Demanda energética

ÍNDICE

1. RESUMEN DEL CÁLCULO DE LA DEMANDA ENERGÉTICA..................................................... 3

2. RESULTADOS MENSUALES................................................................................................. 3
2.1. Balance energético anual del edificio....................................................................... 3
2.2. Demanda energética mensual de calefacción y refrigeración................................... 5
2.3. Evolución de la temperatura.................................................................................... 5
2.4. Resultados numéricos del balance energético por zona y mes................................. 10

3. MODELO DE CÁLCULO DEL EDIFICIO................................................................................. 14


3.1. Agrupaciones de recintos......................................................................................... 14
Demanda energética

1. RESUMEN DEL CÁLCULO DE LA DEMANDA ENERGÉTICA.


La siguiente tabla es un resumen de los resultados obtenidos en el cálculo de la demanda energética de
calefacción y refrigeración de cada zona habitable, junto a la demanda total del edificio.
Su Dcal Dref
Zonas habitables
(m²) (kWh/año) (kWh/m²·año) (kWh/año) (kWh/m²·año)

zona_1 37.85 1266.57 33.46 575.42 15.20


zona_2 22.06 948.26 42.99 398.95 18.09
zona_3 22.56 690.48 30.60 426.91 18.92
zona_4 36.97 1013.41 27.41 616.04 16.66
zona_5 52.24 1525.83 29.21 595.13 11.39
zona_6 35.28 1389.78 39.39 547.19 15.51
zona_7 45.12 2244.69 49.75 439.64 9.74
zona_8 67.75 2306.21 34.04 631.88 9.33
zona_9 51.61 2251.69 43.63 866.39 16.79
zona_10 83.77 4688.84 55.97 1449.07 17.30
zona_11 7.38 931.07 126.21 98.22 13.31
zona_12 41.10 - - - -
503.70 19256.84 38.23 6644.85 13.19
donde:
Su: Superficie útil de la zona habitable, m².
Dcal: Valor calculado de la demanda energética de calefacción, kWh/m²·año.
Dref: Valor calculado de la demanda energética de refrigeración, kWh/m²·año.

2. RESULTADOS MENSUALES.
2.1. Balance energético anual del edificio.
La siguiente gráfica de barras muestra el balance energético del edificio mes a mes, contabilizando la energía
perdida o ganada por transmisión térmica a través de elementos pesados y ligeros (Q op y Qw, respectivamente),
la energía intercambiada por ventilación e infiltraciones (Q ve+inf), la ganancia de calor interna debida a la
ocupación (Qocup), a la iluminación (Qilum) y al equipamiento interno (Qequip), así como el aporte necesario de
calefacción (QH) y refrigeración (QC).

Página 3 - 16
Demanda energética

Energía (kWh)

8000

6000

4000

QH
2000 QC
Qocup
Qilum
0
Qequip
Qve+inf
-2000 Qop
Qw

-4000

-6000

-8000

Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic

En la siguiente tabla se muestran los valores numéricos correspondientes a la gráfica anterior, del balance
energético del edificio completo, como suma de las energías involucradas en el balance energético de cada una
de las zonas térmicas que conforman el modelo de cálculo del edificio.
El criterio de signos adoptado consiste en emplear valores positivos para energías aportadas a la zona de
cálculo, y negativos para la energía extraída.
Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic Año
(kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh/año) (kWh/m²·año)
Balance energético anual del edificio.
1199.5 984.6 1052.1 955.3 681.1 678.9 1019.0 1169.7 934.1 752.9 973.0 1139.8
Qop -28030.70 -55.65
-4786.5 -4266.3 -4231.2 -3416.9 -3545.7 -2464.5 -2235.1 -2053.1 -2002.2 -2501.5 -3604.4 -4463.0
1060.0 1155.7 1512.5 1535.1 1759.8 2190.9 2459.7 2448.7 2162.1 1613.0 1234.3 1014.1
Qw 16084.01 31.93
-529.2 -438.2 -431.6 -350.8 -262.1 -201.9 -167.0 -181.0 -248.2 -322.9 -414.1 -514.7
73.8 143.8 193.0 191.5 371.7 539.6 780.3 682.1 403.6 240.8 125.3 102.1
Qve+inf -11038.22 -21.91
-1955.6 -1598.4 -1674.2 -1471.9 -1145.6 -726.8 -547.8 -604.7 -787.7 -1085.6 -1476.1 -1811.6

Qequip 163.2 145.1 163.2 151.1 163.2 157.2 157.2 163.2 151.1 163.2 157.2 157.2 1891.89 3.76

Qilum 544.0 483.5 544.0 503.7 544.0 523.8 523.8 544.0 503.7 544.0 523.8 523.8 6306.29 12.52

Qocup 217.4 193.3 217.4 201.3 217.4 209.4 209.4 217.4 201.3 217.4 209.4 209.4 2520.48 5.00

QH 4025.8 3218.6 2678.7 1720.3 1279.5 4.1 -- -- -- 399.9 2278.1 3651.9 19256.84 38.23

QC -- -- -- -- -4.0 -850.3 -2143.8 -2346.8 -1299.9 -- -- -- -6644.85 -13.19

QHC 4025.8 3218.6 2678.7 1720.3 1283.5 854.4 2143.8 2346.8 1299.9 399.9 2278.1 3651.9 25901.68 51.42
donde:
Qop: Transferencia de energía correspondiente a la transmisión térmica a través de elementos pesados en contacto con el exterior,
kWh/m²·año.
Qw: Transferencia de energía correspondiente a la transmisión térmica a través de elementos ligeros en contacto con el exterior,
kWh/m²·año.

Página 4 - 16
Demanda energética

Qve+inf: Transferencia de energía correspondiente a la transmisión térmica por ventilación, kWh/m²·año.


Qequip: Transferencia de energía correspondiente a la ganancia interna de calor debida al equipamiento interno, kWh/m²·año.
Qilum: Transferencia de energía correspondiente a la ganancia interna de calor debida a la iluminación, kWh/m²·año.
Qocup: Transferencia de energía correspondiente a la ganancia interna de calor debida a la ocupación, kWh/m²·año.
Q H: Energía aportada de calefacción, kWh/m²·año.
QC: Energía aportada de refrigeración, kWh/m²·año.
QHC: Energía aportada de calefacción y refrigeración, kWh/m²·año.

2.2. Demanda energética mensual de calefacción y refrigeración.


Atendiendo únicamente a la demanda energética a cubrir por los sistemas de calefacción y refrigeración, las
necesidades energéticas y de potencia útil instantánea a lo largo de la simulación anual se muestran en los
siguientes gráficos:
Energía (kWh/mes) Potencia (W)

4500 45000

4000 40000

3500 35000

3000 30000

2500 25000

2000 20000

1500 15000

1000 10000

500 5000

0 0

Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic

2.3. Evolución de la temperatura.


La evolución de la temperatura operativa interior en las zonas modelizadas del edificio objeto de proyecto se
muestra en las siguientes gráficas, que muestran la evolución de las temperaturas mínimas, máximas y medias
de cada día, en cada zona:

zona_1

Temperatura (°C)

40
35
30
25
20
15
10
5
0

Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic

Página 5 - 16
Demanda energética

zona_2

Temperatura (°C)

40
35
30
25
20
15
10
5
0

Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic

zona_3

Temperatura (°C)

40
35
30
25
20
15
10
5
0

Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic

zona_4

Temperatura (°C)

40
35
30
25
20
15
10
5
0

Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic

Página 6 - 16
Demanda energética

zona_5

Temperatura (°C)

40
35
30
25
20
15
10
5
0

Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic

zona_6

Temperatura (°C)

40
35
30
25
20
15
10
5
0

Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic

zona_7

Temperatura (°C)

40
35
30
25
20
15
10
5
0

Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic

Página 7 - 16
Demanda energética

zona_8

Temperatura (°C)

40
35
30
25
20
15
10
5
0

Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic

zona_9

Temperatura (°C)

40
35
30
25
20
15
10
5
0

Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic

zona_10

Temperatura (°C)

40
35
30
25
20
15
10
5
0

Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic

Página 8 - 16
Demanda energética

zona_11

Temperatura (°C)

40
35
30
25
20
15
10
5
0

Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic

zona_12

Temperatura (°C)

40
35
30
25
20
15
10
5
0

Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic

zona_13

Temperatura (°C)

40
35
30
25
20
15
10
5
0

Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic

Página 9 - 16
Demanda energética

2.4. Resultados numéricos del balance energético por zona y mes.


En la siguiente tabla se muestran los resultados de transferencia total de calor por transmisión y ventilación,
calor interno total, y energía necesaria para calefacción y refrigeración, de cada una de las zonas de cálculo del
edificio.
El criterio de signos adoptado consiste en emplear valores positivos para energías aportadas a la zona de
cálculo, y negativos para la energía extraída.
Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic Año
(kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh/año) (kWh/m²·año)
zona_1 (Af = 37.85 m²; V = 132.47 m³)
31.5 25.9 26.0 21.5 16.0 34.3 80.4 93.0 52.0 18.3 24.6 30.3
Qop -1875.04 -49.54
-287.3 -252.5 -250.4 -209.3 -228.2 -162.1 -135.5 -118.4 -98.7 -120.3 -201.2 -264.8
36.4 51.6 88.9 112.7 150.7 182.5 196.5 174.7 130.5 76.9 45.4 33.7
Qw 1032.89 27.29
-31.9 -26.4 -26.1 -21.4 -16.6 -13.0 -10.6 -11.2 -15.1 -19.4 -24.9 -31.1
-- 0.0 0.1 0.2 0.9 5.0 12.6 10.6 5.1 0.4 0.0 --
Qve+inf -640.66 -16.93
-97.5 -79.2 -79.2 -65.0 -55.9 -29.8 -17.4 -19.0 -29.6 -45.6 -68.4 -89.2

Qequip 12.3 10.9 12.3 11.4 12.3 11.8 11.8 12.3 11.4 12.3 11.8 11.8 142.16 3.76

Qilum 40.9 36.3 40.9 37.8 40.9 39.4 39.4 40.9 37.8 40.9 39.4 39.4 473.87 12.52

Qocup 16.3 14.5 16.3 15.1 16.3 15.7 15.7 16.3 15.1 16.3 15.7 15.7 189.39 5.00

QH 279.1 219.1 171.7 97.7 66.7 -- -- -- -- 21.3 157.2 253.8 1266.57 33.46

QC -- -- -- -- -0.4 -80.7 -190.0 -197.1 -107.2 -- -- -- -575.42 -15.20

QHC 279.1 219.1 171.7 97.7 67.1 80.7 190.0 197.1 107.2 21.3 157.2 253.8 1841.99 48.67

zona_2 (Af = 22.06 m²; V = 76.60 m³)


27.2 22.6 22.8 18.5 13.4 23.1 52.2 59.4 39.0 16.2 21.9 26.4
Qop -1891.06 -85.74
-309.7 -265.9 -250.0 -184.7 -162.1 -85.2 -69.4 -81.9 -119.9 -177.5 -239.3 -288.1
129.3 122.8 128.4 96.9 86.6 93.4 111.0 137.8 164.7 156.6 144.9 126.9
Qw 1291.70 58.57
-26.5 -22.2 -22.1 -17.8 -13.4 -10.1 -8.4 -9.3 -13.2 -17.0 -21.4 -26.1
-- -- 0.0 0.1 0.9 3.5 8.3 6.8 3.0 0.1 0.0 --
Qve+inf -415.34 -18.83
-64.0 -52.1 -51.6 -41.7 -33.9 -17.2 -11.1 -12.1 -19.6 -30.7 -45.5 -58.7

Qequip 7.1 6.4 7.1 6.6 7.1 6.9 6.9 7.1 6.6 7.1 6.9 6.9 82.84 3.76

Qilum 23.8 21.2 23.8 22.1 23.8 22.9 22.9 23.8 22.1 23.8 22.9 22.9 276.13 12.52

Qocup 9.5 8.5 9.5 8.8 9.5 9.2 9.2 9.5 8.8 9.5 9.2 9.2 110.36 5.00

QH 203.3 159.0 132.1 91.2 69.3 -- -- -- -- 12.5 100.2 180.6 948.26 42.99

QC -- -- -- -- -0.0 -45.3 -120.9 -140.9 -91.9 -- -- -- -398.95 -18.09

QHC 203.3 159.0 132.1 91.2 69.4 45.3 120.9 140.9 91.9 12.5 100.2 180.6 1347.21 61.08

zona_3 (Af = 22.56 m²; V = 77.91 m³)


21.6 18.0 18.2 15.0 10.9 24.3 54.0 62.5 40.5 14.0 17.4 20.9
Qop -1623.67 -71.96
-263.5 -228.6 -212.2 -152.7 -138.2 -75.4 -60.6 -75.2 -111.1 -168.4 -208.1 -247.2
127.9 121.2 125.7 93.4 81.7 86.4 103.4 131.2 160.2 153.5 143.2 125.7
Qw 1259.68 55.83
-24.9 -20.8 -20.6 -16.6 -12.5 -9.6 -7.7 -8.4 -12.1 -16.2 -20.0 -24.5
-- -- 0.0 0.1 0.6 3.0 7.5 6.1 2.8 0.1 0.0 --
Qve+inf -383.24 -16.98
-58.2 -47.4 -47.1 -38.1 -32.0 -16.8 -9.9 -11.0 -17.8 -30.2 -41.6 -53.4
Qequip 7.3 6.5 7.3 6.8 7.3 7.0 7.0 7.3 6.8 7.3 7.0 7.0 84.75 3.76

Qilum 24.4 21.7 24.4 22.6 24.4 23.5 23.5 24.4 22.6 24.4 23.5 23.5 282.49 12.52

Página 10 - 16
Demanda energética

Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic Año
(kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh/año) (kWh/m²·año)

Qocup 9.7 8.7 9.7 9.0 9.7 9.4 9.4 9.7 9.0 9.7 9.4 9.4 112.91 5.00

QH 155.0 120.3 94.0 60.1 48.8 -- -- -- -- 6.0 68.5 137.8 690.48 30.60

QC -- -- -- -- -0.1 -51.3 -126.5 -147.1 -101.8 -- -- -- -426.91 -18.92

QHC 155.0 120.3 94.0 60.1 48.9 51.3 126.5 147.1 101.8 6.0 68.5 137.8 1117.39 49.52

zona_4 (Af = 36.97 m²; V = 129.41 m³)


32.3 26.6 26.4 21.6 15.8 22.8 41.9 49.9 35.9 19.3 25.3 31.0
Qop -1713.36 -46.34
-250.8 -222.1 -224.1 -195.6 -213.3 -155.4 -104.9 -85.2 -84.9 -122.1 -174.7 -229.2
45.5 61.3 100.1 125.4 149.7 200.6 212.8 194.4 144.6 91.1 53.0 38.6
Qw 1166.03 31.54
-32.7 -27.2 -26.4 -21.7 -16.4 -13.0 -10.2 -10.9 -15.0 -20.4 -25.6 -31.7
-- -- 0.1 0.1 0.7 4.8 12.2 10.2 4.9 0.3 0.0 --
Qve+inf -622.06 -16.82
-94.2 -76.5 -76.4 -62.8 -54.1 -29.6 -16.4 -18.0 -28.4 -46.6 -66.1 -86.1
Qequip 12.0 10.6 12.0 11.1 12.0 11.5 11.5 12.0 11.1 12.0 11.5 11.5 138.87 3.76

Qilum 39.9 35.5 39.9 37.0 39.9 38.5 38.5 39.9 37.0 39.9 38.5 38.5 462.90 12.52

Qocup 16.0 14.2 16.0 14.8 16.0 15.4 15.4 16.0 14.8 16.0 15.4 15.4 185.01 5.00

QH 231.7 177.7 133.0 71.1 54.0 -- -- -- -- 11.9 122.4 211.6 1013.41 27.41

QC -- -- -- -- -1.7 -92.4 -197.7 -205.9 -118.4 -- -- -- -616.04 -16.66

QHC 231.7 177.7 133.0 71.1 55.7 92.4 197.7 205.9 118.4 11.9 122.4 211.6 1629.46 44.07

zona_5 (Af = 52.24 m²; V = 182.81 m³)


26.2 21.5 21.3 17.6 12.5 29.8 75.5 92.3 49.7 15.9 20.5 25.2
Qop -1662.91 -31.84
-314.4 -271.2 -251.0 -190.5 -191.8 -96.1 -55.5 -45.6 -48.7 -102.3 -213.1 -290.8
18.1 27.3 44.5 55.7 75.6 94.0 99.0 86.2 64.4 42.6 24.1 16.7
Qw 413.89 7.92
-31.9 -26.3 -25.1 -20.3 -14.8 -11.0 -8.6 -9.1 -13.2 -18.3 -24.5 -31.0
-- 0.0 0.2 0.4 1.4 6.8 16.4 13.8 6.7 0.6 0.0 --
Qve+inf -788.62 -15.10
-122.0 -98.8 -98.4 -79.5 -68.1 -34.7 -20.3 -22.9 -35.9 -57.3 -85.5 -111.5

Qequip 16.9 15.0 16.9 15.7 16.9 16.3 16.3 16.9 15.7 16.9 16.3 16.3 196.19 3.76

Qilum 56.4 50.1 56.4 52.2 56.4 54.3 54.3 56.4 52.2 56.4 54.3 54.3 653.98 12.52

Qocup 22.5 20.0 22.5 20.9 22.5 21.7 21.7 22.5 20.9 22.5 21.7 21.7 261.38 5.00

QH 327.0 261.5 212.1 127.5 91.0 -- -- -- -- 23.6 185.1 297.9 1525.83 29.21

QC -- -- -- -- -- -78.6 -196.6 -208.8 -111.1 -- -- -- -595.13 -11.39

QHC 327.0 261.5 212.1 127.5 91.0 78.6 196.6 208.8 111.1 23.6 185.1 297.9 2120.96 40.60

zona_6 (Af = 35.28 m²; V = 110.44 m³)


36.6 29.9 30.7 26.3 19.9 29.9 62.0 68.9 41.7 21.3 29.3 35.3
Qop -3009.75 -85.30
-325.1 -303.6 -342.8 -319.3 -364.6 -307.1 -287.0 -253.6 -211.9 -184.8 -242.7 -299.1
51.4 84.3 167.7 217.5 287.3 342.3 376.4 342.0 255.7 133.9 67.1 45.6
Qw 1970.98 55.86
-48.9 -40.8 -41.5 -35.5 -27.8 -22.9 -19.6 -20.7 -26.0 -30.7 -38.4 -47.5
-- 0.0 0.1 0.2 0.5 3.9 9.7 8.2 4.0 0.3 0.0 0.0
Qve+inf -512.14 -14.52
-77.2 -62.7 -63.3 -52.5 -45.3 -24.0 -14.5 -15.9 -23.7 -35.4 -54.2 -70.4
Qequip 11.4 10.2 11.4 10.6 11.4 11.0 11.0 11.4 10.6 11.4 11.0 11.0 132.52 3.76

Qilum 38.1 33.9 38.1 35.3 38.1 36.7 36.7 38.1 35.3 38.1 36.7 36.7 441.73 12.52

Qocup 15.2 13.5 15.2 14.1 15.2 14.7 14.7 15.2 14.1 15.2 14.7 14.7 176.55 5.00

QH 300.1 237.4 187.2 106.8 72.1 -- -- -- -- 33.4 177.8 275.0 1389.78 39.39

Página 11 - 16
Demanda energética

Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic Año
(kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh/año) (kWh/m²·año)

QC -- -- -- -- -0.9 -77.9 -183.4 -188.7 -96.4 -- -- -- -547.19 -15.51

QHC 300.1 237.4 187.2 106.8 73.0 77.9 183.4 188.7 96.4 33.4 177.8 275.0 1936.97 54.90

zona_7 (Af = 45.12 m²; V = 152.51 m³)


19.4 15.6 15.9 13.5 8.5 17.0 58.2 65.7 35.1 9.5 15.0 18.2
Qop -2949.90 -65.38
-506.2 -431.7 -403.8 -297.5 -252.6 -85.7 -58.7 -60.0 -105.3 -201.8 -368.6 -469.4
90.6 84.3 87.4 65.2 57.1 60.2 70.9 90.1 111.1 107.1 100.4 89.3
Qw 902.08 19.99
-14.4 -11.9 -11.9 -9.7 -7.1 -5.4 -4.7 -5.2 -7.0 -8.9 -11.5 -14.0
0.0 0.0 0.2 0.6 3.0 8.3 17.3 14.2 6.6 0.9 0.1 0.0
Qve+inf -727.46 -16.12
-115.8 -93.6 -93.3 -75.8 -60.0 -27.5 -19.7 -22.2 -32.9 -50.5 -81.6 -105.9

Qequip 14.6 13.0 14.6 13.5 14.6 14.1 14.1 14.6 13.5 14.6 14.1 14.1 169.47 3.76

Qilum 48.7 43.3 48.7 45.1 48.7 46.9 46.9 48.7 45.1 48.7 46.9 46.9 564.90 12.52

Qocup 19.5 17.3 19.5 18.0 19.5 18.8 18.8 19.5 18.0 19.5 18.8 18.8 225.78 5.00

QH 442.0 362.4 321.0 225.0 168.6 0.8 -- -- -- 60.0 264.4 400.4 2244.69 49.75

QC -- -- -- -- -- -46.4 -142.3 -165.6 -85.3 -- -- -- -439.64 -9.74

QHC 442.0 362.4 321.0 225.0 168.6 47.3 142.3 165.6 85.3 60.0 264.4 400.4 2684.33 59.49

zona_8 (Af = 67.75 m²; V = 212.11 m³)


37.8 30.8 30.8 25.8 17.8 23.5 58.8 72.4 44.6 20.8 29.7 36.4
Qop -2844.74 -41.99
-462.1 -405.1 -389.0 -303.5 -306.3 -170.6 -120.5 -94.0 -101.0 -167.0 -326.8 -427.8
22.3 35.9 62.1 79.4 113.9 158.2 175.6 153.2 107.1 62.3 31.6 20.5
Qw 634.96 9.37
-53.5 -43.3 -41.8 -33.5 -24.1 -17.8 -14.4 -15.4 -21.8 -29.6 -40.2 -51.8
0.0 0.0 0.2 0.6 1.9 8.2 19.4 16.3 7.9 0.9 0.1 0.0
Qve+inf -901.65 -13.31
-140.9 -113.9 -113.8 -92.1 -77.1 -37.7 -23.8 -26.9 -40.2 -63.1 -98.9 -128.7
Qequip 22.0 19.5 22.0 20.3 22.0 21.1 21.1 22.0 20.3 22.0 21.1 21.1 254.49 3.76

Qilum 73.2 65.0 73.2 67.8 73.2 70.5 70.5 73.2 67.8 73.2 70.5 70.5 848.29 12.52

Qocup 29.2 26.0 29.2 27.1 29.2 28.2 28.2 29.2 27.1 29.2 28.2 28.2 339.04 5.00

QH 470.9 384.4 326.4 207.3 151.6 -- -- -- -- 51.6 283.5 430.5 2306.21 34.04

QC -- -- -- -- -- -80.4 -212.3 -228.1 -111.0 -- -- -- -631.88 -9.33

QHC 470.9 384.4 326.4 207.3 151.6 80.4 212.3 228.1 111.0 51.6 283.5 430.5 2938.09 43.36

zona_9 (Af = 51.61 m²; V = 162.36 m³)


48.8 39.9 40.0 33.2 24.0 30.7 59.0 72.9 52.2 28.5 39.0 47.1
Qop -3483.90 -67.50
-514.7 -452.6 -444.6 -373.4 -386.3 -268.8 -191.6 -157.0 -158.4 -214.0 -365.5 -472.1
74.2 92.4 143.4 188.8 224.0 322.3 354.7 329.5 232.2 142.4 87.3 63.2
Qw 1750.63 33.92
-67.8 -55.3 -53.2 -43.6 -32.0 -24.9 -20.0 -21.6 -29.4 -39.4 -51.4 -65.4
-- 0.0 0.2 0.4 1.2 6.1 15.0 12.7 6.1 0.6 0.0 0.0
Qve+inf -720.33 -13.96
-111.1 -89.9 -89.8 -73.2 -62.1 -32.3 -19.1 -21.4 -32.9 -51.2 -78.1 -101.5

Qequip 16.7 14.9 16.7 15.5 16.7 16.1 16.1 16.7 15.5 16.7 16.1 16.1 193.86 3.76

Qilum 55.7 49.5 55.7 51.6 55.7 53.7 53.7 55.7 51.6 55.7 53.7 53.7 646.20 12.52

Qocup 22.3 19.8 22.3 20.6 22.3 21.5 21.5 22.3 20.6 22.3 21.5 21.5 258.27 5.00

QH 477.2 383.0 311.3 181.9 141.7 -- -- -- -- 40.1 278.1 438.3 2251.69 43.63

QC -- -- -- -- -0.4 -119.1 -284.7 -306.4 -155.7 -- -- -- -866.39 -16.79

QHC 477.2 383.0 311.3 181.9 142.2 119.1 284.7 306.4 155.7 40.1 278.1 438.3 3118.07 60.41

Página 12 - 16
Demanda energética

Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic Año
(kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh/año) (kWh/m²·año)

zona_10 (Af = 83.77 m²; V = 281.05 m³)


161.2 134.2 136.1 110.9 80.4 88.3 160.0 187.2 148.2 97.4 132.7 156.9
Qop -8732.52 -104.24
-1298.5 -1140.5 -1129.3 -889.7 -847.4 -536.0 -475.2 -482.3 -579.9 -735.9 -1004.8 -1206.4
455.7 463.5 546.2 477.6 509.0 617.1 723.2 774.9 765.8 630.9 528.0 446.7
Qw 5426.94 64.78
-195.3 -162.7 -161.5 -129.6 -96.6 -73.5 -62.2 -68.6 -94.6 -121.9 -155.0 -190.2
-- -- 0.1 0.6 3.4 12.6 29.9 24.3 11.0 0.7 0.0 --
Qve+inf -1465.51 -17.49
-227.0 -184.2 -183.6 -149.3 -119.3 -58.9 -40.0 -44.2 -68.3 -104.8 -161.1 -207.5
Qequip 27.1 24.1 27.1 25.1 27.1 26.1 26.1 27.1 25.1 27.1 26.1 26.1 314.64 3.76

Qilum 90.5 80.4 90.5 83.8 90.5 87.1 87.1 90.5 83.8 90.5 87.1 87.1 1048.81 12.52

Qocup 36.2 32.1 36.2 33.5 36.2 34.8 34.8 36.2 33.5 36.2 34.8 34.8 419.18 5.00

QH 966.2 769.7 658.0 456.8 344.3 0.0 -- -- -- 100.1 526.8 866.9 4688.84 55.97

QC -- -- -- -- -0.3 -168.9 -455.7 -520.0 -304.1 -- -- -- -1449.07 -17.30

QHC 966.2 769.7 658.0 456.8 344.7 168.9 455.7 520.0 304.1 100.1 526.8 866.9 6137.91 73.27

zona_11 (Af = 7.38 m²; V = 26.72 m³)


4.1 3.3 3.4 3.1 1.6 6.7 25.3 29.2 14.0 1.7 3.1 3.7
Qop -830.87 -112.62
-163.8 -137.7 -127.2 -93.6 -74.7 -10.7 -5.1 -3.6 -5.5 -44.8 -111.9 -151.4
0.0 0.1 0.2 0.3 1.4 2.9 4.9 4.0 2.0 0.7 0.1 0.1
Qve+inf -159.81 -21.66
-26.9 -21.7 -21.6 -17.6 -13.0 -5.7 -4.5 -5.0 -6.6 -10.8 -18.6 -24.4

Qequip 2.4 2.1 2.4 2.2 2.4 2.3 2.3 2.4 2.2 2.4 2.3 2.3 27.71 3.76

Qilum 8.0 7.1 8.0 7.4 8.0 7.7 7.7 8.0 7.4 8.0 7.7 7.7 92.36 12.52

Qocup 3.2 2.8 3.2 2.9 3.2 3.1 3.1 3.2 2.9 3.2 3.1 3.1 36.92 5.00

QH 173.2 144.1 131.7 95.0 71.3 3.2 -- -- -- 39.4 114.1 159.1 931.07 126.21

QC -- -- -- -- -- -9.3 -33.7 -38.4 -16.9 -- -- -- -98.22 -13.31

QHC 173.2 144.1 131.7 95.0 71.3 12.5 33.7 38.4 16.9 39.4 114.1 159.1 1029.30 139.52

zona_12 (Af = 41.10 m²; V = 137.15 m³)


2.7 1.8 2.1 2.2 1.1 0.9 0.9 1.0 1.1 1.1 1.3 1.6
Qop -447.32 -10.88
-25.0 -25.8 -30.9 -31.7 -41.3 -52.1 -58.5 -55.6 -44.1 -41.6 -32.9 -25.6
0.0 0.2 0.5 0.7 1.6 3.8 6.0 4.2 2.0 0.7 0.3 0.1
Qve+inf -423.72 -10.31
-53.0 -42.6 -46.6 -41.0 -35.5 -24.3 -20.1 -24.7 -29.5 -36.2 -41.6 -48.9
Qequip 13.3 11.8 13.3 12.3 13.3 12.8 12.8 13.3 12.3 13.3 12.8 12.8 154.39 3.76

Qilum 44.4 39.5 44.4 41.1 44.4 42.7 42.7 44.4 41.1 44.4 42.7 42.7 514.62 12.52

Qocup 17.7 15.8 17.7 16.4 17.7 17.1 17.1 17.7 16.4 17.7 17.1 17.1 205.68 5.00

zona_13 (Af = 366.56 m²; V = 1072.56 m³)


750.1 614.4 678.3 646.1 459.4 347.5 290.9 315.4 380.0 489.0 613.3 706.7
Qop 3034.33 8.28
-65.4 -128.9 -175.9 -175.5 -339.0 -459.4 -612.7 -540.8 -332.8 -220.9 -114.7 -91.1
8.7 11.0 18.0 22.4 24.2 33.8 36.2 34.6 25.8 15.7 9.3 7.1
Qw 234.23 0.64
-1.4 -1.2 -1.3 -1.2 -0.8 -0.7 -0.6 -0.7 -0.9 -1.1 -1.2 -1.4
73.8 143.4 191.2 187.2 354.3 470.9 621.1 550.4 341.3 234.4 124.5 101.9
Qve+inf -3277.70 -8.94
-767.9 -635.8 -709.5 -683.2 -489.4 -388.3 -330.9 -361.2 -422.5 -523.2 -635.0 -725.3
Qequip -- -- -- -- -- -- -- -- -- -- -- -- 0.00 0.00

Qilum -- -- -- -- -- -- -- -- -- -- -- -- 0.00 0.00

Página 13 - 16
Demanda energética

Ene Feb Mar Abr May Jun Jul Ago Sep Oct Nov Dic Año
(kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh) (kWh/año) (kWh/m²·año)

Qocup -- -- -- -- -- -- -- -- -- -- -- -- 0.00 0.00


donde:
Af: Superficie útil de la zona térmica, m².
V: Volumen interior neto de la zona térmica, m³.
Qop: Transferencia de energía correspondiente a la transmisión térmica a través de elementos pesados en contacto con el exterior,
kWh/m²·año.
Qw: Transferencia de energía correspondiente a la transmisión térmica a través de elementos ligeros en contacto con el exterior,
kWh/m²·año.
Qve+inf: Transferencia de energía correspondiente a la transmisión térmica por ventilación, kWh/m²·año.
Qequip: Transferencia de energía correspondiente a la ganancia interna de calor debida al equipamiento interno, kWh/m²·año.
Qilum: Transferencia de energía correspondiente a la ganancia interna de calor debida a la iluminación, kWh/m²·año.
Qocup: Transferencia de energía correspondiente a la ganancia interna de calor debida a la ocupación, kWh/m²·año.
Q H: Energía aportada de calefacción, kWh/m²·año.
QC: Energía aportada de refrigeración, kWh/m²·año.
QHC: Energía aportada de calefacción y refrigeración, kWh/m²·año.

3. MODELO DE CÁLCULO DEL EDIFICIO.


3.1. Agrupaciones de recintos.
Se muestra a continuación la caracterización de los espacios que componen cada una de las zonas de cálculo
del edificio.
Tª calef. Tª refrig.
S V renh ΣQ ocup,s ΣQ ocup,l ΣQ equip,s ΣQ equip,l ΣQ ilum
(m²) (m³) (1/h) (kWh/año) (kWh/año) (kWh/año) (kWh/año) (kWh/año)
media media
(°C) (°C)
zona_1 (Zona habitable)
banno2 6.90 24.15 0.63 34.53 21.80 25.92 -- 86.40 20.0 25.0
habitacion1 30.95 108.32 0.63 154.86 97.77 116.24 -- 387.47 20.0 25.0
37.85 132.47 0.63/0.23* 189.39 119.57 142.16 -- 473.87 20.0 25.0

zona_2 (Zona habitable)


banno3 6.60 23.11 0.63 33.03 20.86 24.80 -- 82.65 20.0 25.0
habitacion2 15.45 53.50 0.63 77.33 48.82 58.04 -- 193.48 20.0 25.0
22.06 76.60 0.63/0.26* 110.36 69.67 82.84 -- 276.13 20.0 25.0

zona_3 (Zona habitable)


banno4 6.67 23.34 0.63 33.38 21.07 25.06 -- 83.52 20.0 25.0
habitacion3 15.89 54.57 0.63 79.53 50.21 59.69 -- 198.98 20.0 25.0
22.56 77.91 0.63/0.23* 112.91 71.28 84.75 -- 282.49 20.0 25.0

zona_4 (Zona habitable)


banno5 7.04 24.62 0.63 35.21 22.23 26.43 -- 88.09 20.0 25.0
habitacion4 29.94 104.78 0.63 149.80 94.57 112.44 -- 374.81 20.0 25.0
36.97 129.41 0.63/0.23* 185.01 116.80 138.87 -- 462.90 20.0 25.0

zona_5 (Zona habitable)


banno6 9.59 33.54 0.63 47.96 30.28 36.00 -- 120.01 20.0 25.0
habitacion5 42.65 149.28 0.63 213.42 134.74 160.19 -- 533.98 20.0 25.0
52.24 182.81 0.63/0.21* 261.38 165.02 196.20 -- 653.98 20.0 25.0

Página 14 - 16
Demanda energética

T calef. T refrig.
ª ª

S V renh ΣQ ocup,s ΣQ ocup,l ΣQ equip,s ΣQ equip,l ΣQ ilum


(m²) (m³) (1/h) (kWh/año) (kWh/año) (kWh/año) (kWh/año) (kWh/año)
media media
(°C) (°C)

zona_6 (Zona habitable)


comedor1 35.28 110.44 0.63 176.55 111.46 132.52 -- 441.74 20.0 25.0
35.28 110.44 0.63/0.22* 176.55 111.46 132.52 -- 441.74 20.0 25.0

zona_7 (Zona habitable)


cocina1 45.12 152.51 0.63 225.78 142.54 169.47 -- 564.90 20.0 25.0
45.12 152.51 0.63/0.25* 225.78 142.54 169.47 -- 564.90 20.0 25.0

zona_8 (Zona habitable)


lobby 67.75 212.11 0.63 339.04 214.04 254.49 -- 848.29 20.0 25.0
67.75 212.11 0.63/0.21* 339.04 214.04 254.49 -- 848.29 20.0 25.0

zona_9 (Zona habitable)


oficina1 15.66 49.39 0.63 78.36 49.47 58.81 -- 196.05 20.0 25.0
oficina2 5.73 17.94 0.63 28.68 18.11 21.53 -- 71.77 20.0 25.0
salon 30.22 95.04 0.63 151.23 95.47 113.51 -- 378.38 20.0 25.0
51.61 162.36 0.63/0.22* 258.27 163.05 193.86 -- 646.20 20.0 25.0

zona_10 (Zona habitable)


corredor1 28.16 88.14 0.63 140.92 88.97 105.78 -- 352.60 20.0 25.0
corredor2 15.67 54.84 0.63 78.42 49.51 58.86 -- 196.21 20.0 25.0
corredor3 39.94 138.07 0.63 199.84 126.16 150.00 -- 500.00 20.0 25.0
83.77 281.05 0.63/0.26* 419.18 264.64 314.64 -- 1048.81 20.0 25.0

zona_11 (Zona habitable)


banno1 7.38 26.72 0.63 36.92 23.31 27.71 -- 92.36 20.0 25.0
7.38 26.72 0.63/0.35* 36.92 23.31 27.71 -- 92.36 20.0 25.0

zona_12 (Zona habitable)


closet 5.53 20.09 0.63 27.70 17.49 20.79 -- 69.30 -- --
escalera1 20.10 62.90 0.63 100.56 63.49 75.48 -- 251.60 -- --
escalera2 15.47 54.16 0.63 77.43 48.88 58.12 -- 193.72 -- --
41.10 137.15 0.63/0.20* 205.68 129.85 154.39 -- 514.62 -- --

zona_13 (Zona no habitable)


sotano1 352.77 921.33 1.14 -- -- -- -- --
cuartoDeMaquinas1 13.78 49.77 0.83 -- -- -- -- -- Oscilación libre
bajoCubierta1 -- 101.46 -- -- -- -- -- --
366.56 1072.56 1.02 -- -- -- -- --
donde:
S: Superficie útil interior del recinto, m².
V: Volumen interior neto del recinto, m³.
renh: Número de renovaciones por hora del aire del recinto.

Página 15 - 16
Demanda energética

*: Valor medio del número de renovaciones hora del aire de la zona habitable, incluyendo las infiltraciones calculadas.
Qocup,s: Sumatorio de la carga interna sensible debida a la ocupación del recinto a lo largo del año, kWh/año.
Qocup,l: Sumatorio de la carga interna latente debida a la ocupación del recinto a lo largo del año, kWh/año.
Qequip,s: Sumatorio de la carga interna sensible debida a los equipos presentes en el recinto a lo largo del año, kWh/año.
Qequip,l: Sumatorio de la carga interna latente debida a los equipos presentes en el recinto a lo largo del año, kWh/año.
Qilum: Sumatorio de la carga interna debida a la iluminación del recinto a lo largo del año, kWh/año.
T calef. Valor medio en los intervalos de operación de la temperatura de consigna de calefacción, °C.
ª

media:
T refrig. Valor medio en los intervalos de operación de la temperatura de consigna de refrigeración, °C.
ª

media:

Página 16 - 16