LA FASE DEL PRIMARIO(DELTA)
√3∗V LP
a=
V LS
a= √
3∗15000
=68.37( p . u)
380
I FS
a=
I FP
I FS I LS 50
I FP= = = =0.73 A
a a 68.37
I RS=I ST =I TR =0.73<0 A
SISTEMA BALANCEADO
iS ( t ) =I 1 Ssen ( wt −120 ) + I 3 Ssen 3 ( wt−120 )+ I 5 Ssen 5 ( wt −120 ) + I 7 Ssen 7 ( wt −120 ) + I 9 Ssen 9 ( wt −120 )+ …
¿ ( t )=I 1 Tsen ( wt +120 ) + I 3 Tsen3 ( wt + 120 ) + I 5 Tsen5 ( wt +120 )+ I 7 Tsen7 ( wt + 120 ) + I 9 Tsen 9 ( wt +120 ) +…
LOS VALORES DE CORRIENTES QUE ACOMPAÑAN A LA FUNCION TRIGONOMETRICA SON CANTIDADES RMS
LA CORRIENTE EN EL NEUTRO ES
¿ ( t )=iR ( t ) +iS (t ) +¿ ( t )
¿ ( t )=3∗I 3 sen 3 wt +3∗I 9 sen 9 wt +…
LOS VALORES DE CORRIENTES QUE ACOMPAÑAN A LA FUNCION TRIGONOMETRICA SON CANTIDADES RMS
¿ RMS=√(3∗I 3) +(3∗I 9) +…
2 2
¿ RMS=3 √ I 3 + I 9 + …
2 2
DONDE
EJEMPLO
UN SISTEMA 3Ø CON NEUTRO ALIMENTA CONSUMOS 1Ø REPARTIDOS EN C/U DE LAS FASES . LA CORRIENTE
EN CADA LINEA ES 320 A RMS , DE LOS CUALES 47 A SE DEBEN AL TERCER ARMONICO. CALCULAR EL VALOR
DE CORRIENTE QUE FLUYE POR EL NEUTRO.
SOL
O TAMBIEN
¿ RMS=3 √ I 32 + I 9 2+ …
¿ RMS=3 √ I 3 =3 √ 47 =141 A
2 2
EJEMPLO
EN UN SISTEMA 3Ø BALANCEADO SE MIDIERON LAS SIGUIENTES CORRIENTES RMS
SOL
¿ RMS=3 √ I 3 + I 9 + …
2 2
¿ RMS=3 √ 38 +8 =116 . 49 A
2 2
38+38+38=114(TERCERA)
8+ 8+8=24(NOVENA )
¿ RMS 116.49
= =1.62
I RMS 71.90
EJEMPLO
I 5 T N =10<0+ 8←600+11<600=2.64←79.11 A
I 7 T N =5<0+ 4 ←840+6<840=1.73<90 A
¿ RMS=√ I 1 T N + I 3 T N + I 5T N + I 7 T N + I 9T N
2 2 2 2 2
EJEMPLO
I 1 T N =300<0+200←120+100< 120=173.21←30 A
I 7 T N =42.85< 0+28.57←120+14.28<120=24.74←30 A
¿ ( t )=√ 2∗173.21 sen ( wt−30 )+ √2∗200 sen ( 3 wt + 0 ) + √ 2∗34.64 sen ( 5 wt +30 ) + √2∗24.74 sen ( 7 wt−30 )+ √ 2∗66.66 se
LA CORRIENTE QUE CIRCULA POR EL NEUTRO ESTA COMPUESTA POR UNA CORRIENTE DE DESBALANCE (DEBIDO A
h=1, 5, 7, ARMONICAS NO TRIPLES) Y POR UNA COMPONENTE DEBIDO A LAS ARMONICAS TRIPLES(h=3 , 9) .
UNA APROXIMACION PRACTICA DEL CONTENIDO ARMONICO DEL NEUTRO PUEDE HACERSE AL ASUMIR:
•LA FUNDAMENTAL Y TODOS LOS ARMONICOS NO TRIPLES (1,5,7,11, ETC) EXISTEN EN EL NEUTRO DEBIDO AL
DESBALANCE DE LA CORRIENTE RMS DE CADA FASE
•TODA LA CORRIENTE DEL NEUTRO EXTRA A LA CORRIENTE DE DESBALANCE ES DEBIDO A LAS ARMONICAS TRIPLES
EJEMPLO
IR RMS=326.41 A
IS RMS =217.61 A
¿ RMS =108.80 A
¿ RMS =276.15 A
I desb =188 . 45 A
I 3 h=√ I 3 + I 9
2 2
I desb=√ I 1 + I 5 + I 7
2 2 2
¿=√ I desb + I 3 h
2 2
EJEMPLO
SOL
√ 2
¿= I desb + ∑
h=1,3,5,7,9 ,etc
2
I3 h
EJEMPLO
EJEMPLO
I desb=16 . 09 A
I 3 h=√ 1152−16 . 092=113 . 86 A
EJEMPLO
I desb =13 . 07 A
I N =√ 3∗I F
√
T
1
I F= ∫ if (t)2 dt
T 0
T
EL VALOR RMS DE LA CORRIENTE DEL NEUTRO PUEDE CALCULARSE EN UN PERIODO
3
√ √ √
T/3 T/3 T /3
1 3 1
IN= ∫
T /3 0
¿(t )2 dt =
T
∫ ¿(t )2 dt=√ 3 T
∫ ¿(t )2 dt
0 0
√
T
1
I N =√ 3 ∫ if (t )2 dt=√ 3∗I F
T 0