INFORME FINAL
MAYO DE 2014
1279
Informe de repotenciación Ingenieros Emetres Perú SAC
INDICE
INDICE ...........................................................................................................................................2
I. LINEA DE TRANSMISION ..............................................................................................5
1. ANTECEDENTES............................................................................................................5
2. OBJETIVO..........................................................................................................................5
3. NORMATIVA....................................................................................................................6
4. SITUACIÓN.......................................................................................................................6
5. CARACTERÍSTICAS GENERALES DE LA LÍNEA................................................7
6. DATOS DEL CONDUCTOR..........................................................................................7
7. CAPACIDAD MÁXIMA DE TRANSPORTE ............................................................8
7.1 CÁLCULO TEMPERATURA MÁXIMA DEL CONDUCTOR ................................................................................. 9
7.2 COMPARATIVA DE VALORES ....................................................................................................................... 11
Ref.03056-14 Informev2
1280
Informe de repotenciación Ingenieros Emetres Perú SAC
Ref.03056-14 Informev2
1281
Informe de repotenciación Ingenieros Emetres Perú SAC
Página 4 de 163
Ref.03056-14 Informev2
1282
Informe de repotenciación Ingenieros Emetres Perú SAC
I. LINEA DE TRANSMISION
1. ANTECEDENTES
2. OBJETIVO
Página 5 de 163
Ref.03056-14 Informev2
1283
Informe de repotenciación Ingenieros Emetres Perú SAC
3. NORMATIVA
4. SITUACIÓN
Página 6 de 163
Ref.03056-14 Informev2
1284
Informe de repotenciación Ingenieros Emetres Perú SAC
Código: L-2240
Tensión: 220kV
Longitud: 83km
Ref.03056-14 Informev2
1285
Informe de repotenciación Ingenieros Emetres Perú SAC
Ref.03056-14 Informev2
1286
Informe de repotenciación Ingenieros Emetres Perú SAC
Conductor bearing is 202 (deg) (perpendicular to solar azimuth for maximum solar heating)
Sun time is 11 hours (solar altitude is 75 deg. and solar azimuth is 112 deg.)
Atmosphere is CLEAR
Day of year is 172 (corresponds to junio 21 in year 2014) (day of the year with most solar
heating)
Ref.03056-14 Informev2
1287
Informe de repotenciación Ingenieros Emetres Perú SAC
Solar heat input is 15.791 (Watt/m) (corresponds to Global Solar Radiation of 1079.371
(Watt/m^2) - which was calculated)
Cuando el conductor alcance los 52,5ºC la línea objeto de éste informe podrá
transportar los 250MVA necesarios.
Ref.03056-14 Informev2
1288
Informe de repotenciación Ingenieros Emetres Perú SAC
Calculo según
Parámetro Proyecto original
PR-20 del SEIN
2 2
Radiación solar 1.200 W/m 1.079 W/m
8. DATOS DE PARTIDA
Página 11 de 163
Ref.03056-14 Informev2
1289
Informe de repotenciación Ingenieros Emetres Perú SAC
Las distancias de seguridad verticales de los conductores sobre el nivel del piso
serán determinadas de acuerdo con lo señalado en la Regla 232 del CNE
Página 12 de 163
Ref.03056-14 Informev2
1290
Informe de repotenciación Ingenieros Emetres Perú SAC
DISTANCIA
DESCRIPCIÓN
(m)
A terrenos recorridos por vehículos, tales como cultivos, pastos, bosques, huertos,
8,7
etc.
Página 13 de 163
Ref.03056-14 Informev2
1291
Informe de repotenciación Ingenieros Emetres Perú SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mínima (m) total (km)
(ºC) (m) (m)
T.1 T.2 55 7,2 7,12 14,30 terreno 0,045
Página 14 de 163
Ref.03056-14 Informev2
1292
Informe de repotenciación Ingenieros Emetres Perú SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mínima (m) total (km)
(ºC) (m) (m)
T.12 T.13 55 7,2 0,02 7,20 terreno 4,911
Página 15 de 163
Ref.03056-14 Informev2
1293
Informe de repotenciación Ingenieros Emetres Perú SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mínima (m) total (km)
(ºC) (m) (m)
T.33 T.34 55 7,2 3,76 11,00 terreno 14,761
Página 16 de 163
Ref.03056-14 Informev2
1294
Informe de repotenciación Ingenieros Emetres Perú SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mínima (m) total (km)
(ºC) (m) (m)
T.54 T.55 55 7,2 9,94 17,10 terreno 24,986
Página 17 de 163
Ref.03056-14 Informev2
1295
Informe de repotenciación Ingenieros Emetres Perú SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mínima (m) total (km)
(ºC) (m) (m)
T.75 T.76 55 7,2 0,46 7,70 lateral 35,521
Página 18 de 163
Ref.03056-14 Informev2
1296
Informe de repotenciación Ingenieros Emetres Perú SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mínima (m) total (km)
(ºC) (m) (m)
T.96 T.97 55 7,2 5,23 12,40 terreno 45,172
Página 19 de 163
Ref.03056-14 Informev2
1297
Informe de repotenciación Ingenieros Emetres Perú SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mínima (m) total (km)
(ºC) (m) (m)
T.117 T.118 55 7,2 1,48 8,70 terreno 54,897
Página 20 de 163
Ref.03056-14 Informev2
1298
Informe de repotenciación Ingenieros Emetres Perú SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mínima (m) total (km)
(ºC) (m) (m)
T.138 T.139 55 7,2 0,58 7,80 terreno 63,517
Página 21 de 163
Ref.03056-14 Informev2
1299
Informe de repotenciación Ingenieros Emetres Perú SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mínima (m) total (km)
(ºC) (m) (m)
T.159 T.160 55 7,2 2,43 9,60 terreno 72,465
Página 22 de 163
Ref.03056-14 Informev2
1300
Informe de repotenciación Ingenieros Emetres Perú SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mínima (m) total (km)
(ºC) (m) (m)
T.180 T.181 55 7,2 2,05 9,20 terreno 80,306
Aunque todos los vanos, a excepción de uno, cumplen con la distancia mínima
reglamentaria, existen algunos puntos singulares con un margen inferior al medio
metro que pueden ser objeto de un estudio más detallado, en la tabla anterior se han
marcado en azul.
En el vano T.49 – T.50 existe una distancia inferior a los 7,20 metros definidos como
mínimos para no tener una distancia a terreno crítica. Esto no significa que exista
una distancia antirreglamentaria en éste punto al ser la entidad que limita un lateral,
cuya componente transversal se desconoce y suma vectorialmente al valor de la
tabla.
Con el fin de verificar con mayor precisión distancias al terreno y datos ambientales,
se realizaron mediciones y registros en campo de los vanos muestreados, utilizando
el siguiente procedimiento:
Página 23 de 163
Ref.03056-14 Informev2
1301
Informe de repotenciación Ingenieros Emetres Perú SAC
10. OBSERVACIONES
Página 24 de 163
Ref.03056-14 Informev2
1302
Informe de repotenciación Ingenieros Emetres Perú SAC
Las catenarias del conductor en los vanos más desnivelados difiere con la grafiada
en PLS-CADD, seguramente porqué a parte de lo comentado en el apartado
anterior, en el perfil de proyecto se utilizaron parábolas para representar el conductor
11. CONCLUSIÓNES
Ref.03056-14 Informev2
1303
Informe de repotenciación Ingenieros Emetres Perú SAC
Página 26 de 163
Ref.03056-14 Informev2
1304
Informe de repotenciación Ingenieros Emetres Perú SAC
Página 27 de 163
Ref.03056-14 Informev2
1305
Informe de repotenciación Ingenieros Emetres Perú SAC
Página 28 de 163
Ref.03056-14 Informev2
1306
Informe de repotenciación Ingenieros Emetres Perú SAC
E l S a lt o P a it a Lo bo s de A f ue ra S a la v e rry C him bo t e
( T um be s ) ( P iura ) ( La m ba ye que ) ( La Libe rt a d) ( Á nc a s h)
A ño
P ro P ro P ro P ro P ro
M í n. M á x. M í n. M á x. M í n. M á x. M í n. M á x. M í n. M á x.
m. m. m. m. m.
1988 24,6 21,8 26,9 23,2 19,3 28,3 18,8 16,0 22,6 18,9 16,4 22,4 19,6 16,9 22,7
1989 24,2 21,3 26,8 23,4 19,7 27,6 19,5 16,8 23,7 19,4 17,2 23,8 19,9 17,8 23,1
1990 24,6 21,8 26,9 22,9 19,6 26,3 19,4 16,5 22,6 19,7 17,2 22,9 20,4 18,0 23,4
1991 25,0 22,4 27,5 23,2 20,5 27,6 20,3 18,1 23,3 20,2 17,8 23,6 20,6 19,2 23,1
1992 25,4 22,8 28,2 24,2 20,4 28,7 21,2 17,6 26,4 21,2 17,5 26,0 21,5 19,1 25,3
1993 25,2 23,0 27,1 24,0 21,2 27,4 20,5 18,0 24,2 20,5 17,9 23,6 21,5 19,6 24,5
1994 24,6 21,4 26,7 23,6 20,6 26,4 19,4 16,9 22,4 19,7 17,4 22,1 20,6 18,4 22,4
1995 24,9 22,7 27,0 23,0 20,3 26,9 19,6 17,1 23,6 19,5 17,4 23,5 21,3 18,8 25,5
1996 23,8 21,4 26,5 22,4 19,4 25,6 18,4 16,0 21,9 18,5 16,3 21,7 19,5 15,7 22,9
1997 26,8 25,2 27,5 26,3 24,8 28,0 23,0 20,3 25,6 22,9 21,2 25,4 23,3 21,7 24,5
1998 26,0 23,4 28,1 25,0 21,7 28,5 21,9 17,6 27,8 21,5 17,2 27,3 21,9 17,7 28,2
1999 24,7 21,8 26,9 23,2 20,4 27,2 19,0 16,6 22,9 18,8 16,6 22,8 19,4 17,3 22,9
2000 25,0 23,5 26,5 23,1 20,3 26,5 19,5 17,2 22,8 19,3 17,5 22,4 19,7 17,4 22,6
2001 25,1 22,7 27,8 23,2 19,6 27,5 19,3 16,4 24,1 18,8 16,2 22,6 19,4 16,9 22,9
2002 26,0 23,6 28,1 23,9 20,6 28,0 20,3 17,1 25,6 19,8 17,2 23,3 20,1 17,2 24,9
2003 26,3 23,9 28,3 23,1 20,0 26,9 19,4 16,7 23,4 19,3 16,8 23,0 19,9 17,0 23,7
2004 25,2 23,3 27,1 22,9 19,3 26,8 19,4 16,7 23,1 19,2 16,9 22,9 20,1 17,6 24,0
2005 25,2 22,4 28,1 22,5 20,1 26,1 19,3 16,5 22,8 19,4 16,4 22,7 19,8 17,2 23,3
2006 25,2 23,2 27,2 23,2 21,1 26,2 20,0 18,2 23,8 19,8 18,0 23,0 20,9 18,8 23,7
2007 25,3 23,2 27,4 22,2 18,6 26,7 18,8 15,5 23,7 18,8 15,8 23,7 18,9 16,3 23,0
2008 25,5 24,5 26,7 23,4 20,9 26,9 20,3 17,6 25,1 20,3 18,3 24,6 20,8 18,2 27,0
2009 24,2 19,0 25,6 23,3 20,3 27,8 20,0 17,4 22,7 20,5 18,0 23,6 20,7 18,3 23,0
2010 24,3 21,7 26,3 23,4 20,3 26,9 19,5 15,9 24,0 19,7 16,2 24,3 20,2 16,1 24,8
2011 25,7 24,2 27,7 21,7 18,9 25,4 19,6 16,6 22,6 19,3 16,5 22,5 20,0 17,1 21,9
2012 … … … 27,1 22,5 33,5 20,6 18,2 23,1 21,0 18,5 23,4 21,3 18,8 23,3
pro m e dio últ im o s 10 a ño s 23,43 23,37
Página 29 de 163
Ref.03056-14 Informev2
1307
Informe de repotenciación Ingenieros Emetres Perú SAC
Fuente:http://redpeia.minam.gob.pe/admin/files/item/4d77e7ad5bb27_Resumen_Escenarios_climaticos_del_Peru.pdf
Página 30 de 163
Ref.03056-14 Informev2
1308
Informe de repotenciación Ingenieros Emetres Perú SAC
Página 31 de 163
Ref.03056-14 Informev2
1309
Informe de repotenciación Ingenieros Emetres Perú SAC
Página 32 de 163
Ref.03056-14 Informev2
1310
Informe de repotenciación Ingenieros Emetres Perú SAC
Página 33 de 163
Ref.03056-14 Informev2
1311
Informe de repotenciación Ingenieros Emetres Perú SAC
Criteria Notes:
Ingenieros Emetres
WC Description Air Wind Wind Wire WireWireWire Ambient Weather NESC Wire Wind Wire
(Pa/(m/s)^2)(m/s) (Pa) (cm) (daN/dm^3) (daN/m) (deg C) (deg C) (daN/m) Model Factor
Página 34 de 163
Ref.03056-14 Informev2
1312
Informe de repotenciación Ingenieros Emetres Perú SAC
------------------------------------------------------------------------------------------------------------------------------------
# # Description Condition
-----------------------------------
1 2 T55ºC Creep RS
Survey Point Clearance and Danger Tree Locator functions are considering a Continuous Range
Página 35 de 163
Ref.03056-14 Informev2
1313
Informe de repotenciación Ingenieros Emetres Perú SAC
Survey Point Clearance functions are treating points with insufficient vertical clearance but
Required Clearances
to Spotting
Constraint
----------------(m)------------------
------------------------------------------------------------------------------
Página 36 de 163
Ref.03056-14 Informev2
1314
Informe de repotenciación Ingenieros Emetres Perú SAC
This report includes only survey points that do not have the following feature codes: 504 510 520 600
Página 37 de 163
Ref.03056-14 Informev2
1315
Informe de repotenciación Ingenieros Emetres Perú SAC
This report includes only survey points with a horizontal distance to wire of less than 15.24 (m).
Clearance to ground centerline is not being checked at regular intervals (only being checked at existing survey points) ??
PLS-CADD analyzes clearances for all of the weather cases specified in Criteria/Survey Point Clearances but
reports results only for the weather case it deems the worst case violation (lowest vertical clearance margin).
Detailed results for all weather cases and wind directions can be obtained through Terrain/Clearance if desired.
Ground clear controls: Constrained by required clearance to ground rather than required clearances for point Feature Code.
Point above wires: Aerial obstacle that is above wires for specified criteria.
Closer inspection may be required to ensure wires remain below obstacle at colder temperatures.
Point between wires: Aerial obstacle that is above some wires and below other wires for specified criteria.
Closer inspection may be required to ensure there are no violations when transitioning from cold to hot temperatures.
Nonprojectable: Point can't be projected onto span. Constrained by clearance to end of span.
Página 38 de 163
Ref.03056-14 Informev2
1316
Informe de repotenciación Ingenieros Emetres Perú SAC
Points simultaneously violating both horizontal and vertical clearance requirements are
A clearance value of 10000 indicates the program was unable to calculate a clearance
(no wires in span, no wires crossing point, unknown ground elevation, no points meeting above criteria...).
Number Number Case Vert. Horiz. Violations or Between Point Feature Station Offset Z Height
Description
------------------------------------------------------------------------------------------------------------------------------------------------
T.1 T.2 T55ºC 7.12 -7.20 OK 0 0 DXFterreno 44.74 -0.00 367.64 0.00
T.2 T.3 T55ºC 2.25 -3.40 OK 0 0 DXF Línea electrica 582.96 -0.00 365.29 0.00
T.3 T.4 T55ºC 2.11 -7.20 OK 0 0 DXFterreno 1129.89 -0.00 395.87 0.00
Página 39 de 163
Ref.03056-14 Informev2
1317
Informe de repotenciación Ingenieros Emetres Perú SAC
T.4 T.5 T55ºC 8.01 -7.20 OK 0 0 DXFterreno 1628.32 -0.00 400.08 0.00
T.5 T.6 T55ºC 1.55 -7.20 OK 0 0 DXFterreno 1915.80 -0.00 418.30 0.00
T.6 T.7 T55ºC 10.48 -7.20 OK 0 0 DXFterreno 2273.36 -0.00 435.78 0.00
T.7 T.8 T55ºC 7.29 -7.20 OK 0 0 DXFterreno 2384.18 -0.00 446.19 0.00
T.8 T.9 T55ºC 0.74 -7.20 OK 0 0 DXFterreno 3378.43 -0.00 378.91 0.00
T.9 T.10 T55ºC 4.41 -7.20 OK 0 0 DXFterreno 3785.00 -0.00 429.03 0.00
T.10 T.11 T55ºC 0.81 -7.20 OK 0 0 DXFterreno 3978.58 -0.00 434.56 0.00
T.11 T.12 T55ºC 11.26 -5.12 OK 0 0 DXFterreno 4210.26 -0.00 430.63 0.00
T.12 T.13 T55ºC 0.02 -7.20 OK 0 0 DXFterreno 4911.41 -0.00 469.09 0.00
T.13 T.14 T55ºC 3.17 -7.20 OK 0 0 DXF lateral 5116.02 -0.00 461.42 0.00
T.14 T.15 T55ºC 9.53 -7.20 OK 0 0 DXF lateral 5961.02 -0.00 413.68 0.00
T.15 T.16 T55ºC 8.14 -7.20 OK 0 0 DXF lateral 6688.58 -0.00 335.05 0.00
T.16 T.17 T55ºC 2.94 -7.20 OK 0 0 DXFterreno 6838.11 -0.00 319.51 0.00
T.17 T.18 T55ºC 2.61 -7.20 OK 0 0 DXFterreno 7312.25 -0.00 305.33 0.00
T.18 T.19 T55ºC 4.30 -7.20 OK 0 0 DXFterreno 7648.87 -0.00 312.58 0.00
T.19 T.20 T55ºC 0.64 -7.20 OK 0 0 DXF lateral 8374.35 -0.00 339.74 0.00
T.20 T.21 T55ºC 12.28 -7.20 OK 0 0 DXFterreno 8860.42 -0.00 273.86 0.00
Página 40 de 163
Ref.03056-14 Informev2
1318
Informe de repotenciación Ingenieros Emetres Perú SAC
T.21 T.22 T55ºC 0.52 -7.20 OK 0 0 DXFterreno 9198.66 -0.00 272.90 0.00
T.22 T.23 T55ºC 7.20 -7.20 OK 0 0 DXF lateral 9570.48 -0.00 273.06 0.00
T.23 T.24 T55ºC 10.07 -7.20 OK 0 0 DXFterreno 10199.48 -0.00 325.20 0.00
T.24 T.25 T55ºC 10.52 -7.20 OK 0 0 DXFterreno 10411.52 -0.00 299.72 0.00
T.25 T.26 T55ºC 4.14 -7.20 OK 0 0 DXFterreno 10889.10 -0.00 263.90 0.00
T.26 T.27 T55ºC 3.26 -7.20 OK 0 0 DXFterreno 11148.02 -0.00 267.08 0.00
T.27 T.28 T55ºC 4.26 -7.20 OK 0 0 DXFterreno 12020.01 -0.00 312.84 0.00
T.28 T.29 T55ºC 11.50 -6.11 OK 0 0 DXFterreno 13082.92 -0.00 333.18 0.00
T.29 T.30 T55ºC 8.33 -7.20 OK 0 0 DXF lateral 13426.59 -0.00 339.26 0.00
T.30 T.31 T55ºC 8.00 -7.20 OK 0 0 DXF lateral 13452.09 -0.00 339.30 0.00
T.31 T.32 T55ºC 0.38 -7.20 OK 0 0 DXFterreno 14066.49 -0.00 292.31 0.00
T.32 T.33 T55ºC 4.90 -7.20 OK 0 0 DXFterreno 14303.89 -0.00 273.41 0.00
T.33 T.34 T55ºC 3.76 -7.20 OK 0 0 DXFterreno 14761.38 -0.00 251.47 0.00
T.34 T.35 T55ºC 2.50 -7.20 OK 0 0 DXF lateral 14958.08 -0.00 267.03 0.00
T.35 T.36 T55ºC 7.75 -7.20 OK 0 0 DXFterreno 15674.33 -0.00 231.49 0.00
T.36 T.37 T55ºC 9.72 -7.20 OK 0 0 DXFterreno 15817.13 -0.00 234.10 0.00
T.37 T.38 T55ºC 9.33 -7.20 OK 0 0 DXFterreno 16819.06 -0.00 222.70 0.00
Página 41 de 163
Ref.03056-14 Informev2
1319
Informe de repotenciación Ingenieros Emetres Perú SAC
T.38 T.39 T55ºC 0.09 -7.20 OK 0 0 DXFterreno 17044.07 -0.00 230.44 0.00
T.39 T.40 T55ºC 8.97 -7.20 OK 0 0 DXFterreno 17365.04 -0.00 243.55 0.00
T.40 T.41 T55ºC 8.46 -7.20 OK 0 0 DXF lateral 17713.62 -0.00 258.90 0.00
T.41 T.42 T55ºC 8.18 -7.20 OK 0 0 DXF lateral 18198.25 -0.00 302.22 0.00
T.42 T.43 T55ºC 9.20 -7.20 OK 0 0 DXF lateral 18914.53 -0.00 291.91 0.00
T.43 T.44 T55ºC 7.14 -7.20 OK 0 0 DXF lateral 19295.22 -0.00 318.25 0.00
T.44 T.45 T55ºC 6.99 -3.49 OK 0 0 DXF lateral 19295.22 -0.00 318.25 0.00
T.45 T.46 T55ºC 2.73 -7.20 OK 0 0 DXFterreno 20007.14 -0.00 217.28 0.00
T.46 T.47 T55ºC 8.63 -7.12 OK 0 0 DXF lateral 20704.32 -0.00 281.84 0.00
T.47 T.48 T55ºC 8.61 -7.20 OK 0 0 DXF lateral 20704.32 -0.00 281.84 0.00
T.48 T.49 T55ºC 4.82 7.64 OK 0 0 DXF lateral 22174.21 -0.00 267.52 0.00
T.49 T.50 T55ºC -0.59 -7.20 NG 7 0 DXF lateral 22177.46 -0.00 268.77 0.00
T.50 T.51 T55ºC 10.34 -7.20 OK 0 0 DXFterreno 22390.84 -0.00 221.30 0.00
T.51 T.52 T55ºC 10.96 -7.20 OK 0 0 DXFterreno 23874.16 -0.00 272.14 0.00
T.52 T.53 T55ºC 3.20 -7.20 OK 0 0 DXF lateral 23932.66 -0.00 276.07 0.00
T.53 T.54 T55ºC 3.61 -7.20 OK 0 0 DXFterreno 24599.48 -0.00 243.40 0.00
T.54 T.55 T55ºC 9.94 -7.20 OK 0 0 DXFterreno 24986.24 -0.00 281.63 0.00
Página 42 de 163
Ref.03056-14 Informev2
1320
Informe de repotenciación Ingenieros Emetres Perú SAC
T.55 T.56 T55ºC 3.00 -7.20 OK 0 0 DXFterreno 25606.91 -0.00 163.35 0.00
T.56 T.57 T55ºC 0.57 -7.20 OK 0 0 DXFterreno 26012.85 -0.00 152.53 0.00
T.57 T.58 T55ºC 1.33 -7.20 OK 0 0 DXFterreno 26460.95 -0.00 145.22 0.00
T.58 T.59 T55ºC 1.21 -7.20 OK 0 0 DXFterreno 26865.37 -0.00 144.56 0.00
T.59 T.60 T55ºC 4.86 -7.20 OK 0 0 DXF lateral 27410.98 -0.00 196.22 0.00
T.60 T.61 T55ºC 8.87 -7.20 OK 0 0 DXFterreno 27847.59 -0.00 270.20 0.00
T.61 T.62 T55ºC 0.44 -7.20 OK 0 0 DXF lateral 28929.61 -0.00 251.58 0.00
T.62 T.63 T55ºC 6.38 -7.20 OK 0 0 DXF lateral 28974.53 -0.00 251.08 0.00
T.63 T.64 T55ºC 0.64 -7.20 OK 0 0 DXF lateral 29902.38 -0.00 185.81 0.00
T.64 T.65 T55ºC 7.89 -7.20 OK 0 0 DXFterreno 30559.02 -0.00 143.37 0.00
T.65 T.66 T55ºC 0.89 -7.20 OK 0 0 DXFterreno 30906.20 -0.00 144.43 0.00
T.66 T.67 T55ºC 0.60 -7.20 OK 0 0 DXFterreno 31413.57 -0.00 139.15 0.00
T.67 T.68 T55ºC 8.75 -7.20 OK 0 0 DXFterreno 31780.33 -0.00 137.77 0.00
T.68 T.69 T55ºC 1.49 -7.20 OK 0 0 DXFterreno 32160.63 -0.00 139.00 0.00
T.69 T.70 T55ºC 11.04 -7.20 OK 0 0 DXFterreno 32557.61 -0.00 144.52 0.00
T.70 T.71 T55ºC 0.40 -7.20 OK 0 0 DXFterreno 32756.25 -0.00 149.20 0.00
T.71 T.72 T55ºC 6.74 -7.20 OK 0 0 DXFterreno 33553.69 -0.00 238.03 0.00
Página 43 de 163
Ref.03056-14 Informev2
1321
Informe de repotenciación Ingenieros Emetres Perú SAC
T.72 T.73 T55ºC 7.40 -7.20 OK 0 0 DXF lateral 33868.36 -0.00 197.30 0.00
T.73 T.74 T55ºC 3.96 -7.20 OK 0 0 DXF lateral 34648.19 -0.00 212.26 0.00
T.74 T.75 T55ºC 3.78 7.56 OK 0 0 DXF lateral 35490.01 -0.00 307.08 0.00
T.75 T.76 T55ºC 0.46 -7.20 OK 0 0 DXF lateral 35520.60 -0.00 305.88 0.00
T.76 T.77 T55ºC 5.44 -0.83 OK 0 0 DXF lateral 35653.57 -0.00 294.08 0.00
T.77 T.78 T55ºC 8.47 -7.20 OK 0 0 DXFterreno 36524.77 -0.00 163.92 0.00
T.78 T.79 T55ºC 10.28 -7.20 OK 0 0 DXFterreno 37578.06 -0.00 208.21 0.00
T.79 T.80 T55ºC 6.76 -7.20 OK 0 0 DXFterreno 38022.40 -0.00 141.35 0.00
T.80 T.81 T55ºC 3.70 -7.20 OK 0 0 DXFterreno 38358.38 -0.00 138.33 0.00
T.81 T.82 T55ºC 1.08 -7.20 OK 0 0 DXFterreno 38819.76 -0.00 135.97 0.00
T.82 T.83 T55ºC 1.41 -7.20 OK 0 0 DXFterreno 39260.24 -0.00 130.59 0.00
T.83 T.84 T55ºC 1.27 -7.20 OK 0 0 DXFterreno 39625.92 -0.00 128.07 0.00
T.84 T.85 T55ºC 1.13 -7.20 OK 0 0 DXFterreno 40061.04 -0.00 134.72 0.00
T.85 T.86 T55ºC 0.82 -7.20 OK 0 0 DXFterreno 40435.21 -0.00 134.40 0.00
T.86 T.87 T55ºC 0.92 -9.20 OK 0 0 DXFcaminos 40962.55 -0.00 119.88 0.00
T.87 T.88 T55ºC 1.38 -7.20 OK 0 0 DXFterreno 41308.48 -0.00 122.73 0.00
T.88 T.89 T55ºC 1.28 -7.20 OK 0 0 DXFterreno 41739.23 -0.00 121.94 0.00
Página 44 de 163
Ref.03056-14 Informev2
1322
Informe de repotenciación Ingenieros Emetres Perú SAC
T.89 T.90 T55ºC 0.72 -7.20 OK 0 0 DXFterreno 42197.39 -0.00 121.51 0.00
T.90 T.91 T55ºC 1.68 -7.20 OK 0 0 DXFterreno 42615.09 -0.00 119.64 0.00
T.91 T.92 T55ºC 1.41 -7.20 OK 0 0 DXFterreno 43093.46 -0.00 117.71 0.00
T.92 T.93 T55ºC 1.01 -7.20 OK 0 0 DXFterreno 43584.25 -0.00 112.38 0.00
T.93 T.94 T55ºC 0.11 -7.20 OK 0 0 DXFterreno 44014.76 -0.00 105.30 0.00
T.94 T.95 T55ºC 1.17 -7.20 OK 0 0 DXFterreno 44416.94 -0.00 99.82 0.00
T.95 T.96 T55ºC 0.88 -9.20 OK 0 0 DXFcaminos 44794.63 -0.00 98.34 0.00
T.96 T.97 T55ºC 5.23 -7.20 OK 0 0 DXFterreno 45172.39 -0.00 111.13 0.00
T.97 T.98 T55ºC 8.13 -7.20 OK 0 0 DXFterreno 45455.04 -0.00 128.53 0.00
T.98 T.99 T55ºC 10.02 -7.20 OK 0 0 DXFterreno 46073.92 -0.00 78.86 0.00
T.99 T.100 T55ºC 8.88 -7.20 OK 0 0 DXFterreno 46494.53 -0.00 72.85 0.00
T.100 T.101 T55ºC 8.24 -7.20 OK 0 0 DXFterreno 46945.68 -0.00 70.30 0.00
T.101 T.102 T55ºC 8.73 -7.20 OK 0 0 DXFterreno 47370.72 -0.00 67.99 0.00
T.102 T.103 T55ºC 5.00 -3.40 OK 0 0 DXF Línea electrica 47703.01 -0.00 77.89 0.00
T.103 T.104 T55ºC 7.72 -7.20 OK 0 0 DXFterreno 48235.49 -0.00 66.47 0.00
T.104 T.105 T55ºC 10.04 -7.20 OK 0 0 DXFterreno 48653.29 -0.00 65.80 0.00
T.105 T.106 T55ºC 7.90 -7.20 OK 0 0 DXFterreno 49073.54 -0.00 66.08 0.00
Página 45 de 163
Ref.03056-14 Informev2
1323
Informe de repotenciación Ingenieros Emetres Perú SAC
T.106 T.107 T55ºC 9.76 -7.20 OK 0 0 DXFterreno 49435.87 -0.00 64.51 0.00
T.107 T.108 T55ºC 8.62 -7.20 OK 0 0 DXFterreno 49880.38 -0.00 63.54 0.00
T.108 T.109 T55ºC 6.05 -7.20 OK 0 0 DXFterreno 51044.97 -0.00 226.54 0.00
T.109 T.110 T55ºC 8.45 -7.20 OK 0 0 DXFterreno 51803.36 -0.00 95.16 0.00
T.110 T.111 T55ºC 5.58 -3.40 OK 0 0 DXF Línea electrica 51989.49 -0.00 97.82 0.00
T.111 T.112 T55ºC 1.25 -7.20 OK 0 0 DXFterreno 52337.38 -0.00 84.72 0.00
T.112 T.113 T55ºC 1.31 -7.20 OK 0 0 DXFterreno 52712.95 -0.00 88.16 0.00
T.113 T.114 T55ºC 2.04 -7.20 OK 0 0 DXF lateral 52961.36 -0.00 92.45 0.00
T.114 T.115 T55ºC 4.18 -7.20 OK 0 0 DXFterreno 53497.81 -0.00 74.98 0.00
T.115 T.116 T55ºC 6.87 -3.40 OK 0 0 DXF Línea electrica 54029.64 -0.00 85.22 0.00
T.116 T.117 T55ºC 0.73 -7.20 OK 0 0 DXFterreno 54380.19 -0.00 76.51 0.00
T.117 T.118 T55ºC 1.48 -7.20 OK 0 0 DXFterreno 54896.98 -0.00 74.90 0.00
T.118 T.119 T55ºC 0.74 -7.20 OK 0 0 DXFterreno 55160.43 -0.00 73.80 0.00
T.119 T.120 T55ºC 0.34 -7.20 OK 0 0 DXFterreno 55554.98 -0.00 71.82 0.00
T.120 T.121 T55ºC 0.87 -7.20 OK 0 0 DXFterreno 56016.39 -0.00 73.04 0.00
T.121 T.122 T55ºC 0.77 -7.20 OK 0 0 DXFterreno 56321.06 -0.00 75.79 0.00
T.122 T.123 T55ºC 1.50 -7.20 OK 0 0 DXFterreno 56645.29 -0.00 74.67 0.00
Página 46 de 163
Ref.03056-14 Informev2
1324
Informe de repotenciación Ingenieros Emetres Perú SAC
T.123 T.124 T55ºC 1.13 -7.20 OK 0 0 DXFterreno 57048.69 -0.00 74.78 0.00
T.124 T.125 T55ºC 0.79 -7.20 OK 0 0 DXFterreno 57449.40 -0.00 71.54 0.00
T.125 T.126 T55ºC 0.86 -7.20 OK 0 0 DXFterreno 57971.97 -0.00 70.73 0.00
T.126 T.127 T55ºC 0.64 -7.20 OK 0 0 DXFterreno 58372.61 -0.00 70.35 0.00
T.127 T.128 T55ºC 1.70 -7.20 OK 0 0 DXFterreno 58835.95 -0.00 68.30 0.00
T.128 T.129 T55ºC 2.88 -7.20 OK 0 0 DXFterreno 59202.76 -0.00 64.71 0.00
T.129 T.130 T55ºC 0.67 -7.20 OK 0 0 DXFterreno 59738.38 -0.00 62.50 0.00
T.130 T.131 T55ºC 5.44 -7.20 OK 0 0 DXFterreno 60178.65 -0.00 57.53 0.00
T.131 T.132 T55ºC 1.26 -7.20 OK 0 0 DXFterreno 60500.60 -0.00 56.01 0.00
T.132 T.133 T55ºC 0.69 -7.20 OK 0 0 DXFterreno 60968.78 -0.00 53.33 0.00
T.133 T.134 T55ºC 1.09 -7.20 OK 0 0 DXFterreno 61415.72 -0.00 50.33 0.00
T.134 T.135 T55ºC 0.04 -7.20 OK 0 0 DXFterreno 61801.73 -0.00 46.35 0.00
T.135 T.136 T55ºC 0.42 -7.20 OK 0 0 DXFterreno 62289.75 -0.00 42.50 0.00
T.136 T.137 T55ºC 0.70 -7.20 OK 0 0 DXFterreno 62628.49 -0.00 43.39 0.00
T.137 T.138 T55ºC 0.03 -7.20 OK 0 0 DXFterreno 63150.11 -0.00 41.51 0.00
T.138 T.139 T55ºC 0.58 -7.20 OK 0 0 DXFterreno 63517.45 -0.00 45.24 0.00
T.139 T.140 T55ºC 2.41 -7.20 OK 0 0 DXFterreno 63834.58 -0.00 46.58 0.00
Página 47 de 163
Ref.03056-14 Informev2
1325
Informe de repotenciación Ingenieros Emetres Perú SAC
T.140 T.141 T55ºC 3.90 -7.20 OK 0 0 DXFterreno 64229.76 -0.00 51.44 0.00
T.141 T.142 T55ºC 2.15 -7.20 OK 0 0 DXFterreno 65071.75 -0.00 171.46 0.00
T.142 T.143 T55ºC 10.45 -7.20 OK 0 0 DXFterreno 65197.10 -0.00 160.41 0.00
T.143 T.144 T55ºC 8.30 -7.20 OK 0 0 DXFterreno 66396.76 -0.00 174.14 0.00
T.144 T.145 T55ºC 2.28 -7.20 OK 0 0 DXFterreno 67045.57 -0.00 81.49 0.00
T.145 T.146 T55ºC 4.97 7.73 OK 0 0 DXFterreno 67058.31 -0.00 79.63 0.00
T.146 T.147 T55ºC 5.84 -7.20 OK 0 0 DXFterreno 67954.78 -0.00 100.30 0.00
T.147 T.148 T55ºC 7.32 2.73 OK 0 0 DXFterreno 68236.68 -0.00 81.38 0.00
T.148 T.149 T55ºC 3.92 -7.20 OK 0 0 DXFterreno 68514.46 -0.00 58.58 0.00
T.149 T.150 T55ºC 10.47 7.29 OK 0 0 DXFterreno 68585.14 -0.00 52.70 0.00
T.150 T.151 T55ºC 10.51 -0.53 OK 0 0 DXFterreno 69155.25 -0.00 38.08 0.00
T.151 T.152 T55ºC 5.70 -7.20 OK 0 0 DXFterreno 69371.73 -0.00 26.14 0.00
T.152 T.153 T55ºC 13.41 -7.20 OK 0 0 DXFterreno 69753.57 -0.00 17.47 0.00
T.153 T.154 T55ºC 5.42 -7.20 OK 0 0 DXFterreno 70202.09 -0.00 13.58 0.00
T.154 T.155 T55ºC 1.82 -7.20 OK 0 0 DXFterreno 70501.86 -0.00 17.62 0.00
T.155 T.156 T55ºC 2.07 -7.20 OK 0 0 DXFterreno 70865.22 -0.00 13.66 0.00
T.156 T.157 T55ºC 0.85 -7.20 OK 0 0 DXFterreno 71208.99 -0.00 15.65 0.00
Página 48 de 163
Ref.03056-14 Informev2
1326
Informe de repotenciación Ingenieros Emetres Perú SAC
T.157 T.158 T55ºC 1.44 -7.20 OK 0 0 DXFterreno 71657.92 -0.00 11.00 0.00
T.158 T.159 T55ºC 1.42 -7.20 OK 0 0 DXFterreno 71982.35 -0.00 9.75 0.00
T.159 T.160 T55ºC 2.43 -7.20 OK 0 0 DXFterreno 72465.11 -0.00 7.93 0.00
T.160 T.161 T55ºC 2.23 -7.20 OK 0 0 DXFterreno 72823.28 -0.00 7.86 0.00
T.161 T.162 T55ºC 1.32 -4.00 OK 0 0 DXF Línea telefono 73157.60 -0.00 19.13 0.00
T.162 T.163 T55ºC 7.82 -7.20 OK 0 0 DXFterreno 73732.31 -0.00 9.09 0.00
T.163 T.164 T55ºC 0.59 -4.00 OK 0 0 DXF Línea telefono 73856.87 -0.00 18.57 0.00
T.164 T.165 T55ºC 0.10 -7.20 OK 0 0 DXFterreno 74369.45 -0.00 9.03 0.00
T.165 T.166 T55ºC 1.12 -7.20 OK 0 0 DXFterreno 74768.30 -0.00 9.24 0.00
T.166 T.167 T55ºC 1.51 -6.20 OK 0 0 DXF Edificaciones 75112.74 -0.00 11.07 0.00
T.167 T.168 T55ºC 1.55 -7.20 OK 0 0 DXFterreno 75519.53 -0.00 9.51 0.00
T.168 T.169 T55ºC 2.35 -7.20 OK 0 0 DXFterreno 75909.61 -0.00 11.20 0.00
T.169 T.170 T55ºC 1.93 -7.20 OK 0 0 DXFterreno 76332.24 -0.00 14.57 0.00
T.170 T.171 T55ºC 1.24 -7.20 OK 0 0 DXFterreno 76569.94 -0.00 16.53 0.00
T.171 T.172 T55ºC 5.05 -7.20 OK 0 0 DXFterreno 77012.12 -0.00 10.87 0.00
T.172 T.173 T55ºC 0.81 -9.20 OK 0 0 DXFCtra 77280.41 -0.00 9.36 0.00
T.173 T.174 T55ºC 1.17 -6.20 OK 0 0 DXF Edificaciones 77601.52 -0.00 12.52 0.00
Página 49 de 163
Ref.03056-14 Informev2
1327
Informe de repotenciación Ingenieros Emetres Perú SAC
T.174 T.175 T55ºC 1.77 -6.20 OK 0 0 DXFvalla 78044.43 -0.00 13.89 0.00
T.175 T.176 T55ºC 2.25 -7.20 OK 0 0 DXFterreno 78331.56 -0.00 10.52 0.00
T.176 T.177 T55ºC 1.04 -7.20 OK 0 0 DXFterreno 78646.63 -0.00 11.19 0.00
T.177 T.178 T55ºC 1.07 -7.20 OK 0 0 DXFterreno 79093.68 -0.00 12.79 0.00
T.178 T.179 T55ºC 2.94 -6.20 OK 0 0 DXFvalla 79482.27 -0.00 11.78 0.00
T.179 T.180 T55ºC 2.46 -7.20 OK 0 0 DXFterreno 79873.89 -0.00 9.77 0.00
T.180 T.181 T55ºC 2.05 -7.20 OK 0 0 DXFterreno 80306.19 -0.00 12.23 0.00
T.181 T.182 T55ºC 2.09 -7.20 OK 0 0 DXFterreno 80640.82 -0.00 12.21 0.00
T.182 T.183 T55ºC 2.17 -6.20 OK 0 0 DXFvalla 80971.52 -0.00 13.87 0.00
T.183 T.184 T55ºC 2.31 -6.20 OK 0 0 DXFvalla 81345.65 -0.00 12.79 0.00
T.184 T.185 T55ºC 5.44 -7.20 OK 0 0 DXFterreno 81659.04 -0.00 10.60 0.00
T.185 T.186 T55ºC 4.96 -3.40 OK 0 0 DXF Línea electrica 82065.41 -0.00 17.09 0.00
T.186 T.187 T55ºC 5.63 -7.20 OK 0 0 DXFterreno 82334.37 -0.00 11.79 0.00
T.187 T.188 T55ºC 9.74 -6.20 OK 0 0 DXFvalla 82713.92 -0.00 23.62 0.00
T.188 T.189 T55ºC 9.56 -7.20 OK 0 0 DXFterreno 82780.03 -0.00 21.51 0.00
Página 50 de 163
Ref.03056-14 Informev2
1328
Informe de repotenciación Ingenieros Emetres Perú SAC
Página 51 de 163
Ref.03056-14 Informev2
1329
Informe de repotenciación Ingenieros Emetres Perú SAC
Conductor bearing is 202 (deg) (perpendicular to solar azimuth for maximum solar heating)
Sun time is 11 hours (solar altitude is 75 deg. and solar azimuth is 112 deg.)
Atmosphere is CLEAR
Day of year is 172 (corresponds to junio 21 in year 2014) (day of the year with most solar
heating)
Ref.03056-14 Informev2
1330
Informe de repotenciación Ingenieros Emetres Perú SAC
Solar heat input is 15.791 (Watt/m) (corresponds to Global Solar Radiation of 1079.371
(Watt/m^2) - which was calculated)
Para esta temperatura del conductor de 61ºC la tabla de distáncias queda como
sigue:
Página 53 de 163
Ref.03056-14 Informev2
1331
Informe de repotenciación Ingenieros Emetres Perú SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mínima (m) total (km)
(ºC) (m) (m)
T.1 T.2 61 7,20 6,98 14,20 terreno 0,045
Página 54 de 163
Ref.03056-14 Informev2
1332
Informe de repotenciación Ingenieros Emetres Perú SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mínima (m) total (km)
(ºC) (m) (m)
T.22 T.23 61 7,20 7,15 14,40 lateral 9,570
Página 55 de 163
Ref.03056-14 Informev2
1333
Informe de repotenciación Ingenieros Emetres Perú SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mínima (m) total (km)
(ºC) (m) (m)
T.43 T.44 61 7,20 7,13 14,30 lateral 19,295
Página 56 de 163
Ref.03056-14 Informev2
1334
Informe de repotenciación Ingenieros Emetres Perú SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mínima (m) total (km)
(ºC) (m) (m)
T.64 T.65 61 7,20 7,65 14,90 terreno 30,557
Página 57 de 163
Ref.03056-14 Informev2
1335
Informe de repotenciación Ingenieros Emetres Perú SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mínima (m) total (km)
(ºC) (m) (m)
T.85 T.86 61 7,20 0,55 7,80 terreno 40,435
Página 58 de 163
Ref.03056-14 Informev2
1336
Informe de repotenciación Ingenieros Emetres Perú SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mínima (m) total (km)
(ºC) (m) (m)
T.106 T.107 61 7,20 9,49 16,70 terreno 49,437
Página 59 de 163
Ref.03056-14 Informev2
1337
Informe de repotenciación Ingenieros Emetres Perú SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mínima (m) total (km)
(ºC) (m) (m)
T.127 T.128 61 7,20 1,38 8,60 terreno 58,836
Página 60 de 163
Ref.03056-14 Informev2
1338
Informe de repotenciación Ingenieros Emetres Perú SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mínima (m) total (km)
(ºC) (m) (m)
T.148 T.149 61 7,20 3,70 10,90 terreno 68,514
Página 61 de 163
Ref.03056-14 Informev2
1339
Informe de repotenciación Ingenieros Emetres Perú SAC
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mínima (m) total (km)
(ºC) (m) (m)
T.169 T.170 61 7,20 1,65 8,80 terreno 76,332
Página 62 de 163
Ref.03056-14 Informev2
1340
Informe de repotenciación Ingenieros Emetres Perú SAC
De la tabla anterior se desprende que sería necesario verificar los siguientes vanos:
Torre Torre Temp. Distancia Margen Distancia Entidad que limita P.K.
Inicial final cond. mínima (m) total (km)
(ºC) (m) (m)
T.12 T.13 61 7,20 -0,19 7,00 terreno 4,911
Página 63 de 163
Ref.03056-14 Informev2
1341
Informe de repotenciación Ingenieros Emetres Perú SAC
Dirección
Viento
2 m/s
DV = 9.87 m
Datos de medición:
Fecha : 04.04.2014
Hora : 14:35
Equipos utilizados :
Página 64 de 163
Ref.03056-14 Informev2
1342
Informe de repotenciación Ingenieros Emetres Perú SAC
Dirección
Viento
2.5 m/s
DV = 10.36 m
Datos de medición:
Fecha : 04.04.2014
Hora : 18:15
Equipos utilizados :
Página 65 de 163
Ref.03056-14 Informev2
1343
Informe de repotenciación Ingenieros Emetres Perú SAC
Dirección
Viento
4.3 m/s
DV = 8.57 m
Datos de medición:
Fecha : 10.04.2014
Hora : 14:05
Equipos utilizados :
Página 66 de 163
Ref.03056-14 Informev2
1344
Informe de repotenciación Ingenieros Emetres Perú SAC
Dirección
DV = 13.68 m Viento
3.2 m/s
Datos de medición:
Fecha : 10.04.2014
Hora : 15:15
Equipos utilizados :
Página 67 de 163
Ref.03056-14 Informev2
1345
Informe de repotenciación Ingenieros Emetres Perú SAC
Dirección
Viento
3.3 m/s
DV = 8.50 m
Datos de medición:
Fecha : 10.04.2014
Hora : 17:22
Equipos utilizados :
Página 68 de 163
Ref.03056-14 Informev2
1346
Informe de repotenciación Ingenieros Emetres Perú SAC
Dirección
Viento
3.2 m/s
DV = 9.70 m
Datos de medición:
Fecha : 04.04.2014
Hora : 12:26
Equipos utilizados :
Página 69 de 163
Ref.03056-14 Informev2
1347
Informe de repotenciación Ingenieros Emetres Perú SAC
Página 70 de 163
Ref.03056-14 Informev2
1348
1349
1350
1351
1352
1353
1354
1355
1356
1357
1358
1359
1360
1361
1362
1363
1364
1365
1366
1367
1368
1369
1370
1371
1372
1373
1374
1375
1376
1377
1378
1379
1380
1381
1382
1383
1384
1385
1386
1387
1388
1389
1390
1391
1392
1393
1394
1395
1396
Informe de repotenciación Ingenieros Emetres Perú SAC
12. METRADO
Ref.03056-14 Informev2
1397
Informe de repotenciación Ingenieros Emetres Perú SAC
de la línea de transmisión de 220kV Ref. 03056‐14 Informev2
Chiclayo Oeste – Carhuaquero Rev. 2
METRADO Y VALOR REFERENCIAL (dolares americanos)
REPOTENCIACION LINEA DE TRANSMISION 220 KV : CHICLAYO ‐ CARHUAQUERO
TOTAL 27,500.00
Longitud de la Linea (km) 40.00
Costo por km (US/km) 687.50
PROYECTO DE REPOTENCIACIÓN DE LA LÍNEA DE TRANSMISIÓN DE 220kV
CHICLAYO OESTE – CARHUAQUERO
Ref. 03056‐14 Informev2
Página 120
1398
Informe de repotenciación Ingenieros Emetres Perú SAC
SUBESTACIONES
1. INTRODUCCION Y OBJETIVO
El presente documento tiene como objetivo realizar una evaluación para los equipos
de las subestaciones de cabecera, en las celdas de la línea en 220kV para las
Subestación Chiclayo Oeste y Carhuaquero, como parte del proyecto
“Repotenciación de la línea 220kV Chiclayo Oeste/Carhuaquero a 250MVA”, y
determinar una actuaciones necesarias para lograr dicha finalidad.
2. ANTECEDENTES
3. CONDICIONES AMBIENTALES
El tipo de clima presente en esta localidad es del tipo seco, templado y soleado
durante el día. Refrigerado durante la noche. Clima de selva alta, menos cálido por
encontrarse a mayor altitud, más nuboso y extremo lluvioso. Las condiciones
ambientales con la que deberán ser capaces de trabajar el equipo especificado son
las siguientes:
Página 121 de 165
PROYECTO DEREPOTENCIACIÓN DE LA LÍNEA DE TRANSMISIÓN DE 220kV
CHICLAYO OESTE – CARHUAQUERO
Ref.03056‐14 Informev2
1399
Informe de repotenciación Ingenieros Emetres Perú SAC
CONDICIONES PARAMETROS
Humedad Relativa 70 %
Frecuencia Hz 60
Nº de fases - 3
Efectivamente conectado a
Neutro del sistema -
tierra
Ref.03056-14 Informev2
1400
Informe de repotenciación Ingenieros Emetres Perú SAC
Ref.03056-14 Informev2
1401
Informe de repotenciación Ingenieros Emetres Perú SAC
6.2 UBICACIÓN S/E CARHUAQUERO
La subestación Carhuaquero se ubica al noreste del Perú, en el departamento de
Cajamarca, al este de la ciudad de Chiclayo y es de propiedad de la empresa Duke
Energy Perú. Cuenta con instalaciones en 220 y 10kV.
7. CONFIGURACION Y DESCRIPCION DE LA S/E CHICLAYO OESTE
La subestación Chiclayo Oeste es una subestación de 220/60kV, cuenta con una
configuración de doble barra tanto en el nivel de 220kV como en el nivel de 60kV.
Página 124 de 165
PROYECTO DEREPOTENCIACIÓN DE LA LÍNEA DE TRANSMISIÓN DE 220kV
CHICLAYO OESTE – CARHUAQUERO
Ref.03056‐14 Informev2
1402
Informe de repotenciación Ingenieros Emetres Perú SAC
En 220kV:
Página 125 de 165
PROYECTO DEREPOTENCIACIÓN DE LA LÍNEA DE TRANSMISIÓN DE 220kV
CHICLAYO OESTE – CARHUAQUERO
Ref.03056‐14 Informev2
1403
Informe de repotenciación Ingenieros Emetres Perú SAC
Página 126 de 165
PROYECTO DEREPOTENCIACIÓN DE LA LÍNEA DE TRANSMISIÓN DE 220kV
CHICLAYO OESTE – CARHUAQUERO
Ref.03056‐14 Informev2
1404
Informe de repotenciación Ingenieros Emetres Perú SAC
En 60kV:
Página 127 de 165
PROYECTO DEREPOTENCIACIÓN DE LA LÍNEA DE TRANSMISIÓN DE 220kV
CHICLAYO OESTE – CARHUAQUERO
Ref.03056‐14 Informev2
1405
Informe de repotenciación Ingenieros Emetres Perú SAC
Página 128 de 165
PROYECTO DEREPOTENCIACIÓN DE LA LÍNEA DE TRANSMISIÓN DE 220kV
CHICLAYO OESTE – CARHUAQUERO
Ref.03056‐14 Informev2
1406
Informe de repotenciación Ingenieros Emetres Perú SAC
Un transformador de tensión.
Página 129 de 165
PROYECTO DEREPOTENCIACIÓN DE LA LÍNEA DE TRANSMISIÓN DE 220kV
CHICLAYO OESTE – CARHUAQUERO
Ref.03056‐14 Informev2
1407
Informe de repotenciación Ingenieros Emetres Perú SAC
S/E Chiclayo Oeste: Equipos primarios existentes del bahía de linea Chiclayo Oeste
– Carhuaquero.
Trampa de Onda 2
8. CONFIGURACION Y DESCRIPCION DE LA S/E CARHUAQUERO
La subestación Carhuaquero 220/10 kV cuenta con una configuración de simple
barra tanto en el nivel de 220kV como en el nivel de 10kV. Actualmente la
subestación cuenta con el siguiente equipamiento:
En 220kV:
Página 130 de 165
PROYECTO DEREPOTENCIACIÓN DE LA LÍNEA DE TRANSMISIÓN DE 220kV
CHICLAYO OESTE – CARHUAQUERO
Ref.03056‐14 Informev2
1408
Informe de repotenciación Ingenieros Emetres Perú SAC
Página 131 de 165
PROYECTO DEREPOTENCIACIÓN DE LA LÍNEA DE TRANSMISIÓN DE 220kV
CHICLAYO OESTE – CARHUAQUERO
Ref.03056‐14 Informev2
1409
Informe de repotenciación Ingenieros Emetres Perú SAC
Un autotransformador 220/10kV.
Un interruptor SF6 con una bobina de cierre y dos bobinas de disparo, 245kV,
2000A.
Un interruptor SF6 con una bobina de cierre y dos bobinas de disparo, 245kV, 2000
A.
PROYECTO DEREPOTENCIACIÓN DE LA LÍNEA DE TRANSMISIÓN DE 220kV
CHICLAYO OESTE – CARHUAQUERO
Ref.03056‐14 Informev2
1410
Informe de repotenciación Ingenieros Emetres Perú SAC
En 10kV:
Un autotransformador 220/10kV.
Un interruptor SF6 con una bobina de cierre y dos bobinas de disparo, 12kV, 1250A,
25kA.
Un interruptor SF6 con una bobina de cierre y dos bobinas de disparo, 12kV, 1250A,
25kA.
Un interruptor SF6 con una bobina de cierre y dos bobinas de disparo, 245kV,
2000A.
Página 133 de 165
PROYECTO DEREPOTENCIACIÓN DE LA LÍNEA DE TRANSMISIÓN DE 220kV
CHICLAYO OESTE – CARHUAQUERO
Ref.03056‐14 Informev2
1411
Informe de repotenciación Ingenieros Emetres Perú SAC
Pararrayos 190kV 3
Trampa de Onda 2
Ref.03056-14 Informev2
1412
Informe de repotenciación Ingenieros Emetres Perú SAC
Parámetros Unidades
Cantidad de Alambres y
37/4,18
Diámetro
En el anexo se encuentra una tabla completa con las características eléctricas para
este conductor.
Ref.03056-14 Informev2
1413
Informe de repotenciación Ingenieros Emetres Perú SAC
Considerando:
Es decir;
Ahora se determinara la nueva corriente que transporta la línea por los equipos de la
bahía en condiciones de operación normal para una potencia de 250MVA.
Considerando:
Es decir;
Ref.03056-14 Informev2
1414
Informe de repotenciación Ingenieros Emetres Perú SAC
i. S/E Carhuaquero
Interruptor
Parámetros Unidades
Rango de frecuencia 60 Hz
Se puede apreciar que la nueva corriente nominal de operación está dentro de los
rangos de funcionamiento del interruptor ya que es menor que 2000 A.
Ref.03056-14 Informev2
1415
Informe de repotenciación Ingenieros Emetres Perú SAC
Parámetros Unidades
Rango de corriente de 40 kA
cortocircuito
Rango de frecuencia 60 Hz
Se puede apreciar que la nueva corriente nominal de operación está dentro de los
rangos de funcionamiento del interruptor ya que es menor que 1600 A.
Parámetros Unidades
Rango de corriente de
40 kA
cortocircuito
Rango de frecuencia 60 Hz
Se puede apreciar que la nueva corriente nominal de operación está dentro de los
rangos de funcionamiento del interruptor ya que es menor que 1600 A.
Página 138 de 163
Ref.03056-14 Informev2
1416
Informe de repotenciación Ingenieros Emetres Perú SAC
Transformadores de corriente
Parámetros Unidades
Rango de frecuencia 60 Hz
Se puede apreciar que la nueva corriente nominal de operación está sobre los
valores nominales de corriente del primario, esto provoca que se obtengan valores
de medida con errores mayores a los permitidos en el secundario del trasformador
de corriente, ocasionando malas lecturas de las protecciones en esa bahía. Por esto
es necesario remplazar los transformadores de corriente por unos que tenga mayor
corriente nominal en el primario.
Sólo se deberán reajustar los valores de actuación de los relés de protección según
las nuevas condiciones de operación de la línea.
Ref.03056-14 Informev2
1417
Informe de repotenciación Ingenieros Emetres Perú SAC
Trampas de onda
Parámetros Unidades
Inductancia 0.2 mH
Se puede apreciar que la nueva corriente nominal de operación está sobre el valor
de corriente nominal del equipo, ocasionando el mal funcionamiento de la trampa de
onda y pudiendo comprometer el equipo. Por esto es necesario remplazar la trampa
de onda por una con mayor corriente nominal.
Conductor de barras
Parámetros Unidades
Cantidad de Alambres y
37/4,18
Diámetro
Ref.03056-14 Informev2
1418
Informe de repotenciación Ingenieros Emetres Perú SAC
En el anexo se encuentra una tabla completa con las características eléctricas para
este conductor.
Interruptor
Parámetros Unidades
Rango de corriente de 40 kA
cortocircuito
Rango de frecuencia 60 Hz
Ref.03056-14 Informev2
1419
Informe de repotenciación Ingenieros Emetres Perú SAC
Se puede apreciar que la nueva corriente nominal de operación está dentro de los
rangos de funcionamiento del interruptor ya que es menor que 2500 A.
Parámetros Unidades
Rango de corriente de 40 kA
cortocircuito
Rango de frecuencia 60 Hz
Se puede apreciar que la nueva corriente nominal de operación está dentro de los
rangos de funcionamiento del interruptor ya que es menor que 1600 A.
Parámetros Unidades
Rango de corriente de 40 kA
cortocircuito
Rango de frecuencia 60 Hz
Ref.03056-14 Informev2
1420
Informe de repotenciación Ingenieros Emetres Perú SAC
Se puede apreciar que la nueva corriente nominal de operación está dentro de los
rangos de funcionamiento del interruptor ya que es menor que 1600 A.
Transformadores de corriente
Sólo se deberán reajustar los valores de actuación de los relés de protección según
las nuevas condiciones de operación de la línea.
Trampas de onda
Conductor de barras
Parámetros Unidades
Ref.03056-14 Informev2
1421
Informe de repotenciación Ingenieros Emetres Perú SAC
Cantidad de Alambres y
61/3,56 mm
Diámetro
En el anexo se encuentra una tabla completa con las características eléctricas para
este conductor.
TABLA RESUMEN
SUBESTACION CARHUAQUERO
Ref.03056-14 Informev2
1422
Informe de repotenciación Ingenieros Emetres Perú SAC
Barras
10. CONCLUSIONES
Se puede apreciar que frente a esta repotenciación de la línea, para los equipos de
la bahía correspondiente a la línea de salida a la subestación Carhuaquero, como el
interruptor, los seccionadores con o sin puesta a tierra, no tienen problemas ya que
soportan la nueva corriente que circula por ellos. En el caso de los transformadores
de corriente, la corriente nominal de la línea en el nuevo escenario excede la
nominal de los equipos, esto provoca que se obtengan medidas y lecturas
incorrectas. Por esta razón se deberán remplazar por unos que tengan el rango de
corriente nominal del primario superior al de régimen permanente de operación de la
línea. Pasa lo mismo en el caso de la trampa de onda, la corriente nominal de la
línea excede la nominal del equipo provocando mal funcionamiento y
comprometiendo el equipo. Por esta razón se deberán remplazar por unos que
tengan el rango de corriente nominal superior al de régimen permanente de
operación de la línea.
Para el caso de la subestación Chiclayo Oeste, se puede apreciar que frente a esta
repotenciación de la línea, para los equipos de la bahía de la línea, que tanto el
interruptor, los seccionadores con o sin puesta a tierra, no tienen problemas ya que
soportan la nueva corriente que circula por ellos.
Página 145 de 163
Ref.03056-14 Informev2
1423
Informe de repotenciación Ingenieros Emetres Perú SAC
Por otro lado se puede concluir, que a simple vista, el conductor de barra soporta la
nueva corriente de la línea pero es necesario realizar un análisis más exhaustivo
mediante una simulación de flujo de potencia en las barras de las subestaciones de
la línea involucrada, ya que con esto se obtienen las capacidades de la barra en
operación y los datos con mayor exactitud en relación a la nueva potencia de la
línea.
Página 146 de 165
PROYECTO DEREPOTENCIACIÓN DE LA LÍNEA DE TRANSMISIÓN DE 220kV
CHICLAYO OESTE – CARHUAQUERO
Ref.03056‐14 Informev2
1424
Informe de repotenciación Ingenieros Emetres Perú SAC
11. ANEXO
Ref.03056-14 Informev2
1425
Informe de repotenciación Ingenieros Emetres Perú SAC
Ref.03056-14 Informev2
1426
Informe de repotenciación Ingenieros Emetres Perú SAC
Ref.03056-14 Informev2
1427
Informe de repotenciación Ingenieros Emetres Perú SAC
SE CHICLAYO OESTE
Ref.03056-14 Informev2
1428
Informe de repotenciación Ingenieros Emetres Perú SAC
Ref.03056-14 Informev2
1429
Informe de repotenciación Ingenieros Emetres Perú SAC
Ref.03056-14 Informev2
1430
Informe de repotenciación Ingenieros Emetres Perú SAC
Ref.03056-14 Informev2
1431
Informe de repotenciación Ingenieros Emetres Perú SAC
Ref.03056-14 Informev2
1432
Informe de repotenciación Ingenieros Emetres Perú SAC
Ref.03056-14 Informev2
1433
Informe de repotenciación Ingenieros Emetres Perú SAC
Ref.03056-14 Informev2
1434
Informe de repotenciación Ingenieros Emetres Perú SAC
SE CARHUAQUERO
Ref.03056-14 Informev2
1435
Informe de repotenciación Ingenieros Emetres Perú SAC
Ref.03056-14 Informev2
1436
Informe de repotenciación Ingenieros Emetres Perú SAC
Ref.03056-14 Informev2
1437
Informe de repotenciación Ingenieros Emetres Perú SAC
Ref.03056-14 Informev2
1438
Informe de repotenciación Ingenieros Emetres Perú SAC
Ref.03056-14 Informev2
1439
Informe de repotenciación Ingenieros Emetres Perú SAC
de la línea de transmisión de 220kV Ref. 03056‐14 Informev2
Chiclayo Oeste – Carhuaquero Rev. 2
METRADO Y VALOR REFERENCIAL (dolares americanos)
SUBESTACION CHICLAYO 220 KV ‐ SUMINISTROS DE EQUIPOS Y MATERIALES
METRADO Y VALOR REFERENCIAL (dolares americanos)
SUBESTACION CHICLAYO 220 KV ‐ MONTAJE DE EQUIPOS Y MATERIALES
TOTAL 22,300.00
PROYECTO DE REPOTENCIACIÓN DE LA LÍNEA DE TRANSMISIÓN DE 220kV
CHICLAYO OESTE – CARHUAQUERO
Ref. 03056‐14 Informev2
Página 162
1440
Informe de repotenciación Ingenieros Emetres Perú SAC
de la línea de transmisión de 220kV Ref. 03056‐14 Informev2
Chiclayo Oeste – Carhuaquero Rev. 2
METRADO Y VALOR REFERENCIAL (dolares americanos)
SUBESTACION CARHUAQUERO 220 KV ‐ SUMINISTROS DE EQUIPOS Y MATERIALES
METRADO Y VALOR REFERENCIAL (dolares americanos)
SUBESTACION CARHUAQUERO 220 KV ‐ MONTAJE
TOTAL 22,300.00
PROYECTO DE REPOTENCIACIÓN DE LA LÍNEA DE TRANSMISIÓN DE 220kV
CHICLAYO OESTE – CARHUAQUERO
Ref. 03056‐14 Informev2
Página 163
1441
Informe de repotenciación Ingenieros Emetres Perú SAC
de la línea de transmisión de 220kV Ref. 03056‐14 Informev2
Chiclayo Oeste – Carhuaquero Rev. 2
METRADO Y VALOR REFERENCIAL (dolares americanos)
REPOTENCIACION LINEA DE TRANSMISION 220 KV : CHICLAYO ‐ CARHUAQUERO
TOTAL 27,500.00
Longitud de la Linea (km) 40.00
Costo por km (US/km) 687.50
PROYECTO DE REPOTENCIACIÓN DE LA LÍNEA DE TRANSMISIÓN DE 220kV
CHICLAYO OESTE – CARHUAQUERO
Ref. 03056‐14 Informev2
Página 164
1442
Informe de repotenciación Ingenieros Emetres Perú SAC
de la línea de transmisión de 220kV Ref. 03056‐14 Informev2
Chiclayo Oeste – Carhuaquero Rev. 2
PRESUPUESTO REFERENCIAL (dolares americanos)
RESUMEN REPOTENCIACION LINEA DE TRANSMISION 220 KV : CHICLAYO ‐ CARHUAQUERO
PROYECTO DE REPOTENCIACIÓN DE LA LÍNEA DE TRANSMISIÓN DE 220kV
CHICLAYO OESTE – CARHUAQUERO
Ref. 03056‐14 Informev2
Página 165
1443