Está en la página 1de 1

DIAGRAMA UNIFILAR

S.E. PARTICULAR 10/0.23KV


1 2 1 3

LEYENDA BAJA TENSION


SIMBOLOS DESCRIPCION

TTA

TR

ALARMAS
3

30

Y
Y
G TRANSFORMADOR
TIPO SECO DE 400KVA
26 P.A.T.-1
R<10ohm
10±2x2.5%/0.23kV
Vcc=6%, 3Ø, 60HZ.
GRUPO DE CONEXION
10/0.23KV, Yd11

ESCALA 1/100

TABLERO GENERAL TG
INTERRUPTORES 65 kA - 220 V - 60 Hz.

36 polos
Autosoportado

TTA
2x25A.
30mA.
MOA
EQUIPO DE TENSION ININTERRUMPIDA
220 V, 3Ø.

CAMBIADOR
TRANSFORMADOR DE RED
DE AISLAMIENTO 3 Posiciones
37.5 KVA, 3Ø 100A, 220 V, 3Ø

Data Center

Cuarto de Bombas

RESERVA
Tomacorrientes Subestación
Alumbrado Subestación

Alumbrado Exterior
k13 2 0
1
220/220 V
3x100A.
TVSS

P.A.T.-1
R<10ohm 10 KA
UPS
30 KVA, 3Ø
220 V, 3Ø

1x10 mm2 CPT


TUBO Ø 25 mm PVC-P

P.A.T.-1
R<5ohm

TD-1 TD-2 TD-3 TD-4 TD-5 TC-C TC-BCI


INT. 65 kA - 220 V INT. 65 kA - 220 V INT. 65 kA - 220 V INT. 65 kA.-380 V.
INT. 65 kA - 220 V INT. 65 kA - 220 V INT. 25 kA - 220 V
24 polos 36 polos 12 polos
36 polos 18 polos 36 polos 36 polos
Empotrado Empotrado Empotrado Empotrado Empotrado Autosoportado Empotrado

STD-1

TC-B
2x25A.

2x25A.

2x25A.
30mA.

30mA.

30mA.
MOA
MOA
MOA

P.A.T.-1 P.A.T.-1
P.A.T.-1 P.A.T.-1 P.A.T.-1 P.A.T.-1

R<10ohm R<10ohm R<10ohm R<10ohm R<10ohm R<10ohm


RESERVA

RESERVA
RESERVA

RESERVA

RESERVA

RESERVA
RESERVA

50 HP

1.5 HP
STD-4.1a

STD-4.1b

STD-4.1d

STD-4.2b

STD-4.2d

STD-4.2e

STD-4.2d

STD-4.2e
STD-4.1c

STD-4.2c
STD-3.2c
STD-3.2a

STD-3.2b

STD-3.2d
STD-2.1a

STD-2.2a

STD-3.1a

STD-3.1b

STD-3.1d

STD-5.1a

STD-5.1b

STD-5.1d

STD-5.1e

TDE-A.1

TDE-A.2

TDE-A.3

TDE-A.4

TDE-A.5

TDE-B.1
STD-3.1c

STD-5.1c

TDE-G
TDE-C.1

TDE-D.1
Alumb. Ext.

Alumb. Ext.

Alumb. Ext.
TC-AA3
STD-1.1a

STD-1.1b

STD-1.2a

STD-1.2b

TC-AA1

TC-AA2
TC-A

UNIVERSIDAD NACIONAL AGRARIA


DE LA SELVA
PROYECTO:
"CREACION DE LOS SERVICIOS ACADEMICOS, INVESTIGACIÓN, PROY ECCIÓN Y EXTENSIÓN DE LA
FACULTAD DE INGENIERIA MECANICA ELECTRICA, EN LA UNIVERSIDAD NACIONAL AGRARIA DE LA
S EL V A T I N G O M A R I A , D I ST R I T O D E R U P A R U PA , P R O V I N C I A D E L E O NC I O P R A D O " - ET A P A I

DIAGRAMA UNIFAMILIAR PLANO:


DIAGRAMA UNIFAMILIAR
ESPECIALIDAD:

INSTALACIONES ELECTRICAS
LAMINA:

ESCALA 1/100 RESPONSABLE:


ING. LUIS ALBERTO ROSAS GALAN
DIGITALIZACION:
I.L.A.R.G
FECHA:
OCTUBRE 2022
ESCALA:
INDICADA
IE-DU-01