MEMORIA DE CÁLCULO DEL INTERRUPTOR DE

ENTRADA DE LA UPS
ÁREA: PLAYA NORTE TABLERO No: UPS-01

ALIMENTADO DE: TGE-01

CAPACIDAD = 200 KVA ( 180 KW )

No. DE FASES = 3

No. DE HILOS = 3

Fp = 0.9

FRECUENCIA = 60 HZ

KVA x 1000 x Fd
In = Amp
1.732 x Vf x Ef

DONDE:

In = CORRIENTE NOMINAL DEL TABLERO

Fd = 1.00 (FACTOR DE DEMANDA )

Vf = 220 VOLTS

Ef = 0.8 (EFICIENCIA)

In = 656.10 Amp

CALIBRACIÓN DEL INTERRUPTOR = In x Fsc

DONDE:

Fsc = 1.75

Iint = 1,148.17 Amp

INTERRUPTOR SELECCIONADO:

CALIBRACIÓN: 1,200 Amp

MARCO: 1,200 Amp

No. DE POLOS: 3

653650941.xls HOJA 1 DE 1
MEMORIA DE CÁLCULO DEL INTERRUPTOR DEL MOTOGENERADOR
MG-03

GENERADOR: 400 KW ( 500 KVA)

ÁREA: EDIFICIO DE PLAYA NORTE

FASES = 3

HILOS = 4

FRECUENCIA = 60 HZ

KVA x 1000
In = Amp
1.732 x Vf

DONDE:

KVA = 500 ( 400 KW)

Vf = 220 Volts

Fp = 0.8

In = 1,312.20 Amp

CÁLCULO DEL INTERRUPTOR

Iint = In x Fsc Amp

DONDE:

In = 1,312.20 Amp

Fsc = 1.15 (VER ARTÍCULO 445-5 DE LA NOM-001-


SEDE-2005)
Iint = 1,509.03 Amp

INTERRUPTOR SELECCIONADO:

CALIBRACIÓN: 1,600 Amp DEL TIPO ELECTRONICO PARA


FACILITAR LA COORDINACIÓN DE LAS
PROTECCIONES
MARCO: 2,500 Amp

No. DE POLOS: 3